Plan Review Details - Permit 07080309
Plan Review Stops For Permit 07080309
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-06 Cont ID  
Sent By rmcdouga Date 2007-09-06 Time 13:17 Rev Time 0.00
Received By rmcdouga Date 2007-09-06 Time 13:17 Sent To  
Notes
2007-09-06 16:35:302004 FBC W/2007 SUPPLEMENT
 LEVEL 3 ALTERATION AND ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) CORRECT THE JURISDICTION LISTED ON THE COVERSHEET TO
 THE CITY OF WEST PLAM BEACH.
  
 4) SPECIFY THE OCCUPANCY TYPE OF THE EXISTING
 STRUCTURE. SEE FBC 302.
  
 5) IF THE OCCUPANCY OF THE STRUCTURE IS BEING CHANGED,
 THE FBC EXISTING BUILDING CODE 807.2 REQUIRES THE
 STRUCTURE TO BE ANALYZED AND MADE TO COMPLY WITH THE
 APPLICABLE WIND LOAD PROVISIONS.
  
 6) SPECIFY THE LOCATIONS AND SIZE OF THE VERTICAL
 REINFORCEMENT OF THE MASONRY WALLS.
  
 7) SPECIFY THE SIZE AND REINFORCING OF THE EXISTING
 FOOTING.
  
 8) SPECIFY THE SIZE AND REINFORCING OF THE EXISTING TIE
 BEAM.
  
 10) SPECIFY THE WIDTH OF THE NEW FOOTING FOR THE
 INTERIOR LOAD BEARING WALL.
  
 11) CORRECT THE REINFORCING NOTE ON SHEET A1 FOR THE
 NEW CONCRETE FOOTING THAT SPECIFIES (4) #5 BUCK.
  
 12) THE FLOOR TRUSSES SUPPORTING THE WOOD FRAME
 EXTERIOR WALL DO NOT HAVE AN ID TAG ON S1.
  
 13) SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED.
 THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND
 ITS ATTIC AREA BY NOT LESS THAN 1/2 -INCH (12.7 MM)
 GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES
 BENEATH HABITABLE ROOMS SHALL BE SEPARATED FROM ALL
 HABITABLE ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH
 (15.9 MM) TYPE X GYPSUM BOARD OR EQUIVALENT. WHERE THE
 SEPARATION IS A FLOOR-CEILING ASSEMBLY, THE STRUCTURE
 SUPPORTING THE SEPARATION SHALL ALSO BE PROTECTED BY
 NOT LESS THAN 1/2-INCH (12.7 MM) GYPSUM BOARD OR
 EQUIVALENT.
  
 14) R311.5.3.2 REQUIRES STAIR TREADS AND RISERS TO BE
 PROPORTIONED SUCH THAT THE SUM OF TWO RISERS AND A
 TREAD, EXCLUSIVE OF THE NOSING, IS NOT LESS THAN 24
 INCHES NOR MORE THAN 25 INCHES.
  
 15) SHOW COMPLIANCE WITH R311.2.2 UNDER STAIR
 PROTECTION.
 ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE
 WALLS, UNDER STAIR SURFACE AND ANY SOFFITS PROTECTED ON
 THE ENCLOSED SIDE WITH 1/2 -INCH (12.7 MM) GYPSUM
 BOARD.
  
 16) R312.2 REQUIRES THE INTERMEDIATE RAILS ON GUARDS TO
 PREVENT THE PASSAGE OF A 4" SPHERE. THEREFORE, THE
 OPENINGS MUST BE LESS THAN 4 INCHES. PLEASE REVISE NOTE
 ON S1.
  
 17) THE GABLE END DETAIL ON S1 SHOWS A VENTED VINYL
 SOFFIT AND THE WALL SECTION ON E1 SHOWS A STUCCO
 SOFFIT. PLEASE CORRECT.
  
 18) THE EXTERIOR WALL COVERING IS SPECIFIED AS CEDAR
 SHAKES ON A1 AND THE WALL SECTION ON E1 SHOWS STUCCO.
 PLEASE CORRECT.
  
 19) ASTM C 926 REQUIRES STUCCO APPLIED VERTICALLY TO
 WIRE LATH OF A SOLID BASE TO BE 7/8" THICK. PLEASE
 REVISE THE NOTES ON THEWALL SECTION ON E1.
  
 20) ASTM C 1063 REQUIRES THE NAILS OR STAPLES USED TO
 ATTACH HIGH RIB METAL LATH TO PROVIDE AT LEAST 1-3/4"
 PENETRATION INTO HORIZONTAL WOOD FRAMING MEMBERS AND
 3/4" PENETRATION INTO VERTICAL WOOD FRAMING MEMBERS.
  
 21)THE MTS 12 WOOD TO WOOD CONNECTORS DO NOT PROVIDE
 ANY RESISTANCE TO LATERAL LOADS. SPECIFY HOW THE
 LATERAL LOADS AT THE TOP OF THE SECOND FLOOR WALLS WILL
 BE RESISTED.
  
 22) THE CS18 STRAPS SPECIFIED ON E1 ARE NOT DESIGNED
 FOR USE WITH CONCRETE/MASONRY. PLEASE SPECIFY A STRAP
 THAT IS DESIGNED AND TESTED FOR THIS APPLICATION SUCH
 AS MSTAM OR MSTCM.
  
 23) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR
 THE OVERHEAD DOOR AND THE SIDE SWING DOOR ON SHEET A1.
  
 24) SPECIFY THE INSULATION FOR THE 2 X 6 WOOD FRAME
 WALLS ON THE SECOND FLOOR AND THE FLOOR INSULATION
 ABOVE THE GARAGE ON THE ENERGY CALCULATION FORM.
  
