Plan Review Details - Permit 07080096
Plan Review Stops For Permit 07080096
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-21 Cont ID  
Sent By shill Date 2007-09-21 Time 18:13 Rev Time 0.00
Received By shill Date 2007-09-21 Time 18:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-11 Cont ID  
Sent By shill Date 2007-09-11 Time 16:10 Rev Time 0.00
Received By shill Date 2007-09-11 Time 16:10 Sent To  
Notes
2007-09-11 16:19:34****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)ADDRESSED.
  
 2.)PARTIALLY ADDRESSED, BUT PREVIOUS COMMENT BROUGHT
 YOUR ATTENTION TO EDGE DISTANCE REQUIREMENT, " EDGE
 DISTANCE WAS NOT SPECIFIED; PRIOR TO SUBMITTAL PLEASE
 MAKE NOTE OF THE BOX ON SHEET 14 WHICH REQUIRES A
 FACTOR FOR EDGE DISTANCE LESS THAN 3 1/2"."
  
 A 2 1/2" EDGE DISTANCE REQUIRES A FACTOR OF .66, SEE
 SHEET 14.
  
 3.)ADDRESSED.
  
 4.)ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-29 Cont ID  
Sent By shill Date 2007-08-29 Time 12:28 Rev Time 0.00
Received By shill Date 2007-08-29 Time 12:28 Sent To  
Notes
2007-08-29 12:29:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.)COMPLETE THE INSTALLATION SCHEDULE.TWO SETS
 REQUIRED.ONLY ONE INCOMPLETE SCHEDULE SUBMITTED.
  
 2.)SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH ANCHOR SCHEDULE, IN THIS CASE A THROUGH L.EDGE
 DISTANCE WAS NOT SPECIFIED; PRIOR TO SUBMITTAL PLEASE
 MAKE NOTE OF THE BOX ON SHEET 14 WHICH REQUIRES A
 FACTOR FOR EDGE DISTANCE LESS THAN 3 1/2".
  
 3.)SPANS SHOULD BE BLADE LENGTH.THE SPANS YOU HAVE
 SPECIFIED ARE MUCH LARGER THAN OPENING SIZE AND
 ANCHORING IS NOT COMPLIANT FOR HIGHLIGHTED CONNECTION
 TYPES.YOU'VE HIGHLIGHTED 5', BUT 108" IS GREATER THAN
 5'.
  
 4.)POSITIVE DESIGN PRESSURES ARE TOO LOW.YOU ARE
 USING POSITIVE PRESSURES FROM PARTIALLY ENCLOSED
 CONDITION, BUT THIS BUILDING IS A FULLY ENCLOSED
 BUILDING.NEGATIVE PRESSURES FOR A PARTIALLY ENCLOSED
 BUILDING ARE MORE STRINGENT THAN ENCLOSED, SO USE OF
 NEGATIVE PRESSURES FOR PARTIALLY ENCLOSED CONDITIONS ON
 A FULLY ENCLOSED BUILDING IS ACCEPTABLE (EXCEEDS CODE
 COMPLIANCE).
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 14:00 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 14:00 Sent To B
Notes
2007-09-20 14:00:37TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-07 Cont ID  
Sent By adarroug Date 2007-09-07 Time 12:29 Rev Time 0.00
Received By adarroug Date 2007-09-07 Time 12:29 Sent To B
Notes
2007-09-07 12:29:39TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-29 Cont ID  
Sent By shill Date 2007-08-29 Time 12:30 Rev Time 0.00
Received By shill Date 2007-08-06 Time 13:33 Sent To  
Notes
2007-08-06 13:33:17TO "MISC" BOX#1