| Plan Review Stops For Permit 07080261 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-08-11 |
Time |
16:19 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2008-08-11 |
Time |
16:19 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-07-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-07-09 |
Time |
15:08 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2008-07-09 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2008-07-09 15:19:44 | BEAR LAKES COUNTRY CLUB 1901 VILLAGE BLVD | | | BUILDING PLAN REVIEW | | | PERMIT: 07080261 | | | ADD: 1901 VILLAGE BLVD | | | CONT: GSP & ASSOC | | | TEL: (561)697-8444 | | | DATE: NOV 20,2007 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2) PROVISO:PROVIDE FLOOD ZONE ELEVATION CERTIFICATE | | | FOR NEW CONSTRUTION WITH BASE FLOOD ELEVATION, CITY | | | CODE REQUIRES AN ADDITIONAL 6". THIS IS A LOMR | | | REQUIRING A FINISH FLOOR HEIGTH OF 16'-6". | | | | | | 3-5) COMPLIED. | | | | | | | | | 6-11) COMPLIED | | | | | | 12)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY | | | OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE INFORMATION. | | | | | | 13) NEW COMMENT, THIS SUBMITTAL IS MISSING THE PERMIT | | | APPLICATION, IF LOST ON NEXT REVIEW PLEASE FILL OUT A | | | DUPLICATE AND MARK AS SUCH, THANK YOU. | | | | | | 14) COMPLIED. | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-11-20 |
Time |
07:53 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2007-11-20 |
Time |
07:53 |
Sent To |
|
|
| Notes |
| 2007-11-20 08:26:36 | BEAR LAKES COUNTRY CLUB 1901 VILLAGE BLVDBUILDING | | | PLAN REVIEW | | | PERMIT: 07080261 | | | ADD: 1901 VILLAGE BLVD | | | CONT: GSP & ASSOC | | | TEL: (561)697-8444 | | | DATE: NOV 20,2007 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2) PROVISO:PROVIDE FLOOD ZONE ELEVATION CERTIFICATE | | | FOR NEW CONSTRUTION WITH BASE FLOOD ELEVATION, CITY | | | CODE REQUIRES AN ADDITIONAL 6". THIS IS A LOMR | | | REQUIRING A FINISH FLOOR HEIGTH OF 16'-6". | | | | | | 3-5) COMPLIED. | | | | | | 6) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT | | | INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS | | | ARE AS FOLLOWS: | | | A) WINDOWS- NO REPORTS WERE SUBMITTED | | | B) DOORS- NO REPORTS SUBMITTED, THE FLORIDA PRODUCT | | | APPROVAL WEBSITE HAS 20 DIFFERENT MODELS TO SELECT | | | FROM. | | | C) TRUSS ANCHORS & STRAPS- NO FLORIDA COVERSHEET WAS | | | SUBMITTED | | | D) ROOFING ASSEMBLIES: | | | MONIER ROOF TILE-NO FLORIDA COVERSHEET | | | WAS SUBMITTED 4 REPORTS UNDER THE FLORIDA APPROVAL | | | | | | POLYFOAM- NO FLORIDA COVER SHEET PLUS | | | PRODUCT APPROVAL WAS NOT HIGHLIGHTED AS TO WHAT SIZE | | | PATTY WILL BE USED FOR RESISTANCE TO UPLIFT. | | | 7)2ND REQUEST,PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED | | | TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR | | | SITE SPECIFIC FORM PER RULE 9B-72. | | | | | | 8) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA | | | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY | | | THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. THE DESIGNER OF RECORD LIST | | | CERTAIN PRODUCTS BUT DOES NOT PROVIDE A FLORIDA | | | APPROVAL OR MIAMI-DADE NOA NUMBER TO | | | IDENTIFY WHICH PRODUCTS ARE TO BE USED, PLUS THE | | | DESIGNER OF RECORD HAS A SIGNTURE AND DATE LINE TO BE | | | COMPLETED. | | | | | | 9)2ND REQUEST, THIS STRUCTURE USED TO BE A TRASH | | | ENCLOSURE WITH A CONCRETE SLAB,HOW ARE YOU GOING TO | | | TERMITE TREAT THE SLAB AND PROVIDE A VAPOR BARRIER? | | | | | | 10)2ND REQUEST,PLANS FAIL TO INDICATE ATTIC | | | VENTILATION: 1203.2 ATTIC SPACES.50 PERCENT OF THE | | | REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS | | | LOCATED IN THE UPPER PORTION OF THE SPACE TO BE | | | VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR | | | CORNICE VENTS WITH THE BALANCE OF THE REQUIRED | | | VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. | | | | | | 11) COMPLIED. | | | | | | 12)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY | | | OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE INFORMATION. | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC | | | REQUIREMENT SHALL BE APPLICABLE. | | | | | | | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-09-16 |
Time |
19:29 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-09-16 |
Time |
19:29 |
Sent To |
|
|
| Notes |
| 2007-09-16 20:17:51 | BEAR LAKES COUNTRY CLUB 1901 VILLAGE BLVDBUILDING | | | PLAN REVIEW | | | PERMIT: 07080261 | | | ADD: 1901 VILLAGE BLVD | | | CONT: GSP & ASSOC | | | TEL: (561)697-8444 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)PROVIDE FLOOD ZONE ELEVATION CERTIFICATE FOR NEW | | | CONSTRUTION WITH BASE FLOOD ELEVATION, CITY CODE | | | REQUIRES AN ADDITIONAL 6". THIS IS A LOMR REQUIRING A | | | FINISH FLOOR HEIGTH OF 16'-6". | | | | | | 3) THERE IS ONLY ONE SET OF PLANS, (2) SETS OF ALL | | | PLANS, PRODUCT APPROVAL, SUBMITTALS AND OR REPORTS WILL | | | BE REQUIRED FOR PERMIT ISSUANCE. 106.1.2 ADDITIONAL | | | INFORMATION REQUIRED. | | | | | | 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE | | | OF OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | | DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F) | | | WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | | BUILDING PERMIT | | | . | | | 5)PLANS INDICATE PLYWOOD SUBSHEATHING TO BE WITHIN 6" | | | OF GRADE, ALSO 2X4 STUDS. | | | 2304.11.2.2 FRAMING. | | | WOOD FRAMING MEMBERS, INCLUDING WOOD SHEATHING, WHICH | | | REST ON EXTERIOR FOUNDATION WALLS AND ARE LESS THAN 8 | | | INCHES (203 MM) FROM EXPOSED EARTH SHALL BE OF | | | NATURALLY DURABLE OR PRESERVATIVE-TREATED WOOD. WOOD | | | FRAMING MEMBERS AND FURRING STRIPS ATTACHED DIRECTLY TO | | | MASONRY OR CONCRETE WALLS SHALL BE OF APPROVED | | | NATURALLY DURABLE OR PRESERVATIVE-TREATED WOOD. | | | | | | 2304.11.2.3 SLEEPERS AND SILLS. | | | SLEEPERS AND SILLS ON A CONCRETE OR MASONRY SLAB THAT | | | IS IN DIRECT CONTACT WITH EARTH SHALL BE OF NATURALLY | | | DURABLE OR PRESERVATIVE-TREATED WOOD. | | | | | | 2304.11.2.5 WOOD SIDING. | | | CLEARANCE BETWEEN WOOD SIDING AND EARTH ON THE EXTERIOR | | | OF A BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM) | | | EXCEPT WHERE SIDING, SHEATHING AND WALL FRAMING ARE OF | | | NATURALLY DURABLE OR PRESERVATIVE-TREATED WOOD. | | | | | | 6) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) | | | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) WINDOWS | | | B) DOORS | | | C) TRUSS ANCHORS & STRAPS | | | D) HARDIE PLANK | | | E) ROOFING ASSEMBLIES: | | | UNDERLAYMENT | | | ROOF TILE | | | | | | 7)PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR | | | SITE SPECIFIC FORM PER RULE 9B-72. | | | | | | 8) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | 9) THIS STRUCTURE USED TO BE A TRASH ENCLOSURE WITH A | | | CONCRETE SLAB,HOW ARE YOU GOING TO TERMITE TREAT THE | | | SLAB AND PROVIDE A VAPOR BARRIER? | | | | | | 10)PLANSFAIL TO INDICATE ATTIC VENTILATION: 1203.2 | | | ATTIC SPACES. ENCLOSED ATTICS AND ENCLOSED RAFTER | | | SPACES FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO | | | THE UNDERSIDE OF ROOF FRAMING MEMBERS SHALL HAVE CROSS | | | VENTILATION FOR EACH SEPARATE SPACE BY VENTILATING | | | OPENINGS PROTECTED AGAINST THE ENTRANCE OF RAIN. | | | BLOCKING AND BRIDGING SHALL BE ARRANGED SO AS NOT TO | | | INTERFERE WITH THE MOVEMENT OF AIR. A MINIMUM OF 1 INCH | | | (25 MM) OF AIRSPACE SHALL BE PROVIDED BETWEEN THE | | | INSULATION AND THE ROOF SHEATHING. THE NET FREE | | | VENTILATING AREA SHALL NOT BE LESS THAN 1 / 150 OF THE | | | AREA OF THE SPACE VENTILATED, WITH 50 PERCENT