| 2007-09-05 15:43:42 | RESIDENTIAL ADDITION BUILDING REVIEW FIRST CHECKLIST. |
| | REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC |
| | 2004 WITH 2007 REVISIONS. |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. |
| | NOTE: THIS DOCUMENT MAY BE RECORDED AT A LATER TIME AT |
| | TIME OF PERMIT PICK UP. |
| | |
| | 2-ENGINEER TO PROVIDE THE FIRM'S CERTIFICATE OF |
| | AUTHORIZATION NUMBER IN THE TITLE BLOCK AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 3- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. |
| | VALUE NEEDS TO INCLUDE ALL LABOR,MATERIALS AND |
| | ENGINEER'S FEES.UPDATE VALUE AS REQUIRED AND INCLUDE |
| | ALL WORK TO BE PERFORMED OR IT WILL BE UPDATED USING |
| | THE REFERENCES CITED IN SEC. 108.3 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | 4- SCOPE OF WORK TO BE PERFORMED IS NOT CLEAR.PERMIT |
| | APPLICATION CALLS FOR COVERED PATIO W/ ELECTRIC, WHILE |
| | PLANSSHOWNEW ROOF FRAMING FOR ENTIRE HOUSE, PARTIAL |
| | CARPORT AND NEW COVERED PATIO ADDITION. |
| | PLANS TO PROVIDE ONLY THE INFORMATION THAT PERTAINS TO |
| | THE WORK TO BE PERFORMED.DELETE ALL |
| | DETAILS/SPECIFICATIONS AND NOTESTHAT DON'T APPLY TO |
| | AVOID CONFUSION OR CONFLICTS. AND, CLEARLY IDENTIFY |
| | WHAT'S NEW AND WHAT'S EXISTING.SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 5- SHEET 2: |
| | A) LEFT SIDE FLOOR PLANS STATES"EXISTING ROOF |
| | COVER TO BE REMOVED. RAFTERS & CEILING TO REMAIN". |
| | THEN, CLARIFY WHY PROVIDING NEW ROOF FRAMING PLAN? |
| | |
| | B) MISSINGINFORMATION FOR EXPANSION OF CARPORT. |
| | NEEDS INFORMATION FOR COLUMNS, BEAMS, RAFTERS, ROOF |
| | SHEATHING (OR IS THIS A TRELLIS?),FOOTINGS, ETC. |
| | ALSO, THERE IS A ROOF RAFTER SHOWN AS BEING SUPPORTED |
| | ON THE AIR. PROVIDE COMPLETE INFORMATION. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | C) WINDOW NEXT TO ENTRY DOORAND NEXT TO REAR DOOR |
| | NEEDS TO HAVE SAFETY GLAZING AS REQUIRED BY SEC. R308.4 |
| | OF 2004 FLORIDA RESIDENTIAL CODE. SPECIFY SAFETY |
| | GLAZING AS REQUIRED. |
| | |
| | 6- SHEET 5: |
| | A)NOTE BELOW TRUSS TO CONCRETE SCHEDULE CALLS FOR |
| | HANGERS TO BE CONCEALED. PROVIDE DETAIL SHOWING HOW ARE |
| | HANGERS GOING TO BE CONCEALED. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | B) UPDATETRUSS TO TRUSS CONNECTION SCHEDULE AND |
| | TRUSS TO CONCRETE SCHEDULE. SEE CURRENT CATALOG AND |
| | SPECIFYFASTENER SIZE , TYPE, NUMBER AND UPLIFTS LOADS |
| | AS PUBLISHED BY THE MANUFACTURER.OTHERWISE, PROVIDE |
| | COMPLETE ENGINEERING ANALYSISSHOWING WHY VALUES ARE |
| | DIFFERENT THAN THOSE TESTED AND PUBLISHED BY THE |
| | MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 7- SHEET 8: |
| | A) EXISTING TYPICAL WALL SECTION: |
| | *IT'S NOT CLEAR WHAT'S NEW AND WHAT IS EXISTING. |
| | |
| | ** SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.1.2 OF |
| | 2004 FLORIDA RESIDENTIALCODE. |
| | *** SPECIFY ATTIC VENTILATION AS REQUIRED BY SEC. R806 |
| | OF 2004 FLORIDA RESIDENTIAL CODE. |
| | **** ROOF TRUSS CONNECTOR SHOWN DOESN'T MATCH TRUSS |
| | CONNECTORSPECIFIED ON TRUSS CONNECTORSCHEDULE. THIS |
| | IS A RETROFIT CONNECTOR, NOT AN EMBEDED CONNECTOR. |
| | REVISE AS REQUIRED. |
| | ***** REVISE NAIL TYPE AND SPACING TO BE USED FOR ROOF |
| | SHEATHING. SEE SEC. R803.2.3.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE FOR MINIMUM NAIL TYPE AND SPACING TO |
| | BE USED INCLUDING IN ROOF ZONE 3. |
| | |
| | B) TYPICAL COLUMN SECTION: |
| | * THIS SECTION DOESN'T MATCH INFORMATION SHOWN ON DET-1 |
| | ON PAGE 5. REVISE AS REQUIRED TO MATCH. |
| | ** NUMBER OF REINFORCING BARS SHOWN ON FOOTING DON'T |
| | MATCH NUMBER OF BARS SPECIFIED ON FOOTING SCHEDULE. |
| | REVISE AS REQUIRED. |
| | *** COLUMN SPECIFICATIONS DON'T MATCH SPECIFICATION |
| | SHOWN ON SHEET 4. REVISE/CLARIFYCOLUMN THICKNESS. |
| | |
| | **** IS THERE A NEW OR EXISTING CONCRETE SLAB?.IT'S |
| | NOT CLEAR WHAT'S NEW AND WHAT'S EXISTING. |
| | ***** SPECIFY ATTIC VENTILATION. SEC. R806. |
| | ****** REVISE ROOF SHEATHING NAIL SIZE AND SPACING, |
| | INCLUDINGROOF ZONE 3. SEC. R803.2.3.1. |
| | ****** REVISE FINISH CEILING SPECIFICATIONS. THIS IS A |
| | PATIO CEILING. NEED TO PROVIDE SPECIFICATIONS FOR |
| | EXTERIOR APPLICATION. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | 8- SHEET 9: |
| | A) REVISE CODE SECTION SPECIFIED ON DESIGN CRITERIA. |
| | SEE FBC 2004 AND ANDSECTION IS R301 AND TABLE R301.5 |
| | OF 2004 FLORIDA RESIDENTIAL CODE AND SPECIFIED CORRECT |
| | SECTIONS. |
| | B) SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC. |
| | 602.1 FBC 2004. |
| | C) REVISE ROOF SHEATHING NAILING SCHEDULE, INCLUDING |
| | ROOF ZONE 3.SEE SEC. R803.2.3.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE FOR MIN. NAIL TYPE AND SPACING TO BE |
| | USED. |
| | ALSO, REVISE NOTE REGARDING RING SHANK NAILS NOT |
| | REQUIRED WHEN MEAN ROOF HEIGHT IS LESS THAN 25'. |
| | D)REVISEROOF SHEATHING SPECIFICATIONS SHOWN ON |
| | PLYWOOD NAILING SKETCH TO MATCH ROOF SHEATHING NAILING |
| | SCHEDULE, INCLUDING ROOF SHEATHING THICKNESS. |
| | |
| | 9- PROVIDE 2 COPIES OF PRODUCT APPROVAL AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS AND DETAILS. |
| | B) EXTERIOR DOORS. IF NEW. |
| | C) WINDOWS.IF NEW. |
| | D) STORM SHUTTERS IF WINDOWS AND DOORS WITH GLASS |
| | HAVE NOT IMPACT GLASS. |
| | ALSO, PROVIDE A COMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED SAMPLE. |
| | E) PRECAST LINTELS. IF NEW. |
| | F) ROOF SHINGLES. |
| | G) FLAT ROOF IF ANY ON CARPORT AREA. AND, CLEARLY |
| | SPECIFY WHICH SPECIFIC ASSEMBLYAND FASTENING OPTION |
| | WILL BE INSTALLED. ALSO,PROVIDE RAS 117 CALCULATIONS |
| | FOR PERIMETER AND CORNER AREAS. SEE GENERAL LIMITATION |
| | #7 ON PRODUCT APPROVAL REPORT. |
| | |
| | 10 ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 11- IF THERE ARE NEW WINDOWS AND DOORS ,THEN SPECIFY |
| | TYPE AND SIZES. ALSO, SPECIFY THE DESIGN PRESSURES. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 12- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600.1.C.2 FBC 2004. |
| | NOTE: MAKE SURE CORRECT 2006 REVISED FORM IS USED. |
| | |
| | 13- SPECIFY ATTIC ACCESS AS REQUIRED BY SEC. R807 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |