Plan Review Details - Permit 07080080
Plan Review Stops For Permit 07080080
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-05-06 Cont ID  
Sent By jwitmer Date 2009-05-06 Time 08:01 Rev Time 0.77
Received By jwitmer Date 2009-05-06 Time 08:01 Sent To PC
Notes
2009-05-06 08:03:25DESIGN CRITERIA FOR LIGHT POLES AND BOLT CONNECTION,
 FOUNDATION BY OTHERS
  
 NOTE; REVISED ACCESSIBLE RAMP PULLED BY CONTRACTOR
 REPRESENTATIVE DAVID TREMBLE, WILL REVISE AND RESIBMIT,
 WOULD HAVE FAILED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-03-24 Cont ID  
Sent By mjacobs Date 2009-03-24 Time 10:06 Rev Time 0.00
Received By mjacobs Date 2009-03-24 Time 10:06 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-09-29 Cont ID  
Sent By mjacobs Date 2008-09-29 Time 11:08 Rev Time 0.00
Received By mjacobs Date 2008-09-29 Time 07:25 Sent To  
Notes
2008-09-29 13:46:46PROVISOR:
 THE TRUSS CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL AND SHALL BE PROVIDED TO
 THE BUILDING OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-24 Cont ID  
Sent By mjacobs Date 2008-04-16 Time 10:30 Rev Time 0.00
Received By mjacobs Date 2008-04-15 Time 11:47 Sent To  
Notes
2008-04-24 14:31:34BUILDING PLAN REVIEW #3
 PERMIT: 07080080
 ADD: 301 LAMBERTON DR.
 CONT: THE WEITZ CO.
 TEL: (561)719-0102
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD4-16-08
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 **NOTED**
 2) THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 **3RDREVIEW.**
 3)1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6. THIS IS A QUESTIONABLE
 SOIL AREA SO PLEASE PROVIDE THE SOIL REPORT.
  
 4) OK
 5)OK
 6)OK
 7)OK
 8)OK
 9)OK
 10)OK
 11)OK
  
 3RDREVIEW
 12)THE ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE
 FOLLOWING ITEMS.
 ____1)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY:
 MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF
 EACH ROOF TYPE
 ____ 2) FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
 _XX_ 3) FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY
 YOU ARE USING.ALSO INDICATE WHICH FASTENER IF THE
 OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
 _XX_4)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
 _XX_5)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
 XX6) THE SYSTEM PROVIDED INDICATES LIMITATION #9, NO
 ENHANCED FASTENING IS ALLOWED.
  
 13)OK
  
 3RDREVIEW
 14)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 15)OK
 16)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 (561) 805-6676
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-14 Cont ID  
Sent By mjacobs Date 2008-02-14 Time 15:56 Rev Time 0.00
Received By mjacobs Date 2008-02-13 Time 11:11 Sent To  
Notes
2008-02-14 15:56:27BUILDING PLAN REVIEW
 PERMIT: 07080080
 ADD: 301 LAMBERTON DR.
 CONT: THE WEITZ CO.
 TEL: (561)719-0102
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND 2-14-08
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 **NOTED**
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 **2ND REVIEW.**
 3)1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6. THIS IS A QUESTIONABLE
 SOIL AREA SO PLEASE PROVIDE THE SOIL REPORT.
  
 4) 2ND REVIEW **NOTED**
 HOWEVER, THE USE AND OCCUPANCY, INDICATED ON THE
 DRAWINGS (A-3) DOES NOT CORRESPOND WITH THE MAIN
 STRUCTURE.
  
 **2ND REVIEW.**
 5)SHEET S1.2 THE INTERNAL PRESSURE COEFFICIENT WAS
 CHANGED TO 0.55 FOR PARTIALLY ENCLOSED BUILDINGS,
 HOWEVER THE DESIGN CRITERIA ON S1.2 REFERS TO THE
 BUILDING AS AN ENCLOSED BUILDING. AS STATED IN THE
 FIRST REVIEW, THERE ARE SCREENS INDICATED ON EACH
 ELEVATION OF THE BUILDING. WITHOUT THE INSTALLATIONS OF
 WINDOWS, THE SCREENS WILL ALLOW THE PRESSURES TO BUILD
 IN THE BUILDING DURING HURRICANES /TORNADO OR OTHER
 NATURAL DISASTERS.
  
 6)OK
 7)OK
  
 2ND REVIEW **NOTED**
 8)THE STRUCTURAL SHEETS DO NOT PROVIDE UPLIFT FORCES
 TO BE RESISTED OR THE TYPE OF HARDWARE TO BE USED TO
 RESIST UPLIFT AND LATERAL LOADS. PROVIDE A BEAM AND
 COLUMN SCHEDULE INDICATING THE SIZE OF EACH COLUMN AND
 BEAM. WHAT IS THE SIZE OF L-1 / L-2 AND L-3?
  
 2ND REVIEW
 9)FBC 1609.1.4 COMPONENTS & CLADDING, PROVIDE 2
 COPIES (3 IF THRESHOLD OR RESIDENT INSPECTOR) OF
 PRODUCTS TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS
 A] TRUSS ANCHORS OK
 B] WALL LOUVERS
 C} PANEL WALL SYSTEMS-SCREEN (NOTE: DELETED FROM
 PLANS)
 D] TECO POST ANCHORS AND TECO POST CAPS.
  
 10)OK
  
 2ND REVIEW.
 11)WPB ADMIN CODE 106.3* THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FORJURISDICTIONAL APPROVAL.**ALL SETS OF
 PRODUCT APPROVAL SHALL BE APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. ONLY ONE SET HAS THE APPROVAL OF
 THE DESIGNER.**
  
 2ND REVIEW
 12)THE ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE
 FOLLOWING ITEMS.
 ____1)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY:
 MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF
 EACH ROOF TYPE
 ____ 2) FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
 _XX_ 3) FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY
 YOU ARE USING.ALSO INDICATE WHICH FASTENER IF THE
 OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
 _XX_4)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
 _XX_5)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
 XX6) THE SYSTEM PROVIDED INDICATES LIMITATION #9, NO
 ENHANCED FASTENING IS ALLOWED.
  
 13)OK
  
 2ND REVIEW
 14)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 15)OK
 16)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 (561) 805-6676
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-16 Cont ID  
Sent By jwitmer Date 2007-09-16 Time 20:38 Rev Time 1.55
Received By jwitmer Date 2007-09-16 Time 20:36 Sent To  
Notes
2007-09-16 21:40:53HAWTHORN HOTEL POOL HOUSE
 301 LAMBERTON DR
  
 BUILDING PLAN REVIEW
 PERMIT: 07080080
 ADD: 301 LAMBERTON DR
 CONT: THE WEITZ CO.
 TEL: (561)719-0102
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) FBC 1802.2.1 QUESTIONABLE SOILS, WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 4) SHEET T1.1 THE MINIMUM BUILDING TYPE IS INDICATED AS
 TYPE III-B I BELIEVE THIS IS THE MINIMUM TYPE FOR THE
 HOTEL, PLEASE PROVIDE THE POOL HOUSE MINIMUM BUILDING
 TYPE SEE TABLE 503.
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINEDIN CHAPTER 6,
 TABLE 601 & TABLE 503.
 D) THE OCCUPANT LOAD, SEE 1004.
  
 5)S1.2 INDICATES THIS IS A ENCLOSED BUILDING BUT
 THERE ARE SCREENS NOT WINDOWS IN THE BUILDING,A
 ALLOWING PRESSURES TO BUILD IN THE BUILDING, THE
 APPLICABLE INTERNAL PRESSURE COEFFICIENT WOULD NOT BE
 +-.18 FOR A PARTIALLY ENCLOSED BUILDING.
  
 6)SHEET S1.1 FOUNDATION DETAIL INDICATES IN CERTAIN
 BLOCK CELLS THERE IS TO BE 4 # 5 BARS, IS THIS CORRECT?
 IF WHERE ARE THE REQUIRED HOOPS FOR A 4 BAR COLUMN?
  
 7) PLEASE COORDINATE THE ARCHITECTURAL SHEETS AND
 STRUCTURAL, A3.3 INDICATES THE USE OF WOOD BEAMS OVER
 THE VARIOUS OPENINGS WHERE AS THE STRUCTURAL SHEETS
 INDICATE THE USE OF ANGLES AS LINTELS? PLEASE PROVIDE
 ADDITIONAL INFORMATION.
  
 8) THE STRUCTURAL SHEETS DO NOT PROVIDE UPLIFT FORCES
 TO BE RESISTED NOR THE TYPE OF HARDWARE TO BE USED TO
 RESIST UPLIFT AND LATERAL LOADS.
  
 9) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B)WALL LOUVERS
 C) PANEL WALL SYSTEMS- SCREENS
  
 10)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 11)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 12) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
 ___ CONTRACTOR DID NOT PROVIDE THE MEANROOF
 HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOFPITCH.
 _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
 _XX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 _2&3__ .
 _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7,
 SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THATREQUIRED, AS
 DETERMINED BY THEBUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNEDAND SEALED BY
 A FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 ___THE SYSTEM PROVIDED INDICATESLIMITATION# 9,
 NO ENHANCEDFASTENING ALLOWED.
  
 13)SHEET A2.1 INDICATES THE USE OF A DOWN SPOUT BUT
 NO SPLASH BLOCK.1503.6 PROTECTION AGAINST DECAY AND
 TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 14)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY
 OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION.
  
 15 ) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE FLOWS
 SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE SPECIAL DRAINAGE
 DESIGN COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE
 THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCEL SHALL AS A PERMIT CONDITION, PROVIDE
 A
 PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATION FROM A LICENSED ENGINEER
 SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 16 ) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE
 CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO
 MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR
 PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAILS TO
 COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS
 EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A HURRICANE
 WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00. IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT
 TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-10-03 Cont ID  
Sent By dpalmer Date 2008-10-03 Time 15:10 Rev Time 0.00
Received By dpalmer Date 2008-10-03 Time 15:10 Sent To  
Notes
2008-10-03 15:10:47NEW ELECTRICAL PLANS, SAME SCOPE OF WORK. POOL HOUSE
 ONLY

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-04-08 Cont ID  
Sent By dpalmer Date 2008-04-08 Time 12:19 Rev Time 0.00
Received By dpalmer Date 2008-04-08 Time 12:19 Sent To  
Notes
2008-04-08 12:20:26ALL NEW ELECTRICAL PLANS.
  
 REDLINED 2005 NEC.
 SCOPE OF WORK FOR POOL HOUSE ONLY!

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-30 Cont ID  
Sent By dpalmer Date 2008-01-30 Time 19:14 Rev Time 0.00
Received By dpalmer Date 2008-01-30 Time 19:14 Sent To  
Notes
2008-01-30 19:15:53*** REDLINED **
  
 E-2 SITE PLAN TO BE REVISED BEFORE FINAL AS THIS DOES
 NOT MATCH WITH ALL ITEMS ACTUALLY INSTALLED ON-SITE TO
 DATE.
  
 PLANS FOR POOL HOUSE ONLY, NOT FOR POOL OR DECK.
 ALL STEEL AND BONDING SHALL MEET 680.26

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-04 Cont ID  
Sent By dpalmer Date 2007-09-04 Time 15:47 Rev Time 0.00
Received By dpalmer Date 2007-09-04 Time 13:51 Sent To  
Notes
2007-09-04 15:47:27 
  
 ** DENIED **
  
 1) NOTE: PLEASE SEE THE ADDRESS WHICH HAS NOW BEEN
 ASSIGNED BY THE CITY OF WEST PALM BEACH AND AS APPLIED
 IS 301 LAMBERTON.
 PLEASE ADJUST TITLE BLOCKS FOR LOCATION.
 FAC 61G1-16.004, FAC 61G15-23.002
  
  
 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 3) NOTE: PLEASE KNOW AS THE PRIMARY BUILDING DOES NOT
 YET HAVE A CERTIFICATE OF OCCUPANCY AND THE DESIGNER OF
 RECORD FOR THE ARCHITECTURAL SHEETS IS NOW NEW, PLEASE
 BE SURE THESE PLANS WHICH DIRECTLY AFFECT THE PROJECT
 CONTAIN A *SHOP DRAWING* REVIEW STAMP.
 PLEASE KNOW THAT ANY CHANGES MADE DUE TO LOADS, ENERGY
 CALCULATIONS FOR OUTSIDE LIGHTING ETC WHICH IS FED FROM
 THE BASE BUILDING WILL REQUIRE PLANS FOR THE BASE
 BUILDING ALONG WITH ANY CALCULATIONS TO BE REVISED.
 FBC 106.3.5.1.2, 106.1.2
  
 4) NOTE: PLEASE SEE THE TITLE BLOCKS FOR ARCHITECTURAL
 SHEETS ARE MISSING THE REQUIRED INFORMATION FOR ONE OF
 THE DESIGN FIRMS AS LISTED PER FLORIDA ADMINISTRATIVE
 CODE 61G1-16.004 AND FLORIDA STATUTES 481.219.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHICH CONTAINS THIS INFORMATION ON TITLE BLOCKS. THIS
 COMMENT IS NOT FOR THE ELECTRICAL SHEETS.
  
 5) NOTE: PLEASE SEE THE ELECTRICAL PLANS AS SUBMITTED
 NEED TO MEET FBC 13-415.2
 PLEASE PROVIDE LIGHTING DENSITY INFORMATION.
  
 6) NOTE: PLEASE SEE TWO ELECTRICAL RISERS AND PANEL
 SCHEDULES WERE SUBMITTED.
 IT IS UNCLEAR WHICH ONE IS TO BE REVIEWED FOR CODE
 COMPLIANCE.
 ONE RISER INDICATES A REQUESTED FOR A SEPARATE
 ELECTRICAL SERVICE FROM THE POWER COMPANY ONLY TO THIS
 BUILDING. THIS CONFLICTS WITH THE OTHER RISER WHICH
 INDICATES THE ELECTRICAL BEING FED FROM THE EXISTING
 BASED BUILDING SERVICE.
 PLEASE KNOW THAT GRANTING AN ADDITIONAL SERVICE FOR THE
 POOL HOUSE AS SHOWN IS NOT PERMITTED AS THERE WOULD BE
 ELECTRICAL SYSTEMS BEING CROSSED FROM TWO SEPARATE
 SERVICES.
 FBC 106.1.2, 106.3.5.1.2
 NEC 215.5,230.70, 230.71, 230.2, 310.16, 240.4 ETC.
 PLEASE COORDINATE.
  
 7) NOTE: PLEASE SEE 422.13 IN THE 2005 NEC AS LOADS FOR
 ELECTRICAL WATER HEATERS ARE TO BE FIGURED AT 125% AS
 THESE ARE CONSIDERED CONTINUOUS LOADS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2008-12-26 Cont ID  
Sent By mgonzale Date 2008-12-26 Time 11:44 Rev Time 1.00
Received By mgonzale Date 2008-12-26 Time 11:43 Sent To ENG
Notes
2008-12-26 11:45:45**** PASSED *****
  