OF THE | | | REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS | | | LOCATED IN THE UPPER PORTION OF THE SPACE TO BE | | | VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR | | | CORNICE VENTS WITH THE BALANCE OF THE REQUIRED | | | VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. | | | | | | 11) 1209.2 ATTIC SPACES. AN OPENING NOT LESS THAN 20 | | | INCHES BY 30 INCHES (559 MM BY 762 MM) SHALL BE | | | PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF | | | OVER 30 INCHES (762 MM). A 30-INCH (762 MM) MINIMUM | | | CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT | | | OR ABOVE THE ACCESS OPENING. | | | | | | 12)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY | | | OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE INFORMATION. | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC | | | REQUIREMENT SHALL BE APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-08-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-08-07 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-08-07 |
Time |
09:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-07-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-07-18 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-07-18 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2008-07-18 08:26:41 | ** DENIED ** | | | | | | 1) NOTE: PERMIT APPLICATION IS MISSING FROM PACKAGE. | | | NEEDS NEW OR PLEASE SUBMIT ORIGINAL. | | | | | | 2) NOTE: PLEASE SHOW THE LOCATION OF THE REQUIRED | | | DISCONNECT AT THE DETACHED BUILDING/STRUCTURE. THE | | | PREVIOUS REVIEW REQUESTED TO *SHOW* THE LOCATION TO | | | COMPLY WITH 225.31-225.39. | | | 110.26 ETC | | | | | | 3) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO | | | COMPLETION OF THE GROUNDING ELECTRODE SYSTEM PER | | | 250.50, 250.32, 250.66. THE PLANS ONLY NOTE GROUND | | | RODS. NO CONDUCTOR ETC.? | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-11-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-11-21 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-11-21 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2007-11-21 13:57:07 | ** DENIED 2ND REVIEW ** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW. | | | | | | 1) NOTE: PLEASE COMPLETE CIRCUITING. | | | FBC 106.1.2, | | | | | | 2) NOTE: PLEASE SHOW THE LOCATION OF THE DISCONNECT AS | | | REQUIRED PER 225.31-225.39 | | | | | | 3) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM | | | PER 250.50, 250.32 | | | | | | 4) NOTE: PLEASE LIST RELEVANT CODE. NFPA-70 2005 | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-09-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-08 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-08 |
Time |
17:28 |
Sent To |
|
|
| Notes |
| 2007-09-08 17:52:29 | ** DENIED ** | | | | | | | | | | | | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | | | | 2) NOTE: PLEASE INCLUDE CIRCUITING INFORMATION ON HOW | | | AND WHERE THE POWER IS COMING FROM. (CONDUCTOR(S), | | | GROUNDING, OVER CURRENT PROTECTION ETC. | | | 408.4, 310.16, 240.4 | | | | | | 3) NOTE: PLEASE SEE INCLUDE DISCONNECTING MEANS PER | | | 225.31-225.39. PLEASE KNOW DEPENDING ON CIRCUITING THIS | | | MAY CHANGE. | | | | | | 4) NOTE: PLEASE SEE 250.32 FOR GROUNDING AT THE | | | DETACHED BUILDING REQUIRED. THIS MAY ALSO DEPEND ON THE | | | CIRCUIT(S) BROUGHT TO BUILDING. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-08-11 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-08-11 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2008-08-11 14:44:51 | *****APPROVED****** | | | | | | PLAN SHEET 1 (OF 2) WAS STAMPED, INITIALED, AND DATED. | | | | | | | | | CAPT. MICHEAL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2008-07-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-07-22 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-07-22 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2008-07-22 14:16:36 | *****UNSAT****** | | | | | | THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN | | | THE BELOW COMMENT AS WELL AS THE OTHER REVIEWERS | | | COMMENTS HAVE BEEN SATISFIED.ALL OTHER PREVIOUS FIRE | | | PLAN REVIEW COMMENTS HAVE BEEN ADDRESSED. | | | | | | 1.THE JOB SITE IS IN THE JURISDICTION OF WEST PALM | | | BEACH, NOT PALM BEACH COUNTY (AS INDICATED IN THE TITLE | | | BLOCK OF PLAN SHEET 1 AND 2) . | | | | | | | | | | | | CAPT. MICHEAL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-03 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-03 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2007-12-03 14:12:05 | *****DENIED****** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL TO BE ADDRESSED: | | | | | | 1.THE COMPLETE ADDRESS OF THE PROJECT SITE SHALL BE | | | IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.THE | | | JOB SITE IS IN THE JURISDICTION OF WEST PALM BEACH. | | | ALSO, THE PLANS ARE TO BE PRESENTED WITH NO INK, | | | PENCIL, OR HAND-DRAWN MARKINGS. | | | | | | 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR | | | VICINITY THEREOF (INCLUDING ROADS, FIRE LANES). | | | | | | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 6.SPECIFY THE INTERIOR WALL AND CEILING FINISH | | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 7.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHEAL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-03 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-03 |
Time |
17:30 |
Sent To |
|
|
| Notes |
| 2007-10-03 18:03:18 | *****DENIED****** | | | | | | | | | 1.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR | | | VICINITY THEREOF (INCLUDING ROADS, FIRE LANES). | | | | | | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 5.DECLARE THE CONTENTS OF THIS STORAGE OCCUPANCY BY | | | CLASSIFYING AS LOW HAZARD, ORDINARY HAZARD, OR HIGH | | | HAZARD. | | | | | | 6.SPECIFY THE INTERIOR WALL AND CEILING FINISH | | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 7.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHEAL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-07-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-31 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-31 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2008-07-31 11:14:11 | TO "COMM" BD#42 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-06-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-23 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-23 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2008-06-23 11:11:58 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-11-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-06 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-06 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2007-11-16 10:25:11 | TO "COMM" BD#50 | | 2007-11-06 14:27:02 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-03 |
Time |
17:32 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-08 |
Time |
08:06 |
Sent To |
|
|
| Notes |
| 2007-09-05 10:59:54 | TO "COMM" BD#22 | | 2007-08-08 18:47:51 | WAITING FOR COMMERCIAL BOARD |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2008-07-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-07-21 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-07-21 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2008-07-21 10:40:32 | NO PLUMBING REQUIRED PER SECTION 403.4 EXCEPTION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2007-12-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-11 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-11 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2007-12-11 15:10:14 | NO PLUMBING REQUIRED PER SECTION 403.4 EXCEPTION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-21 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-21 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2007-09-21 17:01:22 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHTS 1 & 2 THE DATE THE SIGNATURE AND SEAL ARE | | | AFFIXED TO THE PLANS IS REQUIRED.--THE PRINTED NAME | | | OF THE PERSON SEALING THE DOCUMENT IS REQUIRED ON EACH | | | SHEET.--THE SIGNATURE IS REQUIRED. IT APPEARS THAT | | | INITIALS ARE USED. IF INDEED THIS IS THE LEGAL | | | SIGNATURE OF THE ARCHITECT, THEN A SIGNED, SEALED, | | | NOTORIZED LETTER SHALL BE SUBMITTED INDICATING THE | | | LEGAL SIGNATURE FOR OUR FILES. FAC 61G1-16.003, | | | 61G1-16.004(5)(6) & FS 481.2055. | | | | | | 2. PLANS INDICATE THE OCCUPANCY OF THE BUILDING AS | | | STORAGE. PER TABLES 1004.1.2 AND 104.3.1 TOILET ROOMS, | | | A SERVICE SINK, A DRINKING FOUNTAIN AND POSSIBLY AN EYE | | | WASH AND/OR EMERGENCY SHOWER MAY BE REQUIRED. ALSO SEE | | | SECTIONS 403.2, 403.4 & 411. | | | | | | 3. PLEASE INDICATE WHAT WILL BE STORED IN THE STORAGE | | | BUILDING. MSDS SHEETS MAY BE REQUIRED ACCORDING TO THE | | | TYPE OF MATERIAL BEING STORED. SECTION 106.1.1. | | | | | | 4. HOT WATER WILL BE REQUIRED TO THE SERVICE SINK PER | | | SECTION 607.1. PLEASE INDICATE THE LOCATION OF THE | | | WATER HEATER. | | | | | | 5. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM SHOWING | | | ALL PIPE SIZES, TRAPS & VENTS AS WELL AS A WATER | | | ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE SIZES, VALVES | | | AND AN RPZV BACKFLOW ON THE WATER SERVICE TO THE | | | BUILDING. SECTION 106.3.5.1.3(3)(5)(6)(8)(10)(13). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2008-08-08 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2008-08-08 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2008-08-08 |
Time |
16:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2008-07-07 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2008-07-07 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2008-07-07 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2008-07-07 10:30:51 | 1. THE APPROVED MINOR AMENDMENT INCLUDED PLANS FOR A | | | DUMPSTER ENCLOSURE.THE PERMIT FOR THE DUMPSTER | | | ENCLSURE AND THE SHED SHALL BE APPLIED FOR | | | SIMULTANEOUSLY. | | | | | | 2. PER SECTION 94-444(B) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS, A FOUR-SIDED ENCLSURE WITH AN | | | OBSCURING GATE IS REQUIRED FOR SITE PLAN APPROVAL. | | | PLANS FOR THE LAYOUT OF TRASH RECEPTACLES SHALL BE IN | | | ACCORDANCE WITH THE MINIMUM REQUIREMTNS SET FORTH IN | | | FIGURE XIV-3 (ATTACHED).THE DUMPSTER ENCLOSURE SHALL | | | BE LANDSCAPED. | | | | | | FOR QUESTIONS OR COMMENTS PLEASE CONTACT; BOBBY POWELL | | | JR., PLANNER, [email protected], (561) 822-1401 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2007-11-30 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2007-11-30 |
Time |
18:23 |
Sent To |
|
|
| Notes |
| 2007-11-30 18:23:00 | 1. A MINOR AMENDMENT IS REQUIRED TO BE APPROVED IN | | | ORDER TO CONVERT A DUMPSTER ENCLOSURE TO A STORAGE | | | FACILITY, PER SEC. 94-207(E). | | | | | | FOR QUESTIONS OR COMMENTS CONTACT; BOBBY POWELL JR., | | | PLANNER, 822-1435 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-17 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2007-09-17 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2007-09-17 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2007-09-17 11:05:02 | 1. A MINOR AMENDMENT WILL BE REQUIRED IN ORDER TO | | | CONVERT A DUMPSTER ENCLOSURE TO A STORAGE FACILITY, PER | | | SEC. 94-207(E). | | | | | | 2. A MEETING WITH STAFF IS RECOMMENDED BEFORE | | | SUBMITTING FOR THE MINOR AMENDMENT. | | | | | | FOR QUESTIONS OR COMMENTS CONTACT: BOBBY POWELL JR., | | | PLANNER, [email protected], (561) 822-1435. |
|
|