 25)SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE 16'
 WIDE OVERHEAD GARAGE DOOR AND THE FIXED GLASS WINDOWS.
  
 26) THE MODEL NUMBER SPECIFIED ON THE PLANS FOR THE
 SINGLE HUNG WINDOWS DOES NOT CORRESPOND TO THE WINDOW
 PRODUCT APPROVALS THAT WERE SUBMITTED. PLEASE CORRECT.
  
 27) THE SH 24 WINDOW SPECIFIED FOR THE SECOND FLOOR
 BEDROOM TYPICALLY WILL NOT MEET THE CLEAR OPENING
 HEIGHT REQUIREMENT. SUBMIT THE CLEAR OPENING DIMENSIONS
 FOR THIS WINDOW FROM THE MANUFACTURER SHOWING
 COMPLIANCE WITH R310 OR SPECIFY ANOTHER WINDOW.
  
 27) THE NOAS THAT WERE SUBMITTED FOR THE FRENCH DOORS
 AND THE SINGLE HUNG WINDOWS WERE INCOMPLETE. SUBMIT THE
 COMPLETE NOAS INCLUDING THE APPROVED DRAWINGS.
  
 28) THE PLANS SHOW A SIX PANEL EXTERIOR DOOR AND THE
 PRODUCT APPROVALS SUBMITTED ARE FOR A GLAZED FRENCH
 DOOR. PLEASE CLARIFY.
  
 29) ON THE SECOND STORY FLOOR PLAN ON A1 THE WINDOWS
 ARE DESIGNATED BY THE LETTER 'C'. THE PRODUCT APPROVALS
 THAT WERE SUBMITTED ARE FOR SINGLE HUNG WINDOWS. PLEASE
 CHANGE THE 'C' TO 'SH' ON THE PLAN TO DENOTE SINGLE
 HUNG WINDOWS AND AVOID CONFUSION.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-20 Cont ID  
Sent By btrobaug Date 2007-08-20 Time 10:19 Rev Time 0.00
Received By btrobaug Date 2007-08-20 Time 09:26 Sent To P
Notes
2007-08-20 10:19:41 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72, 2002,
 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT
 WITH THE FOLLOWING:
  
 THERE IAS NO BUILDING RECORDED AT THIS ADDRESS OR FOR
 THE PCN NUMBER ON THE APPLICATION
  
 1} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 INDICATE IF SERVICE IS NEW OR EXISTING.
  
 3} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 4} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED.
  
 5}SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 NOTE: THE JURISDICTION ON THE COVER SHEET IS
 INCORRECT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-08-09 Cont ID  
Sent By swurafti Date 2007-08-09 Time 16:46 Rev Time 0.00
Received By swurafti Date 2007-08-09 Time 16:46 Sent To  
Notes
2007-08-09 16:46:48HISTORIC APPROVED BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-06 Cont ID  
Sent By rmcdouga Date 2007-09-06 Time 13:17 Rev Time 0.00
Received By rmcdouga Date 2007-08-10 Time 08:12 Sent To Z
Notes
2007-08-10 08:12:32TO SF RACK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-14 Cont ID  
Sent By tgordon Date 2007-08-14 Time 15:55 Rev Time 0.30
Received By tgordon Date 2007-08-14 Time 15:55 Sent To E
Notes
2007-08-14 16:03:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) PLEASE ADD AN A/C EQUIPMENT LISTING WITH ALL
 PERTINENT INFORMATION TO PLANS PAGE E-1.
  
 2) EQUIPMENT LISTED ON COOLING LOAD CALCULATIONS COULD
 NOT BE FOUND ON THE ARI DIRECTORY WEB SITE OR THE TRANE
 WEB SITE, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-05 Cont ID  
Sent By mperson Date 2007-09-05 Time 15:21 Rev Time 0.00
Received By mperson Date 2007-09-05 Time 15:21 Sent To B
Notes
2007-09-05 15:24:28DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING WITH 2006 REVISIONS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-13 Cont ID  
Sent By rmcdouga Date 2007-09-06 Time 13:17 Rev Time 0.00
Received By choops Date 2007-08-13 Time 15:03 Sent To E
Notes
2007-08-13 15:12:19***FAILED***
  
  
 1)***NONCONFORMING STRUCTURE.ACCESSORY STRUCTURE
 NOT PERMITTED ON VACANT LOT.CANNOT INCREASE THE
 NONCONFORMITY BY ADDING 2ND STORY.CONSTRUCTION OF
 PRIMARY STRUCTURE MUST BE COMMENCED BEFORE PERMITTING
 WILL BE ALLOWED FOR ACCESSORY STRUCTURE.EITHER PERMIT
 SEPARATELY AFTER COMMENCEMENT OR INCLUDE IN SCOPE OF
 WORK FOR THE PRINCIPAL BUILDING.***
  
 NOTE:FOLLOWING COMMENTS ARE FYI ONLY.
  
 2)PROVIDE A RECORDED UNITY OF TITLE FOR LOTS 3/4 AND
 5/6.
  
 3)PROVIDE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.
  
 4)INDICATE ELEVATION DIMENSIONS FROM GRADE.
  
 5)ACCESSORY STRUCTURE EXCEEDS PERMITTED SQUARE
 FOOTAGE.SQUARE FOOTAGE IS CALCULATED AS GROSS SQUARE
 FOOTAGE.PROPOSED STRUCTURE IS 1040 SQ.FT. EXCEEDING
 THE 1000 SQ.FT. MAXIMUM.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720