Plan Review Details - Permit 07080259
Plan Review Stops For Permit 07080259
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-27 Cont ID  
Sent By shill Date 2007-09-27 Time 07:45 Rev Time 0.00
Received By shill Date 2007-09-27 Time 07:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-06 Cont ID  
Sent By shill Date 2007-09-06 Time 10:26 Rev Time 0.00
Received By shill Date 2007-09-06 Time 10:26 Sent To  
Notes
2007-09-06 10:29:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEAL IS TO INCLUDE A DATE, SEE FAC61G15-23.002.
  
 2.)CERTIFICATE OF AUTHORIZATOIN REQUIRED AND IS TO BE
 ON EACH SHEET, SEE FAC61G15-23 AND FS471, ALSO
 FBPE.ORG.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-12 Cont ID  
Sent By btrobaug Date 2007-10-12 Time 12:02 Rev Time 0.00
Received By btrobaug Date 2007-10-12 Time 11:55 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-18 Cont ID  
Sent By btrobaug Date 2007-09-18 Time 09:46 Rev Time 0.00
Received By btrobaug Date 2007-09-18 Time 09:41 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-15 Cont ID  
Sent By btrobaug Date 2007-08-15 Time 11:57 Rev Time 0.00
Received By btrobaug Date 2007-08-15 Time 11:49 Sent To P
Notes
2007-08-15 11:57:53 
  
  
  
  
  
 DENIED/INCOMPLETE INFORMATION
  
 THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2007-10-23 Cont ID  
Sent By mperson Date 2007-10-23 Time 14:21 Rev Time 0.00
Received By mperson Date 2007-10-23 Time 14:21 Sent To Z
Notes
2007-10-23 14:22:00NOTE: THERE IS NO POOL HEATER GAS OR ELECTRIC.

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-09-26 Cont ID  
Sent By mperson Date 2007-09-26 Time 15:38 Rev Time 0.00
Received By mperson Date 2007-09-26 Time 15:38 Sent To B
Notes
2007-09-26 15:41:44NOTE: RESUBMITTED PLANS NOW HAVE A GAS POOL HEATER:
  
 CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-08-16 Cont ID  
Sent By mperson Date 2007-08-16 Time 14:04 Rev Time 0.00
Received By mperson Date 2007-08-16 Time 14:04 Sent To B
Notes
2007-08-16 14:06:05NOTE: THERE IS NO GAS OR ELECTRIC POOL HEATER.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 16:03 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 16:02 Sent To E
Notes
2007-10-10 16:03:30TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-12 Cont ID  
Sent By adarroug Date 2007-09-12 Time 09:47 Rev Time 0.00
Received By adarroug Date 2007-09-12 Time 09:47 Sent To Z
Notes
2007-09-12 09:47:46TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-06 Cont ID  
Sent By shill Date 2007-09-06 Time 10:29 Rev Time 0.00
Received By shill Date 2007-08-13 Time 09:26 Sent To  
Notes
2007-08-13 09:26:20TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-10-23 Cont ID  
Sent By mperson Date 2007-10-23 Time 14:20 Rev Time 0.00
Received By mperson Date 2007-10-23 Time 14:20 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-26 Cont ID  
Sent By mperson Date 2007-09-26 Time 15:15 Rev Time 0.00
Received By mperson Date 2007-09-26 Time 15:15 Sent To G
Notes
2007-09-26 15:37:20DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS. SECTIONS 424.2 AND
 R4101 SWIMMING POOLS.
 ** FBC-2004 WITH 05 & 06 REVISIONS,PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 DUE TO THE FACT THAT THE DESIGN PROFESSIONAL HAS
 CHANGED THE FOLLOWING CORRECTIONS/INFORMATION ARE
 REQUIRED FOR PLUMBING PLAN REVIEW TO MEET CODE
 COMPLIANCE:
  
 1. PLEASE CORRELATE THE EQUIPMENT LAYOUT WITH THE
 LEGEND ON THE RESUBMITTAL. THE EQUIPMENT LAYOUT IS
 MISLABELED AS B, C, D, E AND F, IT SHOULD BE LABELED A,
 B, C, D AND E TO CORRELATE WITH THE LEGEND. THE PIPING
 FOR THE EQUIPMENT LAYOUT IS ALSO MISLABELED AS 4, 5, 6,
 AND 8, IT SHOULD BE LABELED AS 1, 2, 3 AND 4 TO
 CORRELATE WITH THE LEGEND. PLEASE CORRECT AND CORRELATE
 ON THE RESUBMITTAL.
  
 2. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 3. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK
 BY THIS PLAN EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-08-16 Cont ID  
Sent By mperson Date 2007-08-16 Time 11:43 Rev Time 0.45
Received By mperson Date 2007-08-16 Time 11:43 Sent To G
Notes
2007-08-16 14:03:59DENIED
 REFERENCE:
 ** FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING POOLS.
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1) COMPLY WITH FBC-2004 SEC 424.2, OR
 FBCR-2004 SEC R4101 PRIVATE SWIMMING
 POOLS. (ADD TO NOTES)
  
 2) FBC-2004 SEC 424.2.6.1, OR FBCR-2004
 SEC R4101.6.1 ENGINEERING DESIGN,
 CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
  
 3) FBC-2004 424.2.6.6.2, OR FBCR-2004
 SEC R4101.6.6.2 SHOW COMPLIANCE WITH
 ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUFACTURER INFORMATION FOR SUCTION
 FITTINGS (MAIN DRAINS).
 (SUBMITTAL OR ADD TO NOTES)
  
 4) FBC-2004424.2.6.6.3, OR FBCR-2004 SEC R4101.6.6.3
 (1,2,3) ENTRAPMENT AVOIDANCE.
 NOTE: POOL DETAIL OF THE VENT PIPE SIZE IS TO VAGUE
 PLEASE CLARIFY THE EXACT SIZE OF THE VENT ON THE
 RESUBMITTAL AND PLEASE ADD TO THE VENT DETAIL THE
 FOLLOWING "LABEL VENT: POOL SAFETY DEVICE - DO NOT
 HANDLE"
  
 5) FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.
 (DETAIL REQUIRED WITH THE MAKE AND MODEL NUMBER OF THE
 CLEANER FITTING)
  
 6) FBC-2004 SEC. 424.2.7.2, OR
 FBCR-2004 SEC. R4101.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK. (DETAIL REQUIRED)
  
 7) FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC.
 R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.(ADD TO NOTES)
  
 8) FBC-2004 SEC. 424.2.12.1, OR
 FBCR-2004 SEC. R4101.12.1 PRESSURE
 TESTS. PER MANUFACTURE RECOMMENDATIONS,
 NO AIR TEST SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS. (ADD TO NOTES)
  
 9) FBC-2004 SEC. 424.2.13.2, OR
 FBCR-2004 SEC.R4101.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING.(ADD TO
 NOTES)
  
 10) FBC-2004 SEC. 424.2.20 OR FBCR-2004 SEC. R4101.20
 FILTERS. THE ENTIRE DESIGN OF MATCHED COMPONENTS SHALL
 HAVE SUFFICIENT CAPACITY TO PROVIDE A COMPLETE TURNOVER
 OF POOL WATER IN 12 HOURS OR LESS.
 NOTE: PLEASE PROVIDE THE TURNOVER TIME OF THE POOL ON
 THE RESUBMITTAL.
  
 11) THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK
 SHALL INDICATE THE CERTIFICATE OF AUTHORIZATION NUMBER
 ALONG WITH OTHER INFORMATION REQUIRED BY 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-23 Cont ID  
Sent By choops Date 2007-10-23 Time 14:30 Rev Time 0.00
Received By choops Date 2007-10-23 Time 14:30 Sent To B
Notes
2007-10-23 14:34:25***APPROVED - RESTAMPED PLANS - RESUB #2***
  
 SENT TO "B" - SH

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-13 Cont ID  
Sent By choops Date 2007-09-13 Time 14:43 Rev Time 0.00
Received By choops Date 2007-09-13 Time 14:43 Sent To E
Notes
2007-09-13 14:44:24FENCE ENCLOSURE ON PERMIT #07080926

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-14 Cont ID  
Sent By choops Date 2007-08-14 Time 08:07 Rev Time 0.00
Received By choops Date 2007-08-14 Time 08:07 Sent To E
Notes
2007-08-14 08:13:30***FAILED***
  
  
 1)INDICATE POOL EQUIPMENT WITH SETBACK DIMENSIONS TO
 THE PROPERTY LINES.
  
 2)SETBACK DIMENSIONS TO BE MEASURED FROM PROPERTY
 LINE...NOT EAST LINE OF LOT 54.
  
 3)AS THE SURVEY DOES NOT SHOW AN EXISTING FENCE
 COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT SHALL
 BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO THE
 MINIMUM STANDARDS PROVIDED BELOW.
  
 AS PER THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
  
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 4)CLARIFY SCOPE OF WORK: GARAGE SLAB TO BE ADDED
 UNDER THIS PERMIT?
  
 5)PROVIDE ELEVATION DETAIL OF DECK (IF ABOVE GRADE).
  
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720