Plan Review Details - Permit 07080129
Plan Review Stops For Permit 07080129
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-10-05 Cont ID  
Sent By mwennerg Date 2007-10-05 Time 10:39 Rev Time 0.00
Received By mwennerg Date 2007-10-05 Time 10:39 Sent To  
Notes
2007-10-05 10:42:12 
 ***PROVISO***
  
 THE FIRE ALARM EQUIPMENT SHALL BE INSTALLED TO MEET
 VOLTAGE, TEMPERATURE AND HUMIDITY REQUIREMENTS IN
 ACCORDANCE WITH NFPA 72.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-17 Cont ID  
Sent By mawillia Date 2007-09-17 Time 18:55 Rev Time 0.00
Received By mawillia Date 2007-09-17 Time 18:31 Sent To  
Notes
2007-09-17 18:50:26*****DENIED*****
  
  
 THE PLAN AS SUBMITTED GIVES THE SPECIFICATION
 INFORMATION FOR THE ALARM PANEL THAT IS TO BE
 INSTALLED.WHAT IS NEEDED IS THE PLAN TO SHOW THE
 LOCATION OF THE OBSELETE PANEL AND THE LOCATION OF THE
 NEW PANEL AND ANY OTHER NEWLY ASSOCIATED
 DEVICES/EQUIPMENT TO BE INSTALLED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-08-15 Cont ID  
Sent By mawillia Date 2007-08-15 Time 15:30 Rev Time 0.00
Received By mawillia Date 2007-08-15 Time 15:13 Sent To  
Notes
2007-08-15 15:29:54*****DENIED*****
  
  
 THE PLAN AS SUBMITTED GIVES THE SPECIFICATION
 INFORMATION FOR THE ALARM PANEL THAT IS TO BE
 INSTALLED.WHAT IS NEEDED IS THE PLAN TO SHOW THE
 LOCATION OF THE OBSELETE PANEL AND THE LOCATION OF THE
 NEW PANEL AND ANY OTHER NEWLY ASSOCIATED
 DEVICES/EQUIPMENT TO BE INSTALLED IN ADDITION TO THE
 SPEC SHEETS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 11:33 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 11:33 Sent To FIRE
Notes
2007-09-24 11:33:39TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 11:25 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 11:25 Sent To FIRE
Notes
2007-08-29 11:25:55TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-15 Cont ID  
Sent By mawillia Date 2007-08-15 Time 15:14 Rev Time 0.00
Received By mawillia Date 2007-08-07 Time 12:38 Sent To  
Notes
2007-08-07 12:39:06TO FIRE BOX./WRT.