Plan Review Details - Permit 07080194
Plan Review Stops For Permit 07080194
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-29 Cont ID  
Sent By jgomez Date 2007-11-29 Time 14:15 Rev Time 0.00
Received By jgomez Date 2007-11-29 Time 12:37 Sent To Z
Notes
2007-11-29 14:59:56RESIDENTIAL ADDITION BUILDING SECONDREVIEW
 CHECKLIST.
 REVIEW DONE UNDERFBC 2004 WITH 2007 REVISIONS.
  
 1-RECORDED NOTICE OF COMMENCEMENT SUBMITTED NEEDS TO
 BE COMPLETE. NEED TO PROVIDE THE DESCRIPTION OF
 PROPERTY (COMPLETE LEGAL DESCRIPTION AND STREET
 ADDRESS), THEN RE-RECORD IT AS REQUIRED BY SEC. 713.13
 FLORIDA STATUTE.
  
 2- SECOND RE-SUBMITTAL FEES WERE NOT PAID. OWES $136.73
 AND FUTURE RE-SUBMITTAL FEES.
  
 3- PROVIDE SOIL TEST REPORT AS REQUIRED BY NOTES ON
 FOUNDATION PLAN AND SEC.R401.4 OF 2004 FLORIDA
 RESIDENTIAL CODE. (REPEAT COMMENT. NOT ADDRESSED).
  
 4- INITIAL COMMENT: "IDENTIFYEXISTING ROOMS ADJACENT
 TO NEW ADDITION TO CHECK IF EGRESS OPENINGS ARE NOT
 BLOCKED AND CHECK COMPLIANCE WITH SEC. R310 OF 2004
 FLORIDA RESIDENTIAL CODE".
 RESPONSE TO INFORMATION PROVIDED: THERE IS AN EXISTING
 BEDROOM WINDOW THAT IS GOING TO BE CLOSED TO ALLOW FOR
 NEW ADDITION. SHOW HOW IS EXISTING BEDROOM COMPLYING
 WITH EGRESS REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 5- ENERGY CALCULATIONS:
 A) PROVIDE 2 COPIES. (REPEAT COMMENT).
 B) PROVIDE REVISED FORM 600A-2004R. (REPEAT
 COMMENT).
 C) COMPLETE ALL INFORMATION ON TOP OF FORM. (REPEAT
 COMMENT).
 D) CLARIFY WHAT ARE ALL THE EXTERIOR AND ADJACENT
 WALLS SHOWN ON ITEM #9. (REPEAT COMMENT).
 E) OWNER/AGENT TO SIGN AND DATE FORM. (REPEAT
 COMMENT).
 F) OVERHANG HEIGHT IS INCORRECT. IT CAN'T BE 1. SEE
 EXTERIOR ELEVATIONS AND REVISE AS REQUIRED. (REPEAT
 COMMENT).
 G) REVISE BUILDING ORIENTATION. SEE PLANS AND SURVEY
 FOR CORRECT BUILDING ORIENTATION AND REVISE AS REQ'D.
 (REPEAT COMMENT).
  
 6- PROVIDE PRODUCT APPROVAL AS REQ'D BY DCA RULE 9B-72
 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVERPAGE AND PAGE WHERE CONNECTOR IS SHOWN.
 GO TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL THE
 REQUIRED INFORMATION. (REPEAT COMMENT).
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS. (REPEAT
 COMMENT).
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQ'D BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 (THIS APPLIES TO PRODUCT APPROVALS NOT SUBMITTED YET).
 ***NOTE: PLEASE MAKE SURE NAME OF ENGINEER IS ON
 APPROVED AND REVIEWED STAMP.
  
 8- SHEET A1:
 A) SPECIFY ATTIC ACCESS LOCATION AND SIZE TO COMPLY
 WITH SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE.
 (REPEAT COMMENT).
  
 B) FLOOR PLAN CALLS FOR KITCHEN AREA. ACCORDING TO
 THIS THERE ARE TWO KITCHENS ON THIS SINGLE FAMILY
 RESIDENCE.TWOKITCHENS ARE NOT ALLOWED ON SAME
 SINGLE FAMILY RESIDENCE. OTHERWISE, REVIEW WILL NEED TO
 BE PERFORMED BASED ON FIRE SEPARATION BETWEEN THETWO
 SEPARATE DWELLING UNITS.ON THE OTHER-HAND ZONING
 DOESN'T ALLOWS TWO KITCHENS. REVISE NAMES OF ROOMS AS
 REQUIRED.
  
 9- TYPICAL WALL SECTION A/A-2:
 A) REVISE SPECIFICATIONS FOR ROOF SHEATHINGNAILING
 SPACING ON ZONE 3 AREAS. SEE SEC. R803.2.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE AND REVISE AS REQ'D. CLEARLY
 IDENTIFY WHAT IS THE FIELD AREA AND WHAT ARE THE EDGES.
 PROVIDE SKETCH SHOWING ROOFING ZONES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) R-11 INSULATION DOESN'T FIT ON A 1X2 P.T. FURRING
 STRIPS. REVISE AS REQUIRED. SEE SEC. 13--602.1.ABC.1 OF
 FBC 2004 AND REVISE AS REQUIRED.
 ALSO,COORDINATE INFORMATION WITH THEENERGY
 CALCULATIONS.
  
 10- PLEASE PROVIDE CHECKLIST RESPONSE LETTER. THIS WILL
 HELPEXPEDITE THE REVIEW PROCESS.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-29 Cont ID  
Sent By jgomez Date 2007-08-29 Time 17:59 Rev Time 0.00
Received By jgomez Date 2007-08-29 Time 17:34 Sent To PC
Notes
2007-08-29 18:00:56RESIDENTIAL ADDITION BUILDING FIRST REVIEW CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC
 2004 WITH 2007 REVISIONS.
  
 1-RECORDED NOTICE OF COMMENCEMENT WILL BE REQUIRED
 PRIOR TO ISSUING THE PERMIT AS REQ'D BY SEC. 713.13
 FLORIDA STATUTE.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.
 (561)233-5115)TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW.PERMIT VALUATION WAS UPDATED TO $86,732 ACCORDING
 TO THE ICC BUILDING VALUATION DATATABLE AS REQ'D BY
 SEC. 108.3 OF CITY AMENDMENTS TO FBC 2004. THEREFORE,
 OWES 1,187.17 FOR BUILDING VALUATION AND RADON FEES.
  
 4- PROVIDE SOIL TEST REPORT AS REQUIRED BY NOTES ON
 FOUNDATION PLAN AND SEC.R401.4 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 5- SPECIFY CONSTRUCTION TYPE ON PLANS AS REQ'D BY SEC.
 602.1 FBC 2004.
  
 6- IDENTIFYEXISTING ROOMS ADJACENT TO NEW ADDITION TO
 CHECK IF EGRESS OPENINGS ARE NOT BLOCKED AND CHECK
 COMPLIANCE WITH SEC. R310 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 7- PLANS ARE MISSING THE SOUTH EXTERIOR ELEVATION.
 PROVIDE THIS ELEVATION. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 8-PROVIDE ALL DIMENSIONS IN THE NEW SURVEY, INCLUDING
 THE BUILDING SETBACKS. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
 ALSO,SURVEY NEEDS TO HAVE ORIGINAL SURVEYOR SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
  
 9- ENERGY CALCULATIONS:
 A) PROVIDE 2 COPIES.
 B) PROVIDE REVISED FORM 600A-2004R.
 C) COMPLETE ALL INFORMATION ON TOP OF FORM.
 D) CLARIFY WHAT ARE ALL THE EXTERIOR AND ADJACENT
 WALLS SHOWN ON ITEM #9.
 E) PREPARER TO SIGN AND DATE FORM.
 F) OWNER/AGENT TO SIGN AND DATE FORM.
 G) OVERHANG HEIGHT IS INCORRECT. IT CAN'T BE 1. SEE
 EXTERIOR ELEVATIONS AND REVISE AS REQUIRED.
 H) REVISE BUILDING ORIENTATION. SEE PLANS AND SURVEY
 FOR CORRECT BUILDING ORIENTATION AND REVISE AS REQ'D.
  
 10- PROVIDE PRODUCT APPROVAL AS REQ'D BY DCA RULE 9B-72
 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVERPAGE AND PAGE WHERE CONNECTOR IS
 SHOWN.
 B) EXTERIOR DOOR. NOA 01-1218.05 SUBMITTED EXPIRED
 ON 08/15/07. NEED TO PROVIDE CURRENT PRODUCT APPROVAL.
 C) SINGLE HUNG WINDOW PRODUCT APPROVAL 05-0729.03
 SUBMITTED EXPIRED ON 07/11/07. PROVIDE CURRENT PRODUCT
 APPROVAL.
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
 E) STORM SHUTTERS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE (SEE ATTACHED SAMPLE)AND KEY
 PLAN.ALSO,CLEARLY MARK ON SHUTTERS DRAWINGS
 SPECIFIC MOUNTING CONDITIONS (EG: WALL MOUNTED, ETC.)
 AND ANCHOR TYPE AND SPACING TO BE USED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQ'D BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 ***NOTE: PLEASE MAKE SURE NAME OF ENGINEER IS ON
 APPROVED AND REVIEWED STAMP.
  
 12- SHEET A1:
 A) REINFORCING STEEL SPECIFICATIONS SHOWN ON
 FOUNDATION SCHEDULE DON'T MATCH SPECS SHOWN ON
 FOUNDATION PLAN. REVISE AS REQUIRED TO MATCH.
 B) SPECIFY ATTIC ACCESS LOCATION AND SIZE TO COMPLY
 WITH SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 13- TYPICAL WALL SECTION A/A-2:
 A) SIZE OF FOOTING DOESN'T MATCH SIZE SHOWN ON
 FOUNDATION PLAN. REVISE AS REQ'D.
 B) REVISE SPECIFICATIONS FOR ROOF SHEATHINGNAILING
 SPACING ON ZONE 3 AREAS. SEE SEC. R803.2.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE AND REVISE AS REQ'D.
 C) CLARIFY SPECS FOR INTERIOR FURRING STRIPS SIZE.
 IS IT REALLY 2X4'S AT 24" O.C. WITH R11 INSULATION?.
 THIS IS TYP. THE SPECS FOR A FRAMED BUILDING. REVISE
 CLARIFY AS REQUIRED.
 ALSO,COORDINATE INFORMATION WITH THEENERGY
 CALCULATIONS.
 D) SPECIFY FIREBLOCKING AS REQ'D BE SEC. R602.1.2 OF
 2004 FLORIDA RESIDENTIAL CODE.
 E0 CLARIFY/REVISE SPECS FOR STUCCO FINISH OVER METAL
 HIGHRIB LATH.ARE THESE THE SPECS FOR THE SOFFIT. IF
 SO, THEN SHOW ARROW POINTING TO CORRECT LOCATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-16 Cont ID  
Sent By btrobaug Date 2007-11-16 Time 12:37 Rev Time 0.00
Received By btrobaug Date 2007-11-05 Time 07:49 Sent To M
Notes
2007-11-05 08:06:12 
  
  
 CALLED JOSEPH, HE SUBMITTED SAME PLANS FROM PREVIOUS
 REVIEW./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-09 Cont ID  
Sent By btrobaug Date 2007-08-09 Time 15:30 Rev Time 0.00
Received By btrobaug Date 2007-08-09 Time 11:59 Sent To M
Notes
2007-08-09 15:29:59 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PER 220.52(B) LAUNDRY CIRCUIT LOAD A LOAD OF NOT
 LESS THAN 1500 VOLT-AMPERES SHALL BE INCLUDED FOR EACH
 2-WIRE LAUNDRY BRANCH CIRCUIT INSTALLED AS REQUIRED BY
 210.11(C)(2). THIS LOAD SHALL BE PERMITTED TO BE
 INCLUDED WITH THE GENERAL LIGHTING LOAD AND SUBJECTED
 TO THE DEMAND FACTORS PROVIDED IN TABLE 220.42.
  
 2} 220.54 ELECTRIC CLOTHES DRYERS ? DWELLING UNIT(S)
 THE LOAD FOR HOUSEHOLD ELECTRIC CLOTHES DRYERS IN A
 DWELLING UNIT(S) SHALL BE EITHER 5000 WATTS
 (VOLT-AMPERES) OR THE NAMEPLATE RATING, WHICHEVER IS
 LARGER, FOR EACH DRYER SERVED.
  
 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES.
  
 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-13 Cont ID  
Sent By adarroug Date 2007-11-13 Time 11:35 Rev Time 0.00
Received By adarroug Date 2007-11-13 Time 11:35 Sent To Z
Notes
2007-11-13 11:36:05TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-31 Cont ID  
Sent By adarroug Date 2007-10-31 Time 15:05 Rev Time 0.00
Received By adarroug Date 2007-10-31 Time 15:05 Sent To Z
Notes
2007-10-31 15:06:12TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-29 Cont ID  
Sent By jgomez Date 2007-08-29 Time 18:00 Rev Time 0.00
Received By jgomez Date 2007-08-07 Time 17:31 Sent To Z
Notes
2007-08-07 17:32:04TO SFR RACK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-16 Cont ID  
Sent By tgordon Date 2007-11-16 Time 15:58 Rev Time 0.30
Received By tgordon Date 2007-11-16 Time 15:58 Sent To P
Notes
2007-11-16 16:06:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 8-10-07. ENERGY CALCULATIONS
 NEED TO BE ON FORM 600A-04R"R" , SEE 2004 FBC
 13-600.3.A. PLEASE CORRECT.
  
 2) AS NOTED IN LAST REVIEW 8-10-07. WHEN RESUBMITTING
 THE ENERGY CALCULATIONS HAVE THEM SIGNED AND DATED BY
 THE PREPARER AND THE "OWNER/AGENT" , SEE 2004 FBC
 13-600.3.A.
  
 3) AS NOTED IN LAST REVIEW 8-10-07 NOTE #4. THE
 BATHROOM WILL REQUIRE AN 50 CFM EXHAUST FAN, SEE 2004
 FBC/R R303.3 EXCEP., SHOW ON ELECTRICAL AND MECHANICAL
 (A/C) PLANS.
  
 4) AS NOTED IN LAST REVIEW 8-10-07 NOTE #5. PLEASE
 SUBMIT TWO COPIES OF ALL PLANS AND DOCUMENTS
 (MECHANICAL PLAN, ENERGY CALCULATIONS, AND COOLING LOAD
 CALCULATIONS), SEE 2004 FBC CITY WPB AMEND. 106.1.
  
 5)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING
 FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-10 Cont ID  
Sent By tgordon Date 2007-08-10 Time 13:36 Rev Time 0.25
Received By tgordon Date 2007-08-10 Time 13:36 Sent To P
Notes
2007-08-10 13:49:56PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, SEE
 2004 FBC 13-600.3.A. PLEASE CORRECT.
  
 2) WHEN RESUBMITTING THE ENERGY CALCULATIONS HAVE THEM
 SIGNED AND DATED BY THE PREPARER AND THE OWNER/AGENT,
 SEE 2004 FBC 13-600.3.A.
  
 3) ENERGY CAL'S. STATE UNDUCTED A/C SYSTEMS TO BE
 INSTALLED, PLEASE SUBMIT MECHANICAL PLANS SHOWING ALL
 A/C EQUIPMENT AND A EQUIPMENT LISTING WITH ALL
 PERTINENT INFORMATION ON IT, SEE 2004 FBC CITY WPB
 AMEND. 106.3.5.4 (10).
  
 4)THE BATHROOM WILL REQUIRE AN 50 CFM EXHAUST FAN, SEE
 2004 FBC/R R303.3 EXCEP., PLEASE CORRECT.
  
 5) PLEASE SUBMIT TWO COPIES OF ALL PLANS AND DOCUMENTS,
 SEE 2004 FBC CITY WPB AMEND. 106.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-28 Cont ID  
Sent By mperson Date 2007-11-28 Time 13:57 Rev Time 0.00
Received By mperson Date 2007-11-28 Time 13:57 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-08-24 Cont ID  
Sent By mperson Date 2007-08-24 Time 16:18 Rev Time 0.00
Received By mperson Date 2007-08-24 Time 16:18 Sent To B
Notes
2007-08-24 16:40:24DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWOFAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: NOT ALL TRAPS AND VENTS ARE SIZED ON SHEET A2
 PLUMBING RISER. PLEASE CORRECT AND RESUBMIT.
  
 2. SHEET A2 SANITARY ISOMETRIC PLUMBING RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN OF SHEET A1: PER
 FBC-2004 CHAPTER 1 SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. PLEASE CORRECT THE
 FOLLOWING ITEMS.
  
 A} THE KITCHEN SINK IS A DOUBLE BOWL SINK PLEASE
 INDICATE THIS ON THE PLUMBING RISER ON THE
 RESUBMITTAL.
  
 B} FLOOR PLAN ON SHEET A1 IS INDICATING A TUB BUT THE
 SANITARY ISOMETRIC RISER DIAGRAM IS INDICATING A
 SHOWER. PLEASE CLARIFY, CORRELATE AND CORRECT ON THE
 RESUBMITTAL.
  
 3. SHEET A2 SANITARY ISOMETRIC PLUMBING RISER DIAGRAM:
 PER FBC-2004 PLUMBING SECTION 708.3.5, A TWO-WAY
 CLEANOUT IS REQUIRED AT THE JUNCTION OF THE BUILDING
 DRAIN AND BUILDING SEWER. PLEASE INDICATE THIS CLEANOUT
 ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK ON
 THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2007-11-15 Cont ID  
Sent By choops Date 2007-11-15 Time 10:43 Rev Time 0.00
Received By choops Date 2007-11-15 Time 10:43 Sent To E
Notes
2007-11-15 10:47:23***FAILED - RESUB #2***
  
  
 1)PLANS STILL LABEL ROOMS AS: "KITCHEN, LIVING ROOM,
 DINING ROOM"THIS INDICATES THE INTENDED USE OF AS A
 SEPARATE DWELLING UNIT.REMOVE SUCH LABELS FROM PLANS
 AND REVISE.
  
 NOTE:NO SEPARATE DWELLING UNIT PERMITTED: NO
 RANGE/STOVE, NO FULL SIZE REFRIGERATOR PERMITTED.MUST
 MAINTAIN INTERIOR ACCESS WITH EXISTING STRUCTURE.NOT
 MORE THAN TWO UNRELATED PEOPLE MAY OCCUPY THE ENTIRE
 BUILDING (ADDITION AND EXISTING).SINGLE FAMILY LOW
 DENSITY (SF7) RESIDENTIAL ZONING DISTRICT.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2007-11-02 Cont ID  
Sent By choops Date 2007-11-02 Time 11:42 Rev Time 0.00
Received By choops Date 2007-11-02 Time 11:42 Sent To E
Notes
2007-11-02 11:45:58***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1)PROVIDE A FLOOR PLAN OF EXISTING RESIDENCE SHOWING
 CORRELATION BETWEEN ADDITION AND EXISTING.
  
 NOTE:**NO ACCESSORY DWELLING UNIT PERMITTED IN SF7
 ZONED DISTRICTS.**NO STOVE/OVEN PERMITTED, NO FULL
 SIZE REFRIGERATOR PERMITTED.MUST MAINTAIN INTERIOR
 ACCESS FROM THE PROPOSED TO THE EXISTING.
  
 2)SHOW ANY PROPOSED A/C EQUIPMENT, IF ANY, WITH
 SETBACKS TO THE PROPERTY LINES FROM THE EQUIPMENT.
  
 3)INDICATE ACTUAL SETBACK DIMENSIONS FROM THE
 PROPOSED TO ALL PROPERTY LINES.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 WHY DID YOU RESUBMIT?YOU HAVE NOT ADDRESSED ANY OF
 THESE COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-08 Cont ID  
Sent By jgomez Date 2007-08-29 Time 18:01 Rev Time 0.00
Received By choops Date 2007-08-08 Time 15:51 Sent To E
Notes
2007-08-08 15:57:59***FAILED***
  
  
 1)PROVIDE A FLOOR PLAN OF EXISTING RESIDENCE SHOWING
 CORRELATION BETWEEN ADDITION AND EXISTING.
  
 NOTE:**NO ACCESSORY DWELLING UNIT PERMITTED IN SF7
 ZONED DISTRICTS.**NO STOVE/OVEN PERMITTED, NO FULL
 SIZE REFRIGERATOR PERMITTED.
  
 2)SHOW ANY PROPOSED A/C EQUIPMENT, IF ANY, WITH
 SETBACKS TO THE PROPERTY LINES FROM THE EQUIPMENT.
  
 3)INDICATE ACTUAL SETBACK DIMENSIONS.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720