 PREVIOUS COMMENTS ADDRESSED. PLANS REVIEWED DATED
 11/17/08 BY EOR DAN DAVILA, P.E.
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6713
 CITY HALL DIRECT: (561) 805-6327
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-12-09 Cont ID  
Sent By dlauderm Date 2008-10-21 Time 14:13 Rev Time 0.00
Received By dlauderm Date 2008-10-21 Time 14:13 Sent To  
Notes
2008-10-21 14:12:25FAILED:
 1-SUPPLY POLLUTION CONTROL PLAN SHOWING:
 A) WHERE SILT SCREENS WILL BE INSTALLED,
 B) SHOW THE PROTECTION OF ALL ON-SITE CATCH BASINS
 C) SHOW PROTECTION OF ALL OFF-SITE CATCH BASINS
 D) INCLUDE DETAILS AS TO THE TYPE OF PROTECTION USED ON
 THE CATCH BASINS
 E) SHOW HOW SITE DIRT WILL NOT BE TRACKED INTO THE
 ROADS
 2-SHEET P-02 STATES "4" SANITARY SEWER FOR CONTINUATION
 REFER TO CIVIL SITE PLAN DRAWINGS." CIVIL SITE PLAN
 DRAWINGS NOT ATTACHED TO THE PLAN.
 3-FINISHED FLOOR ELEVATION (FFE) NOT SUPPLIED. CIVIL
 SITE PLAN REQUIRED TO COMPARE FFE TO THE RIM ELEVATION
 OF THE CLOSEST SANITARY MANHOLE
 4-WHEN CONTACTING REVIEWER PLEASE REFERENCE THE PERMIT
 NUMBER.
 5-IF YOU HAVE ANY QUESTIONS PLEASE FEEL FREE TO CONTACT
 THE REVIEWER:
 DEAN S. LAUDERMILK, PROJECT COORDINATOR
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1041
 45TH DIRECT: 561-494-1083
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-
 CITY HALL DIRECT: (561) 805-6327
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7338
 NEXTEL DIRECT CONNECT: 159*28165*75
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-10-20 Cont ID  
Sent By mawillia Date 2008-10-20 Time 16:56 Rev Time 0.00
Received By mawillia Date 2008-10-20 Time 16:45 Sent To  
Notes
2008-10-20 16:52:58*****APPROVED*****
  
 PLAN SHEET A1.1 STAMPED, INITIALED, AND DATED AS WAS
 PREVIOUSLY ON 04/24/08.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-04-24 Cont ID  
Sent By mawillia Date 2008-04-24 Time 10:25 Rev Time 0.00
Received By mawillia Date 2008-04-24 Time 10:07 Sent To  
Notes
2008-04-24 10:20:04*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEET A1.1 STAMPED, INITIALED, AND
 DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-02-21 Cont ID  
Sent By mawillia Date 2008-02-21 Time 12:29 Rev Time 0.00
Received By mawillia Date 2008-02-21 Time 12:09 Sent To  
Notes
2008-02-21 12:27:35*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE REVIEWED:
  
 1.OK
  
 2.OK
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 COMMENT TO AN APPROPIATE PLAN SHEET
  
 4.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY
 OR VICINITY THEREOF (INCLUDING STREETS, FIRE LANES).
 ADD COMMENT TO AN APPROPIATE PLAN SHEET
  
 5.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.COULD NOT
 LOCATE COMMENT ON SHEET A1.1 AS PER YOUR RESPONSE
 LETTER
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-03 Cont ID  
Sent By mawillia Date 2007-10-03 Time 15:50 Rev Time 0.00
Received By mawillia Date 2007-10-03 Time 14:19 Sent To  
Notes
2007-10-03 15:50:23*****DENIED*****
  
  
 1.THE ACTUAL/CORRECT ADDRESS OF THE PROJECT SITE
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2.NFPA 101 - 2003 EDITION SHALL BE REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY
 OR VICINITY THEREOF (INCLUDING STREETS, FIRE LANES).
  
 5.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2009-02-05 Cont ID  
Sent By lwagner Date 2009-02-05 Time 10:07 Rev Time 0.00
Received By lwagner Date 2009-02-05 Time 09:35 Sent To  
Notes
2009-02-05 10:09:51*****INFORMATION ONLY******
  
 POOL HEATER SPEC. SHEETS ARE WITH POOL PLANS.
  
 LARRY WAGNER
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2008-12-23 Cont ID  
Sent By kstevens Date 2008-12-22 Time 16:35 Rev Time 0.00
Received By kstevens Date 2008-12-22 Time 16:56 Sent To  
Notes
2008-12-23 08:53:31DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEWS:
  
 1. SHT P-03 GAS RISER DIAGRAM DOES NOT REFLECT THE
 PIPING SHOWN ON THE SITE PLAN. THE PIPING ON THE SITE
 PLAN IS INDICATED AS OFFSETTING TO THE NORTH EAST,
 TURNING TO THE SOUTH EAST, AND THEN TURNING TO THE
 NORTH EAST TO THE POOL BUILDING. -- ALSO THE PIPING
 SCALES OUT TO ABOUT 200 FEET FROM THE METER WITH 40
 FEET INSIDE THE BUILDING FOR A TOTAL DEVELOPED LENGTH
 OF ABOUT 240 FEET. PLANS AND RISER DIAGRAM INDICATE 160
 FEET TO THE BUILDING AND A TOTAL DEVELOPED LENGTH OF
 200 FEET. PLEASE CORRELATE AND CLARIFY. TABLE 402.4(3).
 ****NO COMMENT RESPONSE, COMMENT NOT ADDRESSED EXCEPT
 FOR THE DEVELOPED LENGTH.
  
 2. THE PLANS INDICATE THAT THE PIPING WILL ALL BE
 SCHEDULE 40 BLACK IRON PIPE. PER SECTIONS 404.8 &
 404.8.2 PIPES SHALL BE PROTECTED AND THE PROTECTIVE
 COATINGS AND WRAPPING SHALL BE FACTORY INSTALLED.
 ****RESPONSE NOTED, BUT PLANS SHALL INDICATE THE
 REQUIRED PROTECTION FOR THE SCHEDULE 40 BLACK IRON PIPE
 AND THE REQUIRED PROTECTION REQUIRED FOR THE WARDFLEX
 PIPING AS WELL AS THE EDH NUMBER OF THE WARDFLEX
 PIPING.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 THE FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 4. INFORMATIONAL: 3/4" PIPE WILL BE SUFFICIENT ON THE
 2PSI SYSTEM UP TO 500 FT FOR THE SCHEDULE 40 PIPE, AND
 UP TO 600 FT FOR PE PIPE UNDERGROUND. TABLES 402.4.3 &
 402.4(20).
  
 5. TO EXPEDITE THE PERMIT, A SUGGESTION WOULD BE TO
 REMOVE THE GAS PLANS FROM THIS SET OF PLANS FOR THE
 POOL BUILDING AND REFERENCE THE BLD-COM PERMIT FOR THE
 6 STORY BUILDING AS THERE ARE GAS PLANS FOR THE POOL
 HEATER ON THOSE PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-09-24 Cont ID  
Sent By kstevens Date 2008-09-24 Time 17:08 Rev Time 0.00
Received By kstevens Date 2008-09-23 Time 12:38 Sent To  
Notes
2008-09-24 17:21:51DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 1. SHT P-03 GAS RISER DIAGRAM DOES NOT REFLECT THE
 PIPING SHOWN ON THE SITE PLAN. THE PIPING ON THE SITE
 PLAN IS INDICATED AS OFFSETTING TO THE NORTH EAST,
 TURNING TO THE SOUTH EAST, AND THEN TURNING TO THE
 NORTH EAST TO THE POOL BUILDING. -- ALSO THE PIPING
 SCALES OUT TO ABOUT 200 FEET FROM THE METER WITH 40
 FEET INSIDE THE BUILDING FOR A TOTAL DEVELOPED LENGTH
 OF ABOUT 240 FEET. PLANS AND RISER DIAGRAM INDICATE 160
 FEET TO THE BUILDING AND A TOTAL DEVELOPED LENGTH OF
 200 FEET. PLEASE CORRELATE AND CLARIFY. TABLE 402.4(3).
  
 2. THE PLANS INDICATE THAT THE PIPING WILL ALL BE
 SCHEDULE 40 BLACK IRON PIPE. PER SECTIONS 404.8 &
 404.8.2 PIPES SHALL BE PROTECTED AND THE PROTECTIVE
 COATINGS AND WRAPPING SHALL BE FACTORY INSTALLED.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 THE FBC-2004 FUEL GAS CODE SEC 402.2.
  
 4. INFORMATIONAL: 3/4" PIPE WILL BE SUFFICIENT ON THE
 2PSI SYSTEM UP TO 500 FT FOR THE SCHEDULE 40 PIPE, AND
 UP TO 600 FT FOR PE PIPE UNDERGROUND. TABLES 402.4.3 &
 402.4(20).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-02-23 Cont ID  
Sent By kstevens Date 2008-02-23 Time 08:58 Rev Time 0.00
Received By kstevens Date 2008-02-22 Time 19:12 Sent To  
Notes
2008-02-23 08:58:51DENIED--SEE COMMENTS FOR GAS ON PLUMBING REVIEW
 STOP

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-04-22 Cont ID  
Sent By swurafti Date 2009-04-22 Time 15:07 Rev Time 0.00
Received By swurafti Date 2009-04-22 Time 15:07 Sent To B
Notes
2009-04-22 15:26:11TO "LMARTINEZ" DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-03-10 Cont ID  
Sent By adarroug Date 2009-03-10 Time 14:23 Rev Time 0.00
Received By adarroug Date 2009-03-10 Time 14:23 Sent To B
Notes
2009-03-10 14:23:20TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-01-30 Cont ID  
Sent By adarroug Date 2009-01-30 Time 09:04 Rev Time 0.00
Received By adarroug Date 2009-01-30 Time 09:04 Sent To G
Notes
2009-01-30 09:04:59TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-11-19 Cont ID  
Sent By adarroug Date 2008-11-19 Time 09:52 Rev Time 0.00
Received By adarroug Date 2008-11-19 Time 09:52 Sent To  
Notes
2008-11-19 09:52:51TO "COMM" BD#39

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-22 Cont ID  
Sent By adarroug Date 2008-09-22 Time 10:27 Rev Time 0.00
Received By adarroug Date 2008-09-22 Time 09:53 Sent To  
Notes
2008-09-22 10:28:02TO "COMM" BD#43

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 08:45 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 08:45 Sent To  
Notes
2008-04-04 08:45:22TO "COMM" BD#43

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-23 Cont ID  
Sent By adarroug Date 2008-01-23 Time 12:02 Rev Time 0.00
Received By adarroug Date 2008-01-23 Time 12:02 Sent To  
Notes
2008-01-23 12:07:42TO "COMM"BD#32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-03 Cont ID  
Sent By mawillia Date 2007-10-03 Time 14:23 Rev Time 0.00
Received By mawillia Date 2007-08-06 Time 17:29 Sent To  
Notes
2007-08-31 08:24:06TO "COMM" BD#30
2007-08-06 17:29:41WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-10-01 Cont ID  
Sent By rregueir Date 2008-10-01 Time 15:14 Rev Time 0.00
Received By rregueir Date 2008-10-01 Time 15:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-04-23 Cont ID  
Sent By rregueir Date 2008-04-23 Time 15:33 Rev Time 0.00
Received By rregueir Date 2008-04-23 Time 15:35 Sent To  
Notes
2008-04-23 15:35:24REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. NOT ADDRESSED. SEE PREVIOUS COMMENT #1
  
 2. OK
  
 3. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-15 Cont ID  
Sent By rregueir Date 2008-02-15 Time 17:12 Rev Time 0.00
Received By rregueir Date 2008-02-15 Time 17:11 Sent To  
Notes
2008-02-15 17:12:09REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. NOT ADDRESSED. SEE PREVIOUS REVIEW
  
 2. NOT ADDRESSED. SEE PREVIOUS REVIEW>
  
 3. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-09 Cont ID  
Sent By rregueir Date 2007-09-09 Time 13:24 Rev Time 0.00
Received By rregueir Date 2007-09-07 Time 18:06 Sent To  
Notes
2007-09-09 13:24:16REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO MECHANICAL PLANS WERE SUBMITTED WITH THIS
 PACKAGE. THE FOLLOWING INFORMATION AT A MINIMUM IS
 REQUIRED TO SHOW CODE COMPLIANCE:
 - MEANS AND RATE OF VENTILATION REQUIRED AND PROVIDED
 FOR TOILET ROOMS AND POOL EQUIPMENT ROOM. FBC,M 401.2
 AND 401.3
 - LOCATION OF ALL VENT OUTLETS FOR PLUMBING AND GAS,
 EXHAUST OUTLETS AND INTAKE OPENINGS. FBC,M 401.5
 - MEANS AND METHOD (INCLUDING CALCULATIONS) USED TO
 PROVIDE BOTH COMBUSTION AIR AND VENTILATION
 REQUIREMENTS ARE MET FOR THE GAS POOL HEATER/ POOL
 EQUIPMENT ROOM. FBC,FG 304.9 AND 304.10
 - PROTECTION FROM FUMES AND GASSES PER FBC,FG 304.12
  
 2. EXTERIOR WALL LOUVERS ARE LISTED AS PANEL WALLS
 UNDER FAC RULE 9B-72 AND AS SUCH ARE SUBJECT TO THE
 FLORIDA PRODUCT APPROVAL SYSTEM. PROVIDE PRODUCT
 APPROVALS FOR ALL LOUVERS AND THE "INTERCRIMP SCREENS
 BY TWP, INC." ALL OPENINGS INTO THE BUILDING SHALL ALSO
 MEET THE REQUIREMENTS OF FBC,M 401.6 (PROTECTION
 AGAINST LOCAL WEATHER CONDITIONS). FOR ADDITIONAL
 INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM
 PLEASE VISIT: WWW.FLORIDABUILDING.ORG
  
 3. SHOW ON PLANS THE CORRECT ADDRESS OF THE PROPOSED
 WORK TO MATCH THAT SHOWN ON THE PERMIT APPLICATION. FAC
 61G1-16.004
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-09-23 Cont ID  
Sent By kstevens Date 2008-09-23 Time 12:38 Rev Time 0.00
Received By kstevens Date 2008-09-23 Time 12:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-04-15 Cont ID  
Sent By kstevens Date 2008-04-15 Time 09:09 Rev Time 0.00
Received By kstevens Date 2008-04-14 Time 13:56 Sent To  
Notes
2008-04-15 09:11:47PASSED/PROVISO
  
 29" CLEARANCE REQUIRED AT LAV 11-4.19.2
  
 REVISION REQUIRED FOR RISER DIAGRAM THAT REFLECTS THE
 FLOOR PLAN PIPING LAYOUT SHT P-02.

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-02-23 Cont ID  
Sent By kstevens Date 2008-02-23 Time 08:03 Rev Time 0.00
Received By kstevens Date 2008-02-22 Time 19:12 Sent To  
Notes
2008-02-23 08:53:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHTS 1 & 2 OF 2. NO INFORMATION CAN BE GLEANED FROM
 THE SEAL OF EITHER SHEET. FAC 61G15-23.001,
 61G15-23.002 & FS 471.025.PLEASE RESEAL THE PLANS SO
 THAT THE INFORMATION REQUIRED ON THE SEAL IS LEGIBLE.
 ****NO RESPONSE, NOT ADDRESSED.
  
 2. SHTS T1.1, ALL ARCHITECTURAL & STRUCTURAL. THE FIRM
 LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), FOR CDS
 ARCHITECTURAL DESIGN IS REQUIRED IN THE TITLE BLOCK OF
 EACH SHEET. FAC 61G1-16.004(2) & FS 481.219, 481.2055.
 PLEASE INDICATE THE FIRM LICENSE NUMBER IN THE TITLE
 BLOCKS.
 ****RESPONSE NOTED, BUT THE CERTIFICATE OF
 AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK FOR CSD
 ARCHITECTURAL DESIGN AND ALSO FOR BOMFA ARCHITECTURAL
 INC. PLEASE COMPLY WITH THE FLORIDA ADMINISTRATIVE CODE
 AND FLORIDA STATUTES.
  
 3. OK
  
 4. SHT A3.4 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C'S
 A. OK
 B. OK
 ___FOR URINALS
 A. OK
 B. OK
 C. OK
 ___FOR LAVS
 A. 11-4.19.2 CLEARANCES
 ****RESPONSE NOTED, BUT THE CLEARANCE OF 29" IS NOT
 INDICATED. ALSO THE MEASUREMENT OF 2'8" IS NOT TO THE
 FLOOD RIM LEVEL OF THE SINK. PLEASE INDICATE THE HEIGHT
 OF THE SINK PER SECTION 11-4.19.2.
 B. OK
 C. OK
 D. OK
  
 5. SHT P-02 SUBMIT THE RISER DIAGRAMS, (SANITARY &
 WATER), IN ISOMETRIC FORM THAT REFLECT THE PIPING SHOWN
 ON THE FLOOR PLAN. SECTION
 106.3.5.1.3(3)(4)(6)(8)(10)(13). FOR THE SANITARY SHOW
 ALL PIPE SIZES, VENTS & TRAPS. FOR THE WATER SHOW ALL
 PIPE SIZES, VALVES & WATER HAMMER ARRESTORS.
 ****RESPONSE NOTED, BUT THE SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN WHERE THE SECOND WATER
 CLOSET CONNECTS TO THE BRANCH LINE. IT IS SHOWN
 CONNECTING BETWEEN THE FIRST FLOOR DRAIN AND THE URINAL
 ON THE FLOOR PLAN, BUT UPSTREAM OF THE URINAL ON THE
 RISER DIAGRAM. PLEASE CORRELATE.
  
 6. OK
 7. OK
 8. OK
  
 9. ALL PLUMBING SHEETS. THE ADDRESS OF RECORD ON THE
 FLORIDA STATE DBPR WEBSITE DOES NOT REFLECT THE ADDRESS
 SHOWN ON THE ENGINEERS TITLE BLOCK. FAC
 61G15-23.002(2). PLEASE UPDATE THE DBPR WEBSITE OR THE
 TITLE BLOCKS SO THAT THEY CORRELATE PRIOR TO
 RESUBMITTING FOR REVIEW. FS 471.025.
 ****NO RESPONSE, NOT ADDRESSED.
  
 10. THE FOLLOWING INFORMATION REQUIRED FOR THE SEPARATE
 GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT RESPONSE WAS FOR A DIFFERENT
 PERMIT, (05041760). ACCORDING TO THIS PLAN, THE GAS
 SYSTEM IS A SEPARATE SYSTEM WITH A SEPARATE METER. NO
 CORRESPONDING LENGHTS ARE INDICATED FOR THE PIPING FROM
 THE METER TO THE FIRST DROP IN THE SYSTEM, NOR IS THERE
 A CORRESPONDING LENGHT GIVEN FOR THE FIRST DROP AS WELL
 AS THE PIPING FROM THE POOL HEATER TO THE DROP TO THE
 POOL HEATER.
  
 B. OK
  
 C. TYPE OF GAS, (LP OR NATURAL).
 ****NO RESPONSE, NOT ADDRESSED.
  
 D. OK
 E. N/A
 F. OK
 G. OK
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT RESPONSE WAS FOR A DIFFERENT
 PERMIT, (05041760). NO MANUF. SHEETS SUBMITTED.
  
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 ****NO RESPONSE, NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-20 Cont ID  
Sent By kstevens Date 2007-09-20 Time 15:07 Rev Time 0.00
Received By kstevens Date 2007-09-20 Time 15:07 Sent To  
Notes
2007-09-20 15:46:58DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 1. SHTS 1 & 2 OF 2. NO INFORMATION CAN BE GLEANED FROM
 THE SEAL OF EITHER SHEET. FAC 61G15-23.001,
 61G15-23.002 & FS 471.025.PLEASE RESEAL THE PLANS SO
 THAT THE INFORMATION REQUIRED ON THE SEAL IS LEGIBLE.
  
 2. SHTS T1.1, ALL ARCHITECTURAL & STRUCTURAL. THE FIRM
 LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), FOR CDS
 ARCHITECTURAL DESIGN IS REQUIRED IN THE TITLE BLOCK OF
 EACH SHEET. FAC 61G1-16.004(2) & FS 481.219, 481.2055.
 PLEASE INDICATE THE FIRM LICENSE NUMBER IN THE TITLE
 BLOCKS.
  
 3. SHT A1.1 MENS TOILET ROOM. IF TOILET STALLS ARE
 PROVIDED, THEN AT LEAST ONE SHALL BE A STANDARD TOILET
 STALL COMPLYING WITH SECTION 11-4.17.3EXCEPTION NEW
 CONSTRUCTION(1)(2). A LAV IS REQUIRED IN THE STALL.
 (SEE FIG. 11-30E). PLEASE SHOW THE REQUIRED LAV IN THE
 STALL.
  
 4. SHT A3.4 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR
 W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 ___FOR URINALS
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 ___FOR LAVS
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
  
 5. SHT P-02 SUBMIT THE RISER DIAGRAMS, (SANITARY &
 WATER), IN ISOMETRIC FORM THAT REFLECT THE PIPING SHOWN
 ON THE FLOOR PLAN. SECTION
 106.3.5.1.3(3)(4)(6)(8)(10)(13). FOR THE SANITARY SHOW
 ALL PIPE SIZES, VENTS & TRAPS. FOR THE WATER SHOW ALL
 PIPE SIZES, VALVES & WATER HAMMER ARRESTORS.
  
 6. SHT P-02 THE EXTERIOR SHOWER DRAIN IS NOT APPROVED.
 PLEASE DELETE FROM RISER AND FLOOR PLAN. ARTICLE III
 SECTION 90-125(5).
  
 7. SHT P-02 ELECTRIC WATER HEATER DETAIL. THE EMERGENCY
 PAN DRAIN SHALL EXTEND FULL SIZE AND TERMINATE OVER A
 SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR FLOOR DRAIN
 OR EXTEND TO THE EXTERIOR OF THE BUILDING AND TERMINATE
 NOT LESS THAN 6" AND NOT MORE THAN 24" ABOVE THE
 ADJACENT GROUND SURFACE. SECTION 504.7.2. THE DETAIL
 SHOWS THE PAN DRAIN SPILLING OVER THE FLOOR. PLEASE
 CORRECT THE TERMINATION POINT TO COMPLY.
  
 8. SHT P-02 AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE TO THE BUILDING. SECTION 608.13.2. PLEASE SHOW
 THE BACKFLOW ON THE WATER SERVICE.NOTE: THE POOL
 PLANS SHOW A HOSE BIBB WITH A VACUUM BREAKER AS WELL AS
 AN AIR GAP FOR THE MAKE-UP WATER AT THE COLLECTOR TANK.
 THE RPZV BACKFLOW SHOWN FOR THE MAKE-UP WATER WILL NOT
 BE NECESSARY AND CAN BE DELETED.
  
 9. ALL PLUMBING SHEETS. THE ADDRESS OF RECORD ON THE
 FLORIDA STATE DBPR WEBSITE DOES NOT REFLECT THE ADDRESS
 SHOWN ON THE ENGINEERS TITLE BLOCK. FAC
 61G15-23.002(2). PLEASE UPDATE THE DBPR WEBSITE OR THE
 TITLE BLOCKS SO THAT THEY CORRELATE PRIOR TO
 RESUBMITTING FOR REVIEW. FS 471.025.
  
 10. THE FOLLOWING INFORMATION REQUIRED FOR THE SEPARATE
 GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: SHT P-03 INDICATES 7" WC FOR SUPPLY PRESSURE. IF
 NATURAL GAS FLORIDA PUBLIC
 UTILITIES ONLY SUPPLIES 12" TO 14" WC OR
 2PSI. PLEASE CLAIRFY WITH GAS PROVIDER
 PRIOR TO RESUBMITTING FOR CORRECT
 DELIVERY PRESSURE.
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 6 Status P Date 2008-09-25 Cont ID  
Sent By rkussner Date 2008-09-26 Time 4:40 Rev Time 0.00
Received By LFRANCO Date 2008-09-25 Time 2:30 Sent To  
Notes
2008-09-26 17:45:52PLANNING AND ZONING: **** PASSED FOR POOL HOUSE ONLY
 ****
  
 1. THE MSP SITE PLAN OVERALL SHEET WAS NOT APPROVED
 SINCE IT DOES NOT SHOW THE APPROVED PARKING SPACES OF
 116 AND SOME ADDITIONAL CONFIGURATION FOR PARKING
 REVISIONS THAT WILL BE ADDRESSED THROUGH THE MINOR
 AMENDMENT PROCESS. SHEET P-03 STAMPED ONLY SHOWING POOL
 HOUSE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 5 Status P Date 2008-04-15 Cont ID  
Sent By bpowell Date 2008-04-15 Time 10:15 Rev Time 0.00
Received By bpowell Date 2008-04-15 Time 10:15 Sent To  
Notes
2008-04-15 10:22:19**** PASSED WITH PROVISO ****
  
 1. PROVIDE RESPONSES TO COMMENTS IN WRITING.
 2. PLEASE PROVIDE A COPY OF THE POOL HOUSE (BUILDING
 PERMIT) PACKAGE TO THE PLANNING AND ZONING DEPARTMENT
 FOR THE FILE, C/O LINDA MIA FRANCO, SENIOR PLANNER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT LINDA FRANCO
 AT (561) 822-1443 OR [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-02-07 Cont ID  
Sent By lfranco Date 2008-02-07 Time 18:33 Rev Time 0.00
Received By lfranco Date 2008-02-07 Time 18:33 Sent To  
Notes
2008-02-07 18:34:22PLANNING AND ZONING:**** PASSED WITH PROVISO ****
  
 1.PROVIDE RESPONSES TO COMMENTS IN WRITING.
  
 2.PLEASE PROVIDE A COPY OF THE POOL HOUSE (BUILDING
 PERMIT) PACKAGE TO THE PLANNING AND ZONING DEPARTMENT
 FOR THE FILE, C/O LINDA MIA FRANCO, SENIOR PLANNER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2007-09-24 Cont ID  
Sent By lfranco Date 2007-09-13 Time 19:42 Rev Time 0.00
Received By lfranco Date 2007-09-13 Time 19:42 Sent To  
Notes
2007-09-24 19:46:18PLANNING AND ZONING:**** PASSED WITH PROVISO ****
  
 1.PROVIDE RESPONSES TO COMMENTS IN WRITING.
  
 2.PLEASE PROVIDE A COPY OF THE POOL HOUSE (BUILDING
 PERMIT) PACKAGE TO THE PLANNING AND ZONING DEPARTMENT
 FOR THE FILE, C/O LINDA MIA FRANCO, SENIOR PLANNER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 822-1443
 EMAIL: [email protected]
  