| Plan Review Stops For Permit 07080080 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2009-05-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-05-06 |
Time |
08:01 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2009-05-06 |
Time |
08:01 |
Sent To |
PC |
|
| Notes |
| 2009-05-06 08:03:25 | DESIGN CRITERIA FOR LIGHT POLES AND BOLT CONNECTION, | | | FOUNDATION BY OTHERS | | | | | | NOTE; REVISED ACCESSIBLE RAMP PULLED BY CONTRACTOR | | | REPRESENTATIVE DAVID TREMBLE, WILL REVISE AND RESIBMIT, | | | WOULD HAVE FAILED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2009-03-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-03-24 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-03-24 |
Time |
10:06 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-09-29 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-09-29 |
Time |
07:25 |
Sent To |
|
|
| Notes |
| 2008-09-29 13:46:46 | PROVISOR: | | | THE TRUSS CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A | | | REGISTERED DESIGN PROFESSIONAL AND SHALL BE PROVIDED TO | | | THE BUILDING OFFICIAL AND APPROVED PRIOR TO | | | INSTALLATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-04-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-04-16 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-04-15 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2008-04-24 14:31:34 | BUILDING PLAN REVIEW #3 | | | PERMIT: 07080080 | | | ADD: 301 LAMBERTON DR. | | | CONT: THE WEITZ CO. | | | TEL: (561)719-0102 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 3RD4-16-08 | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | **NOTED** | | | 2) THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | **3RDREVIEW.** | | | 3)1802.2.1 QUESTIONABLE SOIL. WHERE THE | | | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE | | | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS | | | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE | | | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH | | | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF | | | SECTIONS 1802.4 THROUGH 1802.6. THIS IS A QUESTIONABLE | | | SOIL AREA SO PLEASE PROVIDE THE SOIL REPORT. | | | | | | 4) OK | | | 5)OK | | | 6)OK | | | 7)OK | | | 8)OK | | | 9)OK | | | 10)OK | | | 11)OK | | | | | | 3RDREVIEW | | | 12)THE ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE | | | FOLLOWING ITEMS. | | | ____1)CONTRACTOR IS TO PROVIDE THE FOLLOWING | | | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY: | | | MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF | | | EACH ROOF TYPE | | | ____ 2) FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | REQUIRED IN ADDITION TO THE EVALUATION REPORT | | | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG | | | _XX_ 3) FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY | | | YOU ARE USING.ALSO INDICATE WHICH FASTENER IF THE | | | OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. | | | _XX_4)FOR THE FLAT DECK, SPECIFY THE ENHANCED | | | FASTENING FOR CORNER AND PERIMETER ZONES. | | | _XX_5)SEE PRODUCT LIMITATION #7.CALCULATIONS | | | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF | | | CONSULTANT REQUIRED FOR ENHANCED FASTENING. | | | XX6) THE SYSTEM PROVIDED INDICATES LIMITATION #9, NO | | | ENHANCED FASTENING IS ALLOWED. | | | | | | 13)OK | | | | | | 3RDREVIEW | | | 14)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 15)OK | | | 16)OK | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | (561) 805-6676 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-02-14 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-02-14 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-02-13 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2008-02-14 15:56:27 | BUILDING PLAN REVIEW | | | PERMIT: 07080080 | | | ADD: 301 LAMBERTON DR. | | | CONT: THE WEITZ CO. | | | TEL: (561)719-0102 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND 2-14-08 | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | **NOTED** | | | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | **2ND REVIEW.** | | | 3)1802.2.1 QUESTIONABLE SOIL. WHERE THE | | | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE | | | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS | | | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE | | | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH | | | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF | | | SECTIONS 1802.4 THROUGH 1802.6. THIS IS A QUESTIONABLE | | | SOIL AREA SO PLEASE PROVIDE THE SOIL REPORT. | | | | | | 4) 2ND REVIEW **NOTED** | | | HOWEVER, THE USE AND OCCUPANCY, INDICATED ON THE | | | DRAWINGS (A-3) DOES NOT CORRESPOND WITH THE MAIN | | | STRUCTURE. | | | | | | **2ND REVIEW.** | | | 5)SHEET S1.2 THE INTERNAL PRESSURE COEFFICIENT WAS | | | CHANGED TO 0.55 FOR PARTIALLY ENCLOSED BUILDINGS, | | | HOWEVER THE DESIGN CRITERIA ON S1.2 REFERS TO THE | | | BUILDING AS AN ENCLOSED BUILDING. AS STATED IN THE | | | FIRST REVIEW, THERE ARE SCREENS INDICATED ON EACH | | | ELEVATION OF THE BUILDING. WITHOUT THE INSTALLATIONS OF | | | WINDOWS, THE SCREENS WILL ALLOW THE PRESSURES TO BUILD | | | IN THE BUILDING DURING HURRICANES /TORNADO OR OTHER | | | NATURAL DISASTERS. | | | | | | 6)OK | | | 7)OK | | | | | | 2ND REVIEW **NOTED** | | | 8)THE STRUCTURAL SHEETS DO NOT PROVIDE UPLIFT FORCES | | | TO BE RESISTED OR THE TYPE OF HARDWARE TO BE USED TO | | | RESIST UPLIFT AND LATERAL LOADS. PROVIDE A BEAM AND | | | COLUMN SCHEDULE INDICATING THE SIZE OF EACH COLUMN AND | | | BEAM. WHAT IS THE SIZE OF L-1 / L-2 AND L-3? | | | | | | 2ND REVIEW | | | 9)FBC 1609.1.4 COMPONENTS & CLADDING, PROVIDE 2 | | | COPIES (3 IF THRESHOLD OR RESIDENT INSPECTOR) OF | | | PRODUCTS TESTING REPORTS, MISSING REPORTS ARE AS | | | FOLLOWS | | | A] TRUSS ANCHORS OK | | | B] WALL LOUVERS | | | C} PANEL WALL SYSTEMS-SCREEN (NOTE: DELETED FROM | | | PLANS) | | | D] TECO POST ANCHORS AND TECO POST CAPS. | | | | | | 10)OK | | | | | | 2ND REVIEW. | | | 11)WPB ADMIN CODE 106.3* THOSE PRODUCTS WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FORJURISDICTIONAL APPROVAL.