Plan Review Details - Permit 07080141
Plan Review Stops For Permit 07080141
Review Stop AD ADDRESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2007-08-06 13:00:31PLEASE CREATE PARCEL NUMBER FOR COMMON AREA OF BLDG
 OWNED BY CHARTER CENTER CONDO...THIS INFO IS NOT IN OUR
 SYS OR THE PROPERTY APPRAISER'S SYS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-19 Cont ID  
Sent By mjacobs Date 2007-09-19 Time 07:42 Rev Time 0.00
Received By mjacobs Date 2007-09-14 Time 11:24 Sent To  
Notes
2007-09-18 06:13:34BUILDING PLAN REVIEW
 PERMIT: 07080141
 ADD: 5730 CORPORATE WAY
 CONT: LTL BUILDERS INC.
 TEL: (561) 478-1845
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 . -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
  
 3)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. SUBMIT PRODUCT APPROVAL FOR
 THE METAL ROOFING SYSTEM INDICATED.
  
 4)PROVIDE A WALL LEGEND SHOWING CLEARLY WHICH WALLS
 WILL BE DEMOED AND WHICH WALLS WILL REMAIN. ON SHEET 2
 OF 4, WILL THE DOUBLE DOORS AND WALLS IN THE FOYER AREA
 BE REMOVED? IF SO, PRODUCT APPROVALS WILL BE REQUIRED
 FOR THOSE DOORS AND MULLIONS.
  
 5)THE SCALE INDICATED ON THE DRAWINGS DOES NOT MATCH
 THE DIMENSION SHOWN. THE DIMENSIONS SHALL MATCH THE
 SCALE INDICATED. THE PLANS SHALL BE DRAWN TO A MINIMUM
 1/8 INCH SCALE. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. WPB AMENDMENTS 106.1.3.
  
 6)SUBMIT THE NORTH, SOUTH, EAST AND WEST ELEVATIONS.
  
 7)WAS THE ENTRY TOTALLY COVERED INCLUDING THE TRELLIS
 AREA? IF NOT, SHOW THE OPEN AREA ABOVE ON THE
 DRAWINGS.
  
  
 8)FBC 1503.4. UNLESS ROOFS ARE SLOPED TO DRAIN OVER
 EDGES, DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS
 SHALL COMPLY WITH THE FBC PLUMBING CH. 11. INDICATE ON
 THE PLANS THE DRAINAGE SYSTEM OF THE NEW ROOF.
  
 9)PROVIDE A FRAMING HEADER DETAIL FOR THE FOUR NEW
 WINGUARDFIXED WINDOWS.
  
 10)ON SHEET T1 OF THE TRUSS PLACEMENT PLAN, INDICATE
 WHICH TRUSSES ARE DESIGN FOR THE ENCLOSE SECTION OF THE
 BUILDING AND THE TRUSSES DESIGN FOR THE OPEN SECTION.
 THE TRUSSES SHALL BE LABELED TO SHOW THE CORRECT
 PLACEMENT OF EACH TRUSS. THE FRONT AND REAR SECTION OF
 THE ROOF SHALL ALSO BE INDICATED.
  
 11)SHOW A CONNECTION AND FRAMING DETAIL OF THE NEW
 2X8 METAL STUDS AND INDICATE THE LOAD BEARING CAPACITY
 OF THE BEAM WHERE THE WALL IS CONSTRUCTED.
  
  
 12) 2004 FL. BLDG CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE
 CONSTRUCTION DRAWINGS,
 1) - BASIC WIND SPEED, MPH
 2) - WIND IMPORTANCE FACTOR, & BUILDING CATEGORY
 3) - WIND EXPOSURE
 4) - INTERNAL PRESSURE COEFFICIENT,
 5) - COMPONENTS & CLADDING, THE DESIGN WIND PRESSURES
 IN TERMS OF PSF.
  
 13)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-04 Cont ID  
Sent By dpalmer Date 2007-09-04 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2007-09-04 Time 19:21 Sent To  
Notes
2007-09-04 19:34:25** DENIED**
  
 1) NOTE: PLEASE SEE THE INCORRECT ELECTRICAL CODE IS
 BEING REFLECTED ON PLANS.
 PLEASE KNOW ANY PERMIT APPLICATIONS APPLIED FOR AFTER
 DECEMBER 8TH, 2006 PLACES PROJECTS UNDER THE 2005 NEC/
 NFPA-70
  
 2) NOTE: PLEASE SUBMIT INFORMATION ON ANY EXTERIOR
 LIGHTING BEING REPAIRED OR REPLACED DU TO DAMAGE AS
 NOTED.
 PLANS MENTIONS THE NEC IS PART OF THE SCOPE ON PLANS
 HOWEVER NO INFORMATION WAS LOCATED.
 FBC 106.3.5.1.2.
  
 PLEASE KNOW THAT ANY NEW LIGHTING INSTALLED OUTSIDE
 WOULD BE REQUIRED TO COMPLY WITH FBC 13-415.2.ABC.1.3
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By mwennerg Date 2007-09-27 Time 10:39 Rev Time 0.00
Received By mwennerg Date 2007-09-27 Time 10:39 Sent To  
Notes
2007-09-27 10:42:50***DENIED***
  
 1) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 2) WILL ANY EXISTING BUILDING FIRE PROTECTION EQUIPMENT
 BE IMPACTED BY THIS WORK?
  
 3) WILL THIS WORK IMPACT EXISTING BUILDING ADDRESS?
  
 4) WHAT PRECAUTIONS ARE BE TAKEN TO EXIT PERSONS FROM
 THE BUILDING DURING THIS WORK?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-27 Cont ID  
Sent By mwennerg Date 2007-09-27 Time 10:48 Rev Time 0.00
Received By mwennerg Date 2007-08-07 Time 21:08 Sent To  
Notes
2007-09-04 12:26:29TO "COMM" BD#9
2007-08-07 21:08:39WAITING FOR COMM BOARD.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-09-24 Cont ID  
Sent By jleech Date 2007-09-24 Time 07:27 Rev Time 0.00
Received By jleech Date 2007-09-24 Time 07:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-10 Cont ID  
Sent By choops Date 2007-09-10 Time 16:53 Rev Time 0.00
Received By choops Date 2007-09-10 Time 16:53 Sent To  
Notes
2007-09-10 16:57:27***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE SCOPE OF WORK WITH DIMENSIONS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720