Plan Review Details - Permit 07080166
Plan Review Stops For Permit 07080166
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-01-10 Cont ID  
Sent By mcarsill Date 2008-01-10 Time 17:52 Rev Time 0.00
Received By mcarsill Date 2008-01-10 Time 17:44 Sent To  
Notes
2008-01-10 17:51:321. FLOOR PLAN STILL ILLUSTRATES THAT DOORS INTO THE
 COMPUTER ROOM SWING IN HOWEVER THE NOTES INDICATE THAT
 THE DOORS TO THE ROOM WILL SWING IN THE DIRECTION OF
 EXIT TRAVEL. THIS NOTE HAS BEEN PREVIOUSLY COMMENTED
 ON. PLEASE CORRELATE THESE TWO ITEMS SO THEY PROPERLY
 MATCH ONE ANOTHER.
  
 2. THE ENTIRE INSTALLATION IS SUBJECT TO FIELD
 INSPECTION AND TESTING BY THE INSTALLERS AND WITH THE
 FIRE RESCUE DEPARTMENT.
  
 3. A SEQUENCE OF OPERATION SHEET IS TO BE PROVIDED TO
 THE OWNER AT TIME OF ACCEPTANCE SO THAT IT CAN BE
 CONSULTED WHENEVER NECESSARY.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-09-10 Cont ID  
Sent By mcarsill Date 2007-09-10 Time 13:06 Rev Time 0.00
Received By mcarsill Date 2007-09-10 Time 12:35 Sent To  
Notes
2007-09-10 13:06:361. SINCE THE BUILDING IS FIRE SPRINKLER PROTECTED, THE
 ROOM WHERE THE PROPOSED FM 200 SYSTEM IS BEING PLANNED
 MUST BE EQUIPPED WITH AUTOMATIC FIRE SPRINKLER HEADS
 CONNECTED TO THE MAIN BUILDING'S SYSTEM. THE SERVER
 ROOM WILL CONTAIN THE FM 200 SYSTEM AND THE REQUIRED
 FIRE SPRINKLER PROTECTION THAT IS REQUIRED PER NFPA
 75.
  
 2. THE PRORPOSED FM 200 SYSTEM SHALL BE INSTALLED IN AN
 APPROVED MANNER AND COMPLY WITH ALL OF THE TECHNICAL
 REQUIREMENTS OF NFPA 2001 AND ALL OTHER APPLICABLE
 CODES AND STANDARDS.
  
 3. FLOOR PLAN NOTES INDICATES THAT "ALL DOORS SWING
 OUT" BY OTHERS. PLANS DISPLAY DOORS SWINGING IN.
  
 4. THE FM 200 SYSTEM MUST BE INSPECTED, TESTED, AND
 APPROVED BY THIS OFFICE AS WELL AS THE MECHANICAL AND
 PLUBMING DEPARTMENTS PRIOR TO RECEIVING FINAL
 APPROVAL.
  
 5. ALL WARNING DEVICES ILLUSTRATED ON THE PLANS SHALL
 PROVIDE THE WARNING MESSAGES OR SIGNALS AS INTENDED.
  
 6. ALL WORK SUBJECT TO FIELD INSPECTION.
  
 7. PLANS PROVIDES THE NECESSARY INSTALLATION AND
 TESTING INFORMATION FOR THE SYSTEM.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 15:34 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 15:34 Sent To FIRE
Notes
2007-08-07 17:23:14SENT TO FIRE BOX