Plan Review Details - Permit 07080087
Plan Review Stops For Permit 07080087
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-16 Cont ID  
Sent By jwitmer Date 2007-09-16 Time 18:39 Rev Time 0.55
Received By jwitmer Date 2007-09-16 Time 18:32 Sent To  
Notes
2007-09-16 18:53:15BUILDING PLAN REVIEW
 PERMIT: 07080087
 ADD: 2000 PALM BEACH LAKES - ROOFTOP
 CONT: MACTEC ENGINEERING & CONSULTING
 TEL: (305)826-5588
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET T1 NEEDS TO BE SEALED AND DATED BY THE DESIGN
 PROFESSIONAL. PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4) MISSING INFORMATION ON WIND DESIGN, 2004 FL. BLD
 CODE 1603.1.4 THE FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTIONDRAWINGS,
 ASCE 7-02
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY NOTE A
 1.15 IMPORTANCE FACTOR SHOULD BE USED SINCE THE
 ANTENNAS FOR CELL PHONES WILL BE PART OF HURRICANE
 RECOVERY EFFORTS!
 3)- WIND EXPOSURE
 4) POSITIVE & NEGATIVE PSF
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-31 Cont ID  
Sent By dpalmer Date 2007-08-31 Time 15:43 Rev Time 0.00
Received By dpalmer Date 2007-08-31 Time 15:43 Sent To  
Notes
2007-08-31 15:43:43** DENIED**
  
 1) NOTE: PLEASE BE SURE ELECTRICAL AND ARCHITECTURAL
 SHEETS STATE THE FOLLOWING MINIMUM CODES.
 2006 FBC W/2006 REVISIONS.
 2005 NFPA-70.
 2003 NFPA-101
  
 ** SOME OF THESE ARE ALREADY ON SOME SHEETS.
  
 2) NOTE: PLEASE BE SURE ALL SHEETS ARE SIGNED, DATED
 AND SEALED BY THE RESPECTIVE DESIGN PROFESSIONALS.(SEE
 T-1)
  
 3) NOTE:PLEASE KNOW BASED ON THE PLANS SUBMITTED, THE
 VALUE FOR THE COMPLETE SCOPE OF WORK SHALL COMPLY WITH
 THE FBC 108.3 TO INCLUDE ALL LABOR, MATERIALS,
 EQUIPMENT, DESIGN COST ETC AS STATED IN THE CODE.
 MINIMUM VALUATION TABLES MAY BE USED FOR SCOPE OF WORK
 AS SHOWN ON PLANS AND MAY ALSO BE ADJUSTED BY THIS
 OFFICE ONCE THE ACTUAL COMPLETE SCOPE HAS BEEN
 DETERMINED.
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-02 Cont ID  
Sent By mawillia Date 2007-10-02 Time 15:06 Rev Time 0.00
Received By mawillia Date 2007-10-02 Time 14:41 Sent To  
Notes
2007-10-02 15:06:37*****PROVISO*****
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 ALL OTHER REVIEWERS HAVE BEEN SATISFIED.THE
 ERECTION/INSTALLATION OF THE ANTENNA SHALL IN NO WAY
 CAUSE PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE ASSEMBLYAS PER NFPA 101 - 2003 EDITION
 7.1.3.2.1 (6)

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-02 Cont ID  
Sent By mawillia Date 2007-10-02 Time 14:42 Rev Time 0.00
Received By mawillia Date 2007-08-06 Time 13:41 Sent To  
Notes
2007-08-31 08:28:12TO "COMM" BD#13
2007-08-06 13:41:37WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By choops Date 2007-09-11 Time 16:44 Rev Time 0.00
Received By choops Date 2007-09-11 Time 16:44 Sent To  
Notes
2007-09-11 16:45:40***FAILED***
  
  
 1)PRIOR THE ISSUANCE OF A BUILDING PERMIT, THE
 APPLICATION MUST UNDERGO AN INFORMAL SITE PLAN REVIEW
 THROUGH THE PLANNING AND ZONING DEPARTMENT.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720