| 2007-08-15 17:39:36 | ROOFING BUILDING FIRST REVIEW CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC 2004 |
| | WITH 2006 REVISIONS. |
| | |
| | 1-ACCORDING TO MIAMI DADEPRODUCT APPROVAL WEBSITE |
| | NOA 06-0310.06 SUBMITTED IS CLOSED.THEREFORE, IT |
| | CAN'T BE USED.CONTRACTOR MAY USE NOA 06-0606.05 |
| | WHICH WAS ALREADY APPROVED.ASK GENERAL CONTRACTOR FOR |
| | APPROVED PRODUCT APPROVALS, INCLUDING THEFLAT ROOF |
| | ASSEMBLY OVER WOOD DECKS. SEE APPROVEDNOA 04-0506.03 |
| | FOR FLAT ROOF SPECIFIC ASSEMBLY AND FASTENING OPTION TO |
| | BE USED.PROVIDE NEW FLAT ROOF PRODUCT APPROVAL IF |
| | NOT USING APPROVED PRODUCT APPROVALS. |
| | |
| | 2- NOA 06-0913.06 SUBMITTED IS FOR ROOF COATING. NEED |
| | TO PROVIDE THE SPECIFIC ROOF ASSEMBLY PRODUCT CONTROL |
| | NOTICE OF ACCEPTANCE( FOR CONCRETE APPLICATION) AS |
| | REQUIRED BY APPLICATION RATE NOTE ON SHEET 7 OF 7 OF |
| | NOA SUBMITTED. |
| | NOTE:ON NOA CLEARLY IDENTIFY SPECIFICAPPROVED |
| | ASSEMBLY TO BE INSTALLED AND SPECIFIC FASTENING OPTION |
| | AS REQUIRED BY CITY POLICY FOR ROOFING PERMITS. SEE |
| | ATTACHED COPY. |
| | NOTE: CHECK IF SELECTED ASSEMBLY IS LIMITED BY GENERAL |
| | LIMITATION #7 OR #9 AND PROVIDE REQUIRED INFORMATION AS |
| | REQUIRED. |
| | |
| | 3- ARCHITECT OF RECORD NEED TO REVIEW AND APPROVE IN |
| | WRITING (NOT SIGNING AND SEALING)ALL PRODUCT |
| | APPROVALS AS REQUIRED BYSEC. 106.3.3 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |