Plan Review Details - Permit 07080262
Plan Review Stops For Permit 07080262
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-29 Cont ID  
Sent By mjacobs Date 2008-02-29 Time 10:45 Rev Time 0.00
Received By mjacobs Date 2008-02-29 Time 09:39 Sent To  
Notes
2008-02-29 10:44:53PROVISOR: THE ROOFING CONTRACTOR WAS NOT RREGISTERED AT
 THE TIME OF APPLICATION THEREFORE, THE SIGNATURE WAS
 STRUCT FROM THE APPLICATION. A SEPERATE PERMIT IS
 REQUIRED FOR THE ROOFING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-20 Cont ID  
Sent By jwitmer Date 2007-11-20 Time 09:54 Rev Time 1.33
Received By jwitmer Date 2007-11-20 Time 09:32 Sent To  
Notes
2007-11-20 09:43:40BEAR LAKES COUNTRY CLUB 1901 VILLAGE BLVD
 SEPT 16,2007
  
 BUILDING PLAN REVIEW
 PERMIT: 07080262
 ADD: 1901 VILLAGE BLVD
 CONT: GSP & ASSOC
 TEL: (561)697-8444
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1-4 COMPLIED.
  
 5) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A)C) TRUSS ANCHORS & STRAPS SIMPSON NO FLORIDA
 APPROVAL PROVIDED.
 B) ROOFING ASSEMBLIES:
 POLY FOAM - NO FLORIDA APPROVAL, A MIAM-DADE
 REPORT WAS SUBMITTED, WHERE AS A ERD REPORT WAS
 SUBMITTED TO THE STATE.
 ROOF TILE-MONIER ROOF TILE SUBMITTED, THE
 DESIGN PROFESSIONAL INDICATES ON PLANS HANSON ROOF TILE
 TO BE INSTALLED, ALSO PROVIDE FLORIDA APPROVAL.
  
 6)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 7) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 8) BUILDING PROVISO:THE BEAM ON THE PAVILLION IS
 ASSUMED TO RUN CONTINIOUS ACROSS THE FRONT OF THE
 STRUCTURE. 102.1* WHERE, IN ANY SPECIFIC CASE,
 DIFFERENT SECTIONS OF THIS CODE SPECIFY DIFFERENT
 MATERIALS, METHODS OF CONSTRUCTION OR OTHER
 REQUIREMENTS, THE MOST RESTRICTIVE SHALL GOVERN. WHERE
 THERE IS A CONFLICT BETWEEN A GENERAL REQUIREMENT AND A
 SPECIFIC REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-16 Cont ID  
Sent By jwitmer Date 2007-09-16 Time 20:18 Rev Time 0.77
Received By jwitmer Date 2007-09-16 Time 20:18 Sent To  
Notes
2007-09-16 20:31:21BEAR LAKES COUNTRY CLUB 1901 VILLAGE BLVD
 SEPT 16,2007
  
 BUILDING PLAN REVIEW
 PERMIT: 07080262
 ADD: 1901 VILLAGE BLVD
 CONT: GSP & ASSOC
 TEL: (561)697-8444
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)PROVIDE FLOOD ZONE ELEVATION CERTIFICATE FOR NEW
 CONSTRUCTION WITH BASE FLOOD ELEVATION, CITY CODE
 REQUIRES AN ADDITIONAL 6". THIS IS A LOMR REQUIRING A
 FINISH FLOOR HEIGHT OF 16'-6".
  
 3) THERE IS ONLY ONE SET OF PLANS, (2) SETS OF ALL
 PLANS, PRODUCT APPROVAL, SUBMITTALS AND OR REPORTS WILL
 BE REQUIRED FOR PERMIT ISSUANCE. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 .
  
  
  
 5) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A)C) TRUSS ANCHORS & STRAPS
 B) ROOFING ASSEMBLIES:
 UNDERLAYMENT
 ROOF TILE-HIGHLIGHT WHICH TYPE OF FOAM PATTY
 SIZE TO BE USED!
  
 6)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 7) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 8) THIS STRUCTURE APPEARS TO HAVE A BEAM IN THE FRONT
 PORTION OF THE STRUCTURE WHERE THE TRUSS ENDS LAND BUT
 THE PLAN FAILS TO IDENTIFY THE BEAM?
  
 9) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 10)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMITSET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-03-04 Cont ID  
Sent By dpalmer Date 2008-03-04 Time 08:02 Rev Time 0.00
Received By dpalmer Date 2008-03-04 Time 08:02 Sent To  
Notes
2008-03-04 08:03:49REDLINED LOCATION OF REQUIRED DISCONNECT ON PLANS AS
 THE DETACHED STRUCTURE DID NOT SHOW NEW DISCONNECT.
 225.31-225.39
 REDLINED NEC 2005

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-21 Cont ID  
Sent By dpalmer Date 2007-11-21 Time 13:59 Rev Time 0.00
Received By dpalmer Date 2007-11-21 Time 13:59 Sent To  
Notes
2007-11-21 14:00:34** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW.
  
 1) NOTE: PLEASE COMPLETE CIRCUITING. PLANS NOW SHOW TWO
 CIRCUITS GOING TO SHED/BUILDING.
 FBC 106.1.2,
  
 2) NOTE: PLEASE SHOW THE LOCATION OF THE DISCONNECT AS
 REQUIRED PER 225.31-225.39
  
 3) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM
 PER 250.50, 250.32
  
 4) NOTE: PLEASE LIST RELEVANT CODE. NFPA-70 2005
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-08 Cont ID  
Sent By dpalmer Date 2007-09-08 Time 18:03 Rev Time 0.00
Received By dpalmer Date 2007-09-08 Time 18:01 Sent To  
Notes
2007-09-08 18:03:25** DENIED **
  
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
  
 2) NOTE: PLEASE INCLUDE CIRCUITING INFORMATION ON HOW
 AND WHERE THE POWER IS COMING FROM. (CONDUCTOR(S),
 GROUNDING, OVER CURRENT PROTECTION ETC.
 408.4, 310.16, 240.4
  
 3) NOTE: PLEASE SEE INCLUDE DISCONNECTING MEANS PER
 225.31-225.39. PLEASE KNOW DEPENDING ON CIRCUITING THIS
 MAY CHANGE.
  
 4) NOTE: PLEASE SEE 250.32 FOR GROUNDING AT THE
 DETACHED BUILDING REQUIRED. THIS MAY ALSO DEPEND ON THE
 CIRCUIT(S) BROUGHT TO BUILDING.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-03-04 Cont ID  
Sent By mawillia Date 2008-03-04 Time 11:08 Rev Time 0.00
Received By mawillia Date 2008-03-04 Time 10:25 Sent To  
Notes
2008-03-04 10:38:49*****PROVISO******
  
 (PLAN SHEET D-1 STAMPED, INITIALED, AND DATED WITH
 THE FOLLOWING PROVISIONS)
  
 * THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING ROADS, FIRE LANES).
  
 * STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
  
  
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By mawillia Date 2007-12-03 Time 16:09 Rev Time 0.00
Received By mawillia Date 2007-12-03 Time 15:58 Sent To  
Notes
2007-12-03 16:09:35*****UNSAT******
  
 PLEASE ACKNOWLEDGE THE FOLLOWING COMMENTS (TAKEN FROM
 THE PREVIOUS FIRE REVIEW) ON THE PLAN:
  
 1.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.NOTE:THE
 JOB SITE IS IN THE JURIDICTION OF WEST PALM BEACH.
 ALSO, THE PLANS ARE TO BE SUBMITTED WITH NO INK,
 PENCIL, OR OTHER HAND-DRAWN MARKINGS.
  
 2.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING ROADS, FIRE LANES).
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-03 Cont ID  
Sent By mawillia Date 2007-10-03 Time 17:27 Rev Time 0.00
Received By mawillia Date 2007-10-03 Time 17:18 Sent To  
Notes
2007-10-03 17:24:57*****UNSAT******
  
  
 1.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING ROADS, FIRE LANES).
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 14:28 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 14:28 Sent To  
Notes
2008-02-19 14:32:36TO "COMM" BD#18

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 14:21 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 14:21 Sent To  
Notes
2007-11-16 10:24:55TO "COMM" BD#50
2007-11-06 14:21:49WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-03 Cont ID  
Sent By mawillia Date 2007-10-03 Time 17:18 Rev Time 0.00
Received By mawillia Date 2007-08-08 Time 18:48 Sent To  
Notes
2007-09-07 15:56:31TO "COMM" BD#22
2007-08-08 18:48:34WAITING FOR COMMERCIAL BOARD

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-12-11 Cont ID  
Sent By kstevens Date 2007-12-11 Time 15:11 Rev Time 0.00
Received By kstevens Date 2007-12-11 Time 15:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-02-21 Cont ID  
Sent By bpowell Date 2008-02-21 Time 16:30 Rev Time 0.00
Received By bpowell Date 2008-02-21 Time 16:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-11-30 Cont ID  
Sent By bpowell Date 2007-11-30 Time 18:24 Rev Time 0.00
Received By bpowell Date 2007-11-30 Time 18:24 Sent To  
Notes
2007-11-30 18:25:171.A MINOR AMENDMENT WILL BE REQUIRED IF THE SHELTER
 IS DIFFERENT FROM WHAT IS SHOWN ON THE ORIGINAL
 APPROVED SITE PLAN.HOWEVER, IF THE RECONSTRUCTION OF
 THE SHELTER IS THE SAMETHEN THE AMENDMENT WILL NOT BE
 NECESSARY.
  
 FOR QUESTIONS OR COMMENTS CONTACT:BOBBY POWELL JR.,
 PLANNER, [email protected], (561) 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By bpowell Date 2007-09-17 Time 10:27 Rev Time 0.00
Received By bpowell Date 2007-09-17 Time 10:25 Sent To  
Notes
2007-09-17 10:39:111.A SURVEY OF THE PROPERTY, SHOWING THE LOCATION AND
 DIMENSIONS OF THE EXISTING SHELTER, NEEDS TO BE
 PROVIDED.
  
 2.A MINOR AMENDMENT WILL BE REQUIRED IF THE SHELTER
 IS DIFFERENT FROM WHAT IS SHOWN ON THE ORIGINAL
 APPROVED SITE PLAN.HOWEVER, IF THE RECONSTRUCTION OF
 THE SHELTER IS THE SAMETHEN THE AMENDMENT WILL NOT BE
 NECESSARY.
  
 FOR QUESTIONS OR COMMENTS CONTACT:BOBBY POWELL JR.,
 PLANNER, [email protected], (561) 822-1435