Plan Review Details - Permit 07080220
Plan Review Stops For Permit 07080220
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-11-04 Cont ID  
Sent By jwitmer Date 2008-11-04 Time 14:27 Rev Time 0.55
Received By jwitmer Date 2008-11-04 Time 14:27 Sent To P
Notes
2008-11-04 14:35:47REVISION# 2 SHEET A-3 PLUS LETTER FROM RAY ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-09 Cont ID  
Sent By jjohnsto Date 2007-11-09 Time 09:20 Rev Time 1.00
Received By jjohnsto Date 2007-11-09 Time 09:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By jwitmer Date 2007-09-17 Time 19:46 Rev Time 1.22
Received By jwitmer Date 2007-09-17 Time 19:45 Sent To  
Notes
2007-09-17 20:35:24TRUMP PLAZA
 525 S FLAGLER DR
 SEPT17,2007
 BUILDING PLAN REVIEW
 PERMIT: 07080220
 ADD: 525 S FLAGLER DR FLOOR# 6
 CONT: DESIGN CONTRACTING INCORPORATED
 TEL: (561)248-5278
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) RAY ENGINEERING CONSULTING ENGINEERS, IS MISSING
 THEIR CERTIFICATE OF AUTHORIZATION. ) 471.023 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
  
 4) SHET A-1 INDICATES 4 AND POSSIBLE 5 AREAS WHERE
 EXISTING HANDICAPPED RAMPS AND HANDRAILS ARE BEING
 DEMOLISHED. THE PLANS DO NOT PROVIDE CLEAR CUT SECTIONS
 AS TO WHAT WALLS ARE BEING REPLACED AND OR WHAT
 HANDRAILS ARE BEING REPLACED AT THE HANDICAPPED
 RAMPS.SCOPE OF WORK INDICATES # 13 INSTALL GAURDRAILS
 AND HANDRAILS AS SHOWN. PROVIDE DETAILS.
 11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS.
 THIS EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS,
 STRUCTURES OR FACILITIES WHICH WERE IN EXISTENCE ON
 OCTOBER 1,1997,(1) GENERAL. ALTERATIONS TO EXISTING
 BUILDINGS AND FACILITIES SHALL COMPLY WITH THE
 FOLLOWING:
 (A)NO ALTERATION SHALL BE UNDERTAKEN WHICH
 DECREASES OR HAS THE EFFECT OF DECREASING ACCESSIBILITY
 OR USABILITY OF A BUILDING OR FACILITY BELOW THE
 REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME OF
 ALTERATION.
 (B)IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS
 ARE ALTERED, THEN EACH SUCH ALTERED ELEMENT, SPACE,
 FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3 ,
 MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. IF THE
 APPLICABLE PROVISION FOR NEW CONSTRUCTION REQUIRES THAT
 AN ELEMENT, SPACE, OR COMMON AREA BE ON AN ACCESSIBLE
 ROUTE, THE ALTERED ELEMENT, SPACE, OR COMMON AREA IS
 NOT REQUIRED TO BE ON AN ACCESSIBLE ROUTE EXCEPT AS
 PROVIDED IN SECTION 11-4.1.6 (2), ALTERATIONS TO AN
 AREA CONTAINING A PRIMARY FUNCTION.
  
 5) PLEASE PROVIDE INFORMATION ON THE TYPE OF DECKING
 THAT IS GOING TO BE INSTALLED ON THE POOL DECK SURFACE?
 106.1.2* ADDITIONAL INFORMATION REQUIRED. HOW WILL IT
 BE BONDED?SHEET A-3INDICATES A NEW SKIMMER ATOP OF
 THE OLD DECK WHAT WILL STOP WATER FROM THE POOL FROM
 LEAKING OUT THIS COLD JOINT?
  
 6) SHEET A-3 INDICATES NOT ONLY IS THE DECK BEING
 REFINISHED BUT THE POOL AS WELL, PLEASE PROVIDE
 ADDITIONAL INFORMATION AS TO THE RIGID POLYSTYRENE
 INSULATION AND LIGHTWEIGHT NEW POOL SHELL?
 PLEASE PROVIDE THE NEW DEPTH MARKERS REQUIRED FOR THE
 POOL.424.1.2.3.1 DEPTH MARKINGS.
 DEPTH MARKINGS SHALL MEET THE FOLLOWING CRITERIA:
 1.PERMANENT DEPTH MARKINGS FOLLOWED BY THE
 APPROPRIATE FULL OR ABBREVIATED WORDS "FEET" OR
 "INCHES" SHALL BE INSTALLED IN MINIMUM 4-INCH-HIGH (102
 MM) NUMBERS AND LETTERS ON A CONTRASTING BACKGROUND.
 DEPTH MARKERS SHALL INDICATE THE ACTUAL POOL DEPTH ,
 WITHIN 3 INCHES (76 MM), AT NORMAL OPERATING WATER
 LEVEL WHEN MEASURED 3 FEET (914 M 3 ) FROM THE POOL
 WALL. SYMMETRICAL POOL DESIGNS WITH THE DEEP POINT AT
 THE CENTER MAY BE ALLOWED PROVIDED A DUAL MARKING
 SYSTEM IS USED WHICH INDICATES THE DEPTH AT THE WALL
 AND AT THE DEEP POINT.
 2.THE MARKINGS SHALL BE LOCATED ON BOTH SIDES OF
 THE POOL AT THE SHALLOW END, SLOPE BREAK, DEEP END WALL
 AND DEEP POINT (IF LOCATED MORE THAN FIVE FEET FROM THE
 DEEP END WALL) WITH A MAXIMUM PERIMETER DISTANCE
 BETWEEN DEPTH MARKINGS OF 25 FEET (7620 MM)AND SHALL BE
 LEGIBLE FROM INSIDE THE POOL AND ALSO FROM THE POOL
 DECK.
 3.WHEN A CURB IS PROVIDED, THE DEPTH MARKINGS
 SHALL BE INSTALLED ON THE INSIDE AND OUTSIDE OR TOP OF
 THE POOL CURB. WHEN A POOL CURB IS NOT PROVIDED, THE
 DEPTH MARKINGS SHALL BE LOCATED ON THE INSIDE VERTICAL
 WALL AT OR ABOVE THE WATER LEVEL AND ON THE EDGE OF THE
 DECK WITHIN TWO FEET OF THE POOL WATER. WHEN OPEN TYPE
 GUTTER DESIGNS ARE UTILIZED, DEPTH MARKERS SHALL BE
 LOCATED ON THE BACK OF THE GUTTER WALL.
 4.WHEN DECK LEVEL PERIMETER OVERFLOW SYSTEMS ARE
 UTILIZED, ADDITIONAL DEPTH MARKERS SHALL BE PLACED ON
 ADJACENT FENCING OR WALLS AND THE SIZE SHALL BE
 INCREASED SO THEY ARE RECOGNIZABLE FROM INSIDE THE
 SWIMMING POOL. DEPTH MARKERS ON THE POOL DECK SHALL BE
 WITHIN THREE FEET OF THE WATER.
 5.THOSE AREAS OF THE POOL THAT ARE NOT PART OF AN
 APPROVED DIVING BOWL SHALL HAVE DARK CONTRASTING,
 PERMANENT, 4-INCH-HIGH (102 MM) "NO DIVING" MARKINGS
 INSTALLED ON THE TOP OF THE POOL CURB OR DECK WITHIN 2
 FEET (610 MM)OF THE POOL WATER ON EACH SIDE OF THE POOL
 WITH A MAXIMUM DISTANCE OF 25 FEET (7620 MM) BETWEEN
 MARKINGS. A 6-INCH (152 MM) TILE WITH A 4-INCH (102 MM)
 OR LARGER RED, INTERNATIONAL "NO DIVING" SYMBOL MAY BE
 SUBSTITUTED FOR THE "NO DIVING" MARKINGS.
 6.ALL DEPTH MARKINGS SHALL BE TILE, EXCEPT THAT
 POOLS CONSTRUCTED OF FIBERGLASS, THERMOPLASTIC OR
 STAINLESS STEEL MAY SUBSTITUTE OTHER TYPE MARKINGS WHEN
 IT CAN BE SHOWN THAT SAID MARKINGS ARE PERMANENT AND
 WILL NOT FADE OVER TIME. THIS EXEMPTION DOES NOT EXTEND
 TO CONCRETE POOLS THAT ARE COATED WITH FIBERGLASS. ALL
 DEPTH AND "NO DIVING" MARKINGS INSTALLED ON HORIZONTAL
 SURFACES SHALL HAVE A SLIP-RESISTANT FINISH.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-12-21 Cont ID  
Sent By dpalmer Date 2007-12-21 Time 13:05 Rev Time 0.00
Received By dpalmer Date 2007-12-21 Time 13:05 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 10:13 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 10:13 Sent To FIRE
Notes
2007-12-03 10:13:17 
  
  
  
 ** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW
 COMMENTS BASED ON REVISED AND NEW PLANS SUBMITTED.
  
 1) NOTE: PLEASE SEE PLANS MAY NOT CONTAIN ANY WHITE-OUT
 AND NO HAND DRAWN CHANGES ARE PERMITTED.
 PLEAS HAVE SHEETS REPRINTED AND THEN RE-SIGNED, DATED
 AND SEALED BY THE DESIGN PROFESSIONAL.
 PLEASE SEE THE NEW PHOTO-METRIC SHEETS SUBMITTED DO NOT
 CONTAIN ANY TITLE BLOCKS AS REQUIRED PER FAC
 61G15-23.002. PLEASE COMPLETE. PLEASE SEE THE FOLLOWING
 COMMENT FOR REVISED SHEETS AS NEEDED.
  
 2) NOTE: PLEASE SEE THE LIGHTING LEVELS DO NOT MEET THE
 MINIMUM PER NFPA-101 LIFE SAFETY CODE.
 PLEASE SEE 7.8.1.3 AS THE NORMAL LIGHTING LEVELS ON
 STAIRS MUST BE 10FT CANDLES MINIMUM AND IS PERMITTED TO
 GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS.
 PLEASE SEE THE LEVELS ARE ONLY SUBMITTED AND SHOWN FOR
 THREE STAIRS WHEN PLANS ACTUALLY CONTAIN MORE STAIRS
 WHICH ARE BEING WORKED ON IN THIS SCOPE AND ARE PART OF
 THE EGRESS, EXIT DISCHARGE AREA. PLEASE COMPLETE ALL
 AREAS AS NOTED ON PREVIOUS REVIEWS.
 ** PLEASE BE SURE TO INDICATE THE LEVELS UNDER
 EMERGENCY ALSO BASED ON FIXTURES PROVIDED.
  
 3) NOTE: PLEASE SEE THAT THE EQUAL-POTENTIAL BONDING
 DETAILS ADDED ARE TO MEET NOTE #1.
  
 *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-04 Cont ID  
Sent By dpalmer Date 2007-11-04 Time 10:25 Rev Time 0.00
Received By dpalmer Date 2007-11-04 Time 10:13 Sent To I
Notes
2007-11-04 10:26:05PLANS REMOVED FROM INCOMING AND WILL BE RETURNED TO
 INCOMING ONCE REVIEW IS COMPLETED WAITING FOR COMM
 BOARD.
  
  
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
 AS SOME INFORMATION WAS STILL NOT SUBMITTED, A COMPLETE
 REVIEW FOR CODE COMPLIANCE COULD NOT BE DONE.
  
 1) NOTE: PLEASE SEE NOTES 3, 4 AND 5 FROM PREVIOUS
 REVIEW BELOW.
  
 NOTE#3, AS NO SCALE IS ON ELECTRICAL PLANS OR
 DIMENSIONS FOR LIGHTING ETC IS ALSO NOT ON PLANS,
 COMPLIANCE WITH THE CODES GIVEN CAN NOT BE DETERMINED.
  
 NOTE #4, A BONDING GRID IS NOTED, HOWEVER NO ENOUGH
 INFORMATION OR DETAILS IS PROVIDED FOR DIMENSIONS ETC.
 QUOTING ONE REQUIRED IN LIEU OF DETAIL IS NOT PERMITTED
 BY CODE.
  
 NOTE #5, NO PHOTO-METRICS SUBMITTED, NO REVIEW DONE.
 PLEASE AS THIS *IS* AS LIFE SAFETY ISSUE THE MINIMUM
 LIGHTING LEVELS FOR EXIT AND EGRESS PATHS AND DISCHARGE
 AREAS IS REQUIRED.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ******** NOTES FROM PREVIOUS REVIEWS *********
  
 3) NOTE: PLEASE INCLUDE THE INFORMATION FOR ALL NEW
 LIGHTING BEING PROPOSED ON PLANS.
 PLEASE INCLUDE VOLTAGE AND PROTECTION FOR FIXTURES PER
 680.22. PLEASE INDICATE THE REQUIRED GFI RECEPTACLE
 WITHIN 20FT OF POOL. (NEW OR EXISTING).
 PLEASE SEE 411.4B IF ANY LIGHTING FIXTURES ARE LOW
 VOLTAGE (30VOLTS OR LESS).
 PLEASE INCLUDE CIRCUITING INFORMATION ON HOW AND WHERE
 THE POWER IS COMING FROM. (CONDUCTOR(S), GROUNDING,
 OVER CURRENT PROTECTION ETC.
 408.4, 310.16, 240.4
  
 4) NOTE: PLEASE SEE 2005NEC680.26 FOR THE REQUIRED
 EQUAL-POTENTIAL BONDING GRID REQUIRED.
  
 5) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR ALL EGRESS
 STAIR LOCATIONS AND EGRESS PATHS UNDER NORMAL AND UNDER
 EMERGENCY CONDITIONS.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2.
 PLEASE ALSO SEE FAC 61G15-33.004.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-08 Cont ID  
Sent By dpalmer Date 2007-09-08 Time 18:33 Rev Time 0.00
Received By dpalmer Date 2007-09-08 Time 18:06 Sent To  
Notes
2007-09-08 18:33:16** DENIED **
  
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE ENGINEERING FIRM, ETC PER FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES
 471.023.
 PLEASE SEE MISSING PRINTED NAME.
 PLEASE SEE MISSING PRINTED LICENSE NUMBER FOR PE.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER
 ALSO KNOWN AS THE ENGINEERING BUSINESS NUMBER.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE INCLUDE THE INFORMATION FOR ALL NEW
 LIGHTING BEING PROPOSED ON PLANS.
 PLEASE INCLUDE VOLTAGE AND PROTECTION FOR FIXTURES PER
 680.22. PLEASE INDICATE THE REQUIRED GFI RECEPTACLE
 WITHIN 20FT OF POOL. (NEW OR EXISTING).
 PLEASE SEE 411.4B IF ANY LIGHTING FIXTURES ARE LOW
 VOLTAGE (30VOLTS OR LESS).
 PLEASE INCLUDE CIRCUITING INFORMATION ON HOW AND WHERE
 THE POWER IS COMING FROM. (CONDUCTOR(S), GROUNDING,
 OVER CURRENT PROTECTION ETC.
 408.4, 310.16, 240.4
  
 4) NOTE: PLEASE SEE 2005NEC680.26 FOR THE REQUIRED
 EQUAL-POTENTIAL BONDING GRID REQUIRED.
  
 5) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR ALL EGRESS
 STAIR LOCATIONS AND EGRESS PATHS UNDER NORMAL AND UNDER
 EMERGENCY CONDITIONS.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2.
 PLEASE ALSO SEE FAC 61G15-33.004.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, A FULL REVIEW FOR CODE COMPLIANCE
 CAN NOT BE DONE AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-04 Cont ID  
Sent By mawillia Date 2007-12-04 Time 14:43 Rev Time 0.00
Received By mawillia Date 2007-12-04 Time 14:40 Sent To  
Notes
2007-12-04 14:42:57*****PROVISO*****
  
  
 ALL MEANS OF EGRESS COMPONENTS AND THE ILLUMINATION OF
 THE MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH NFPA
 101, LIFE SAFETY CODE, 2003 EDITION.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
 **THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 ALL REVIEWERS HAVE BEEN SATISFIED**

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-12-04 Cont ID  
Sent By mawillia Date 2007-11-05 Time 10:10 Rev Time 0.00
Received By mawillia Date 2007-11-05 Time 10:09 Sent To  
Notes
2007-12-04 14:17:28*****PROVISO*****
  
  
 ALL MEANS OF EGRESS COMPONENTS AND THE ILLUMINATION OF
 THE MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH NFPA
 101, LIFE SAFETY CODE, 2003 EDITION.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-11-04 Cont ID  
Sent By adarroug Date 2008-11-04 Time 08:41 Rev Time 0.00
Received By adarroug Date 2008-11-04 Time 08:41 Sent To  
Notes
2008-11-04 08:44:57TO "COMM" BD#7

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 16:47 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 16:47 Sent To E
Notes
2007-12-19 16:48:04TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-30 Cont ID  
Sent By adarroug Date 2007-11-30 Time 09:05 Rev Time 0.00
Received By adarroug Date 2007-11-30 Time 09:05 Sent To E
Notes
2007-11-30 09:06:10TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-16 Cont ID  
Sent By adarroug Date 2007-10-16 Time 08:48 Rev Time 0.00
Received By adarroug Date 2007-10-16 Time 08:48 Sent To  
Notes
2007-10-16 08:49:24WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-21 Cont ID  
Sent By adarroug Date 2007-09-21 Time 08:47 Rev Time 0.00
Received By adarroug Date 2007-08-08 Time 18:46 Sent To  
Notes
2007-09-07 16:05:04TO "COMM" BD#27
2007-08-08 18:47:11WAITING FOR COMMERICAL BOARD

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-11-21 Cont ID  
Sent By kstevens Date 2008-11-21 Time 09:38 Rev Time 0.00
Received By kstevens Date 2008-11-21 Time 09:38 Sent To  
Notes
2008-11-21 09:38:37REVISION OK -- SHT A-3

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-29 Cont ID  
Sent By jleech Date 2007-11-29 Time 07:48 Rev Time 0.00
Received By jleech Date 2007-11-29 Time 07:42 Sent To  
Notes
2007-11-29 07:52:56PROVISO;
 PLUMBING DEMO WORK WILL BE DONE BY A LICENSED PLUMBING
 CONTRACTOR. PERMIT AND INSPECTIONS REQUIRED. NO DEAD
 ENDS PERMITED IN THE RAIN WATER DRAINAGE SYSTEMLONGER
 THAN 2'.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-21 Cont ID  
Sent By kstevens Date 2007-09-21 Time 17:57 Rev Time 0.00
Received By kstevens Date 2007-09-21 Time 17:57 Sent To  
Notes
2007-09-21 18:13:48DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND
 LICENSE NUMBER ON EACH SHEET AND IF PRACTICING THROUGH
 A DULY AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET.
 FAC61G15-23.002(2) & FS 471.025.
  
 2. PLANS INDICATE THE DEMOLITION OF PLANTERS. PLEASE
 INDICATE IF THE PLANTER DRAINS WILL BE CONVERTED TO
 DECK DRAINS. SECTION 106.1.2.--IF THE DECK DRAINS
 WILL BE REMOVED, THEN DEAD ENDS SHALL BE PROHIBITED PER
 SECTION 704.5.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status N Date 2008-11-14 Cont ID  
Sent By mflis Date 2008-11-14 Time 10:45 Rev Time 0.00
Received By mflis Date 2008-11-14 Time 10:45 Sent To  
Notes
2008-11-14 10:46:31ZONING REVIEW: NOT REQUIRED
  
 ** DRAIN DETAILS ONLY
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-15 Cont ID  
Sent By mflis Date 2007-11-15 Time 16:34 Rev Time 0.00
Received By mflis Date 2007-11-15 Time 16:34 Sent To  
Notes
2007-11-15 16:34:58ZONING REVIEW: PASSED
  
 * LANDSCAPE PERMIT/PLAN SHALL BE SUBMITTED FOR MODIFIED
 PLANTERS
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-13 Cont ID  
Sent By mflis Date 2007-09-13 Time 15:05 Rev Time 0.00
Received By mflis Date 2007-09-13 Time 15:05 Sent To  
Notes
2007-09-13 15:08:10ZONING REVIEW: FAILED
  
 1) TRUMP PLAZA IS A PLANNED DEVELOPMENT; MODIFICATIONS
 WILL REQUIRE A MINOR AMENDMENT TO THE DEVELOPMENT.
 PLEASE CONTACT PLANNING DEPARTMENT FOR AN APPLICATION
 AND THE REQUIREMENTS FOR SUBMITTAL. MINOR AMENDMENT
 MUST BE APPROVED PRIOR TO PERMIT APPROVAL.
 2) PLEASE SUBMIT LANDSCAPE PLANS FOR NEW AND/OR
 MODIFIED PLANTERS. IT APPEARS NEW PLANT MATERIAL WILL
 BE INSTALLED.
  
 MATT FLIS - 822-1445.