**ALL SETS OF | | | PRODUCT APPROVAL SHALL BE APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. ONLY ONE SET HAS THE APPROVAL OF | | | THE DESIGNER.** | | | | | | 2ND REVIEW | | | 12)THE ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE | | | FOLLOWING ITEMS. | | | ____1)CONTRACTOR IS TO PROVIDE THE FOLLOWING | | | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY: | | | MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF | | | EACH ROOF TYPE | | | ____ 2) FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | REQUIRED IN ADDITION TO THE EVALUATION REPORT | | | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG | | | _XX_ 3) FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY | | | YOU ARE USING.ALSO INDICATE WHICH FASTENER IF THE | | | OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. | | | _XX_4)FOR THE FLAT DECK, SPECIFY THE ENHANCED | | | FASTENING FOR CORNER AND PERIMETER ZONES. | | | _XX_5)SEE PRODUCT LIMITATION #7.CALCULATIONS | | | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF | | | CONSULTANT REQUIRED FOR ENHANCED FASTENING. | | | XX6) THE SYSTEM PROVIDED INDICATES LIMITATION #9, NO | | | ENHANCED FASTENING IS ALLOWED. | | | | | | 13)OK | | | | | | 2ND REVIEW | | | 14)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 15)OK | | | 16)OK | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | (561) 805-6676 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-09-16 |
Time |
20:38 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2007-09-16 |
Time |
20:36 |
Sent To |
|
|
| Notes |
| 2007-09-16 21:40:53 | HAWTHORN HOTEL POOL HOUSE | | | 301 LAMBERTON DR | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07080080 | | | ADD: 301 LAMBERTON DR | | | CONT: THE WEITZ CO. | | | TEL: (561)719-0102 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) FBC 1802.2.1 QUESTIONABLE SOILS, WHERE THE | | | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE | | | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS | | | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE | | | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH | | | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF | | | SECTIONS 1802.4 THROUGH 1802.6 . | | | | | | 4) SHEET T1.1 THE MINIMUM BUILDING TYPE IS INDICATED AS | | | TYPE III-B I BELIEVE THIS IS THE MINIMUM TYPE FOR THE | | | HOTEL, PLEASE PROVIDE THE POOL HOUSE MINIMUM BUILDING | | | TYPE SEE TABLE 503. | | | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT | | | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | | DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINEDIN CHAPTER 6, | | | TABLE 601 & TABLE 503. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | | | | 5)S1.2 INDICATES THIS IS A ENCLOSED BUILDING BUT | | | THERE ARE SCREENS NOT WINDOWS IN THE BUILDING,A | | | ALLOWING PRESSURES TO BUILD IN THE BUILDING, THE | | | APPLICABLE INTERNAL PRESSURE COEFFICIENT WOULD NOT BE | | | +-.18 FOR A PARTIALLY ENCLOSED BUILDING. | | | | | | 6)SHEET S1.1 FOUNDATION DETAIL INDICATES IN CERTAIN | | | BLOCK CELLS THERE IS TO BE 4 # 5 BARS, IS THIS CORRECT? | | | IF WHERE ARE THE REQUIRED HOOPS FOR A 4 BAR COLUMN? | | | | | | 7) PLEASE COORDINATE THE ARCHITECTURAL SHEETS AND | | | STRUCTURAL, A3.3 INDICATES THE USE OF WOOD BEAMS OVER | | | THE VARIOUS OPENINGS WHERE AS THE STRUCTURAL SHEETS | | | INDICATE THE USE OF ANGLES AS LINTELS? PLEASE PROVIDE | | | ADDITIONAL INFORMATION. | | | | | | 8) THE STRUCTURAL SHEETS DO NOT PROVIDE UPLIFT FORCES | | | TO BE RESISTED NOR THE TYPE OF HARDWARE TO BE USED TO | | | RESIST UPLIFT AND LATERAL LOADS. | | | | | | 9) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) | | | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) TRUSS ANCHORS | | | B)WALL LOUVERS | | | C) PANEL WALL SYSTEMS- SCREENS | | | | | | 10)PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR | | | SITE SPECIFIC FORM PER RULE 9B-72. | | | | | | 11)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | 12) THIS ROOF IS MISSING OR NOT IN | | | COMPLIANCE WITH THE FOLLOW ITEMS: | | | ___ CONTRACTOR DID NOT PROVIDE THE MEANROOF | | | HEIGHT. | | | ___ CONTRACTOR DID NOT INDICATE THE ROOFPITCH. | | | _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE | | | USED. | | | _XX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE | | | _2&3__ . | | | _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7, | | | SHOULD THE FASTENER | | | RESISTANCE BE LESS THAN THATREQUIRED, AS | | | DETERMINED BY THEBUILDING OFFICIAL, A REVISED | | | FASTENER SPACING, PREPARED , SIGNEDAND SEALED BY | | | A FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED | | | ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE | | | SUBMITTED. | | | ___THE SYSTEM PROVIDED INDICATESLIMITATION# 9, | | | NO ENHANCEDFASTENING ALLOWED. | | | | | | 13)SHEET A2.1 INDICATES THE USE OF A DOWN SPOUT BUT | | | NO SPLASH BLOCK.1503.6 PROTECTION AGAINST DECAY AND | | | TERMITES. | | | CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT | | | LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, | | | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR | | | SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON | | | ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) | | | HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON | | | A ROOF ABOVE ANOTHER ROOF. | | | | | | 14)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY | | | OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE INFORMATION. | | | | | | 15 ) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION | | | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A | | | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF | | | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO | | | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE | | | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS | | | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS | | | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, | | | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE | | | STORAGE OF CONSTRUCTION | | | MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL NOT | | | ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE FLOWS | | | SERVING | | | ADJACENT PROPERTIES, & MAY REQUIRE SPECIAL DRAINAGE | | | DESIGN COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE | | | THE | | | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, | | | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW | | | RESIDENTIAL | | | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, | | | DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING | | | PROPERTIES RESULTING | | | IN A DECREASE IN EXCESS OF 800SQ FT OF PERMEABLE LAND | | | AREA ON ANY PARCEL SHALL AS A PERMIT CONDITION, PROVIDE | | | A | | | PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY | | | INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON | | | COMPLETION OF THE | | | IMPROVEMENT, A CERTIFICATION FROM A LICENSED ENGINEER | | | SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE | | | APPROVAL OF THE FINAL INSPECTION. | | | | | | 16 ) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE | | | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED | | | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR | | | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. | | | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE | | | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH | | | CONSTRUCTION MATERIALS, | | | EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE | | | CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO | | | MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS, | | | EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR | | | PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAILS TO | | | COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS | | | EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A HURRICANE | | | WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A FINE NOT TO | | | EXCEED $500.00. IN ADDITION TO THE ABOVE, A LICENSED | | | CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT | | | TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS CHAPTER. | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC | | | REQUIREMENT SHALL BE APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-10-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-03 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-03 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2008-10-03 15:10:47 | NEW ELECTRICAL PLANS, SAME SCOPE OF WORK. POOL HOUSE | | | ONLY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-04-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-04-08 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-04-08 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2008-04-08 12:20:26 | ALL NEW ELECTRICAL PLANS. | | | | | | REDLINED 2005 NEC. | | | SCOPE OF WORK FOR POOL HOUSE ONLY! |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-01-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-30 |
Time |
19:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-30 |
Time |
19:14 |
Sent To |
|
|
| Notes |
| 2008-01-30 19:15:53 | *** REDLINED ** | | | | | | E-2 SITE PLAN TO BE REVISED BEFORE FINAL AS THIS DOES | | | NOT MATCH WITH ALL ITEMS ACTUALLY INSTALLED ON-SITE TO | | | DATE. | | | | | | PLANS FOR POOL HOUSE ONLY, NOT FOR POOL OR DECK. | | | ALL STEEL AND BONDING SHALL MEET 680.26 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-09-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-04 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-04 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2007-09-04 15:47:27 | | | | | | | ** DENIED ** | | | | | | 1) NOTE: PLEASE SEE THE ADDRESS WHICH HAS NOW BEEN | | | ASSIGNED BY THE CITY OF WEST PALM BEACH AND AS APPLIED | | | IS 301 LAMBERTON. | | | PLEASE ADJUST TITLE BLOCKS FOR LOCATION. | | | FAC 61G1-16.004, FAC 61G15-23.002 | | | | | | | | | 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | | | | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED | | | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS | | | NOT MADE BY OTHER TRADE(S). | | | | | | 3) NOTE: PLEASE KNOW AS THE PRIMARY BUILDING DOES NOT | | | YET HAVE A CERTIFICATE OF OCCUPANCY AND THE DESIGNER OF | | | RECORD FOR THE ARCHITECTURAL SHEETS IS NOW NEW, PLEASE | | | BE SURE THESE PLANS WHICH DIRECTLY AFFECT THE PROJECT | | | CONTAIN A *SHOP DRAWING* REVIEW STAMP. | | | PLEASE KNOW THAT ANY CHANGES MADE DUE TO LOADS, ENERGY | | | CALCULATIONS FOR OUTSIDE LIGHTING ETC WHICH IS FED FROM | | | THE BASE BUILDING WILL REQUIRE PLANS FOR THE BASE | | | BUILDING ALONG WITH ANY CALCULATIONS TO BE REVISED. | | | FBC 106.3.5.1.2, 106.1.2 | | | | | | 4) NOTE: PLEASE SEE THE TITLE BLOCKS FOR ARCHITECTURAL | | | SHEETS ARE MISSING THE REQUIRED INFORMATION FOR ONE OF | | | THE DESIGN FIRMS AS LISTED PER FLORIDA ADMINISTRATIVE | | | CODE 61G1-16.004 AND FLORIDA STATUTES 481.219. | | | THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES | | | WHICH CONTAINS THIS INFORMATION ON TITLE BLOCKS. THIS | | | COMMENT IS NOT FOR THE ELECTRICAL SHEETS. | | | | | | 5) NOTE: PLEASE SEE THE ELECTRICAL PLANS AS SUBMITTED | | | NEED TO MEET FBC 13-415.2 | | | PLEASE PROVIDE LIGHTING DENSITY INFORMATION. | | | | | | 6) NOTE: PLEASE SEE TWO ELECTRICAL RISERS AND PANEL | | | SCHEDULES WERE SUBMITTED. | | | IT IS UNCLEAR WHICH ONE IS TO BE REVIEWED FOR CODE | | | COMPLIANCE. | | | ONE RISER INDICATES A REQUESTED FOR A SEPARATE | | | ELECTRICAL SERVICE FROM THE POWER COMPANY ONLY TO THIS | | | BUILDING. THIS CONFLICTS WITH THE OTHER RISER WHICH | | | INDICATES THE ELECTRICAL BEING FED FROM THE EXISTING | | | BASED BUILDING SERVICE. | | | PLEASE KNOW THAT GRANTING AN ADDITIONAL SERVICE FOR THE | | | POOL HOUSE AS SHOWN IS NOT PERMITTED AS THERE WOULD BE | | | ELECTRICAL SYSTEMS BEING CROSSED FROM TWO SEPARATE | | | SERVICES. | | | FBC 106.1.2, 106.3.5.1.2 | | | NEC 215.5,230.70, 230.71, 230.2, 310.16, 240.4 ETC. | | | PLEASE COORDINATE. | | | | | | 7) NOTE: PLEASE SEE 422.13 IN THE 2005 NEC AS LOADS FOR | | | ELECTRICAL WATER HEATERS ARE TO BE FIGURED AT 125% AS | | | THESE ARE CONSIDERED CONTINUOUS LOADS. | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2008-12-26 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2008-12-26 |
Time |
11:44 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2008-12-26 |
Time |
11:43 |
Sent To |
ENG |
|
| Notes |
| 2008-12-26 11:45:45 | **** PASSED ***** | | | | | | PREVIOUS COMMENTS ADDRESSED. PLANS REVIEWED DATED | | | 11/17/08 BY EOR DAN DAVILA, P.E. | | | | | | MANUEL J GONZALEZ, PROJECT COORDINATOR | | | LOCATION ADDRESS: | | | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | 1000 - 45TH STREET, SUITE 15 | | | WEST PALM BEACH FL 33407 | | | MAILING ADDRESS: | | | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | P.O. BOX 3506 | | | WEST PALM BEACH FL 33401 | | | TELEPHONE: | | | 45TH STREET OFFICE : 561-494-1040 | | | 45TH DIRECT: 561-494-1085 | | | FAX: 561-494-1117 | | | CITY HALL OFFICE: (561) 805-6713 | | | CITY HALL DIRECT: (561) 805-6327 | | | CITY HALL FAX: (561) 805-6731 OR 805-6676 | | | NEXTEL: 561-644-7301 | | | NEXTEL DIRECT CONNECT: 159*28165*38 | | | EMERGENCIES: | | | CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210 | | | E-MAIL: | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2008-12-09 |
|
|
Cont ID |
|
| Sent By |
dlauderm |
Date |
2008-10-21 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
dlauderm |
Date |
2008-10-21 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2008-10-21 14:12:25 | FAILED: | | | 1-SUPPLY POLLUTION CONTROL PLAN SHOWING: | | | A) WHERE SILT SCREENS WILL BE INSTALLED, | | | B) SHOW THE PROTECTION OF ALL ON-SITE CATCH BASINS | | | C) SHOW PROTECTION OF ALL OFF-SITE CATCH BASINS | | | D) INCLUDE DETAILS AS TO THE TYPE OF PROTECTION USED ON | | | THE CATCH BASINS | | | E) SHOW HOW SITE DIRT WILL NOT BE TRACKED INTO THE | | | ROADS | | | 2-SHEET P-02 STATES "4" SANITARY SEWER FOR CONTINUATION | | | REFER TO CIVIL SITE PLAN DRAWINGS." CIVIL SITE PLAN | | | DRAWINGS NOT ATTACHED TO THE PLAN. | | | 3-FINISHED FLOOR ELEVATION (FFE) NOT SUPPLIED. CIVIL | | | SITE PLAN REQUIRED TO COMPARE FFE TO THE RIM ELEVATION | | | OF THE CLOSEST SANITARY MANHOLE | | | 4-WHEN CONTACTING REVIEWER PLEASE REFERENCE THE PERMIT | | | NUMBER. | | | 5-IF YOU HAVE ANY QUESTIONS PLEASE FEEL FREE TO CONTACT | | | THE REVIEWER: | | | DEAN S. LAUDERMILK, PROJECT COORDINATOR | | | LOCATION ADDRESS: | | | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | 1000 - 45TH STREET, SUITE 15 | | | WEST PALM BEACH FL 33407 | | | MAILING ADDRESS: | | | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | P.O. BOX 3506 | | | WEST PALM BEACH FL 33401 | | | TELEPHONE: | | | 45TH STREET OFFICE : 561-494-1041 | | | 45TH DIRECT: 561-494-1083 | | | FAX: 561-494-1117 | | | CITY HALL OFFICE: (561) 805- | | | CITY HALL DIRECT: (561) 805-6327 | | | CITY HALL FAX: (561) 805-6731 OR 805-6676 | | | NEXTEL: 561-644-7338 | | | NEXTEL DIRECT CONNECT: 159*28165*75 | | | EMERGENCIES: | | | CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210 | | | E-MAIL: | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-10-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-10-20 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-10-20 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2008-10-20 16:52:58 | *****APPROVED***** | | | | | | PLAN SHEET A1.1 STAMPED, INITIALED, AND DATED AS WAS | | | PREVIOUSLY ON 04/24/08. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-04-24 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-04-24 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-04-24 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2008-04-24 10:20:04 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED; PLAN SHEET A1.1 STAMPED, INITIALED, AND | | | DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-02-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-02-21 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-21 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2008-02-21 12:27:35 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE REVIEWED: | | | | | | 1.OK | | | | | | 2.OK | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD | | | COMMENT TO AN APPROPIATE PLAN SHEET | | | | | | 4.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR | | | HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY | | | OR VICINITY THEREOF (INCLUDING STREETS, FIRE LANES). | | | ADD COMMENT TO AN APPROPIATE PLAN SHEET | | | | | | 5.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN | | | TERMS OF CLASS A, CLASS B, OR CLASS C.COULD NOT | | | LOCATE COMMENT ON SHEET A1.1 AS PER YOUR RESPONSE | | | LETTER | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-03 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-03 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2007-10-03 15:50:23 | *****DENIED***** | | | | | | | | | 1.THE ACTUAL/CORRECT ADDRESS OF THE PROJECT SITE | | | SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN | | | SHEET. | | | | | | 2.NFPA 101 - 2003 EDITION SHALL BE REFERENCED. | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 4.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR | | | HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY | | | OR VICINITY THEREOF (INCLUDING STREETS, FIRE LANES). | | | | | | 5.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN | | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2009-02-05 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2009-02-05 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2009-02-05 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2009-02-05 10:09:51 | *****INFORMATION ONLY****** | | | | | | POOL HEATER SPEC. SHEETS ARE WITH POOL PLANS. | | | | | | LARRY WAGNER | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2008-12-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-12-22 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-12-22 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2008-12-23 08:53:31 | DENIED | | | REFERENCE: | | | FBC-2004 FUEL GAS | | | | | | ****FROM PREVIOUS REVIEWS: | | | | | | 1. SHT P-03 GAS RISER DIAGRAM DOES NOT REFLECT THE | | | PIPING SHOWN ON THE SITE PLAN. THE PIPING ON THE SITE | | | PLAN IS INDICATED AS OFFSETTING TO THE NORTH EAST, | | | TURNING TO THE SOUTH EAST, AND THEN TURNING TO THE | | | NORTH EAST TO THE POOL BUILDING. -- ALSO THE PIPING | | | SCALES OUT TO ABOUT 200 FEET FROM THE METER WITH 40 | | | FEET INSIDE THE BUILDING FOR A TOTAL DEVELOPED LENGTH | | | OF ABOUT 240 FEET. PLANS AND RISER DIAGRAM INDICATE 160 | | | FEET TO THE BUILDING AND A TOTAL DEVELOPED LENGTH OF | | | 200 FEET. PLEASE CORRELATE AND CLARIFY. TABLE 402.4(3). | | | ****NO COMMENT RESPONSE, COMMENT NOT ADDRESSED EXCEPT | | | FOR THE DEVELOPED LENGTH. | | | | | | 2. THE PLANS INDICATE THAT THE PIPING WILL ALL BE | | | SCHEDULE 40 BLACK IRON PIPE. PER SECTIONS 404.8 & | | | 404.8.2 PIPES SHALL BE PROTECTED AND THE PROTECTIVE | | | COATINGS AND WRAPPING SHALL BE FACTORY INSTALLED. | | | ****RESPONSE NOTED, BUT PLANS SHALL INDICATE THE | | | REQUIRED PROTECTION FOR THE SCHEDULE 40 BLACK IRON PIPE | | | AND THE REQUIRED PROTECTION REQUIRED FOR THE WARDFLEX | | | PIPING AS WELL AS THE EDH NUMBER OF THE WARDFLEX | | | PIPING. | | | | | | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | THE FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 4. INFORMATIONAL: 3/4" PIPE WILL BE SUFFICIENT ON THE | | | 2PSI SYSTEM UP TO 500 FT FOR THE SCHEDULE 40 PIPE, AND | | | UP TO 600 FT FOR PE PIPE UNDERGROUND. TABLES 402.4.3 & | | | 402.4(20). | | | | | | 5. TO EXPEDITE THE PERMIT, A SUGGESTION WOULD BE TO | | | REMOVE THE GAS PLANS FROM THIS SET OF PLANS FOR THE | | | POOL BUILDING AND REFERENCE THE BLD-COM PERMIT FOR THE | | | 6 STORY BUILDING AS THERE ARE GAS PLANS FOR THE POOL | | | HEATER ON THOSE PLANS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2008-09-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-09-24 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-09-23 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2008-09-24 17:21:51 | DENIED | | | REFERENCE: | | | FBC-2004 FUEL GAS | | | | | | 1. SHT P-03 GAS RISER DIAGRAM DOES NOT REFLECT THE | | | PIPING SHOWN ON THE SITE PLAN. THE PIPING ON THE SITE | | | PLAN IS INDICATED AS OFFSETTING TO THE NORTH EAST, | | | TURNING TO THE SOUTH EAST, AND THEN TURNING TO THE | | | NORTH EAST TO THE POOL BUILDING. -- ALSO THE PIPING | | | SCALES OUT TO ABOUT 200 FEET FROM THE METER WITH 40 | | | FEET INSIDE THE BUILDING FOR A TOTAL DEVELOPED LENGTH | | | OF ABOUT 240 FEET. PLANS AND RISER DIAGRAM INDICATE 160 | | | FEET TO THE BUILDING AND A TOTAL DEVELOPED LENGTH OF | | | 200 FEET. PLEASE CORRELATE AND CLARIFY. TABLE 402.4(3). | | | | | | 2. THE PLANS INDICATE THAT THE PIPING WILL ALL BE | | | SCHEDULE 40 BLACK IRON PIPE. PER SECTIONS 404.8 & | | | 404.8.2 PIPES SHALL BE PROTECTED AND THE PROTECTIVE | | | COATINGS AND WRAPPING SHALL BE FACTORY INSTALLED. | | | | | | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | THE FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | 4. INFORMATIONAL: 3/4" PIPE WILL BE SUFFICIENT ON THE | | | 2PSI SYSTEM UP TO 500 FT FOR THE SCHEDULE 40 PIPE, AND | | | UP TO 600 FT FOR PE PIPE UNDERGROUND. TABLES 402.4.3 & | | | 402.4(20). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2008-02-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-23 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-22 |
Time |
19:12 |
Sent To |
|
|
| Notes |
| 2008-02-23 08:58:51 | DENIED--SEE COMMENTS FOR GAS ON PLUMBING REVIEW | | | STOP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2009-04-22 |
|
|
Cont ID |
|
| Sent By |
swurafti |
Date |
2009-04-22 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
swurafti |
Date |
2009-04-22 |
Time |
15:07 |
Sent To |
B |
|
| Notes |
| 2009-04-22 15:26:11 | TO "LMARTINEZ" DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2009-03-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-03-10 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-03-10 |
Time |
14:23 |
Sent To |
B |
|
| Notes |
| 2009-03-10 14:23:20 | TO "MJACOBS" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2009-01-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-30 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-30 |
Time |
09:04 |
Sent To |
G |
|
| Notes |
| 2009-01-30 09:04:59 | TO "G" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-11-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-19 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-19 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2008-11-19 09:52:51 | TO "COMM" BD#39 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-09-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-22 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-22 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2008-09-22 10:28:02 | TO "COMM" BD#43 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-04-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-04 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-04 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2008-04-04 08:45:22 | TO "COMM" BD#43 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-01-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-23 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-23 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2008-01-23 12:07:42 | TO "COMM"BD#32 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-03 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-06 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2007-08-31 08:24:06 | TO "COMM" BD#30 | | 2007-08-06 17:29:41 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2008-10-01 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-10-01 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-10-01 |
Time |
15:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2008-04-23 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-04-23 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-04-23 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2008-04-23 15:35:24 | REVIEW #: 3RD | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. NOT ADDRESSED. SEE PREVIOUS COMMENT #1 | | | | | | 2. OK | | | | | | 3. OK | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-02-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-02-15 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-02-15 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2008-02-15 17:12:09 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. NOT ADDRESSED. SEE PREVIOUS REVIEW | | | | | | 2. NOT ADDRESSED. SEE PREVIOUS REVIEW> | | | | | | 3. OK | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-09 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-09-09 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-09-07 |
Time |
18:06 |
Sent To |
|
|
| Notes |
| 2007-09-09 13:24:16 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. NO MECHANICAL PLANS WERE SUBMITTED WITH THIS | | | PACKAGE. THE FOLLOWING INFORMATION AT A MINIMUM IS | | | REQUIRED TO SHOW CODE COMPLIANCE: | | | - MEANS AND RATE OF VENTILATION REQUIRED AND PROVIDED | | | FOR TOILET ROOMS AND POOL EQUIPMENT ROOM. FBC,M 401.2 | | | AND 401.3 | | | - LOCATION OF ALL VENT OUTLETS FOR PLUMBING AND GAS, | | | EXHAUST OUTLETS AND INTAKE OPENINGS. FBC,M 401.5 | | | - MEANS AND METHOD (INCLUDING CALCULATIONS) USED TO | | | PROVIDE BOTH COMBUSTION AIR AND VENTILATION | | | REQUIREMENTS ARE MET FOR THE GAS POOL HEATER/ POOL | | | EQUIPMENT ROOM. FBC,FG 304.9 AND 304.10 | | | - PROTECTION FROM FUMES AND GASSES PER FBC,FG 304.12 | | | | | | 2. EXTERIOR WALL LOUVERS ARE LISTED AS PANEL WALLS | | | UNDER FAC RULE 9B-72 AND AS SUCH ARE SUBJECT TO THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. PROVIDE PRODUCT | | | APPROVALS FOR ALL LOUVERS AND THE "INTERCRIMP SCREENS | | | BY TWP, INC." ALL OPENINGS INTO THE BUILDING SHALL ALSO | | | MEET THE REQUIREMENTS OF FBC,M 401.6 (PROTECTION | | | AGAINST LOCAL WEATHER CONDITIONS). FOR ADDITIONAL | | | INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM | | | PLEASE VISIT: WWW.FLORIDABUILDING.ORG | | | | | | 3. SHOW ON PLANS THE CORRECT ADDRESS OF THE PROPOSED | | | WORK TO MATCH THAT SHOWN ON THE PERMIT APPLICATION. FAC | | | 61G1-16.004 | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2008-09-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-09-23 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-09-23 |
Time |
12:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-04-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-04-15 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-04-14 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2008-04-15 09:11:47 | PASSED/PROVISO | | | | | | 29" CLEARANCE REQUIRED AT LAV 11-4.19.2 | | | | | | REVISION REQUIRED FOR RISER DIAGRAM THAT REFLECTS THE | | | FLOOR PLAN PIPING LAYOUT SHT P-02. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-02-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-23 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-22 |
Time |
19:12 |
Sent To |
|
|
| Notes |
| 2008-02-23 08:53:04 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | CITY WPB MUNICIPAL CODE | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. SHTS 1 & 2 OF 2. NO INFORMATION CAN BE GLEANED FROM | | | THE SEAL OF EITHER SHEET. FAC 61G15-23.001, | | | 61G15-23.002 & FS 471.025.PLEASE RESEAL THE PLANS SO | | | THAT THE INFORMATION REQUIRED ON THE SEAL IS LEGIBLE. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 2. SHTS T1.1, ALL ARCHITECTURAL & STRUCTURAL. THE FIRM | | | LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), FOR CDS | | | ARCHITECTURAL DESIGN IS REQUIRED IN THE TITLE BLOCK OF | | | EACH SHEET. FAC 61G1-16.004(2) & FS 481.219, 481.2055. | | | PLEASE INDICATE THE FIRM LICENSE NUMBER IN THE TITLE | | | BLOCKS. | | | ****RESPONSE NOTED, BUT THE CERTIFICATE OF | | | AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK FOR CSD | | | ARCHITECTURAL DESIGN AND ALSO FOR BOMFA ARCHITECTURAL | | | INC. PLEASE COMPLY WITH THE FLORIDA ADMINISTRATIVE CODE | | | AND FLORIDA STATUTES. | | | | | | 3. OK | | | | | | 4. SHT A3.4 SHOW COMPLIANCE WITH THE FOLLOWING: | | | ___FOR W/C'S | | | A. OK | | | B. OK | | | ___FOR URINALS | | | A. OK | | | B. OK | | | C. OK | | | ___FOR LAVS | | | A. 11-4.19.2 CLEARANCES | | | ****RESPONSE NOTED, BUT THE CLEARANCE OF 29" IS NOT | | | INDICATED. ALSO THE MEASUREMENT OF 2'8" IS NOT TO THE | | | FLOOD RIM LEVEL OF THE SINK. PLEASE INDICATE THE HEIGHT | | | OF THE SINK PER SECTION 11-4.19.2. | | | B. OK | | | C. OK | | | D. OK | | | | | | 5. SHT P-02 SUBMIT THE RISER DIAGRAMS, (SANITARY & | | | WATER), IN ISOMETRIC FORM THAT REFLECT THE PIPING SHOWN | | | ON THE FLOOR PLAN. SECTION | | | 106.3.5.1.3(3)(4)(6)(8)(10)(13). FOR THE SANITARY SHOW | | | ALL PIPE SIZES, VENTS & TRAPS. FOR THE WATER SHOW ALL | | | PIPE SIZES, VALVES & WATER HAMMER ARRESTORS. | | | ****RESPONSE NOTED, BUT THE SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN WHERE THE SECOND WATER | | | CLOSET CONNECTS TO THE BRANCH LINE. IT IS SHOWN | | | CONNECTING BETWEEN THE FIRST FLOOR DRAIN AND THE URINAL | | | ON THE FLOOR PLAN, BUT UPSTREAM OF THE URINAL ON THE | | | RISER DIAGRAM. PLEASE CORRELATE. | | | | | | 6. OK | | | 7. OK | | | 8. OK | | | | | | 9. ALL PLUMBING SHEETS. THE ADDRESS OF RECORD ON THE | | | FLORIDA STATE DBPR WEBSITE DOES NOT REFLECT THE ADDRESS | | | SHOWN ON THE ENGINEERS TITLE BLOCK. FAC | | | 61G15-23.002(2). PLEASE UPDATE THE DBPR WEBSITE OR THE | | | TITLE BLOCKS SO THAT THEY CORRELATE PRIOR TO | | | RESUBMITTING FOR REVIEW. FS 471.025. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 10. THE FOLLOWING INFORMATION REQUIRED FOR THE SEPARATE | | | GAS PERMIT: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | ****RESPONSE NOTED, BUT RESPONSE WAS FOR A DIFFERENT | | | PERMIT, (05041760). ACCORDING TO THIS PLAN, THE GAS | | | SYSTEM IS A SEPARATE SYSTEM WITH A SEPARATE METER. NO | | | CORRESPONDING LENGHTS ARE INDICATED FOR THE PIPING FROM | | | THE METER TO THE FIRST DROP IN THE SYSTEM, NOR IS THERE | | | A CORRESPONDING LENGHT GIVEN FOR THE FIRST DROP AS WELL | | | AS THE PIPING FROM THE POOL HEATER TO THE DROP TO THE | | | POOL HEATER. | | | | | | B. OK | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | D. OK | | | E. N/A | | | F. OK | | | G. OK | | | | | | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT RESPONSE WAS FOR A DIFFERENT | | | PERMIT, (05041760). NO MANUF. SHEETS SUBMITTED. | | | | | | I. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | J. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-20 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-20 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2007-09-20 15:46:58 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | CITY WPB MUNICIPAL CODE | | | | | | 1. SHTS 1 & 2 OF 2. NO INFORMATION CAN BE GLEANED FROM | | | THE SEAL OF EITHER SHEET. FAC 61G15-23.001, | | | 61G15-23.002 & FS 471.025.PLEASE RESEAL THE PLANS SO | | | THAT THE INFORMATION REQUIRED ON THE SEAL IS LEGIBLE. | | | | | | 2. SHTS T1.1, ALL ARCHITECTURAL & STRUCTURAL. THE FIRM | | | LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), FOR CDS | | | ARCHITECTURAL DESIGN IS REQUIRED IN THE TITLE BLOCK OF | | | EACH SHEET. FAC 61G1-16.004(2) & FS 481.219, 481.2055. | | | PLEASE INDICATE THE FIRM LICENSE NUMBER IN THE TITLE | | | BLOCKS. | | | | | | 3. SHT A1.1 MENS TOILET ROOM. IF TOILET STALLS ARE | | | PROVIDED, THEN AT LEAST ONE SHALL BE A STANDARD TOILET | | | STALL COMPLYING WITH SECTION 11-4.17.3EXCEPTION NEW | | | CONSTRUCTION(1)(2). A LAV IS REQUIRED IN THE STALL. | | | (SEE FIG. 11-30E). PLEASE SHOW THE REQUIRED LAV IN THE | | | STALL. | | | | | | 4. SHT A3.4 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR | | | W/C'S | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.5 FLUSH CONTROLS | | | ___FOR URINALS | | | A. 11-4.18.2 HEIGHT | | | B. 11-4.18.3 CLEAR FLOOR SPACE | | | C. 11-4.18.4 FLUSH CONTROLS | | | ___FOR LAVS | | | A. 11-4.19.2 CLEARANCES | | | B. 11-4.19.3 CLEAR FLOOR SPACE | | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | | D. 11-4.19.5 FAUCETS | | | | | | 5. SHT P-02 SUBMIT THE RISER DIAGRAMS, (SANITARY & | | | WATER), IN ISOMETRIC FORM THAT REFLECT THE PIPING SHOWN | | | ON THE FLOOR PLAN. SECTION | | | 106.3.5.1.3(3)(4)(6)(8)(10)(13). FOR THE SANITARY SHOW | | | ALL PIPE SIZES, VENTS & TRAPS. FOR THE WATER SHOW ALL | | | PIPE SIZES, VALVES & WATER HAMMER ARRESTORS. | | | | | | 6. SHT P-02 THE EXTERIOR SHOWER DRAIN IS NOT APPROVED. | | | PLEASE DELETE FROM RISER AND FLOOR PLAN. ARTICLE III | | | SECTION 90-125(5). | | | | | | 7. SHT P-02 ELECTRIC WATER HEATER DETAIL. THE EMERGENCY | | | PAN DRAIN SHALL EXTEND FULL SIZE AND TERMINATE OVER A | | | SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR FLOOR DRAIN | | | OR EXTEND TO THE EXTERIOR OF THE BUILDING AND TERMINATE | | | NOT LESS THAN 6" AND NOT MORE THAN 24" ABOVE THE | | | ADJACENT GROUND SURFACE. SECTION 504.7.2. THE DETAIL | | | SHOWS THE PAN DRAIN SPILLING OVER THE FLOOR. PLEASE | | | CORRECT THE TERMINATION POINT TO COMPLY. | | | | | | 8. SHT P-02 AN RPZV BACKFLOW IS REQUIRED ON THE WATER | | | SERVICE TO THE BUILDING. SECTION 608.13.2. PLEASE SHOW | | | THE BACKFLOW ON THE WATER SERVICE.NOTE: THE POOL | | | PLANS SHOW A HOSE BIBB WITH A VACUUM BREAKER AS WELL AS | | | AN AIR GAP FOR THE MAKE-UP WATER AT THE COLLECTOR TANK. | | | THE RPZV BACKFLOW SHOWN FOR THE MAKE-UP WATER WILL NOT | | | BE NECESSARY AND CAN BE DELETED. | | | | | | 9. ALL PLUMBING SHEETS. THE ADDRESS OF RECORD ON THE | | | FLORIDA STATE DBPR WEBSITE DOES NOT REFLECT THE ADDRESS | | | SHOWN ON THE ENGINEERS TITLE BLOCK. FAC | | | 61G15-23.002(2). PLEASE UPDATE THE DBPR WEBSITE OR THE | | | TITLE BLOCKS SO THAT THEY CORRELATE PRIOR TO | | | RESUBMITTING FOR REVIEW. FS 471.025. | | | | | | 10. THE FOLLOWING INFORMATION REQUIRED FOR THE SEPARATE | | | GAS PERMIT: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | E. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | NOTE: SHT P-03 INDICATES 7" WC FOR SUPPLY PRESSURE. IF | | | NATURAL GAS FLORIDA PUBLIC | | | UTILITIES ONLY SUPPLIES 12" TO 14" WC OR | | | 2PSI. PLEASE CLAIRFY WITH GAS PROVIDER | | | PRIOR TO RESUBMITTING FOR CORRECT | | | DELIVERY PRESSURE. | | | | | | G. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | I. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | J. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2008-09-25 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2008-09-26 |
Time |
4:40 |
Rev Time |
0.00 |
| Received By |
LFRANCO |
Date |
2008-09-25 |
Time |
2:30 |
Sent To |
|
|
| Notes |
| 2008-09-26 17:45:52 | PLANNING AND ZONING: **** PASSED FOR POOL HOUSE ONLY | | | **** | | | | | | 1. THE MSP SITE PLAN OVERALL SHEET WAS NOT APPROVED | | | SINCE IT DOES NOT SHOW THE APPROVED PARKING SPACES OF | | | 116 AND SOME ADDITIONAL CONFIGURATION FOR PARKING | | | REVISIONS THAT WILL BE ADDRESSED THROUGH THE MINOR | | | AMENDMENT PROCESS. SHEET P-03 STAMPED ONLY SHOWING POOL | | | HOUSE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE | | | NUMBER BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2008-04-15 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2008-04-15 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2008-04-15 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2008-04-15 10:22:19 | **** PASSED WITH PROVISO **** | | | | | | 1. PROVIDE RESPONSES TO COMMENTS IN WRITING. | | | 2. PLEASE PROVIDE A COPY OF THE POOL HOUSE (BUILDING | | | PERMIT) PACKAGE TO THE PLANNING AND ZONING DEPARTMENT | | | FOR THE FILE, C/O LINDA MIA FRANCO, SENIOR PLANNER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT LINDA FRANCO | | | AT (561) 822-1443 OR [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2008-02-07 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2008-02-07 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2008-02-07 |
Time |
18:33 |
Sent To |
|
|
| Notes |
| 2008-02-07 18:34:22 | PLANNING AND ZONING:**** PASSED WITH PROVISO **** | | | | | | 1.PROVIDE RESPONSES TO COMMENTS IN WRITING. | | | | | | 2.PLEASE PROVIDE A COPY OF THE POOL HOUSE (BUILDING | | | PERMIT) PACKAGE TO THE PLANNING AND ZONING DEPARTMENT | | | FOR THE FILE, C/O LINDA MIA FRANCO, SENIOR PLANNER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 822-1443 | | | EMAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2007-09-24 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2007-09-13 |
Time |
19:42 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2007-09-13 |
Time |
19:42 |
Sent To |
|
|
| Notes |
| 2007-09-24 19:46:18 | PLANNING AND ZONING:**** PASSED WITH PROVISO **** | | | | | | 1.PROVIDE RESPONSES TO COMMENTS IN WRITING. | | | | | | 2.PLEASE PROVIDE A COPY OF THE POOL HOUSE (BUILDING | | | PERMIT) PACKAGE TO THE PLANNING AND ZONING DEPARTMENT | | | FOR THE FILE, C/O LINDA MIA FRANCO, SENIOR PLANNER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 822-1443 | | | EMAIL: [email protected] | | | |
|
|