Plan Review Details - Permit 07080077
Plan Review Stops For Permit 07080077
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-01-22 Cont ID  
Sent By lursu Date 2008-01-22 Time 08:27 Rev Time 0.00
Received By lursu Date 2008-01-07 Time 12:18 Sent To  
Notes
2008-01-22 08:28:54THE RESTAURANT SUITE NUMBER IS 100 .PERMIT OK.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-08-31 Cont ID  
Sent By lursu Date 2007-08-31 Time 11:18 Rev Time 0.00
Received By lursu Date 2007-08-31 Time 11:18 Sent To  
Notes
2007-08-31 11:22:21PLEASE SPECIFY THE UNIT NUMBER OF THIS LOCATION .IS THE
 MAIN ENTRANCE DIRECTLY FROM S FLAGLER DR OR FROM
 LAKEVIEW AVE.PLEASE CLARIFY .ALSO CORRECT THE PERMIT
 APPLICATION WITH THE CORRECT INFORMATION REGARDING THE
 OWNER OF RECORD OF THIS PROPERTY PCN =
 74434322300010060 .
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-08 Cont ID  
Sent By jjohnsto Date 2007-11-08 Time 14:13 Rev Time 2.00
Received By jjohnsto Date 2007-11-08 Time 14:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-13 Cont ID  
Sent By jjohnsto Date 2007-09-13 Time 11:39 Rev Time 3.00
Received By jjohnsto Date 2007-09-13 Time 11:36 Sent To  
Notes
2007-09-13 11:37:38CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON,CBO PERMIT NO 07080077
 BUILDING PLAN EXAMINERII PROJECT MORTON?S OF
 CHICAGO
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 777 S. FLAGLER
 STREET CONTRACTOR RCC ASSOCIATES, INC.
  DATE SEPTEMBER 12, 2007
 STRUCTURALPLANREVIEW
  
 1. THE ARCHITECT OF RECORDIS MISSING THE FOLLOWING
 INFORMATION IN THEIR TITLE BLOCK,
 CERTIFICATE OF AUTHORIZATION NUMBER AS PERF.S.
 489.219
 61G15-23.002 THE PRINTED NAME AND LICENSE NUMBER AND
 THE FIRMS CERTIFICATE OF AUTHORIZATION.THIS IS THE
 AUTHORIZATION NUMBER ASSOCIATED WITH THE ARCHITECTS
 LICENSE NUMBER THAT QUALIFIES THE FIRM PAYC.IN LIEU
 OF OBTAINING AN ADDITIONAL QUALIFYING NUMBER FROM THE
 STATE, THE ARCHITECT CAN REMOVE ALL REFERENCE TO THE
 COMPANY PAYC AND SIGN AS AN INDIVIDUAL.
  
 2. TA1.1CODES
 STATEON COVER SHEET, FBC WITH 2005 AND 2006
 REVISIONS
  
 3. TA1.1CODES
 STATEON COVER SHEET, FBC 2004EXISTING BUILDINGS
  
 4. TA1.1FBC EXISTING303ALTERATION LEVEL 1 TYPE OF
 CONSTRUCTION CLASSIFICATION,STATE ON COVER SHEET
 THIS IS A LEVEL 1 ALTERATION
  
 5. CORRECTION SUBMITTAL
 WHEN RE-SUBMITTING CORRECTED PLANS FOR PERMITTING,
 PLEASE REMOVE AND REPLACE ANY SHEETS AS NECESSARY.
 INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER WITH A DESCRIPTION OF THE
 CORRECTIONS MADE. ALSO IDENTIFY THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND. THIS
 SHALL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 6. 109.3.
 10.1 HURRICANE PROTECTION
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
  
 7. OCCUPANCY CLASSIFICATION
 A-2ASSEMBLY USES INTENDED FOR FOOD AND/OR DRINK
 CONSUMPTION INCLUDING, BUT NOT LIMITED TO: RESTAURANT
  
  
  
 8. FBC1004.1.2OCCUPANT LOAD TABLE KITCHEN
 AREA CANNOT INCLUDE STORAGE/OFFICE/ LIQUOR/ ELECTRICAL
 ROOMS, SEE TABLE FOR CORRECT ALLOWANCES PER DEFINED
 SPACE
  
  
 10. FBC803.1INTERIOR FINISHES FLAME SPREAD CLASS B
 FOR A-2 OCCUPANCYSEE TABLE803.5

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-07 Cont ID  
Sent By dpalmer Date 2008-01-07 Time 10:21 Rev Time 0.00
Received By dpalmer Date 2008-01-07 Time 10:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-05 Cont ID  
Sent By dpalmer Date 2007-11-05 Time 16:44 Rev Time 0.00
Received By dpalmer Date 2007-11-05 Time 16:05 Sent To  
Notes
2007-11-05 16:45:00** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
 PLEASE ALSO SEE THERE ARE NEW COMMENTS DUE TO CHANGES
 MADE ON PLANS AND INFORMATION NOW SUBMITTED WHICH WAS
 NOT ON PREVIOUSLY REVIEWED PLANS.
  
 1) NOTE: PLEASE SEE THE PLANS ARE NOW SIGNED, DATED AND
 SEALED BY AN ENGINEER HOWEVER THE PLANS DO NOT INDICATE
 ANY TITLE BLOCKS AS REQUIRED PER FAC 61G15-23.002, FS
 471.023
  
 2) NOTE: PLEASE SEE THE RISER NOW CONTAINS NOTES FOR
 THE EXISTING SERVICE WITH SOME ITEMS BEING NEW OR
 NEEDING TO MEET MINIMUM CODE FOR SAFETY.
 PLEASE SEE SOME ITEMS ARE NOT POSSIBLE AS SHOWN. PLEASE
 SEE THE BELOW FOR SOME EXAMPLES.
 RISER CONTAINS A NOTE #2 FOR CONDUCTORS FROM GUTTER TO
 MAIN DISCONNECT WHICH READS THE CONDUCTORS MUST BE
 SIZED FOR 400AMPS. HOW IS THIS POSSIBLE WHEN THE MAIN
 IS 600AMP RATED?
 RISER ALSO CONTAINS A NOTE #1 AS LISTED ON NOTES ON
 UPPER LEFT HAND CORNER OF PLANS WHICH STATES CONDUCTORS
 ARE TO BE RATED FOR 200AMPS. HOW IS THIS POSSIBLE WHEN
 THIS SAME MAIN IS 600AMPS AND THE CONDUCTORS ON HDP FOR
 FEEDERS IS THAT OF TWO SETS OF 350MCM.
 PLEASE ALSO SEE NOTE #1 FOR CONDUCTORS FROM TRANSFORMER
 TO LDP WHICH STATES CONDUCTORS ARE TO BE RATED FOR
 200AMPS! HOW IS THIS POSSIBLE WHEN THE MINIMUM RATING
 OF CONDUCTORS SHALL BE 400AMPS? THE RESPONSE MENTIONS
 THAT TWO CONDUITS ARE PRESENT AND IT IS BEING ASSUMED
 THAT THESE CONTAIN 3/0S. THE LDP PANEL STATES THE
 FEEDERS ARE 500 MCM. IN EITHER CASE THE CONDUCTORS
 WHICH ARE SHOWN ARE NOT RATED PER 310.16, 240.21.
 ** PLEASE CORRELATE NOTES AS THE AMPERAGES DO NOT
 CORRELATE WITH THE MINIMUM SIZES FOR LIFE SAFETY AND
 FIRE HAZARD.
  
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-29 Cont ID  
Sent By dpalmer Date 2007-08-29 Time 17:53 Rev Time 0.00
Received By dpalmer Date 2007-08-29 Time 11:30 Sent To  
Notes
2007-08-29 17:53:392007-08-29 17:53:39
  
 ** DENIED **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** SOME OF THESE CODES ARE SHOWN ON THE ARCHITECTURAL
 SHEETS HOWEVER SOME ARE NOTE. PLEASE BE SURE THE
 RELEVANT CODES ARE ON ELECTRICAL SHEETS ALSO.
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE
 REQUIRED MISSING INFORMATION AS STATED BY THE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004.
 PLEASE SEE MISSING PRINTED NAME, PRINTED FIRM LICENSE
 NUMBER WHICH IS ALSO KNOW AS A CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE SEE FLORIDA STATUTES 481.219
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 3) NOTE: PLEASE SEE ALL THREE SETS OF PLANS SUBMITTED
 IN FACT CONTAIN A *RUBBER-STAMP* FOR THE SIGNATURE OF
 THE ARCHITECT. THIS IS NOT PERMITTED PER FAC
 61G1-16.003, FS 481.221. MUST CONTAIN AN *ORIGINAL
 SIGNATURE AND DATE* WHEN SIGNING AND SEALING PLANS. **
 THIS COMMENT IS REQUIRED FOR ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 REVIEWER(S).
  
 4) NOTE: THE SCOPE OF WORK IS NOT COMPLETELY CLEAR AT
 THIS TIME FOR THE ELECTRICAL SERVICE.
 THE RISER CONTAINS A NOTE WHICH MENTIONS TO *PROVIDE
 BID TO RE-USE EXISTING TRANSFORMER* WHICH LEADS TO THE
 SERVICE SHOWN ON RISER BEING A NEW SERVICE TO THE
 SPACE.
 PLEASE KNOW BASED ON FS 471.003 THE SERVICE AS SHOWN
 MAY NOT BE DESIGNED BY AN ARCHITECT AND IN FACT NEEDS
 TO BE DONE BY A PE LICENSED UNDER FS 471 AND FAC
 61G15-23
 PLEASE ADJUST AND COMPLETE. PLEASE ALSO SEE COMMENTS
 BELOW AS THE RISER SHOWN NEW OR EXISTING DOES NOT MEET
 THE NEC FOR SOME MINIMUM REQUIREMENTS. SOME OF THESE
 ARE MINIMUM FOR FIRE HAZARD AND LIFE SAFETY.
  
 5) NOTE: PLEASE SEE THE SUITE/UNIT NUMBER NEEDS TO BE
 ON PLANS AND ALSO ON PERMIT APPLICATION.
 THE PLANS WILL BE ROUTED TO OUR ADDRESSING REVIEW TO
 CONFIRM.
 PLEASE REVISE TITLE BLOCKS ONCE SUITE/UNIT IS DONE. FAC
 61G1-16.004, 61G15-23.002
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE 408.36, 240.21 AS THE TAPPED
 CONDUCTORS ON THE SECONDARY SIDE OF THE TRANSFORMER
 SHALL TERMINATE IN OVER CURRENT PROTECTION WHICH LIMITS
 THE LOAD ON THE CONDUCTOR FOR ITS RATED AMPERAGE.
 310.16.
 RISER INDICATES THIS PANEL AS A 400AMP MLO PANEL WHICH
 DOES NOT MEET NEC.
 PLEASE SEE THE CONDUCTORS AS SHOWN AS 500MCM DO NOT
 MEET THE MINIMUM FOR CODE AS STATED ABOVE.
 PLEASE REVISE AND MAKE CORRECTIONS.
 ** IF THIS RISER AS SHOWN IN FACT EXISTS, THE RISER
 WILL STILL NEED TO MEET MINIMUM CODE AS THESE ITEMS FOR
 TAPPED CONDUCTORS, OVER CURRENT PROTECTION AND LACK OF
 CORRECT GROUNDING IS NOT SAFE.
 THIS INFORMATION HAS BEEN FORWARDED TO THE CHIEF
 ELECTRICAL INSPECTOR FOR SITE VISIT. THIS OFFICE MAY
 ALSO OBTAIN A SITE VISIT TO GO OVER SCOPE WITH PLANS AS
 SHOWN ON ANY SPECIFIC ITEMS WHICH MAY PRESENTLY BE
 UNSAFE AND NEED TO BE CORRECTED.
  
 7) NOTE: PLEASE RISER IS MISSING ALL EQUIPMENT
 GROUNDING CONDUCTORS AFTER THE FIRST MEANS OF
 DISCONNECT INCLUDING ON THE LINE AND LOAD SIDE OF THE
 TRANSFORMER.
 250.20, 250.30, 250.110, 250.122 ETC.
  
 8) NOTE: PLEASE SUBMIT AND SHOW ALL AIC RATINGS FOR NEW
 SERVICE EQUIPMENT.
 110.9
 FBC 106.1.2, 106.1.1, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE THE PLANS MENTIONS IN THE KEYED
 NOTES THAT THERE ARE LOCATIONS WHICH NEW RECEPTACLES
 WILL BE INSTALLED YET I COULD NOT LOCATE THESE NEW
 RECEPTACLES AND LOW VOLTAGE LOCATIONS ON PLANS? PLEASE
 COMPLETE PLANS BY SHOWING THESE LOCATIONS, SUBMIT THE
 PANEL SCHEDULE(S) FOR NEW CIRCUITS ETC FBC 106.3.5.1.2,
 NEC 310.16, 240.4, 408.4 ETC
  
 10) NOTE: PLEASE CLARIFY WHERE THE LIGHTING CONTROLS
 FOR NEW LIGHTING PER 13-415.1.ABC.1.1, .1.2 OF THE FBC
 ARE?
 13-101
 PLEASE GIVE THE LIGHTING POWER DENSITIES PER 13-415.2
  
 11) NOTE: PLEASE VERIFY WITH THE FLORIDA POWER AND
 LIGHT (FPL) THE RISER AS SHOWN WHICH INDICATES THE CT
 CAN ON THE LOAD SIDE OF THE SERVICE MAINS.
 PLEASE SEE SERVICE STANDARDS WHERE THESE ARE REQUIRED.
 ( LINE SIDE)
  
 12) NOTE: PLEASE KNOW DUE TO COMMENT #3 AND #2 ABOVE
 ONE SET OF THE PLANS ARE BEING RETAINED BY THIS
 OFFICE.
  
  
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-11-12 Cont ID  
Sent By mawillia Date 2007-11-12 Time 14:56 Rev Time 0.00
Received By mawillia Date 2007-11-12 Time 14:26 Sent To  
Notes
2007-11-12 14:52:22*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S)
 TO BE FIRE-STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-25 Cont ID  
Sent By mawillia Date 2007-09-25 Time 17:29 Rev Time 0.00
Received By mawillia Date 2007-09-25 Time 15:53 Sent To  
Notes
2007-09-25 16:23:52*****DENIED*****
  
  
 1.PLEASE BE ADVISED THAT THE OCCUPANCY IS LOCATED IN
 THE JURISDICTION OF WEST PALM BEACH, NOT PALM BEACH AS
 INDICATED ON THE COVER SHEET (TA1.1) OR IN THE TITLE
 BLOCK OF THE SUBMITTED PLAN SHEETS.
  
 2.THE ACTUAL LOCATION OF THE PROJECTED SCOPE OF WORK,
 INCLUDING THE SUITE NUMBER AND THE TOWER (EAST OR WEST)
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.ON SHEET A2.1 UNDER THE DINING UPGRADE NOTES,
 REFERENCES ARE MADE TO SEE SHEET A1.3;HOWEVER THERE
 IS NO SUCH SHEET AS PER YOUR DRAWING INDEX OR INCLUDED
 IN THE PLAN.
  
 5.NO EXIT LIGHTS, EMERGENCY LIGHTS SHOWN ON SHEET
 A1.1, A2.1, OR E1.1.
  
 6.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS
 TO BE INSTALLED IN TERMS OF CLASS A, CLASS B, OR CLASS
 C.
  
 7.DETAIL THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHERS WHICH SATISFIES THE 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-07 Cont ID  
Sent By adarroug Date 2008-01-07 Time 08:48 Rev Time 0.00
Received By adarroug Date 2008-01-07 Time 08:48 Sent To  
Notes
2008-01-07 08:48:30TO "COMM" BD#12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 12:18 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 12:18 Sent To  
Notes
2007-11-05 10:27:21TO "COMM" BD#23
2007-10-17 12:19:17WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-25 Cont ID  
Sent By mawillia Date 2007-09-25 Time 15:53 Rev Time 0.00
Received By mawillia Date 2007-08-06 Time 18:27 Sent To  
Notes
2007-08-29 09:10:21TO "COMM" BD#45
2007-08-06 18:27:39WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-01-22 Cont ID  
Sent By kstevens Date 2008-01-22 Time 10:09 Rev Time 0.00
Received By kstevens Date 2008-01-22 Time 10:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-04 Cont ID  
Sent By kstevens Date 2007-12-04 Time 17:55 Rev Time 0.00
Received By kstevens Date 2007-12-04 Time 17:55 Sent To  
Notes
2007-12-04 17:57:40DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. THE APPLICATION REQUIREMENT TO "DESCRIBE PROJECT IN
 DETAIL" INDICATES NO PLUMBING WORK. ON SHT D1.1
 KEYNOTES 17 PLUMBING WORK IS INDICATED AS WELL AS ON
 SHT MP1.1. TO INDICATE THAT NO PLUMBING WORK WILL BE
 DONE IS MISLEADING AND NOT CORRECT. PLEASE INDICATE ALL
 WORK TO BE DONE WHEN DESCRIBING THE PROJECT. SECTION
 105.3.
 ****RESPONSE NOTED, BUT CONTRACTOR HAS NOT CHANGED THE
 APPLICATION.
  
 2. ALL SHEETS PER FAC 61G1-16.004(2)(5)(6) THE FIRM
 LICENSE, DATED SEAL & PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT SHALL BE ON EACH SHEET. FS
 481.219, 481.2055. PLEASE DATE THE SEAL WHEN THE SEAL
 AND SIGNATURE ARE AFFIXED TO THE DOCUMENTS, INDICATE
 THE FIRM LICENSE, (CERTIFICATE OF AUTHORIZATION), AND
 PRINT THE NAME OF THE ARCHITECT ON EACH SHEET.
 ****RESPONSE NOTED, BUT THE DATE THE SEAL & SIGNATURE
 WERE AFFIXED IS NOT PLACED ON THE PLANS AS REQUIRED.
  
 3. OK
 4. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By kstevens Date 2007-09-17 Time 17:33 Rev Time 0.00
Received By kstevens Date 2007-09-17 Time 17:33 Sent To  
Notes
2007-09-17 18:07:27DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE APPLICATION REQUIREMENT TO "DESCRIBE PROJECT IN
 DETAIL" INDICATES NO PLUMBING WORK. ON SHT D1.1
 KEYNOTES 17 PLUMBING WORK IS INDICATED AS WELL AS ON
 SHT MP1.1. TO INDICATE THAT NO PLUMBING WORK WILL BE
 DONE IS MISLEADING AND NOT CORRECT. PLEASE INDICATE ALL
 WORK TO BE DONE WHEN DESCRIBING THE PROJECT. SECTION
 105.3.
  
 2. ALL SHEETS PER FAC 61G1-16.004(2)(5)(6) THE FIRM
 LICENSE, DATED SEAL & PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT SHALL BE ON EACH SHEET. FS
 481.219, 481.2055. PLEASE DATE THE SEAL WHEN THE SEAL
 AND SIGNATURE ARE AFFIXED TO THE DOCUMENTS, INDICATE
 THE FIRM LICENSE, (CERTIFICATE OF AUTHORIZATION), AND
 PRINT THE NAME OF THE ARCHITECT ON EACH SHEET.
  
 3. ALL SHEETS THE SIGNATURE IS REQUIRED ON EACH SHEET
 WHEN SEALING. AS SUBMITTED IT APPEARS TO BE IN FACT A
 SIGNATURE STAMP WHICH IS NOT APPROVED. PLEASE SIGN EACH
 SEAL WITH A "WET OR ORIGINAL SIGNATURE". FAC
 61G1-16.003 61G1-16.004(5) & FS 481.2055.
  
 4. SHT MP-1.1 INDICATES DEMO AND REROUTING WATER LINES.
 PLEASE SUBMIT AN ISOMETRIC WATER RISER DIAGRAM SHOWING
 THE EXTENT OF THE WORK. SHOW ALL PIPE SIZES, VALVES
 ETC. SHOW WHERE THE CONNECTIONS WILL BE AND INDICATE
 THE MATERIAL TYPE. SECTION 106.3.1.5(3)(10)(13).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]