| Plan Review Stops For Permit 07080262 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-02-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-02-29 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-02-29 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2008-02-29 10:44:53 | PROVISOR: THE ROOFING CONTRACTOR WAS NOT RREGISTERED AT | | | THE TIME OF APPLICATION THEREFORE, THE SIGNATURE WAS | | | STRUCT FROM THE APPLICATION. A SEPERATE PERMIT IS | | | REQUIRED FOR THE ROOFING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-11-20 |
Time |
09:54 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2007-11-20 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2007-11-20 09:43:40 | BEAR LAKES COUNTRY CLUB 1901 VILLAGE BLVD | | | SEPT 16,2007 | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07080262 | | | ADD: 1901 VILLAGE BLVD | | | CONT: GSP & ASSOC | | | TEL: (561)697-8444 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1-4 COMPLIED. | | | | | | 5) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) | | | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A)C) TRUSS ANCHORS & STRAPS SIMPSON NO FLORIDA | | | APPROVAL PROVIDED. | | | B) ROOFING ASSEMBLIES: | | | POLY FOAM - NO FLORIDA APPROVAL, A MIAM-DADE | | | REPORT WAS SUBMITTED, WHERE AS A ERD REPORT WAS | | | SUBMITTED TO THE STATE. | | | ROOF TILE-MONIER ROOF TILE SUBMITTED, THE | | | DESIGN PROFESSIONAL INDICATES ON PLANS HANSON ROOF TILE | | | TO BE INSTALLED, ALSO PROVIDE FLORIDA APPROVAL. | | | | | | 6)PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR | | | SITE SPECIFIC FORM PER RULE 9B-72. | | | | | | 7) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | 8) BUILDING PROVISO:THE BEAM ON THE PAVILLION IS | | | ASSUMED TO RUN CONTINIOUS ACROSS THE FRONT OF THE | | | STRUCTURE. 102.1* WHERE, IN ANY SPECIFIC CASE, | | | DIFFERENT SECTIONS OF THIS CODE SPECIFY DIFFERENT | | | MATERIALS, METHODS OF CONSTRUCTION OR OTHER | | | REQUIREMENTS, THE MOST RESTRICTIVE SHALL GOVERN. WHERE | | | THERE IS A CONFLICT BETWEEN A GENERAL REQUIREMENT AND A | | | SPECIFIC REQUIREMENT, THE SPECIFIC | | | REQUIREMENT SHALL BE APPLICABLE. | | | | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-09-16 |
Time |
20:18 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-09-16 |
Time |
20:18 |
Sent To |
|
|
| Notes |
| 2007-09-16 20:31:21 | BEAR LAKES COUNTRY CLUB 1901 VILLAGE BLVD | | | SEPT 16,2007 | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07080262 | | | ADD: 1901 VILLAGE BLVD | | | CONT: GSP & ASSOC | | | TEL: (561)697-8444 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)PROVIDE FLOOD ZONE ELEVATION CERTIFICATE FOR NEW | | | CONSTRUCTION WITH BASE FLOOD ELEVATION, CITY CODE | | | REQUIRES AN ADDITIONAL 6". THIS IS A LOMR REQUIRING A | | | FINISH FLOOR HEIGHT OF 16'-6". | | | | | | 3) THERE IS ONLY ONE SET OF PLANS, (2) SETS OF ALL | | | PLANS, PRODUCT APPROVAL, SUBMITTALS AND OR REPORTS WILL | | | BE REQUIRED FOR PERMIT ISSUANCE. 106.1.2 ADDITIONAL | | | INFORMATION REQUIRED. | | | | | | 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE | | | OF OCCUPANCY: | | | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT | | | IS DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F) | | | WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | | BUILDING PERMIT | | | . | | | | | | | | | | | | 5) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) | | | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A)C) TRUSS ANCHORS & STRAPS | | | B) ROOFING ASSEMBLIES: | | | UNDERLAYMENT | | | ROOF TILE-HIGHLIGHT WHICH TYPE OF FOAM PATTY | | | SIZE TO BE USED! | | | | | | 6)PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR | | | SITE SPECIFIC FORM PER RULE 9B-72. | | | | | | 7) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | 8) THIS STRUCTURE APPEARS TO HAVE A BEAM IN THE FRONT | | | PORTION OF THE STRUCTURE WHERE THE TRUSS ENDS LAND BUT | | | THE PLAN FAILS TO IDENTIFY THE BEAM? | | | | | | 9) 2004 FL. BLD CODE 1603.1.4 THE | | | FOLLOWING INFORMATION RELATED TO WIND | | | SHALL BE SHOWN ON THE CONSTRUCTION | | | DRAWINGS, | | | 1)- BASIC WIND SPEED, MPH | | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | | CATEGORY | | | 3)- WIND EXPOSURE | | | 4)- INTERNAL PRESSURE COEFFICIENT, | | | 5)- COMPONENTS & CLADDING, THE DESIGN | | | WIND PRESSURES IN TERMS OF PSF. | | | 10)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMITSET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC | | | REQUIREMENT SHALL BE APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-03-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-04 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-04 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2008-03-04 08:03:49 | REDLINED LOCATION OF REQUIRED DISCONNECT ON PLANS AS | | | THE DETACHED STRUCTURE DID NOT SHOW NEW DISCONNECT. | | | 225.31-225.39 | | | REDLINED NEC 2005 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-11-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-11-21 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-11-21 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2007-11-21 14:00:34 | ** DENIED 2ND REVIEW ** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW. | | | | | | 1) NOTE: PLEASE COMPLETE CIRCUITING. PLANS NOW SHOW TWO | | | CIRCUITS GOING TO SHED/BUILDING. | | | FBC 106.1.2, | | | | | | 2) NOTE: PLEASE SHOW THE LOCATION OF THE DISCONNECT AS | | | REQUIRED PER 225.31-225.39 | | | | | | 3) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM | | | PER 250.50, 250.32 | | | | | | 4) NOTE: PLEASE LIST RELEVANT CODE. NFPA-70 2005 | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-09-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-08 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-08 |
