| 2007-08-28 07:26:16 | |
| | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLANS, SHEET A-1 MENTIONS TO PROVIDE NEW |
| | ELECTRICAL SWITCH, YET NO INFORMATION WAS PROVIDED FOR |
| | THIS DEVICE(S). |
| | PLEASE SEE FBC 13-415.1.ABC.1.1, 13-101 AS A NEW |
| | AUTOMATED DEVICE OF SOME KIND WILL BE REQUIRED. |
| | PLEASE PROVIDE AND SHOW THE LOCATION OF THE NEW DEVICE |
| | OR DEVICES DEPENDING ON THE TYPE OF DEVICE AND COVERAGE |
| | FOR CONTROLS. |
| | PLEASE PROVIDE THE MAXIMUM TIME(S) FOR DEVICE(S). |
| | |
| | 2) NOTE: PLEASE PROVIDE INFORMATION FOR CIRCUITING OF |
| | WHAT IS BEING CALLED EXISTING EXIT AND EMERGENCY LIGHTS |
| | PER 700.12F OF THE 2005 NEC> |
| | |
| | 3) NOTE: PLEASE STATE THE FOLLOWING CODES ON PLANS. |
| | 2005 NFPA-70 (NEC) |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 4) NOTE: IF SPACE AND PR BUILDING CONTAINS A FA SYSTEM, |
| | PLEASE LOCATE THE NEW OR EXISTING HORNS/STROBE DEVICES |
| | FOR MINIMUM ADA REQUIREMENTS PER FBC 11-4.28.1,.2 AND |
| | .3(4). |
| | IF INSTALLATION ANY NEW DEVICES, OR RELOCATING THE |
| | MINIMUM LEVELS FOR DEVICES NEED TO MEET THE ADA |
| | STANDARDS AS STATED IN THE SECTION OF THE CODE ABOVE. |
| | |
| | ** THE SCOPE OF WORK IN MINOR IN NATURE AND THERE ARE |
| | ONLY A FEW ITEMS NEEDED ON PLANS. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |