Plan Review Details - Permit 07080166
| Plan Review Stops For Permit 07080166 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-01-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2008-01-10 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2008-01-10 |
Time |
17:44 |
Sent To |
|
|
| Notes |
| 2008-01-10 17:51:32 | 1. FLOOR PLAN STILL ILLUSTRATES THAT DOORS INTO THE | | | COMPUTER ROOM SWING IN HOWEVER THE NOTES INDICATE THAT | | | THE DOORS TO THE ROOM WILL SWING IN THE DIRECTION OF | | | EXIT TRAVEL. THIS NOTE HAS BEEN PREVIOUSLY COMMENTED | | | ON. PLEASE CORRELATE THESE TWO ITEMS SO THEY PROPERLY | | | MATCH ONE ANOTHER. | | | | | | 2. THE ENTIRE INSTALLATION IS SUBJECT TO FIELD | | | INSPECTION AND TESTING BY THE INSTALLERS AND WITH THE | | | FIRE RESCUE DEPARTMENT. | | | | | | 3. A SEQUENCE OF OPERATION SHEET IS TO BE PROVIDED TO | | | THE OWNER AT TIME OF ACCEPTANCE SO THAT IT CAN BE | | | CONSULTED WHENEVER NECESSARY. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2007-09-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2007-09-10 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2007-09-10 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2007-09-10 13:06:36 | 1. SINCE THE BUILDING IS FIRE SPRINKLER PROTECTED, THE | | | ROOM WHERE THE PROPOSED FM 200 SYSTEM IS BEING PLANNED | | | MUST BE EQUIPPED WITH AUTOMATIC FIRE SPRINKLER HEADS | | | CONNECTED TO THE MAIN BUILDING'S SYSTEM. THE SERVER | | | ROOM WILL CONTAIN THE FM 200 SYSTEM AND THE REQUIRED | | | FIRE SPRINKLER PROTECTION THAT IS REQUIRED PER NFPA | | | 75. | | | | | | 2. THE PRORPOSED FM 200 SYSTEM SHALL BE INSTALLED IN AN | | | APPROVED MANNER AND COMPLY WITH ALL OF THE TECHNICAL | | | REQUIREMENTS OF NFPA 2001 AND ALL OTHER APPLICABLE | | | CODES AND STANDARDS. | | | | | | 3. FLOOR PLAN NOTES INDICATES THAT "ALL DOORS SWING | | | OUT" BY OTHERS. PLANS DISPLAY DOORS SWINGING IN. | | | | | | 4. THE FM 200 SYSTEM MUST BE INSPECTED, TESTED, AND | | | APPROVED BY THIS OFFICE AS WELL AS THE MECHANICAL AND | | | PLUBMING DEPARTMENTS PRIOR TO RECEIVING FINAL | | | APPROVAL. | | | | | | 5. ALL WARNING DEVICES ILLUSTRATED ON THE PLANS SHALL | | | PROVIDE THE WARNING MESSAGES OR SIGNALS AS INTENDED. | | | | | | 6. ALL WORK SUBJECT TO FIELD INSPECTION. | | | | | | 7. PLANS PROVIDES THE NECESSARY INSTALLATION AND | | | TESTING INFORMATION FOR THE SYSTEM. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-01-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-04 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-04 |
Time |
15:34 |
Sent To |
FIRE |
|
| Notes |
| 2007-08-07 17:23:14 | SENT TO FIRE BOX |
|
|
|