Time |
18:01 |
Sent To |
|
|
| Notes |
| 2007-09-08 18:03:25 | ** DENIED ** | | | | | | | | | | | | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | | | | 2) NOTE: PLEASE INCLUDE CIRCUITING INFORMATION ON HOW | | | AND WHERE THE POWER IS COMING FROM. (CONDUCTOR(S), | | | GROUNDING, OVER CURRENT PROTECTION ETC. | | | 408.4, 310.16, 240.4 | | | | | | 3) NOTE: PLEASE SEE INCLUDE DISCONNECTING MEANS PER | | | 225.31-225.39. PLEASE KNOW DEPENDING ON CIRCUITING THIS | | | MAY CHANGE. | | | | | | 4) NOTE: PLEASE SEE 250.32 FOR GROUNDING AT THE | | | DETACHED BUILDING REQUIRED. THIS MAY ALSO DEPEND ON THE | | | CIRCUIT(S) BROUGHT TO BUILDING. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-03-04 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-04 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-03-04 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2008-03-04 10:38:49 | *****PROVISO****** | | | | | | (PLAN SHEET D-1 STAMPED, INITIALED, AND DATED WITH | | | THE FOLLOWING PROVISIONS) | | | | | | * THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR | | | VICINITY THEREOF (INCLUDING ROADS, FIRE LANES). | | | | | | * STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | | | | | | | | | | | | | CAPT. MICHEAL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-03 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-03 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2007-12-03 16:09:35 | *****UNSAT****** | | | | | | PLEASE ACKNOWLEDGE THE FOLLOWING COMMENTS (TAKEN FROM | | | THE PREVIOUS FIRE REVIEW) ON THE PLAN: | | | | | | 1.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.NOTE:THE | | | JOB SITE IS IN THE JURIDICTION OF WEST PALM BEACH. | | | ALSO, THE PLANS ARE TO BE SUBMITTED WITH NO INK, | | | PENCIL, OR OTHER HAND-DRAWN MARKINGS. | | | | | | 2.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR | | | VICINITY THEREOF (INCLUDING ROADS, FIRE LANES). | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHEAL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-03 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-03 |
Time |
17:18 |
Sent To |
|
|
| Notes |
| 2007-10-03 17:24:57 | *****UNSAT****** | | | | | | | | | 1.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 2.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR | | | VICINITY THEREOF (INCLUDING ROADS, FIRE LANES). | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHEAL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-19 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-19 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2008-02-19 14:32:36 | TO "COMM" BD#18 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-11-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-06 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-06 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2007-11-16 10:24:55 | TO "COMM" BD#50 | | 2007-11-06 14:21:49 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-03 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-08 |
Time |
18:48 |
Sent To |
|
|
| Notes |
| 2007-09-07 15:56:31 | TO "COMM" BD#22 | | 2007-08-08 18:48:34 | WAITING FOR COMMERCIAL BOARD |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2007-12-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-11 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-11 |
Time |
15:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-02-21 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2008-02-21 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2008-02-21 |
Time |
16:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2007-11-30 |
Time |
18:24 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2007-11-30 |
Time |
18:24 |
Sent To |
|
|
| Notes |
| 2007-11-30 18:25:17 | 1.A MINOR AMENDMENT WILL BE REQUIRED IF THE SHELTER | | | IS DIFFERENT FROM WHAT IS SHOWN ON THE ORIGINAL | | | APPROVED SITE PLAN.HOWEVER, IF THE RECONSTRUCTION OF | | | THE SHELTER IS THE SAMETHEN THE AMENDMENT WILL NOT BE | | | NECESSARY. | | | | | | FOR QUESTIONS OR COMMENTS CONTACT:BOBBY POWELL JR., | | | PLANNER, [email protected], (561) 822-1435 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-17 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2007-09-17 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2007-09-17 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2007-09-17 10:39:11 | 1.A SURVEY OF THE PROPERTY, SHOWING THE LOCATION AND | | | DIMENSIONS OF THE EXISTING SHELTER, NEEDS TO BE | | | PROVIDED. | | | | | | 2.A MINOR AMENDMENT WILL BE REQUIRED IF THE SHELTER | | | IS DIFFERENT FROM WHAT IS SHOWN ON THE ORIGINAL | | | APPROVED SITE PLAN.HOWEVER, IF THE RECONSTRUCTION OF | | | THE SHELTER IS THE SAMETHEN THE AMENDMENT WILL NOT BE | | | NECESSARY. | | | | | | FOR QUESTIONS OR COMMENTS CONTACT:BOBBY POWELL JR., | | | PLANNER, [email protected], (561) 822-1435 |
|
|