Plan Review Details - Permit 07080307
Plan Review Stops For Permit 07080307
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-10-09 Cont ID  
Sent By mperson Date 2008-10-09 Time 14:14 Rev Time 1.00
Received By mperson Date 2008-10-09 Time 14:14 Sent To PC
Notes
2008-10-09 14:18:22GAS REVISION #13, SHEETS 06 AND 08: "OK" CHANGE DRYER
 AND BBQ TO "FUTURE". *MRPERSON.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-10-04 Cont ID  
Sent By mperson Date 2007-10-04 Time 08:12 Rev Time 0.00
Received By mperson Date 2007-10-04 Time 08:12 Sent To PC
Notes
2007-10-04 08:25:20****************PROVISO****************
 A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 B} NOTE: THE FOLLOWING SHEETS ARE APPROVED FOR THE
 YELLOW HIGHLIGHTED GAS PIPING ONLY.1ST FLOOR PLAN SHEET
 06: 2ND FLOOR PLAN SHEET 07:3RD FLOOR PLAN SHEET 08:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-08-16 Cont ID  
Sent By mperson Date 2007-08-16 Time 16:31 Rev Time 0.45
Received By mperson Date 2007-08-16 Time 16:04 Sent To PC
Notes
2007-08-16 16:27:48DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE CORRELATE THE GAS ISOMETRIC WITH THE FLOOR
 PLAN PER FBC-2004 CHAPTER 1 SECTION 106.1.1. THE GAS
 ISOMETRIC DOES NOT REFLECT THE FLOOR PLAN IN THE
 FOLLOWING AREAS. PLEASE SEE THE RED LINE CORRECTIONS
 MADE BY THIS PLAN REVIEWER REFLECTING THIS.
  
 A} SHEET 06: DRYER IS LOCATED IN THE WRONG PLACE ON
 THE ISOMETRIC.
  
 B} SHEET 06: THE GAS PIPE DROP TO THE COOK TOP IS
 MISSING FROM THE FLOOR PLAN DRAWING.
  
 2. PLEASE CLEARLY INDICATE THE GAS TYPE ON SHEET 06 AS
 BEING NATURALGAS ON THE RESUBMITTAL.
  
 3. PLEASE SUBMIT MANUFACTURER SPECIFICATIONS ON THE MP
 REGULATORS BEING USED WITH THE FOLLOWING INFORMATION.
  
 A} MAKE.
  
 B} MODEL NUMBER.
  
 C} LOAD CAPACITY.
  
 D} A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 AGENCY.
  
 4. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. PLEASE CLEARLY
 INDICATE THESE SHUT OFF VALVES ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-07 Cont ID  
Sent By adarroug Date 2008-10-07 Time 15:14 Rev Time 0.00
Received By adarroug Date 2008-10-07 Time 15:14 Sent To G
Notes
2008-10-07 15:14:36TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-19 Cont ID  
Sent By adarroug Date 2007-09-19 Time 16:36 Rev Time 0.00
Received By adarroug Date 2007-09-19 Time 16:36 Sent To G
Notes
2007-09-19 16:36:58TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-16 Cont ID  
Sent By mperson Date 2007-08-16 Time 16:30 Rev Time 0.00
Received By mperson Date 2007-08-10 Time 08:19 Sent To G
Notes
2007-08-10 08:20:03TO GAS INBOX