Plan Review Details - Permit 07080384
Plan Review Stops For Permit 07080384
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-29 Cont ID  
Sent By rbrown Date 2007-08-29 Time 20:37 Rev Time 0.00
Received By rbrown Date 2007-08-29 Time 20:37 Sent To  
Notes
2007-08-29 20:46:19BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2004 (WITH 2007
 AMENDMENTS)
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 2002.4.1LOADS, STRUCTURAL MEMBERS AND
 CONNECTIONS.THE PLANS MAKE REFERENCE TO SENATE BILL
 404.SENATE BILL 404 STATES THAT SITE SPECIFIC
 ENGINEERING IS NOT REQUIRED FOR SCREEN ENCLOSURES.IT
 ALSO STATES THAT A"MASTER DESIGN MANUAL" CAN BE USED
 IF IT IS PREPARED BY A LICENSED ENGINEER, STATES THE
 DESIGN LIMITATIONS, STATES THE TRAINING REQUIRED TO BE
 A QUALIFIED USER, AND IDENTIFIES THE NAME OF THE
 ENGINEER WHO DID PEER REVIEW OF THE "MASTER DESIGN
 MANUAL".NO SUCH "MASTER DESIGN MANUAL" IS REFERENCED
 ON THE PLANS, SO WITH THE EXCEPTION OF THE
 SITE-SPECIFIC LAYOUT THE PLANS MUST BE PREPARED BY A
 LICENSED ENGINEER.THE STRUCTURAL MEMBERS SHALL BE
 DESIGNED IN ACCORDANCE WITH ESTABLISHED ENGINEERING
 PRACTICES.NO ENGINEERED PLANS WERE SUBMITTED FOR THE
 DESIGN OF THE STRUCTURAL MEMBERS.NON-ENGINEERS WHO
 ARE REGISTERED USERS OF AAF GUIDE TO ALUMINUM
 CONSTRUCTION IN HIGH WIND AREAS CAN SUBMIT DESIGNS
 BASED ON THAT GUIDE, BUT SCREEN PROFESSIONALS INC. IS
 NOT LISTED AS A REGISTERED USER. SUBMIT PLANS FROM A
 LICENSED ENGINEER, OR MAKE REFERENCE TO AN "MASTER
 DESIGN MANUAL" THAT MEETS THE ABOVE CRITERIA.
  
 2) FBC 2002.4TRAC SELF MATING BEAM.SHEET 2 OF THE
 SUBMITTED PRODUCT APROVAL FL 7350.1 STATES THAT "SITE
 SPECIFIC ENGINEERING MUST ACCOMPANY THIS PRODUCT
 APPROVAL FOR EACH STRUCTURE INSTALLED".NO SITE
 SPECIFIC ENGINEERING WAS SUBMITTED.SUBMIT ENGINEERING
 TO JUSTIFY THE PROPOSED STRUCTURAL MEMBER SIZES.
  
 3) FBC 2002.4CORNER POSTS.THE CORNER POST SIZE (AND
 WALL THICKNESS) IS NOT STATED ON THE PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-08-16 Cont ID  
Sent By pschmitz Date 2007-08-16 Time 11:06 Rev Time 0.00
Received By pschmitz Date 2007-08-16 Time 11:05 Sent To PC
Notes
2007-08-16 11:09:49REPLACE SCREEN ENCLOSSURE DAMAGED BY HURRICANE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-16 Cont ID  
Sent By pschmitz Date 2007-08-16 Time 11:14 Rev Time 0.00
Received By pschmitz Date 2007-08-14 Time 10:44 Sent To  
Notes
2007-08-14 10:44:22TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2007-08-15 Cont ID  
Sent By choops Date 2007-08-15 Time 12:17 Rev Time 0.00
Received By choops Date 2007-08-16 Time 11:16 Sent To B
Notes
2007-08-15 12:17:23SENT TO "B" - PAUL SCHMITZ


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved