Plan Review Details - Permit 07080073
Plan Review Stops For Permit 07080073
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-09-12 Cont ID  
Sent By lursu Date 2007-09-12 Time 10:33 Rev Time 0.00
Received By lursu Date 2007-09-12 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-22 Cont ID  
Sent By jwitmer Date 2007-09-22 Time 16:50 Rev Time 30.00
Received By jwitmer Date 2007-09-22 Time 16:50 Sent To  
Notes
2007-09-22 16:53:17THE LAKES AT PALM BEACH
 LUGANO BUILDING NO. 5
 SEPT.22,2007
  
 BUILDING PLAN REVIEW
 PERMIT: 07080073
 ADD:1580 SAMANTHA LANE
 CONT: AVS CONSTRUCTION
 TEL: (954)655-5162
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)PLANS SUBMITTED AFTER JULY 1, 2007WILL BE
 REVIEWED UNDER THE 2004 BASE FLORIDA BUILDING CODE,
 BUILDING WITH 2006 AMENDMENTS AND THE 2007WIND
 PROVISIONS. PLEASE CORRECT
 SHEET A-002 BUILDING NO. 5 DATA, THE WRONG YEAR CODE.
  
 3) SHEET A-002 BUILDING DATA ALSO CORRECT THE HEIGHT
 AND AREA LIMITATIONS, AND THE REFERENCE TO TABLE 500
 PLEASE UPDATE TO THE 2004 NOMENCLATURE. PLEASE
 CORRELATE WITH THE LIFE SAFETY SHEET FOUND ON SHEET
 A-251.
  
 4) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS. 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE
 A SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS
 ON A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 7) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY553.79(5) FLORIDA STATUTES TO
 THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT
 HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM
 AT (561) 805-6711 FOR FURTHER INFORMATION BEFORE THE
 PERMIT MAY BE ISSUED.
  
 8)W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 10) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 11) HURRICANE PREPAREDNESS
  
 12) CORRELATE PLANS IT APPEARS THAT ON THE CIVIL PLANS
 THE PROJECT NAME STILL INDICATES MIZNER LAKES AND NOT
 THE LAKES AT PALM BEACH, PLEASE CORRECT.
  
 13) SHEETS A-003- A004 INDICATE THE FAIR HOUSING
 GUIDELINES, PLEASE NOTE THAT THE FIRST FLOOR MERCANTILE
 OCCUPANCY WILL BE UNDER 2004 FBC CHAPTER 11 FLORIDA
 ACCESSIBILITY.
  
 14) SHEET A-102 & A-202 THE COVERED ENTRY LOADING SPACE
 BY THE FRONT ELEVATOR LOBBY # 100 INDICATES STAIRS BUT
 NO VERTICAL ACCESSIBILITYIN UNDER THE COVERED CANOPY.
 AGAIN
 11-2.2EQUIVALENT FACILITATION, YOU CAN?T DISCRIMINATE
 AGAINST TOUGHS WITH DISABILITIES
 REQUIRING THEM TO TAKE A ROUTE THAT IS NOT COVERED.
  
 15) SHEET A-102 & A-202 AND A-502 ALL INDICATE A
 SECURITY OFFICE AND A VALET STATION WITH
 WHAT APPEARS TO BE A COUNTER AND SLIDING GLASS WINDOWS,
 PLEASE PROVIDE A SECTION OF THIS AREA WITH THE COUNTER
 HEIGHT PROVIDED TO MEET FAIR HOUSING GUIDE LINES.
  
 16) SHEET A-102 & A-202 BOTH HAVE RAMPS:
 16A) BY THE CONDO UNITTH-1E THERE 2 ACCESSIBLE
 PARKING SPACES WITH A 5?-0? WIDE ACCESS AISLE, THIS
 AREA IS ALSO THE BOTTOM LANDING FOR TWO RAMPS, THE
 BOTTOM LANDING FOR RAMPS REQUIRES A 72? LANDING NOT A
 60? LANDING. 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON
 RAMPS SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF
 EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARANCE.
  
 16B) THE SAME TYPE SITUATION OCCURS AT CONDO UNIT TH-1A
 , THE BOTTOM LANDING FROM RAMPS IS ONLY 5?-0? NOT THE
 REQUIRED 72?. .(2) LANDINGS. ALL LANDINGS ON RAMPS
 SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL
 CLEARANCE.
  
 17) A-202 DOOR OR GATE G06 & G07 PLEASE PROVIDE
 MANUFACTURERS? INFORMATION ON HOW
 THESE UNITS WILL OPEN? 106.1.2* ADDITIONAL INFORMATION
 REQUIRED.
  
 18) A-201, THE HANDICAPPED RAMP IN THE UPPER RIGHT
 PORTION OF THE SHEET IS MISSING THE BOTTOM LANDING.
 .11-4.8.4(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT
 BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS
 THAN 72" OF STRAIGHT & LEVEL CLEARANCE.
  
 19) SHEETA-201 THE HANDICAPPED RAMP ALSO APPEARS THAT
 IT IS DIRECTLY IN FRONT OF 5 EXHAUST FANS FOR THE
 ENCLOSED PARING GARAGE,THE DISABLED COULD MAKE A
 STRONG CASE OF
 EQUIVALENT FACILITATION 11-2.2, THAT THEY ARE FORCED TO
 USE THE RAMP WHERE THEY WOULD BE SUBJECT TO THE CAR
 EXHAUST WHILE OTHERS WHO ARE NOT DISABLED DO NOT HAVE
 TO BE OBJECTED TO THE EXHAUST FUMES.
  
 20) A-201 WHAT AGAIN ARE RAMPS OR CURB CUTS THE BOTTOM
 LANDING IS 5?-0? WHERE :
 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT
 BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL CLEARANCE.
  
 21) A-201 & A-501 BOTH INDICATE STAIRS TO THE COVERED
 ARCADE BUT THE TREAD DISTANCE IS NOT PROVIDED? PLEASE
 PROVIDE A SECTION OF THIS AREA. 1003.5.1
 WHERE A CHANGE IN LEVEL MEANS OF EGRESS NOT EXCEEDING
 21 INCHES (533 MM) IS ACHIEVED BY A STAIR, THE MINIMUM
 TREAD DEPTH OF SUCH STAIR SHALL BE 13 INCHES (330 MM)
 AND THE PRESENCE AND LOCATION OF EACH STEP SHALL BE
 READILY APPARENT. EXCEPTION: WITHIN DWELLING LEVEL.
 1003.5.2 WHERE CHANGE IN ELEVATION OF 12 INCHES (305
 MM) OR LESS OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND
 EXIT DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL
 BE PROVIDED.
  
 22)1009.12 ACCESS TO ROOF.BUILDINGS FOUR STORIES OR
 MORE IN HEIGHT, EXCEPT THOSE WITH A ROOF SLOPE GREATER
 THAN 4:12, SHALL BE PROVIDED WITH A STAIRWAY TO THE
 ROOF. SUCH STAIRWAY SHALL BE MARKED AT STREET AND FLOOR
 LEVELS WITH A SIGN INDICATING THAT IT CONTINUES TO THE
 ROOF. WHERE ROOFS ARE USED FOR ROOF GARDENS OR FOR
 OTHER PURPOSES, STAIRWAYS SHALL BE PROVIDED AS REQUIRED
 FOR SUCH USE OR OCCUPANCY.
  
 23) SHEET A-201 G-05 DOES NOT HAVE A CURB CUT, THERE IS
 NO DESIGNATION FOR AN ACCESSIBLE PATH ACROSS THE ENTRY
 AREAS FOR BOTH ENTRIES INTO THE BUILDING BY VEHICLE AND
 THERE IS A
 CENTER AISLE THAT ALSO DOES NOT HAVE ACCESS ACROSS.
  
  
 24) HANDICAPPED PARKING SPACES IN THE GARAGE NEED TO
 COMPLY WITH 11-4.1.2(5)(B)IN PARKING STRUCTURES, ONE
 IN EVERY EIGHT ACCESSIBLE SPACES, BUT NOT LESS THAN
 ONE, SHALL BE ?VAN
 ACCESSIBLE? AND SHALL BE DESIGNED AS REQUIRED BY
 SECTION 11-4.6.3. THE VERTICAL CLEARANCE AT SUCH SPACES
 SHALL COMPLY WITH SECTION 11-4.6.5. ALL SUCH SPACES MAY
 BE GROUPED ON THE SAME LEVEL OF A PARKING STRUCTURE.
 WHEN SUCH SPACES ARE PROVIDED IN A PARKING STRUCTURE
 AND ONLY ONE IN EIGHT MEET THE HEIGHT REQUIREMENT OF
 SECTION 11-4.6.5, THEY SHALL BE DESIGNATED BY SECTION
 11.6.4.
  
 25) A-201 & A-703 BOTH INDICATE A GATE BENEATH THE
 STAIRWELL, AND A NOTE ON SHEET A-703 INDICATES THIS IS
 A MAINTENANCE GATE. ENCLOSURES UNDER STAIRWAYS.
 1019.1.5.
 THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES
 UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE
 PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION,
 OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY
 ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED
 USABLE SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE
 STAIR ENCLOSURE.
  
 26) SINCE THE LAST REVIEW UNDER PERMIT # 05091456,THE
 CONFIGURATION OF LOFT UNITS VERSES PASSAGE TO THE
 PARKING GARAGE WITH NO EXIT ACCESS CORRIDOR WAS BROUGHT
 TO THE ATTENTION OF THE BUILDING OFFICIAL. WE ARE
 SEEING MORE OF THIS TYPE DESIGN AND THE BUILDING
 OFFICIAL
 HAS RULED THAT THIS IS AN UNSAFE PRACTICE. THE
 OCCUPANTS LEAVE THE R-2 UNIT AND HAVE NO EXIT ACCESS
 CORRIDOR WHEN ENTERING THE PARKING GARAGE AREA.
 ALTHOUGH THE CODE DOESN'T QUOTE A
 SECTION, THAT AN EXIT ACCESS CORRIDOR IS REQUIRED THE
 BUILDING OFFICIAL IS USING THESE (2) CODE SECTIONS TO
 ENFORCE REQUIRING A EXIT ACCESS CORRIDOR TAKING THE
 OCCUPANT TO THE SAFETY OF AN EXIT. 103.6**
 REQUIREMENTS NOT COVERED BY THE CODE. ANY REQUIREMENTS
 NECESSARY FOR THE STRENGTH, STABILITY OR PROPER
 OPERATION OF EXITING OR PROPOSED BUILDING, STRUCTURE,
 ELECTRIC, GAS, MECHANICAL OR PLUMBING SYSTEM, OR FOR
 PUBLIC SAFETY, HEALTH AND GENERAL WELFARE , NOT
 SPECIFICALLY COVERED BY THIS OR OTHER TECHNICAL CODES,
 SHALL BE DETERMINED BY THE BUILDING OFFICIAL. IN
 ADDITION, OTHER REQUIREMENTS TO IMPLEMENT, CLARIFY OR
 SET PROCEDURES TO IMPLEMENT THIS CODE MAY BE SET IN
 WRITING BY THE BUILDING OFFICIAL AND BE POSTED
 ELECTRONICALLY FOR PUBLIC ACCESS. 1001.1.4 WHEN
 UNUSUALLY HAZARDOUS CONDITIONS EXIST, THE BUILDING
 OFFICIAL MAY REQUIRE ADDITIONAL MEANS OF EGRESS TO
 ASSURE THE SAFETY OF
 THE OCCUPANTS. 1016.1 CONSTRUCTION. CORRIDORS SHALL BE
 FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLE 1016.1 .
 THE CORRIDOR WALLS REQUIRED TO BE FIRE-RESISTANCE RATED
 SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS. 27)
 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN
 CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES;
 RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED,
 INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING
 UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 28) 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
  
 29)DOOR SCHEDULE A-901. SEE TABLE 302.3.REQUIRING A
 2HR WALLSS2 TO R2, OPENING PROTECTIVES
 715.3 1 / HR OPENING PROTECTIVES.
  
 30) THIS WILL BE A COMMON NOTE FOR ALL R2 UNITS FOR
 WALL AND FLOOR SOUND INSULATION REQUIREMENTS27) SHEET
 A-201 THE CONDO ENTRY UNIT DOORS 133 & 134 BOTH ARE
 MISSING AFIRE RATING ON THE. LEASE PLEASE PROVIDE THE
 STC RATINGS FOR WALLS AND FLOORS WHERE REQUIRED. SEE
 CODE SECTIONS BELOW
  
  
 31) SHEET A-202THE DOOR SCHEDULE THAT TIES TO DOORS
 111, 1132 & 115 CONDO ENTRY DOORS ARE NOT FIRE RATED.
 RS2 VS S2 TABLE 302.3.2 2HR WALLS 715.3 11/2 HR OPENING
 PROTECTIVE.
  
 32) 32) SHEET A-205 DOOR 342, 347,367 & 358 ALL
 INDICATE THE USE OF SLIDING GLASS DOORS ONTO
 PATIO DECKS, PLANS DO NOT INDICATE (3) ITEMS THAT ARE
 CONCERNS TO FAIR HOUSING REQUIREMENTS FOR SLIDING GLASS
 DOORS (SECONDARY DOORS) THAT LEAD ONTO A IMPERVIOUS
 SURFACE.
 A) PLEASE PROVIDE A DETAIL INDICATING THE BOTTOM TRACK
 HEIGHT IN RELATIONSHIP TO THE INTERIOR FINISH FLOOR AND
 THE FINISH FLOOR OF THE PATIO ON THE EXTERIOR.
 B) PLEASE PROVIDE THE CLEAR OPENING SIZE FOR THE 6?-2?
 SLIDING GLASS DOORS.
 C) PROVIDE DETAILS FOR THE LATCHING MECHANISM FOR THE
 SLIDING GLASS DOOR.
 PLEASE SEE PAGE 4.14 OF FAIR HOUSING MANUAL DETAIL FOR
 SLIDING GLASS DOORS AT CONCRETE LANDINGS.
  
  
  
  
 32) SHEET A-203 DOOR # 208 DOOR TO STAIR# 4 NOT RATED,
 TABLE 715.3 OPENING PROTECTIVE
 < THAN 4STORIES 45 MINUTE DOOR.
  
 33) SHEET A-206 THE STAIR# 1 DOOR 302 IS MISSING FROM
 THE DOOR SCHEDULE, TABLE 715.3 OPENING PROTECTIVE 2HR
 SHAFT REQUIRES 1 ? HR OPENING PROTECTIVE.
  
 34) SHEET A-205 DOOR 342, 347,367 & 358 ALL INDICATE
 THE USE OF SLIDING GLASS DOORS ONTO
 PATIO DECKS, PLANS DO NOT INDICATE (3) ITEMS THAT ARE
 CONCERNS TO FAIR HOUSING REQUIREMENTS FOR SLIDING GLASS
 DOORS (SECONDARY DOORS) THAT LEAD ONTO A IMPERVIOUS
 SURFACE.
 A) PLEASE PROVIDE A DETAIL INDICATING THE BOTTOM TRACK
 HEIGHT IN RELATIONSHIP TO THE INTERIOR FINISH FLOOR AND
 THE FINISH FLOOR OF THE PATIO ON THE EXTERIOR.
 B) PLEASE PROVIDE THE CLEAR OPENING SIZE FOR THE 6?-2?
 SLIDING GLASS DOORS.
 C) PROVIDE DETAILS FOR THE LATCHING MECHANISM FOR THE
 SLIDING GLASS DOOR.
  
  
 35) SHEET A-300 THE ELEVATOR LOBBY# 100 IT APPEARS THIS
 AREA MAY BE CONSIDERED EITHER A MEZZANINE OR ATRIUM,
 PLEASE PROVIDE THE AREA CALCULATIONS OF THE AND THE
 ADJOINING AREAS AND PLEASE DO SO FOR THE AREA ABOVE
 THAT HAS A 42? HANDRAIL. IT APPEARS THIS AREA MAY
 QUALIFY FOR BEING CONSIDERED A MEZZANINE. IF IT DOES
 NOT MEET THE QUALIFICATION BY AREA WE WILL THEN
 CONSIDER IT A 2 STORY ATRIUM AND THE ASSOCIATED
 REQUIREMENTS OF AN ATRIUM WITH THE EXCEPTION OF 404 FOR
 A 2 STORY ATRIUM.
  
 36) SHEET A-300 PLEASE SEE ROOMS 120 -123 IN EACH OF
 THESE ROOMS THERE IS A CHANGE OF GRADE,
 PLEASE SEE1003.5.2 WHERE CHANGE IN ELEVATION OF 12
 INCHES (305 MM) OR LESS OCCURS IN EXIT ACCESS
 CORRIDORS, EXITS AND EXIT DISCHARGE, RAMPS COMPLYING
 WITH SECTION 1010 SHALL BE PROVIDED. 1003.5.3
  
 37) SHEET A-300, THIS NOTE WILL BE COMMON TO ALL ??
 FLOOR PLANS, THESE SHEETS INDICATE THE WALL TYPES BUT
 NEGLECT TO IDENTIFY ALL DOORS. WHEN REVIEWING FOR WALL
 RATINGS IN SECTION 708 WE REVIEW ALSO FOR THE
 CORRESPONDINGOPENING PROTECTIVE IN SECTION 715 AND
 TABLE 715.3 PLEASE IDENTIFY BOTH ON THE SAME SHEET,
 ADDITIONAL INFORMATION REQUIRED, 106.1.2, IN COMPLYING
 WITH THIS REQUEST IT MAY SAVE THE CONTRACTOR &
 DEVELOPER TIME AND MONEY IN MISTAKES THAT MAY NOT OF
 BEEN CAUGHT IN PLAN REVIEW BUT CAUGHT IN INSPECTIONS IN
 THE CONSTRUCTION PHASE OF THE PROJECT.THIS IS
 SOMETHING WE TRY TO AVOID BUT THE HARDER IT IS TO FIND
 THE WALL AND ASSOCIATED DOOR RATINGS, MISTAKES CAN
 HAPPEN.
  
 38) SHEET A-300,STAIRWELL# 1, IS MISSING WALL I. D.
 TAGS ON VARIOUS WALLS REQUIRES 2 HR RATING, SECTION
 707.4.MISSING TAGSH.C. RESTROOM, TRASH TERMINATION
 ROOM WALL LEADING TO ELEVATOR LOBBY.
  
 39) THE SHEET A-905 INDICATES WALL TYPE AND UL NUMBERS
 ASSOCIATED WITH MASONRY WALLS.
 PLEASE PROVIDE LETTERS FROM THE BLOCK MANUFACTURER
 INDICATING THE MINIMUM EQUIVALENT THICKNESS FOR THE
 MASONRY UNITS. SECTION 721.3.8EQUIVALENT THICKNESS.
  
 40) SHEET A-300 TRASH TERMINATION ROOM, IT APPEARS
 THERE IS AN UNIDENTIFIED OBJECT IN THE UPPER LEFT HAND
 CORNER OF THIS ROOM. ADDITIONAL INFORMATION REQUIRED
 106.1.2.
  
 41) SHEET A-300/ A-202 THE TRASH COMPACTOR ROOMS DOOR
 146 IS MISSING THE FIRE RATING AND THE DOOR SCHEDULE
 INDICATES IT AS A TYPE ?E? LOUVER DOOR.710.5.1
 LOUVERS .
 DOORS IN SMOKE PARTITIONS SHALL NOT INCLUDE LOUVERS.
 707.13.4 TERMINATION ROOM.
  
 42) SHEET A-300/ A-202 BOTH FAIL TO INDICATE WALL
 RATINGS ON THE COMMON WALL TO THE S2 OCCUPANCY, THE
 DOOR SCHEDULE INDICATES A 45 MINUTE RATED DOOR E & F
 BOTH BEING LOUVERED DOORS. 710.5.1 LOUVERS . DOORS IN
 SMOKE PARTITIONS SHALL NOT INCLUDE LOUVERS.
  
 43)SHEET A-300/ A-202 FPL TRANSFORMER VAULT, PLEASE
 TAKE NOTE THAT FPL MAY HAVE HIGHER WALL RATING AND
 CEILING RATINGS THAN INDICATED. 106.1.2. ADDITIONAL
 INFORMATION REQUIRED.
  
 44) SHEET A-300/ A-202 BOTH INDICATE 2 ELEVATORS, SHEET
 A-701 INDICATES STAIR AND ELEVATOR SECTION PLAN NO
 PLANS INDICATE COMPLIANCE WITH STRETCHER REQUIREMENTS,
 PLEASE PROVIDE DETAIL.
 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER.
 IN BUILDINGS FOUR STORIES IN HEIGHT OR MORE, AT LEAST
 ONE ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR SHALL
 BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE A
 24-INCH BY 76-INCH (610 MM BY 1930 MM) AMBULANCE
 STRETCHERIN THE HORIZONTAL, OPEN POSITION AND SHALL
 BE IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY
 MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL NOT
 BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL BE PLACED
 INSIDE ON BOTH SIDES OF THE HOIST WAY DOOR FRAME.
  
 45) SHEET A-300/ A-202 THE EGRESS PATH IN FRONT OF
 REFUSE TERMINATION ROOM, FIRE BOOSTER PUMP AND THE MAIN
 ELECTRIC ROOM ALL SWING INTO THE EGRESS PATHWAY. 1005.2
 DOOR ENCROACHMENT.
 DOORS OPENING INTO THE PATH OF EGRESS TRAVEL SHALL NOT
 REDUCE THE REQUIRED WIDTH TO LESS THAN ONE-HALF DURING
 THE COURSE OF THE SWING. WHEN FULLY OPEN, THE DOOR
 SHALL NOT PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH.
  
 46) SHEET A-202 STAIR TOWER# 2 WHEN YOU LEAVE THE 2
 HOUR RATED ENCLOSURE YOU ARE STILL UNDER THE BUILDING,
 AND DOES NOT QUALIFY FOR ANY EXEMPTION UNDER 1023.1
 GENERAL. EXITS SHALL DISCHARGE DIRECTLY TO THE EXTERIOR
 OF THE BUILDING. THE EXIT DISCHARGE SHALL BE AT GRADE
 OR SHALL PROVIDE DIRECT ACCESS TO GRADE. THE EXIT
 DISCHARGE SHALL NOT REENTER A BUILDING.PLANS ALSO
 INDICATE A 54"X96" LOUVER WHICH WOULD NOT MAKE ANY FIRE
 RATING OF THE EXTERIOR WALL THAT BACKS UP TO THE EXIT
 DISCHARGE OF THE STAIR TOWER.
  
 46) FL BLD CODE 1606.1.5: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTINGREPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED/ STOREFRONT
 B) WINDOWS OPERABLE
 C) MULLIONS
 D) EXTERIOR DOORS GLAZED, SLIDERS
 E) EXTERIOR LOUVERED DOORS
 F) DOORS STEEL
 G)EXTERIOR OVERHEAD DOORS
 H)HANDRAILS
 I) STORM SHUTTERS
 J) TRUSS ANCHORS
 K) ROOFING ASSEMBLIES
 L) PRE-MANUFACTURED A/C STANDS
 M) STORM SHUTTERS
  
 47) NOTE)) AN INTERPRETATION FROM THE BUILDING OFFICIAL
 ON STORM SHUTTERS THAT ARE USED ON LARGE PROJECTS:
 QUESTION# 13) RECOGNIZING SUCH CONCERNS AS ABSENTEE
 OWNERS, OR CASES WHERE LONGER TIME AND EFFORT IS
 NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR
 IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR
 SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004 EDITION,
 PROVIDES THE ABILITY FOR THE BUILDING OFFICIAL TO
 IMPLEMENT REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF EXISTING BUILDINGS.
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE SAME PROPERTY,
 PRE-STORM PREPARATION PLANS MUST BE SUBMITTED BY THE
 PROPERTY OWNERS OR MANAGING AGENTS FOR REVIEW BY THE
 CONSTRUCTION SERVICES DEPARTMENT. ANY SUCH PLAN SHALL
 INCLUDE, AT A MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE SHUTTERS (SAID
 PARTIES MUST BE LOCATED WITHIN PALM BEACH COUNTY),
 TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND TOTAL TIME
 REQUIRED TO SECURE ALL OPENINGS. PROTECTION OF OPENINGS
 SHALL BE ACCOMPLISHED WITHIN TWELVE (12) HOURS OR LESS
 OF THE OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER
 SERVICE OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE BUILDING OFFICIAL
 TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN QUALITY, STRENGTH,
 EFFECTIVENESS, FIRE RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE PROVISION,
 ACCEPTANCE OF ALTERNATE MATERIALSAND METHODS MAY BE
 APPROVED ON A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO SUBSTANTIATE ANY CLAIM
 MADE REGARDING THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS APPROPRIATE
 FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES? NO, EXCEPT ON THE GROUND
 FLOOR. ON COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL, IMPACT RESISTANT
 GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE INSTALLED.
 PERMANENTLY AFFIXED PROTECTIVE DEVICES SHALL REQUIRE
 THE WRITTEN APPROVAL OF THE BUILDING OFFICIAL.
  
 48) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 48A) FL BLD CODE 2001 SECTION 1609.1.4, 1714.5
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC.,
 SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO
 FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.
  
 48B) PROVIDE ROOF PRESSURE ZONES FOR ZONES 4&5. SEE
 1609.1.1/ ASCE 7-02.
  
  
 49) SHEET A-650 SHOWS VARIOUS SUN SHADES, DETAIL 1& 5
 INDICATE THE USE OF CLOTH SUN SHADES, NOTE HOW YOU WILL
 MEET THE WIND REQUIREMENTS OF 3105.4.2.1 OR 3105.4.2.2.
 SHOP DRAWINGS MAY BE SUBMITTED AFTER PERMIT.
  
 50) PLEASE COMPLY WITH FIRE TREATED FABRIC FOR AWNINGS.
 3105.3.1FABRIC USED FOR AWNINGS OR FABRIC-COVERED
 FRAMES SHALL BE FLAME RESISTANT IN ACCORDANCE WITH NFPA
 701.
  
 51) SHEET A652 DETAIL# 06 PROVIDEPRODUCT TESTING
 REPORT FOR EXHAUST FAN AND PRE-MANUFACTURED CURB,
 PROVIDE THE +/- PRESSURES THIS ASSEMBLY HAS BEEN TESTED
 FOR.
 1609.6. 1.2 COMPONENTS & CLADDING.
  
 52) SHEET A-652 DETAILS 24 & 26 BOTH SHOW RAIN WATER
 LITER DETAILS, THESE ARE GOING TO BE PLACED IN 1 HR
 FIRE RATED CORRIDORS, BUT THERE IS ONLY 1 LAYER OF
 DRYWALL AROUND THE PIPE, PLEASE PROVIDE UL RATING OR
 SOME OTHER APPROVED AGENCY THAT THIS IS A 1 HR FIRE
 RATED SYSTEM. TABLE 1016.1.
  
 53)SHEETS A801-A801E ALL INDICATE A DOOR D-11 BUT NOT
 FOUND ON THE DOOR SCHEDULE
 A-903. PLEASE PROVIDE ADDITIONAL INFORMATION, 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 54) SHEET A801 TH1A UNITS (2STORY CONDOS) THE GROUND
 FLOOR OF THESE UNITS STILL HAVE TO COMPLY WITH FAIR
 HOUSING, DOOR D-1 IS A 2?-6? DOOR AND BY DEFINITION A
 USEABLE DOOR A NOMINAL 32? CLEAR.
  
 55) SHEET A801 TH1A UNITS THERE ARE DOORS ON THE FIRST
 FLOOR AND ALSO THE 2ND FLOOR LOFT PORTION OF THE UNIT
 THAT BOTH HAVE EXTERIOR DOORS LEADING TO BALCONIES AND
 DO NOT HAVE A DOOR IDENTIFICATION MARKER. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 56) SHEET A801B-E TH1B-E UNITS(2STORY CONDOS) THE
 GROUND FLOOR OF THESE UNITS STILL HAVE TO COMPLY WITH
 FAIR HOUSING, DOOR D-1 IS A 2?-6? DOOR AND BY
 DEFINITION A USEABLE DOOR A NOMINAL 32? CLEAR.
  
 57) SHEET A801B-E TH1B-E UNITS THERE ARE DOORS ON THE
 FIRST FLOOR AND ALSO THE 2ND FLOOR LOFT PORTION OF THE
 UNIT THAT BOTH HAVE EXTERIOR DOORS LEADING TO BALCONIES
 AND DO NOT HAVE A DOOR IDENTIFICATION MARKER. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 58) SHEET A802- A802C (2STORY CONDOS) THE GROUND FLOOR
 OF THESE UNITS STILL HAVE TO COMPLY WITH FAIR HOUSING,
 DOOR D-1 IS A 2?-6? DOOR AND BY DEFINITION A USEABLE
 DOOR A NOMINAL 32? CLEAR.
  
 59) SHEET A802-A802C THE DOORS ON THE FIRST FLOOR AND
 ALSO THE 2ND FLOOR LOFT PORTION OF THE UNIT THAT BOTH
 HAVE EXTERIOR DOORS LEADING TO BALCONIES AND DO NOT
 HAVE A DOOR IDENTIFICATION MARKER. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 60) SHEET A-803 FRONT ENTRY DOOR, AGAIN THIS DOOR IS
 NOT LISTED ON THE DOOR SCHEDULE, THIS FRONT ENTRY DOOR
 IS IN A FIRE RATED WALL BEING BETWEEN A S2 OCCUPANCY
 AND R2 OCCUPANCY, THIS DOOR WILL NEED A CLOSER AND
 LATCH AS WELL AS FIRE RATING, PLEASE SEE ANSI A117.1-
 98 DOOR CLEAR WIDTH 404.2.3 AND MINIMUM CLEARANCES SEE
 FIGURE 404.2.4.1(B)REQUIRES 12 INCHES WHERE BOTH A
 DOOR CLOSER AND LATCH ARE PROVIDED. ALSO FBC TABLE
 715.3, COMMON TO ALL UNITS.
  
 61) SHEET A-803A- A-803B BOTH ARE MISSING INFORMATION
 ON THE FRONT DOOR AS WELL AS THE SECONDARY DOOR LEADING
 TO THE BALCONY, PLEASE SEE COMMENT ABOVE NUMBER 60 ALSO
 RELATES, 106.1.2 ADDITIONAL INFORMATION REQUIRED. ALSO
 SEE TABLE 715.3.
  
 62)SHEET A-804A- A-804HTHE FRONT DOOR AND BALCONY
 DOORS DO NOT HAVE IDENTIFICATION TAGS INDICATING THEIR
 SIZE AND OR FIRE RATING. FAIR HOUSING ACCESSIBLE DOORS
 AND FBC TABLE 715.3.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 63) SHEET A-804D AT BEDROOM NUMBER 2 ON THE BALCONY
 THERE APPEARS TO BE A LINE INDICATING A CHANGE IN
 GRADE, 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 64) SHEET A-801 SERIES IS MISSING THE DIMENSION BETWEEN
 DOORS IN THE VESTIBULE, FAIR HOSING
 ANSI 4.13 MINIMUM SPACE BETWEEN DOORS IN SERIES 4?-0?
 PLUS DOOR WIDTH IF SWINGS IN.
 PROVIDE DIMENSION.
  
 65) SHEET A-805, A-806, A-807 & A-807A ALL NEED TO
 PROVIDE THE CLEAR OPENING WIDTH FOR THE 6?-0? SLIDING
 GLASS DOORS FOR SECONDARY DOORS MINIMUM OF 32? CLEAR,
 SEE FAIR HOUSING
 404.2.3 (B).
  
 66) SHEET A-903 DOOR NOTES, HURRICANE MISSILE IMPACT
 NOTES, FRENCH DOORS TO COMPLY WITH
 COMMENT 47 & 48A.
  
 67) SHEET A-903 BURGLAR INTRUSION NOTES (3), INDICATES
 THE USE OF PINS FOR EXTRA SECURITY DEVICES, SEE FAIR
 HOUSING SECONDARY EXTERIOR DOORS SLIDING GLASS DOORS
 PAGE 3.10-3.12 CLEAR WIDTH AND HARDWARE REQUIREMENTS
 AND RECOMMENDATIONS.
  
 68)SHEET A-903 BURGLAR INTRUSION NOTE NUMBER (7),
 INACTIVE LEAF OF A PAIR OF DOORS SHALL BE PROVIDED WITH
 MULTIPLE POINT LOCKS AS REQUIRED BY THE PRODUCT
 APPROVALS. AGAIN THESE LOCKS HAVE TO BE ABLE TO OPERATE
 FROM A WHEELCHAIR.ANSI A117.1-98, 404.2.7.
  
 69) SHEET S4.5 DETAIL SECTION 5-4.5 INDICATES USE OF
 5/8? EXTERIOR GRADE PLYWOOD PLEASE SEE
 TABLE 601 FOOTNOTE ( C ) (2) WHEN FIRE TREATED PLYWOOD
 CAN AND CAN NOT BE USED. THIS BUILDING IS CLASSIFIED AS
 A TYPE IB BUILDING.
  
 70) ?S? SHEETS THE SEAL IS NOT EMBOSSED TO WHERE IT IS
 LEGIBLE AND OR SOME SHEETS ARE NOT SEALED AT ALL. THE
 EMBOSSED SEAL SHALL BE LEGIBLE 61G15-23.002.
  
 71) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-15 Cont ID  
Sent By dpalmer Date 2007-09-15 Time 21:30 Rev Time 0.00
Received By dpalmer Date 2007-09-15 Time 18:19 Sent To  
Notes
2007-09-15 21:32:432007-09-15 21:32:43
  
 ** DENIED **
  
 LAKES AT PALM BEACH/ AKA MIZNER LAKES ON SOME SHEETS.
 BUILDING #5.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-20
 ** SOME OF THE ABOVE ARE REFERENCED ON PLANS HOWEVER
 MOST REFERENCE PREVIOUS CODES WHICH ARE NO LONGER IN
 EFFECT.
 PLEASE SEE THAT ALL SHEETS CONTAIN THE RELEVANT CODES
 FOR DESIGN E, FA, FP ETC.
 FBC 106.1.2, 106.1.3, 110.1.2
  
 2) NOTE: PLEASE SEE THE DATE ON THE PLANS IN WHICH THE
 ENGINEERED SIGNED PLANS IS DATED BEFORE THEY WERE
 ISSUED. HOW IS THIS POSSIBLE?
 PLEASE SEE FLORIDA STATUTES 471.025 AS THIS REQUIRES
 THE DESIGN PROFESSIONAL TO SIGN AND DATE EACH SHEET
 WHEN SIGNING, DATING AND SEALING SAID PLANS.
  
 3) NOTE: PLEASE SEE ELECTRICAL PLANS ARE NOT COMPLETE
 WITH ALL CIRCUITING, LIGHTING CONTROLS, COORDINATION
 WITH MANY OF THE SHEETS. PLEASE SEE MOST OF THE NOTES
 BELOW ADDRESS THESE HOWEVER NOT ALL.
 PLEASE SEE FOR EXAMPLE THAT SOME SHEETS ARE NOT
 COMPLETE AND SOME AREAS CAN NOT BE REVIEWED AT THIS
 TIME.
 SEE E2.1.2 COMPARED TO E3.1.2, WEST SIDE OF BUILDING IS
 NOT THE SAME, DOES NOT SHOW THE SAME LAYOUTS FOR POWER
 AND LIGHTING ETC.
 FBC 106.3.5.1.2
 NEC 2005
  
 4) NOTE: PLEASE BE SURE THE LIGHTING SHOWN ON THE
 LANDSCAPE SHEETS CORRELATE WITH THE LIGHTING ON THE
 ELECTRICAL PLANS.
 FBC 106.1.2 FOR COORDINATION.
  
 5) NOTE: PLEASE SEE THE ADDRESS ON THE PERMIT
 APPLICATION INDICATES 715 HANK AARON DR, HOWEVER THE
 ASSIGNED ADDRESS FOR THIS BUILDING #5 IS 1580 SAMANTHA
 LN.
 **PLEASE KNOW THERE ARE STILL SEVERAL SHEETS IN PLANS
 SETS WHICH REFLECT THE PREVIOUS PROJECT NAME OF MIZNER
 LAKES AND SHEETS WHICH NOW REFLECT LAKES AT PALM
 BEACH.
 ** PLEASE BE SURE TO COORDINATE SHEETS. (NOT A KAMM
 CONSULTING COMMENT)
  
 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED ARE IN NEED OF CORRECTIONS.
 PLEASE SEE THE ADDRESS AND BUILDING INFORMATION NEEDS
 TO MATCH WITH PLANS AND PROJECT. COVER SHEET CALLS FOR
 AN ADDRESS LOCATED IN MIAMI OR SOME OTHER LOCATION.
 PLEASE SEE THE INFORMATION ON LIGHTING NEEDS TO
 CORRELATE WITH PLANS. PLEASE SEE THE SUMMARY SHEETS AND
 THE INPUT DATA REPORT DOES NOT CONTAIN ANY *EXTERIOR
 LIGHTING* ENTERED. HOW IS THIS POSSIBLE WHEN THE PLANS
 CONTAIN DOZENS OF EXTERIOR LIGHT FIXTURES?
 PLEASE SEE LANDSCAPE PLANS AND ELECTRICAL PLANS WHICH
 INDICATE LANDSCAPE LIGHTING FIXTURES.
 PLEASE ALSO SEE THE INFORMATION ON THE INPUT DATA
 REPORT FOR THE INTERIOR LIGHTING WHICH ALSO DOES NOT
 MATCH WITH PLANS. PLEASE SEE THERE ARE ONLY 1 OF EACH
 TYPE OF FIXTURE ENTERED WHICH IS NOT POSSIBLE. PLEASE
 COORDINATE ALL INFORMATION ON CALCULATIONS WITH PLANS.
 PLEASE SEE 13-415.1.A, 13-415.2, 13-415.2.ABC.1.3 ETC
  
 7) NOTE: PLEASE SEE THERE ARE A FEW AREAS ON PLANS
 WHICH SOME DEVICES FOR CONTROLS ON LIGHTING AS REQUIRED
 PER 13-415.1.ABC.1.1, .1.2 NEEDS ADDRESSING. PLEASE SEE
 METHODS OF CONTROLS FOR EXTERIOR LIGHTING. PLEASE SEE
 SOME ROOMS FOR EXAMPLE, CUSTODIAN CLOSET, WOMEN RR AND
 MEN RR, RESIDENT STORAGE AREAS, ON E2.3.2 NEAR THE POOL
 DECK ACCESS DOORS.
 PLEASE KNOW AREA FOR RESTROOMS NEEDS TO PROVIDE DEVICES
 WHICH PROVIDE COVERAGE IN ALL AREAS FOR LIFE SAFETY AND
 EGRESS SAFETY.
 PLEASE ALSO SEE RETAIL TEMPORARY SPACES LOCATED ON
 E2.1.1 AND 2.1.2.
  
 8) NOTE: PLEASE SEE SHEET E2.1.2 WHICH MENTIONS TO SEE
 THE ELECTRICAL ROOM DETAIL ON E5.1.3 HOWEVER E5.1.3 IS
 THE TELEPHONE RISER SHEETS.
 PLEASE SEE NOTES ETC ON ARCHITECTURAL PLANS WHICH WERE
 NOTED UNDER BUILDING
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE PROVIDE THE INFORMATION ON PLANS FOR
 THE *EQUAL-POTENTIAL POOL GROUNDING GRID* AS REQUIRED
 PER 680.26.
 PLEASE KNOW EVEN THOUGH THE POOL IT SELF WILL BE UNDER
 SEPARATE PERMIT THE MAIN STRUCTURAL CONTENTS OF THE
 POOL WILL BE PART OF THE BUILDING AND WILL REQUIRE THIS
 GROUNDING.
  
 10) NOTE: PLEASE KNOW THAT THE PLANS WILL BE REQUIRED
 TO STATE *NO DUSK TO DAWN SWIMMING*. PLEASE KNOW IF ANY
 AFTER DISK SWIMMING WILL TAKE PLACE THE REQUIRED
 MINIMUM SIGNED, DATED AND SEALED PHOTO-METRICS WILL BE
 REQUIRED TO BE SUBMITTED TO PALM BEACH COUNTY HEALTH
 DEPARTMENT FOR REVIEW AND STAMPING. THESE WOULD BE
 REQUIRED TO BE SUBMITTED WITH BOTH THE BASE BUILDING
 PLANS AND ALONG WITH THE POOL PERMIT.
 AS MUCH OF THE ELECTRICAL CONDUITS, LIGHTING CONDUITS
 AND GROUNDING OF SYSTEMS IS PART OF THE BASE BUILDING;
 THESE PLANS WILL BE REQUIRED TO CONTAIN MUCH OF THIS
 INFORMATION.
 FBC 106.1.2, NEC 680
  
 11) NOTE: PLEASE SEE SHEET A-SHEETS AND BE SURE THIS
 AND ANY OTHER ELECTRICAL REFLECTED ON OTHER SHEETS
 COORDINATE WITH THE ELECTRICAL PLANS AS SEVERAL CHANGES
 WILL BE MADE AND THE REFLECTED LIGHTING/CEILING PLANS
 ETC WILL NEED TO BE ADJUSTED.
 FBC 106.3.5.1.2
  
 12) NOTE: PLEASE SEE THAT THE INFORMATION FOR THIS PUMP
 HOUSE ELECTRICAL FOR LIGHTING, SERVICE RECEPTACLES ETC
 NEEDS TO BE ADJUSTED.
 PLEASE SEE THE ELECTRICAL RISER AND MSB INDICATES A
 CIRCUIT TO *PUMP HOUSE* AND NO INFORMATION COULD BE
 FOUND FOR THIS. PLEASE ALSO SEE THE CONDUCTORS ARE
 SIZED AT 4-#4MCM?
 PLEASE SEE CIRCUITING ON PUMP HOUSE PLANS INDICATE A
 3-POLE CIRCUIT COMING FROM A L1SA WHICH LENDS TO A
 SEPARATE SERVICE. PLEASE KNOW THAT ELECTRICAL EQUIPMENT
 IN THE FIRE PUMP LOCATION WHICH IS FROM ONE SERVICE MAY
 NOT CONTAIN ANY CIRCUITING FROM ANOTHER SERVICE..
 PLEASE KNOW AS THIS IS A SEPARATE BUILDING PLEASE SEE
 225.31-225.39, 250.32.
 230.70, 230.71,408.4, 310.16, 240.4 ETC
 THE COORDINATION WITH BUILDING #4 AND COORDINATION OF
 FIRE PUMPS ELECTRICALAND FIRE MARSHAL OFFICE COMMENTS
 WILL ALL AFFECT THE ELECTRICAL PLANS AS SUBMITTED. 13)
 NOTE: PLEASE PROVIDE ALL INFORMATION ON THE FIRE PUMPS
 AND MINIMUM FUEL BEING PROVIDED PER NFPA-20 11.4.3.
 PLACING A NOTE ON THE FP SHEETS WHICH STATES THE FIRE
 SPRINKLER CONTRACTOR SHALL PROVIDE A *BIG ENOUGH TANK*
 IS NOT ACCEPTABLE IN LIEU OF PROVIDING THE MINIMUM
 DESIGN FOR CODE COMPLIANCE. PLEASE SEE FIRE MARSHAL
 REVIEW COMMENTS FOR THIS.
 ** PLEASE SEE ALL OF CHAPTER 11 IN NFPA-20 2003
  
 14) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS
 FOR FIRE PUMP, FIRE PUMP CONTROLLER AND FUEL
 TANKS.110.3, 90.7, NFPA-20 CHAPTER 10, 11 ETC. PLEASE
 KNOW MUCH OF THIS WILL ALSO BE REVIEWED BY THE
 MECHANICAL, BUILDING AND FIRE MARSHAL.
 **PLEASE BE SURE TO SEE ANY COMMENTS FROM FIRE MARSHAL
 WITH RESPECT TO BOTH BUILDINGS BEING FED FROM ONE FIRE
 PUMP AND LOCATION.
  
 15) NOTE: PLEASE SEE PLANS ARE MISSING COMPLETED
 PHOTO-METRICS FOR ALL EGRESS PATHS UNDER NORMAL AND
 EMERGENCY. PLEASE KNOW AS THE GARAGE INDICATES SOME OF
 THE LEVELS UNDER EMERGENCY. PLEASE SEE THE GARAGE LEVEL
 UNDER NORMAL INDICATES ALL OF THE FIXTURES WITHOUT
 BATTERY BACK UP. PLEASE SEE ONLY ONE FIXTURE ON THE
 GARAGE PLANS FIRST FLOOR INDICATES A BATTERY BACK UP.
 PLEASE CORRELATE WITH EMERGENCY LIGHTING PLANS. PLEASE
 SEE STAIRS WHICH INDICATE SOME LEVELS, HOWEVER AS THESE
 NUMERIC DESIGNATIONS ARE VERY SMALL THEY ARE NOT EASILY
 READ. PLEASE KNOW THE LEVELS ARE REQUIRED TO BE SHOWN
 THAT ALL STAIR SURFACE AREAS ARE TO HAVE 10FT CANDLES
 MINIMUM UNDER NORMAL AND IS PERMITTED DOWN TO 1FT
 CANDLE UNDER EMERGENCY.
 FAC 61G15-33.004
 NFPA-101 7.8.1.3, 7.9.2.2
  
 16) NOTE: PLEASE CLARIFY HOW PHOTO-METRIC LEVELS WERE
 SUBMITTED FOR POOL DECK AREA UNDER EMERGENCY WHEN THE
 FIXTURES ON PLANS DO NOT INDICATE BATTERY BACK UP?
 COULD NOT LOCATE THESE?
 PLEASE SEE SOME PHOTO-METRICS ARE SHOWN HOWEVER NORMAL
 LEVELS FOR STAIR AREAS DO NOT MEET THE MINIMUM UNDER
 THE LIFE SAFETY CODE AS SECTIONS NOTED ABOVE. PLEASE
 SEE E2.3.1 FOR WHAT ARE SHOWN AS NORMAL AND SEE E3.3.1
 WHICH IS BLANK AND NO LEVELS ARE SHOWN.
 LS 101 7.8 AND 7.9
  
 17) NOTE: PLEASE SEE THERE ARE FIXTURE DESIGNATIONS ON
 PLANS WHICH DO NOT CORRELATE WITH THE LIGHTING FIXTURE
 LEGEND.
 PLEASE ALSO SEE THERE ARE EXIT LIGHTING FIXTURES
 MISSING IN STAIR TOWERS. PLEASE SEE SHEET E2.1.1 AND
 E2.1.2 AS NO EXIT LIGHTS ARE SHOWN.
 THESE ARE REQUIRED UNDER NORMAL AND EMERGENCY. PLEASE
 SEE SOME OF THESE ARE SHOWN ON THE EMERGENCY LIGHTING
 PLANS HOWEVER THEY ARE NOT CIRCUITED OR CONTAIN FIXTURE
 DESIGNATIONS. PLEASE SEE SHEET E3.1.1FOR EXAMPLE.
 PLEASE KNOW AS NOTED ABOVE IN NOTE #3 PLEASE COMPLETE
 AND COORDINATE ALL PLANS AND SHEETS.
 FBC 106.3.5.1.2, 106.1.2
  
 18) NOTE: PLEASE SEE THE FOLLOWING ROOMS WILL BE
 REQUIRED TO CONTAIN BATTERY BACK UP LIGHT FIXTURES OF
 SOME KIND. MAIN ELECTRICAL ROOM, RETAIL ELECTRICAL
 ROOM, TELEPHONE EQUIPMENT ROOM AND RETAIL SPACE WHICH
 CONTAIN FIXTURES. THE RETAIL SPACES TO HAVE A BATTERY
 BACK UP LIGHT FIXTURE OF SOME TYPE HAS BEEN CONFIRMED
 WITH THE FIRE MARSHAL'S OFFICE.
 PLEASE SEE 700.16, 700.12F, LS 101 7.8 AND 7.9 PLEASE
 BE SURE TO SEE OTHER COMMENTS FROM THIS REVIEW OR FIRE
 MARSHAL FOR ANY OTHER LOCATIONS.
  
 19) NOTE: PLEASE SEE PHOTO-METRICS FOR E2.2.2WHICH
 DOES NOT INDICATE TABLES FOR AVERAGE LEVELS.
 FBC 106.3.5.1.2, 106.1.2
 SAME CODE SECTIONS AS NOTED ABOVE FOR LS. PLEASE ALSO
 SEE SOME OTHER SHEETS AND AREAS WHICH NEED TO GIVE THE
 AVERAGE ON TABLES.
  
 20) NOTE: PLEASE SEE ELEVATOR ROOMSAND PITS SHALL
 CONTAIN DEDICATED CIRCUITS FOR RECEPTACLES AND LIGHTING
 PER 620.23 AND 620.24.
 PLEASE SEE AS THE PLANS ARE MISSING FOR FIRST FLOOR
 WEST SIDE, REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE.
 PLEASE SEE HOWEVER THE CIRCUIT WHICH IS NOTED FOR
 ROOF-TOP ROOM ACTUALLY FEEDS OUTSIDE LIGHTING AND OTHER
 AREAS BESIDE THIS ROOM WHICH IS NOT PERMITTED. PLEASE
 ADJUST ALL CIRCUITING ON PLANS.
  
 21) NOTE: PLEASE SEE NOTE #5 ON SHEET E2.1.1 WHICH
 CONTAINS A NOTE FOR RATING THE J-BOX AT 500LBS? PLEASE
 CLARIFY THIS? WHAT TYPE OF FIXTURE/EQUIPMENT WILL BE
 PLACED ON THIS?
 FBC 106.1.2
  
 22) NOTE: PLEASE PROVIDE INFORMATION FOR FAIL SAFE
 OPERATION OF DEVICES FOR ACCESS GATES, DOORS, AND
 PERSONNEL GATES.
 PLEASE SEE LS 101 7.2.1.5, 7.2.1.5.4, 7.2.1.6.2 ETC **
 PLEASE SEE FIRE MARSHAL REVIEW COMMENTS.
  
 23) NOTE: PLEASE CLARIFY MINIMUM LIGHTING LEVELS IN
 ELEVATOR PITS PER 620.24.
 PLEASE SEE COMMENTARY PROVIDED IN THE NEC FOR STANDARDS
 FROM THE ELEVATOR SAFETY CODE.
 PLEASE BE SURE TO CONTACT OR SEE ANY STATE ELEVATOR
 CODES WHICH ACTUALLY MAY BE MORE RESTRICTIVE FOR
 LIGHTING LEVELS.
 "ASME/ANSIA17.1-2004, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.*
  
 24) NOTE: PLEASE PROVIDE INFORMATION FOR EMERGENCY SHUT
 OFF OF SPA PER 680.41.
 THE DEVICE AS SHOWN DOES NOT PROVIDE LOCATION AND EM
 SHUT OFF INFORMATION.
  
 25) NOTE: PLEASE KNOW AS THE TIMERS AS SHOWN IN MOST
 ELECTRICAL ROOMS DO NOT MEET 110.26D, PLEASE PROVIDE A
 DIFFERENT WAY FOR CONTROLLING LIGHTING.(MULTIPLE METHOD
 TO ALLEVIATE A SAFETY OR HAZARDOUS CONDITION. PLEASE
 SEE13-415.1.ABC.1.1 EXCEPT *C*.
  
 26) NOTE: PLEASE CLARIFY WHERE THE LIGHTING IS LOCATED
 IN THE ELEVATOR EQUIPMENT ROOM ABOVE THE ELEVATOR
 MOTORS. PLEASE KNOW AS PER INFORMATION FROM THE STATE
 ELEVATOR CODE, THIS AREA WILL REQUIRE ADDITIONAL
 LIGHTING. THIS IS NOT IN THE NEC OR LS CODE, HOWEVER IT
 MAY BE OF INTEREST TO PLACE ON PLANS AT THIS TIME.
 PLEASE VERIFY WITH THE STATE.
 FBC 106.3.5.1.2, 106.1.2
 NO CHANGES ARE REQUIRED TO PLANS AND THIS NOTE IS FOR
 INFORMATIONAL PURPOSE.
  
 27) NOTE: PLEASE PROVIDE DISCONNECT DETAILS FOR ROOF
 TOP EQUIPMENT FOR SELECTIVE MECHANICAL AND OTHER
 EQUIPMENT.
 PLEASE SEE MECHANICAL REVIEW COMMENTS FOR POSSIBLE
 LOCATIONS AND INFORMATION NEEDED.
 440.11, 422.30 ETC THIS CAN BE A TYPICAL DETAIL FOR ANY
 EQUIPMENT WHICH IS MULTIPLE OF THE SAME USE ETC. FBC
 106.1.2
  
 28) NOTE: PLEASE BE SURE THE PANEL SCHEDULE FOR UNITS
 ARE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED.
 PLEAS SEE SECTION 408.4 AND THE FOLLOWING TEXT WHICH IS
 EXTRACTED DIRECTLY FROM THE NEC AND COMMENTARY.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 29) NOTE: PLEASE SEE C2L WHICH INDICATES CONDUCTORS AND
 CONDUIT FOR CIRCUIT #24 AS BLANK.
  
 30) NOTE: PLEASE SEE UNIT C-5 WHICH CIRCUIT C5L-13 IS
 ALSO FEEDING THE MASTER BEDROOM HALL LIGHTING AND
 RECEPTACLE WHICH IS NOTE PERMITTED PER 210.52D,
 210.11C3.
  
 31) NOTE: PLEASE SEE UNIT C-3 WHICH IS SHOWN FOR THE
 BATHROOM LIGHTING CIRCUIT IN GUEST BATH ALSO FEEDING
 THE CIRCUIT FOR HALF BATH WHICH IS NOT PERMITTED.
 PLEASE SEE 210.52D, 210.11.C3.
  
 32) NOTE: PLEASE SEE UNIT C-4 WHICH IS MISSING GFI FOR
 KITCHEN COUNTER SPACE PER 210.52C1
  
 33) NOTE: PLEASE SEE DINING AREA IN TH1 WHICH DOES NOT
 SEEM TO BE DEFINED AND PART OF DINING AREA SEEMS TO BE
 ON LIVING ROOM CIRCUIT.
 PLEASE BE SURE TO CIRCUIT PER 210.52B1, 210.11C1,
 220.53
  
 34) NOTE: PLEASE SEE UNIT TH2 WHICH IS MISSING
 RECEPTACLES REQUIRED FOR WALL SPACE PER 210.52. THIS IS
 THE RAIL AREA ON SECOND FLOOR WHICH PER NEC IS
 CONSIDERED WALL SPACE. THIS WAS DONE ON BUILDING #4.
  
 35) NOTE: PLEASE SEE THE DINING AREA IN UNIT TH2 AS
 THIS AREA CONTAINS RECEPTACLES CIRCUITED TO THE LIVING
 ROOM/OTHER AREAS.
 PLEASE SEE 210.52B1, 210.11C1.
  
 36) NOTE:PLEASE SEE NFPA-72FOR DEFINITIONS OF SMOKE
 DETECTION DEVICES.
 PLANS INDICATE ALL DEVICES IN UNITS AS *SMOKE
 DETECTORS* AND NOT * SMOKE ALARMS*.
 PLEASE KNOW IF THESE ARE DEVICES WHICH DETECT AND SOUND
 AN ALARM.
 PLEASE ADJUST PLANS.
 PLEASE ALSO BE SURE ALL SMOKE ALARMS ARE MOUNTED ON
 WALL LEADING TO THE FLOOR ABOVE. A NOTE IS LOCATED FOR
 THIS HOWEVER THE NOTE COULD ALSO BE READ TO MOUNT THIS
 UNIT ON WALL ON THE UPPER LEVEL.
 PLEASE ADJUST NOTE.
 NFPA-7211.5.1.1, 11.8.3
  
 38) NOTE: PLEASE SEE MAIN #4 WHICH IS SHOWN AS 1600AMPS
 YET THE RISER ONLY INDICATES ONE RUN OF 500MCM WHICH IS
 ONLY RATED FOR 380AMPS.
 PLEASE SEE THIS IS THE SAME FOR THE FEEDER/SERVICE
 CONDUCTOR LEGEND AND FS DESIGNATIONS.
 PLEASE SEE 240.4B FOR DEVICES RATED OVER 800AMPS.
 110.14, 310.16
  
 39) NOTE: PLEASE CLARIFY AND COORDINATE THE FS-1 AND
 FS-6 ON RISER.
 THE RISER SHOWS FS-1 BEING STUBBED UP IN MAIN
 ELECTRICAL ROOM, HOWEVER THE MAIN ELECTRICAL ROOM
 LAYOUT ON E5.1.4 INDICATES THIS AS FS-6?
 PLEASE ALSO SEE THE RISER SHOWS FS-6 WHICH SEEM TO BE
 OUTSIDE OR AT ANOTHER LOCATION FOR STUB UP.
 PLEASE SEE ANY FUTURE SERVICES WILL BE REVIEWED PER AHJ
 AND IN EITHER AS SHOWN ON THE RISER, FS-6 DOES NOT
 APPEAR TO STUB UP IN ROOM, ONLY WHAT E5.1.4 SHOWS.
 PLEASE CORRELATE AND COMPLETE SHOWING FS-1 ON FLOOR
 LAYOUT ALSO.
 FBC 106.3.5.1.2
 NEC 230.72, 230.70, 90.4
  
 40) NOTE: PLEASE SUBMIT WORST CASE VOLTAGE DROP
 CALCULATIONS FOR FEEDER(S) AND BRANCH CIRCUIT(S) PER
 13-413.1ABC.1
  
 41) NOTE: PLEASE SEE 422.13 AS LOADS FOR WATER HEATERS
 ARE NOW REQUIRED TO BE FIGURED INTO LOAD CALCULATIONS
 AT 125% FOR CONTINUOUS LOADS.
 THIS CHANGED IN THE 2005 NEC.
  
 42) NOTE: PLEASE BE SURE THE ARCHITECT AND STRUCTURAL
 ENGINEER OBTAINS THE BUS-WAY/DUCT CURBING DETAIL AND
 PLACES ON THEIR RESPECTIVE SHEETS.
 THIS AHJ HAS HAD SEVERAL NOT INSTALLED AND CONSTRUCTED
 CORRECTLY AS THE DETAIL WAS NOT ON THE A AND S SHEETS
 FOR THE BUILDING CONTRACTOR.
 THIS IS NOT AN ITEM TO CONSTRUCT AFTER INSTALLATION OF
 BUS-WAY.
 106.1.2
  
 43) NOTE: PLEASE SEE THE GUTTER ON E5.1.5 DOES NOT
 COORDINATE WITH THE GUTTER ON THE ELECTRICAL RISER.
 PLEASE VERIFY SIZE AS THE CONDUCTORS ON RISER WERE NOT
 SHOWN FOR 1600AMPS AND THE SIZE OF THE GUTTER CAN NOT
 BE CONFIRMED AT THIS TIME.
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND NEC 366
 FOR SIZING.
  
 44) NOTE:PLEASE PROVIDE INFORMATION ON MAINS FOR MSB,
 SBA, MDR AND MC1A. PLEASE VERIFY MANUAL MEANS OF
 DISCONNECT RATED FOR THE LOAD SERVED PER 230.76,
 230.79
 ** PLEASE ALSO SEE THE LOAD SUMMARY FOR MSB SEEMS TO BE
 LABELED MSB-1. THIS SEEMS TO BE THE SAME, BUT ONLY
 LABELED DIFFERENT. (TYPE-O)
  
 45) NOTE: PLEASE SEE RISER IS INDICATING 105 UNITS.
 PLEASE BE SURE TO COORDINATE WITH ALL OTHER SHEETS AND
 OTHER TRADES.
 PLEASE CORRELATE AND ADJUST ALL PLANS AS NEEDED. FBC
 106.3.5.1.2
  
 46) NOTE: PLEASE SEE MC 1,3,4,5,6 AND 7 WHICH ALL
 CONTAIN A NOTE #1 IN A CIRCLE AT THE LOWER LEFT HAND
 SIDE OF SCHEDULE, HOWEVER NO NOTE #1 COULD BE LOCATED
 ON THIS SHEET.
  
 47) NOTE: PLEASE SEE MECHANICAL REVIEW SEEMS TO HAVE A
 SUBSTANTIAL AMOUNT OF COMMENTS WHICH MAY MOST CERTAINLY
 NEED CHANGES ON ELECTRICAL PLANS. PLEASE BE SURE TO SEE
 OTHER NOTES FROM ALL TRADES WHICH MAY AFFECT THE
 ELECTRICAL SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-15 18:20:06 
  
 IN ELEC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-09-19 Cont ID  
Sent By rchokshi Date 2007-09-19 Time 14:34 Rev Time 0.00
Received By rchokshi Date 2007-09-19 Time 14:34 Sent To  
Notes
2007-09-19 14:34:27***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 PLEASE PROVIDE LATEST REVISED DRAWINGSAS YOU
 SUBMITTED FOR SITE / STORM WATER PERMIT #07040152.
 JUST TO LET YOU KNOW A HEAD OF TIME THATWE NEED FOR
 ENG REVIEWSTORM WATER CALS, POLLUTION PREVENTION
 PLANS, CITY STANDARDS SHOWN ON CIVIL DRAWINGS ETC, ETC.
 SO, PLEASE PROVIDE SEPARATE SET OF CIVIL DRAWINGS.WE
 ARE ASKING YOU TO INCLUDE THE FOLLOWING WHEN YOU SUBMIT
 CIVIL DRAWINGS FOR ENGINEERING REVIEW, SO WE CAN
 EXPEDITE OUR ENG REVIEW PROCESS.
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON CIVIL DRAWING THE SITE PLAN SHOWING
 STREETS/ROADS AROUND THE SITE WITH NORTH ARROW.
 3.PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 5. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, PLEASE SHOW IN YOUR STORM WATER CALS
 THAT HOW DID YOU DETERMINE THE FIRST FLOOR
 ELEVATION??.
 6. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT,
 LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE
 THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED
 IN STORM WATER QUALITY CALCULATIONS.
 7.PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES,PLEASE SHOW HOW DID YOU DETERMINE
 THE LENGTH OF THE EXFILTRATION TRENCH?? PLEASE SHOW DRY
 DETENTION/WET DETENTION AREAS IN STORM WATER CALS.
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 9. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
 10. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 11. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-31 Cont ID  
Sent By mawillia Date 2007-10-31 Time 19:26 Rev Time 0.00
Received By mawillia Date 2007-10-30 Time 12:03 Sent To  
Notes
2007-10-31 19:27:25*****DENIED*****
  
 PLEASE BE ADVISED THAT THIS BUILDING AND/OR PHASE SHALL
 STAND UPON ITS OWN MERITS ( I.E. WATER SUPPLY, FIRE
 ALARM SYSTEM, FIRE SPRINKLER SYSTEM).
  
 01.FIRE HYDRANTS TO BE OPERATIONAL BEFORE, DURING,
 AND AFTER CONSTRUCTION.
  
 02.A TEMPORARY STANDPIPE IS REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 03.THE CONSTRUCTION AND PROTECTION OF OF THE
 STRUCTURE'S PARKING GARAGE AS WELL AS THE CONTROL OF
 HAZARDS SHALL COMPLY WITH NFPA 88A.
  
 04.WHAT IS THE VERTICAL CLEARANCE AT THE POINT OF
 VEHICLE ENTRY?
  
 05.BASED UPON NFPA 72 - 2002 EDITION - EXPLAIN
 CRITERIA FOR THE USE OF THE CEILING MOUNTED FIRE ALARM
 HORN/STROBE COMBO DEVICE IN THE PARKING GARAGE AS SHOWN
 ON A-251 AND A-252 SHEETS.
  
 06.WHAT IS THE EXIT AISLE CLEARANCE BETWEEN THE
 EXTERIOR REAR WALL OF THE CONDO UNITS AND THE VEHICLE
 PARKING SPACES?BE ADVISED THAT DURING ITS SWING, ANY
 DOOR IN A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN
 ONE-HALF THE WIDTH OF THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, OR PASSAGEWAY.
  
 07.ON SHEET A-251, IT APPEARS THAT THE SWING OF THE
 DOOR IS AGAINST THE PATH OF EGRESS IN STAIR #2 AND
 STAIR #4.
  
 08.PLEASE EXPLAIN EXIT LIGHTS SHOWN IN THE CONDO
 UNITS AT GRADE LEVEL.THESE LIGHTS ARE SHOWN ON SHEET
 A-251 BUT NOT SHOWN ON SHEET A-350.THE MEANS OF
 EGRESS SHALL NOT BE FROM AN AREA TO A MORE HAZARDOUS
 AREA (PARKING GARAGE).
  
 09.IN THE LIFE SAFETY SHEETS, CLARIFY THE USE OF
 SMOKE DETECTORS OR SMOKE ALARMS IN THE CONDO UNITS.BE
 ADVISED THAT SMOKE DETECTORS ARE TIED INTO THE
 BUILDING'S FIRE ALARM SYSTEM, WHEREAS SMOKE ALARMS
 ALERT THE OCCUPANTS OF THE DWELLING UNIT ONLY.
  
 10.ON SHEETS A-251 AND A-252,SOME PATHS OF EGRESS
 ARE ILLUSTRATED PASSING THRU PARKING SPACES AND OTHER
 CHANGES IN ELEVATION.
  
 11.POST/DISPLAY THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS SAMANTHA
 LANE.AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL
 BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 STROKE.
  
 12.PROVIDE FLAME SPREAD DETAILS ON ALL FABRIC
 CANOPIES PLANNED FOR USE.
  
 13.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE ALUMINUM
 RAILINGS.
  
 14. ELEVATORS SHALL BE PROVIDED WITH FIRE FIGHTER
 SERVICE IN ACCORDANCE WITH ASMEA17.1
  
 15.WARNING SIGNS (DO NOT USE IN THE EVENT OF A FIRE)
 SHALL BE REQUIRED IN THE ELEVATOR LOBBIES.
  
 16.STAIRWELL IDENTIFICATION SIGNS REQUIRED.THE
 SIGNAGE SHALL IDENTIFY FLOOR LEVEL, STAIR NUMBER, AND
 TERMINUS TOP AND BOTTOM.
  
 17.FIRE DOORS AND FIRE WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 18.ON SHEET A-901 (IN REFERENCE TO DOOR REMARK #2),
 HOW IS RE-ENTRY ACCOMPLISHED DURING NORMAL OPERATION.
  
 19.ON SHEET FA2.1.2, NO FIRE ALARM DEVICE IS SHOWN IN
 THE TRANSFORMER ROOM.PROVIDE CRITERIA THAT THIS
 ARRANGEMENT IS ACEPTABLE AS PER NFPA 72 - 2002
 EDITION.
  
 20.PLEASE EXPLAIN THE LACK OF SMOKE DETECTORS/SMOKE
 ALARMS IN THE RETAIL TENANT SPACES.
  
 21.ON SHEET FS0.1 IN GENERAL NOTE # 1 AND # 12,THE
 2003 EDITION OF NFPA 20 SHALL BE REFERENCED (NOT
 1999).
  
 22.ON SHEET FS4.1.1 THRU FS4.1.3, THE WORDING UNDER
 THE LAYOUTS AND THE LAYOUTS ARE GARBLED AND UNCLEAR AS
 TO INTENT.
  
 23.SHOW THE LOCATION OF THE KNOX BOX (USUALLY AT THE
 MAIN ENTRANCE AREA).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-11-29 Cont ID  
Sent By kstevens Date 2007-11-29 Time 15:00 Rev Time 0.00
Received By kstevens Date 2007-11-29 Time 15:00 Sent To  
Notes
2007-11-29 15:01:25DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT P6.1.5 A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT
 THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - INDICATE ALL CUT SECTIONS DOWNSTREAM
 OF THE REGULATOR FOR THE GAS WATER HEATERS. FINAL DROP
 LENGTH NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. - SIZE OF PIPE
 SHOWS 1-1/4" REDUCING TO 1" THEN BACK TO 1-1/4". PLEASE
 CLARIFY.--ALSO SHOW THE MATERIAL TYPE OF THE
 VENTING FROM THE REGULATORS. (MATERIAL SHALL BE NON
 COMBUSTABLE).
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - ALSO SHOW THE TOTAL
 DISTANCE FROM THE REGULATOR TO THE MOST REMOTE OUTLET
 DOWNSTREAM OF THE REGULATOR FOR THE GAS WATER HEATERS.
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - PLEASE SUBMIT AN
 APPROVED TABLE FOR 7"W.C. OR INDICATE 1/2PSI DOWNSTREAM
 OF THE REGULATOR. FBC-2004 FUEL GAS HAS NO 7" W.C.
 TABLES TO VERIFY PIPE SIZES.
  
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. SUBMIT MANUF. SPECIFICATION SHEETS FOR THE GAS
 REGULATORS. INDICATE MODEL NUMBER FOR EACH REGULATOR.
 --A UNION IS REQUIRED NEXT TO THE REGULATOR NOT AT
 THE END OF A RUN. (SEE GAS WATER HEATERS & HVAC SYSTEM
 REGULATORS).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-29 Cont ID  
Sent By kstevens Date 2007-11-29 Time 15:31 Rev Time 0.00
Received By kstevens Date 2007-08-02 Time 15:07 Sent To  
Notes
2007-08-28 15:07:29TO "COMM" BD#34/PLANS ON RACK 4 ROLLS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By rregueir Date 2007-09-11 Time 14:07 Rev Time 0.00
Received By rregueir Date 2007-09-02 Time 11:04 Sent To  
Notes
2007-09-10 18:16:43REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 AMENDMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PERMIT APPLICATION INDICATES AN ADDRESS ON HANK
 AARON DRIVE, BUT PLANS SHOW AN ADDRESS ON SAMANTHA
 LANE. ENERGY CALCULATIONS SHOW AN ADDRESS ON N.E. 3RD
 AVENUE. PLEASE SHOW CORRECT ADDRESS ON ALL 3 LOCATIONS.
 FBC 106.1.3
  
 2. M0.1: OUTSIDE AIR AND EXHAUST AIR CALCULATIONS,
 INCORRECT CODES AND REFERENCE STANDARDS ARE CITED.
 REFERENCE THE CORRECT STANDARDS WHICH ARE IN EFFECT AT
 TIME OF PERMIT APPLICATION SUCH AS FBC,M 2004 TABLE
 403.3 AND ASHRAE 62.1-2004. SEE FBC,M CH.15. ALSO, THE
 VENTILATION SYSTEMS SHALL BE DESIGNED BY EITHER FBC,M
 TABLE 403.3 OR ASHRAE 62.1-2004. SELECT AND DECLARE ONE
 METHOD OR THE OTHER TO BE USED AS ALLOWED BY FBC,M
 403.4.
  
 3. M0.2 PROVISIONS (A): IF THERE ARE CONFLICTS BETWEEN
 ANY OF THE LISTED CODES OR STANDARDS AND THE ONES
 CURRENTLY ADOPTED BY THE STATE OF FLORIDA, THE
 CURRENTLY ADOPTED CODE SHALL PREVAIL.
  
 4. M0.2 PROVISIONS (B): DUCT SMOKE DETECTORS SHALL BE
 INSTALLED IN THE SUPPLY DUCT OF ANY SYSTEM WITH A
 DESIGN CAPACITY EXCEEDING 2000 CFM, NOT JUST THOSE WITH
 COMMON PLENUMS. FBC,M 606.2.1
  
 5. M0.2 PROVISIONS (D): ALL THERMOSTATS WITHIN DWELLING
 UNITS SHALL BE AT A MAXIMUM HEIGHT OF 48" PROVIDED
 THERE IS AN UNOBSTRUCTED FORWARD APPROACH IN ACCORDANCE
 WITH FBC CH.11 PART B SECTION 5, REQUIREMENT 5.
  
 6. EXTERIOR WALL LOUVERS ARE CLASSIFIED AS PANEL WALLS
 PER FAC RULE 9B-72. AS SUCH, THEY ARE SUBJECT TO THE
 FLORIDA PRODUCT APPROVAL SYSTEM. PROVIDE PRODUCT
 APPROVALS FOR ALL WALL LOUVERS TO BE USED ON THIS
 PROJECT. FOR MORE INFORMATION ON THE FLORIDA PRODUCT
 APPROVAL SYSTEM PLEASE VISIT: WWW.FLORIDABUILDING.ORG
  
 7. M2.1.1: PROVIDE C.O. DETECTION SYSTEM SUBMITTAL WITH
 INSTALLATION INSTRUCTIONS TO FACILITATE A THOROUGH
 REVIEW OF THE GARAGE VENTILATION SYSTEM. FBC 106.1.2
  
 8. M2.1.1: SHOW EF-8 TO BE PROTECTED FROM POTENTIAL
 VEHICLE IMPACT IN ACCORDANCE WITH FBC,M 304.5.
  
 9. M2.1.2: EF-8,9,10,11,12 ARE DISCHARGING ONTO A
 WALKWAY (ACCESSIBLE RAMP) WHICH IS PROHIBITED BY FBC,M
 401.5.2. ALSO, SEE FBC,M 401.7 AND 501.2.
  
 10. M2.1.2 AND THROUGHOUT: EQUIPMENT DESIGNATIONS ON
 FLOOR PLANS DO NOT MATCH DESIGNATIONS ON EQUIPMENT
 SCHEDULE (M6.1). EXAMPLES: UNIT IN MAIL ROOM IS MARKED
 HP-14 ON M2.2.1 BUT IS MARKED AHU-14 ON SCHEDULE.
 PLEASE COORDINATE FLOOR PLANS AND SCHEDULES. FBC
 106.1.3
  
 11. M2.1.2 AND M6.1: THERE IS NO INDICATION OF THE
 AMOUNT OF OUTDOOR AIR SUPPLIED TO HP-14, EITHER ON THE
 OUTSIDE AIR CALCULATIONS OR THE WATER SOURCE HEAT PUMP
 SCHEDULE. PROVIDE INFORMATION NEEDED TO DETERMIN THE
 REQUIRED OUTDOOR AIR QUANTITIES. ALSO, SEE COMMENT #2.
  
 12. M2.1.2: HP-14 (AND ALL UNITS WITH INDIVIDUAL O.A.
 INTAKES) OUTDOOR AIR INTAKE REQUIRES A VOLUME DAMPER
 PER FBC 13-409.1.ABC.1.1. ALSO, A MOTORIZED OR GRAVITY
 OPERATED DAMPER IS REQUIRED PER FBC 13-409.1.ABC.3.3.
  
 13. M2.2.1: SHOW EF-13 TO BE PROTECTED FROM POTENTIAL
 VEHICLE IMPACT PER FBC,M 304.5.
  
 14. M2.2.1: IF DRYER EXHAUST RISERS ARE OPEN AT THE
 BOTTOM WITH A GRILL, AS INDICATED ON PG M5.1, THE
 OPENINGS SHALL BE PROTECTED WITH FIRE AND SMOKE DAMPERS
 IN ACCORDANCE WITH FBC,M 607.5.5.1.
  
 15. M2.2.1 AND M2.2.2: DRYER EXHAUST RISER DUCTS WHICH
 ARE OPEN AT THE BOTTOM ARE FUNCTIONING IN ONE OF THE
 TWO FOLLOWING PROHIBITED CONDITIONS:
 A) GARAGE EXHAUST; IN THIS CASE FBC,M 504.1 REQUIRES
 DRYER EXHAUST SYSTEMS TO BE INDEPENDENT OF ALL OTHER
 SYSTEMS.
 B) MAKE-UP AIR FOR DRYER FANS; IN THIS CASE FBC,M
 401.5.1 REQUIRES INTAKE OPENINGS AT LEAST 10' FROM
 ALLEYS, STREETS OR PARKING LOTS. ALSO, MAKE-UP OR
 TRANSFER AIR CAN NOT BE DRAWN FROM DISSIMILAR
 OCCUPANCIES PER FBC,M 403.2.1(1).
  
 16. M2.2.2: HP-13 IS SERVING THE MAINTENANCE OFFICE.
 WHAT IS THE SOURCE OF OUTDOOR AIR FOR THIS SPACE?
 MAKE-UP OR SUPPLY AIR IS ALSO REQUIRED FOR EF-1 IN THE
 TOILET ROOM. PROVIDE OUTDOOR AIR AS REQUIRED BY FBC,M
 403.3 AND TABLE 403.3. THE OFFICE SPACE SHALL BE
 MAINTAINED AT A POSITIVE PRESSURE WITH RESPECT TO THE
 GARAGE AREA PER FBC,M 404.3.
  
 17. M2.2.2: SHOW SIZE OF TOILET EXHAUST DUCT FOR EF-1
 IN MAINTENANCE OFFICE. FBC 106.3.5.1.4
  
 18. M2.3.1 THROUGH M2.6.2: SMOKE DAMPERS (AS WELL AS
 THE FIRE DAMPERS SHOWN ON PLAN) ARE REQUIRED IN ALL RTU
 DUCT PENETRATIONS OF CORRIDOR WALLS PER FBC,M 607.5.4.
  
 19. M2.3.1 AND ALL FLOORS: RISERS PAU-1 AND PAU-2 AS
 SHOWN ON FLOOR PLAN DOES NOT CORRESPOND WITH ANY RISERS
 ON THE RISER DETAILS ON PG M5.1. IS THIS SUPPOSED TO BE
 RISERS RTU-1 AND RTU-2? PLEASE COORDINATE FLOOR PLANS
 AND RISER PLANS.
  
 20: M2.3.1 AND ALL FLOORS: RISER PAU-1, FIRE AND SMOKE
 DAMPER IS REQUIRED AT ALL DUCT PENETRATIONS OF THE
 SHAFT PER FBC,M 607.5.5.1.
  
 21. M2.3.2: SUPPLY DROPS IN CORRIDOR ARE MISSING SIZE
 AND CFM DESIGNATIONS. PLEASE CORRECT AND RESUBMIT. FBC
 106.3.5.1.4
  
 22. M2.3.2 AND ALL FLOORS: RISER PAU-2, FIRE AND SMOKE
 DAMPER IS REQUIRED AT ALL DUCT PENETRATIONS OF THE
 SHAFT PER FBC,M 607.5.5.1.
  
 23. M2.3.2: MEN'S RESTROOM (337). FLOOR PLAN SHOWS 240
 CFM OF SUPPLY WITH 200 CFM OF EXHAUST. ALL AIR SUPPLIED
 TO SUCT SPACES SHALL BE EXHAUSTED, INCLUDING ANY AIR IN
 EXCESS OF THAT REQUIRED BY TABLE 403.3 IN ACCORDANCE
 WITH FBC,M 403.2.1(3).
  
 24. M2.3.2: RESIDENT STORAGE A/C CLOSET (313A), WHAT IS
 THE SOURCE OF R/A FOR HP-7? ROOM 313A COULD NOT BE
 FOUND ON DOOR SCHEDULE TO CHECK FOR GRILL OR LOUVERED
 DOOR. NOTE: 313A IS A PLENUM AND ALL MATERIALS USED
 SHALL BE APPROPRIATE FOR THAT APPLICATION. SEE FBC,M
 602.2.1 AND FBC,M 603.9. DOOR SHALL BE OF
 NON-COMBUSTIBLE MATERIALS OR MEET THE 25/50 RATING AS
 REQUIRED BY THIS CODE. THIS APPLIES TO ALL DOORS USED
 IN PLENUM CLOSETS IN ALL AREAS.
  
 25. M2.4.2: SHOW THE DESIGNATION FOR THE HP SERVING
 FITNESS ROOM 431. ALSO, SHOW SOURCE OF RETURN PER FBC,M
 601.4 AND MEANS OF SERVICE ACCESS PER FBC,M SEC.306.
  
 26. M2.4.2 PG A-106 SHOWS HP-7 IN RESIDENT STORAGE 411
 TO BE IN A CLOSET (411A). THIS DOES NOT MATCH M2.4.2
 FLOOR PLAN, WHICH SHOWS HP-7 IN A CAGE. COORDINATE
 PLANS, SHOWING COMPLIANCE WITH ALL PLENUM, SERVICE
 ACCESS AND R/A REQUIREMENTS AS STATED IN COMMENTS 24
 AND 25. NOTE: ROOM 411 IN ITS ENTIRETY WILL BE
 CONSIDERED A PLENUM UNLESS THE 8X6 O.A. DUCT TIES INTO
 A DUCTED RETURN.
  
 27. M2.5.2: RESIDENT CONFERENCE CENTER 533 DOES NOT
 APPEAR ON HEAT PUMP SCHEDULE OR OUTSIDE AIR SCHEDULE.
 PROVIDE MISSING INFORMATION ON FLOOR PLAN AND
 SCHEDULES. ALSO, SHOW THE SOURCE OF R/A AND MEANS OF
 SERVICE ACCESS.
  
 28. M2.5.2: FOR STORAGE ROOM 511, SEE COMMENT #26 AND
 SHOW COMPLIANCE WITH THE SAME. COORDINATE MECHANICAL
 FLOOR PLAN WITH PG A-106.
  
 29. M2.4.2 AND M2.5.2: NO SOURCE OF CONDENSER WATER FOR
 UNDESIGNATED HEAT PUMPS. SHOW SOURCE OF CONDENSER WATER
 AND LOCATION OF RISERS/PIPING ON FLOOR PLANS AND RISER
 DIAGRAMS. FBC 106.1.1 AND FBC 106.3.5.1.4.
  
 30. M2.6.2: HP-8 IN STORAGE 611 AND 711, COORDINATE
 MECHANICAL FLOOR PLANS WITH A-107. SEE A/C CLOSET. SHOW
 COMPLIANCE WITH REQUIREMENTS AS STATED IN COMMENT #26.
  
 31. M2.7.1: CONDENSER WATER LINE SIZES ON ROOF PLAN DO
 NOT MATCH THOSE ON RISERS AS SHOWN ON M5.2.1. EXAMPLE:
 RISER DIAGRAM SHOWS 3" LINES FEEDINGCWR-1 (2 1/2")
 AND CWR-2 (2"), BUT ROOF PLAN SHOWS A 4" LINE FEEDING
 BOTH RISERS WITH THE 4" LINES CONTINUING TO CWR-2.
 PLEASE COORDINATE DRAWINGS.
  
 32. M2.7.2: CONDENSER WATER LINE SIZES ON ROOF PLAN DO
 NOT MATCH THOSE ON RISER DIAGRAMS AS SHOWN ON M5.2.1
 AND M2.5.2. EXAMPLE: CWR-10 ON ROOF PLAN SHOWS 2 1/2"
 LINES BUT RISER DIAGRAM SHOWS 2" LINES. PLEASE
 COORDINATE DRAWINGS.
  
 33. M 2.7.2: TX-21 RISER TERMINATES IN OR UNDER THE
 ELEVATOR MACHINE ROOM. MECHANICAL EXHAUST SHALL BE
 DISCHARGED TO THE OUTDOORS PER FBC,M 501.2.
  
 34. M2.7.22: AC BOILER, THIS DOES NOT APPEAR ON ANY
 MECHANICAL EQUIPMENT SCHEDULES OR IN PLUMBING PLANS
 OTHER THAN THE GAS ISOMENTRIC DIAGRAM. SHOW THE TOTAL
 BTU/H OF ALL GAS APPLIANCES IN THE BOILER ROOM (SEE
 COMMENT #58 REGARDING SIZE OF BOILER), SIZE AND
 LOCATION OF VENTING, AMOUNT OF COMBUSTION AIR REQUIRED,
 METHOD USED TO CALCULATE COMBUSTION AIR (FBC,FG 304.6)
 AND FREE AREA ASSOCIATED WITH ALL LOUVERS AND GRILLS
 USED FOR COMBUSTION AIR (FBC,FG 304.10).
  
 35. M2.7.1 AND 2.7.2: VERIFY THAT OARTU'S HAVE
 SUFFICIENT CLEARANCE FOR SERVICE AND VENTILATION
 RELATED TO POTENTIAL OBSTRUCTIONS SUCH AS MANSARD ROOF
 STRUCTURES AND MECHANICAL SCREEN WALLS. FBC,M 306.1
  
 36. M4.1 - 4.3: SEVERAL EXHAUST DUCTS ARE MISSING
 SIZES. PLEASE CORRECT.
  
 37. M4.1: UNIT C3A, SHOW CFM AND GRILL SIZE FOR SUPPLY
 DROP IN MASTER BATHROOM.
  
 38. M4.1 - 4.3: SOME SUPPLY FLEX DROPS ARE MISSING
 INFORMATION SUCH AS DUCT SIZE, CFM AND GRILL SIZE.
 PLEASE PROVIDE ALL MISSING INFORMATION ON APARTMENT
 FLOOR PLANS. IF A SUPPLY DROP CFM FALLS OUTSIDE THE CFM
 RANGE OF THE FLEX DUCT SCHEDULE AS SHOWN ON M6.1,
 EITHER REVISE THE SCHEDULE TO SHOW THE SIZE TO BE USED
 OR SHOW ALL DUCT SIZES ON FLOOR PLANS. SHOWING ALL FLEX
 DUCT SIZES ON FLOOR PLANS WOULD BE BENEFICIAL DURING
 THE INSPECTION PROCESS.
  
 39. M4.1 - 4.3: SEVERAL BRANCH AND TRANSFER RECTANGULAR
 DUCTS ARE MISSING SIZES FOR SUPPLY AND RETURN. PLEASE
 PROVIDE ALL MISSING INFORMATION. FBC 106.1.1 AND FBC
 106.3.5.1.4
  
 40. M4.1 - 4.3: SOME R/A TRANSFER DUCTS, ESPECIALLY IN
 THE MASTER SUITES ARE NOT DESIGNED TO MEET THE BALANCED
 RETURN EXCEPTIONS UNDER FBC,M 601.4. IF TRANSFERS AND
 JUMPERS ARE NOT DESIGNED TO MEET THESE EXCEPTIONS, A
 FIELD TEST WILL BE REQUIRED AAT FINAL INSPECTION TO
 VERIFY PRESSURE DIFFERENTIALS ACROSS CLOSED BEDROOM
 DOORS DO NOT EXCEED 0.01" W.C. IN ACCORDANCE WITH THIS
 SECTION.
  
 41. M4.1, 4.2, 5.1: BATH AND DRYER EXHAUST DUCTS WHICH
 ENTER A SHAFT AND UTILIZE A SUBDUCT SYSTEM ARE EXEMPT
 FROM FIRE DAMPERS UNDER THE EXCEPTIONS LISTED IN FBC,M
 607.5.5.1. HOWEVER, THEY ARE NOT EXEMPT FROM SMOKE
 DAMPERS WHICH ARE REQUIRED BY THIS SECTION. NOTE: SMOKE
 DAMPERS SHALL NOT BE INSTALLED IN CLOTHES DRYER EXHAUST
 DUCTS PER FBC,M 504.2. ALSO, AN INLINE BACKDRAFT DAMPER
 IS ALSO PROHIBITED UNDER THIS SECTION. SEE ALSO
 COMMENTS # 14 AND 15.
  
 42. M4.1, 4.2, 5.1: BATH EXHAUST SUBDUCT SYSTEM
 REQUIRES A CONTINUOUS AIRFLOW UPWARD TO THE OUTSIDE IF
 THE FIRE DAMPER EXCEPTION IS TO BE CLAIMED UNDER FBC,M
 607.5.5.1 (1.1). THIS WOULD REQUIRE A FAN ON THE ROOF
 ABOVE THE SUBDUCT SYSTEM WHICH WOUDL RUN CONTINUOUSLY,
 EVEN UNDER EMERGENCY CONDITIONS.
  
 43. M4.1: NO DRYER EXHAUST DUCT IS SHOWN IN UNIT C2.
 SHOW MEANS OF DRYER EXHAUST PER FBC,M 504.6.2. ALSO, SE
 COMMENT #41.
  
 44. M4.1 AND 4.2: MECHANICAL FLOOR PLANS SHOW RETURNS
 DUCTED TO A/C CLOSETS WHICH ARE BEING USED AS PLENUMS
 (WITH SOLID DOORS). FLOOR PLAN ON A-803 SHOWS A/C
 CLOSETS WITH 7'8" CEILINGS, WHICH WOULD NOT ALLOW FOR
 THE DUCTED RETURN TO GET BACK TO THE A/C UNIT, AND
 BIFOLD DOORS. IS THE R/A TO BE DUCTED TO THE CLOSET OR
 THROUGH BIFOLD LOVER DOORS? MECHANICAL AND
 ARCHITECTURAL PLANS ARE IN CONFLICT. PLEASE CLARIFY.
 NOTE: SEE COMMENT #24 REGARDING A/C CLOSET DOORS.
  
 45. M4.3: TH1 PLAN SHOWS A 12X8 SUPPLY RISER DUCT IN
 THE MIDDLE OF A WALL. PLEASE CLARIFY.
  
 46. M4.3: TH1 FLOOR PLAN SHOWS A/C UNIT IN THE SAME
 LOCATION WHERE PG A-801 SHOWS THE CLOTHES DRYER. DRYER
 EXHAUST DUCT IS SHOWN AT THE AHU CLOSET. COORDINATE
 DRAWINGS AND FLOOR PLANS TO SHOW CODE COMPLIANCE.
  
 47. M4.3: TH2, NONE OF THE SUPPLY OR RETURN DUCT IS
 ACTUALLY ROUTED TO THE A/C CLOSET OR THE A/C UNIT.
 PLEASE CORRECT.
  
 48. M4.4: IF LOWER AND UPPER LOBBY AREAS ARE DEEMED TO
 BE AN ATRIUM RATHER THAN A MEZZANINE DURING BUILDING
 PLAN REVIEW, SMOKE CONTROL SHALL BE REQUIRED PER FBC
 SEC. 404.
  
 49. M4.4: UPPER FLOOR PLAN SHOWS SUPPLY RISER DUCT SIZE
 AS 14X10, BUT LOWER FLOOR PLAN SHOWS THE SAME DUCT AS
 14X12. PLEASE COORDINATE. ALSO, MECHANICAL FLOOR PLAN
 SHOWS THE SUPPLY RISER GOING DOWN THROUGH THE CORNER OF
 A CONCRETE BLOCK WALL TO THE FIRST FLOOR. THE FLOOR
 PLAN OR A-301 SHOWS A CHASE IN THE A/C CLOSET (PROBABLY
 FOR A/C DUCT) AND THE DOOR TO THE A/C CLOSET IS SHOWN
 WHERE THE RETURN WALL GRILL IS LOCATED. PLEASE
 COORDINATE PLANS. IS THERE ANY FIRE OR SMOKE BARRIER
 PROTECTION REQUIRED IN THIS AREA?
  
 50. M4.4: WHAT IS THE PURPOSE OF THE ACCESS PANELS IN
 THE 2-HOUR RATED ENCLOSURES? IF THIS IS THE LOCATION OF
 SUPPLY FANS, PLEASE SHOW THE FANS ON THE PLANS. FBC
 106.1.1 AND FBC 106.3.5.1.4
  
 51. M4.4: EF-1 IN TOILET ROOM 124 SHALL BE INTERLOCKED
 TO RUN WITH HP-6 TO ENSURE ALL AIR SUPPLIED TO THAT
 SPACE IS EXHAUSTED IN ACCORDANCE WITH FBC,M 403.2.1(3).
 PROVISIONS SHALL ALSO BE MADE TO ASSURE THAT BOTH THE
 HP AND THE EF ARE RUNNING WHENEVER THE SPACE IS
 OCCUPIED IN ACCORDANCE WITH FBC,M 401.3 (UNLESS BOTH
 ARE SET TO RUN CONTINUOUS).
  
 52. M5.1: PLAN SHOWS ROOF CURBS FOR RTU 1 AND 2 USED
 FOR SUPPLY DUCT. IF SO, CURBS SHALL BE LINED WITH MIN.
 R-8, UL-181 APPROVED DUCT MATERIAL IN ACCORDANCE WITH
 FBC TABLE 13-410.1.ABC.2.2 AND FBC,M 604.13. IF THIS IS
 A LISTED SYSTEM, PROVIDE SUBMITTAL.
  
 53. M5.1: ALL DUCT PENETRATIONS OF SHAFT FOR RTU 1 AND
 2 SHALL BE PROTECTED BY FIRE AND SMOKE DAMPERS PER
 FBC,M 607.5.5.1. SEE COMMENTS 20 AND 22.
  
 54. M5.1: TOILET EXHAUST RISER PENETRATIONS REQUIRE
 SMOKE DAMPERS AND ROOFTOP EXHAUST FANS TO RUN
 CONTINUOUS UNDER ALL CONDITIONS PER FBC,M 607.5.5.1.
 SEE COMMENT #42.
  
 55. M5.1: DRYER EXHAUST RISERS ARE NOT EXEMPT FROM
 SMOKE DAMPER REQUIREMENTS. SEE COMMENT #41.
  
 56. M5.2: COORDINATE PIPE SIZES WITH THOSE SHOWN ON
 ROOF PLAN. ALSO, SHOW ALL PIPE SIZES, INCLUDING
 BRANCHES FOR HP'S 5,6,13,14.
  
 57. M5.3: COORDINATE PIPE SIZES WITH THOSE SHOWN ON
 ROOF PLAN. ALSO, SHOW ALL PIPE SIZES, INCLUDING
 BRANCHES FOR HP'S 10,11,12.
  
 58. M5.3: DIAGRAM ON THIS PAGE SHOWS AC BOILER TO BE
 600,000 BTU/H BUT PLUMBING PLAN SHOWS THE BOILER AT
 200,000 BTU/H. PLEASE CLARIFY. PROVIDE SUBMITTAL FOR
 THE BOILER AND ALL EQUIPMENT SHOWN ON THIS PAGE. FBC
 106.1.2.
  
 59. M6.1: EF-3, 4 POOL TOILET AND POOL EQUIPMENT ROOMS
 COULD NOT BE LOCATED ON MECHANICAL PLANS. PROVIDE
 MISSING INFORMATION. FBC 106.1.1
  
 60. M6.1: SHOW LOCATION OF EF-7 AND FIRE PUMP ROOM ON
 PLANS. ELECTRICAL PLAN INDICATES FIRE PUMPS ARE DIESEL
 OPERATED. PROVIDE INFORMATION ON FUEL STORAGE MEANS,
 LOCATION AND QUANTITIES AS WELL AS LOCATION AND DETAILS
 OF ALL FUEL DELIVERY AND REFUELING LINES. PROVIDE
 SUBMITTALS FOR ALL LISTED EQUIPMENT USED FOR FUEL
 STORAGE AND DELIVERY. STATIONARY COMBUSTION ENGINES
 SHALL COMPLY WITH NFPA 37-02 AND FUEL STORAGE SHALL
 COMPLY WITH NFPA 30-00.
  
 61. M6.1: RTU-1 ON FLOOR PLANS CALLS FOR A TOTAL OF
 6920 CFM. EQUIPMENT SCHEDULE SHOWS 8500 CFM. WHICH IS
 CORRECT? RTU-2, TOO MUCH INFORMATION IS MISSING TO
 DETERMINE TOTAL CFM ON FLOOR PLANS.
  
 62. M6.1: HEAT PUMPS, NOTE INDICATES HONEYWELL "T-87"
 THERMOSTAT. THIS TYPE OF THERMOSTAT IS NOT PROGRAMMABLE
 AS CALLED FOR ON PG M0.2 AUTOMATIC TEMPERATURE CONTROLS
 NOTE (A). THERMOSTATS SHALL COMPLY WITH FBC
 13-407.1.ABC.2.4.1.
  
 63. M6.1: WATER SOURCE HEAT PUMPS SHALL HAVE
 TWO-POSITION AUTOMATIC VALVES INTERLOCKED TO SHUT OFF
 WATER FLOW WHEN THE COMPRESSOR IS OFF IN ACCORDANCE
 WITH FBC 13-411.1.ABC.1.4.
  
 64. M7.1: ROOFTOP CLEARANCE SCHEDULE, THE INCORRECT
 CODE YEAR AND CODE SECTION ARE REFERENCED. THE CORRECT
 YEAR/SECTION ARE AS FOLLOWS: FBC 2004 TABLE 1509.7.
  
 65. M7.1: INSULATED DUCT THRU ROOF DETAIL, THIS DETAIL
 DOES NOT MAKE SENSE AS THE NOTES POINT TO STRUCTURAL
 STEEL COMPONENTS WHERE NONE EXIST. THE DETAIL ALSO
 INDICATES PENETRATION OF AN EXISTING ROOF DECK. THIS IS
 NEW CONSTRUCTION. NOTHING IS EXISTING. ALSO, IF
 FLASHING AND DUCT ARE TO BE WELDED, PLEASE PROVIDE
 ADDDITIONAL INFO, SUCH AS METHOD OF WELDING AND
 REQUIRED THICKNESS OF SHEET METAL FOR EACH.
  
 66. M7.1: CLOSED CIRCUIT COOLER DETAIL, WHERE VIBRATION
 ISOLATION IS EMPLOYED, AN APPROVED MEANS OF
 SUPPLEMENTAL RESTRAINT SHALL BE USED TO ACCOMPLISH
 SUPPORT AND RESTRAINT IN ACCORDANCE WITH FBC,M 301.10.
 ALSO, SHOW COMPLIANCE WITH FBC,M 301.13 FOR WIND
 RESISTANCE.
  
 67. M7.1: HEAT PUMP DETAIL, THERE IS ANOTHER DETAIL FOR
 THIS SAME INSTALLATION ON M7.3, BUT THE DETAILS DO NOT
 MATCH. PLEASE CHOOSE ONE METHOD AND REMOVE THE OTHER
 FROM PLANS TO AVOID CONFLICT. FBC 106.1.1.
  
 68. M7.2: DUCT SUPPORT DETAIL, THERE IS ANOTHER DETAIL
 FOR THIS SAME INSTALLATION ON M7.3, BUT THE DETAILS DO
 NOT MATCH. PLEASE CHOOSE ONE METHOD AND REMOVE THE
 OTHER FROM PLANS TO AVOID CONFLICT. FBC 106.1.1. NOTE:
 COMPLIANCE WITH FBC,M 301.13 AND FBC TABLE 1509.7 IS
 REQUIRED.
  
 69. M7.3: SHOW HOW AIR SEPARATOR AND EXPANSION TANK ARE
 TO BE SECURED TO STRUCTURE IN A MANNER THAT MEETS WIND
 LOAD REQUIREMENTS OF FBC,M 301.13 AND FBC CH.16.
  
 70. M7.2 AND 7.3: FIRE DAMPERS, SMOKE DAMPERS AND
 COMBINATION FIRE/SMOKE DAMPERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S
 INSTALLATION INSTRUCTIONS PER FBC,M 607.2. WHERE
 CONFLICTS BETWEEN DETAIL ON PLANS AND MANUFACTURER'S
 INSTRUCTIONS OCCUR, THE MANUFACTURER'S INSTRUCTIONS
 SHALL GOVERN.
  
 71. M7.3:THERE ARE TWO DETAILS FOR VERTICAL PIPE FLOOR
 PENETRATIONS ON THIS PAGE. WHICH IS TO BE USED? PROVIDE
 MANUFACTURER AND LISTING FOR ALL THROUGH-PENETRATION
 FIRESTOP SYSTEMS TO BE USED AT RATED ASSEMBLIES.
  
 72. M7.3: GARAGE EF MOUNTING DETAIL DOES NOT SHOW HOW
 FANS, SLEEVES OR SOUND ATTENUATION BOXES ARE TO BE
 SECURED TO STRUCTURE. PROVIDE SUFFICIENT DETAIL AND
 EQUIPMENT SUBMITTALS.
  
 73. M7.3: VERTICAL HP DETAIL, SHOW MEANS OF AUXILIARY
 DRAIN PROTECTION PER FBC,M 307.2.3.
  
 74. M7.4: RISER TERMINATION DAMPER, SEE COMMENTS 14 AND
 15. ALSO, IF FIRE DAMPER IS TO BE USED IN THIS MANNER,
 PROVIDE CORRESPONDING RUSKIN INSTALLATION INSTRUCTIONS
 TO DETERMINE VIABILITY OF THIS UNORTHODOX APPLICATION.
 FBC 106.1.2 AND FBC,M 607.2.
  
 75. M7.4: DUCT SMOKE DETECTORS SHALL BE CONNECTED TO
 THE BUILDING FIRE ALARM SYSTEM PER FBC,M 606.4.1.
  
 76. M7.3: ROOF MOUNTED EF DETAIL HAS A NOTE FOR
 STRUCTURAL ENGINEER TO DETERMINE AND VERIFY ATTACHMENT
 DETAILS FOR REQUIRED WIND LOADS. NO SUCH INFORMATION
 COULD BE FOUND IN STRUCTURAL PLANS. FBC 301.13
  
 77. PROVIDE SUBMITTALS FOR ALL LISTED MECHANICAL
 EQUIPMENT, APPLIANCES AND DEVICES TO BE USED IN THIS
 PROJECT. FBC 106.1.2
  
 ENERGY:
  
 78. OUTDOOR AIR QUANTITIES SHOWN ON SIZING SUMMARY DO
 NOT MATCH THOSE GIVEN ON PG M0.1. THESE VALUES SHOULD
 CORRESPOND. EXAMPLE: EXERCISE ROOM ON SCHEDULE CALLS
 FOR 240 CFM O.A. WHILE THE SUMMARY SHOWS 120 CFM O.A.
  
 79. COIL SIZING/ COOLING CAPACITY SHOWN ON SIZING
 SUMMARY DO NOT MATCH THOSE GIVEN ON PG M6.1. EXAMPLE:
 APT C1 ON SCHEDULE SHOWS 2.5 TONS OR 29.92 MBH AND APT
 C1 ON SUMMARY SHOWS 1.9 TONS OR 23.3 MBH. HVAC SYSTEMS
 AND EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE THAN
 THE SPACE AND SYSTEM LOADS CALCULATED IN ACCORDANCE
 WITH FBC 13-407.1.ABC.1.
  
 80. SYSTEM REPORT COMPLIANCE: SYSTEM SIZES AS SHOWN ON
 REPORT DO NOT CORRESPOND WITH SYSTEMS IN THE SYSTEM
 SIZING SUMMARY. GROUPING OF SYSTEMS WILL INCREASE THE
 SIZE OF THE SYSTEM IN THE REPORT WILL DISTORT THE
 ALLOWED EFFICIENCY CRITERIA WHICH WOULD PROVIDE UNDUE
 TRADE-OFF CREDIT FOR EFFICIENCY OF THE COOLING SYSTEMS.
 EXAMPLE: SYSTEM 1 IS LISTED FOR ALL TOWNHOMES AS ONE
 "WATER COOLED >240,000 BTU/H" UNIT. THE TOWNHOMES ARE
 EACH COOLED BY INDIVIDUAL UNITS AND WOULD BE
 CATEGORIZED AS "WATER COOLED 17,000 17,000 TO <135,000
 BTU/H" IN ACCORDANCE WITH FBC TABLE 13-407.1.ABC.3.2B.
 THIS TABLE GIVES A MINIMUM EFFICIENCY CRITERIA OF 12.00
 EER. "SYSTEMS" SHOULD CORRESPOND WITH "ZONES" IN THE
 INPUT DATA REPORT. FOR GUIDANCE AS TO WHAT ACTUALLY
 CONSTITUTES A ZONE, PLEASE SEE FBC 13-407.1.ABC.2.2.1.
  
 81. INPUT DATA REPORT: BUILDING ENVELOPE COMPONENTS AS
 SHOWN ON THE INPUT DATE REPORT DO NOT CORRESPOND WITH
 THE TYPE OF CONSTRUCTION SHOWN ON PLANS. EXAMPLE:
 REPORT SHOWS THE ROOF TO BE INSULATED WITH R-19 BATTS.
 DETAILS ON A-652 INDICATE THE ROOF INSULATED WITH RIGID
 BOARD TO A VALUE OF R-14 IN A BUILT-UP ROOF SYSTEM.
 ALSO, NO INFORMATION COULD BE FOUND REGARDING TYPE OR
 R-VALUE OF INSULATION TO BE USED IN THE MANSARD ROOF
 SECTIONS WHICH ARE ABOVE CONDITIONED SPACES. NO
 INFORMATION COULD BE FOUND IN ARCHITECTURAL PLANS OR
 DETAILS SHOWING 1.36" INSULATION AT EXTERIOR WALLS AS
 INDICATED ON THE REPORT. PLEASE CLARIFY ON PLANS AND
 PROVIDE CORRESPONDING INFORMATION ON CALCULATIONS.
  
 82. WHAT IS THE R-VALUE OF THE 3RD FLOOR FLOOR/CEILING
 ASSEMBLY BETWEEN THE PARKING GARAGE AND THE 3RD FLOOR
 APARTMENTS? THIS INFORMATION IS NOT SHOWN ON PLANS OR
 IN THE REPORT. ALSO, PLEASE EXPLAIN HOW AN 8"
 LIGHTWEIGHT CONCRETE BLOCK WITH 1.36" INSULATION SYSTEM
 IS TO BE USED FOR THE FLOOR IN THE LOBBY AS INDICATED
 IN THE REPORT.
  
 83. STAIR AND ELEVATOR SHAFT VENTS SHALL BE EQUIPPED
 WITH MOTORIZED DAMPERS THAT ARE CAPABLE OF BEING
 AUTOMATICALLY CLOSED DURING NORMAL BUILDING OPERATION
 AND ARE INTERLOCKED TO OPEN AS REQUIRED BY FIRE AND
 SMOKE DETECTION SYSTEMS. FBC 13-409.1.ABC.3.1
  
 84. MECHANICAL SYSTEMS SHALL BE DESIGNED TO ASSURE THAT
 BUILDINGS ARE PRESSURIZED WITH RESPECT TO OUTDOORS.
 PROVIDE AIR BALANCE SCHEDULE(S) SHOWING COMPLIANCE FOR
 ALL ZONES/FLOORS. FBC 13-409.1.ABC.2
  
 85. SHOW SHUTOFF DAMPER CONTROLS FOR O.A. SUPPLY AND
 EXHAUST SYSTEMS AS REQUIRED BY FBC 13-409.1.ABC.3.3.
  
 86. ENERGY CALCULATIONS SHOW A "PLANT" CHILLER AT 390
 TONS. THERE IS NO CHILLER SHOWN AS PART OF THIS SYSTEM.
 ALSO, THE CLOSED CIRCUIT COOLERS AND A/C BOILER WERE
 OMITTED FROM THE CALCULATIONS. PLEASE CORRECT AND
 RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status   Date 2007-11-29 Cont ID  
Sent By kstevens Date 2007-11-29 Time 14:43 Rev Time 0.00
Received By kstevens Date 2007-10-17 Time 17:40 Sent To  
Notes
2007-10-17 18:51:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB MUNICIPAL CODE
  
 1. ALL ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT IS REQUIRED IN THE TITLE
 BLOCK OF EACH SHEET. FAC 61G1-16.004(6) & FS 481.2055.
 PLEASE SHOW PRINTED NAME IN TITLE BLOCK OF EACH SHEET.
  
 2. SHT A-002 BUILDING #4 DATA. THE BUILDING CODE
 EDITION IS SHOWN AS 2001 FBC. THE CODE IN EFFECT IS THE
 FBC-2004. PLEASE CORRECT CODE REFERENCE.
  
 3. SHT A-200 BUILDING #4 DATA. ONE INTENDED USE
 ACCESSORY OCCUPANCY IS INDICATED AS MERCANTILE RETAIL
 AREA. PLEASE INDICATE THE LOCATION OF THE RETAIL AREA.
 SECTION 106.1.1.
  
 4. SHT A-003 DETAIL E. THE CLEAR FLOOR SPACE FOR THE
 LAV IS NOT SHOWN. PLEASE SHOW CLEAR FLOOR SPACE AS
 INDICATED ON PAGE 7.47. ALSO SHTS A-801, A-801A,
 A-801B, A-801C, A-801D, A-801E, A-802, A-802B & A-802C
 SHALL COMPLY WITH THE FHA-08 DESIGN MANUAL FOR THE
 PRIMARY ENTRY LEVEL. PLEASE INDICATED ON THE PLANS AND
 SHOW COMPLIANCE WITH REQUIREMENTS 1 THRU 7. SEE PAGE 7
 OF THE FHA DESIGN MANUAL.
  
 5. SHT A-0003A DETAILS A & B. THE WATER CLOSET CAN NOT
 BE IN THE CLEAR FLOOR SPACE REQUIRED FOR THE LAV,
 (DETAIL A), OR SHOWER, (DETAIL B). PLEASE SHOW
 COMPLIANCE WITH THE CLEAR FLOOR SPACE REQUIREMENTS.
  
 6. SHT A-104 ROOF DRAIN CALCULATIONS. NO MENTION OF THE
 CONTRIBUTION FROM THE ROOF AREA ABOVE DRAINING ONTO THE
 ROOF AREAS. SECTION 1106.3. PLEASE SHOW THE UPPER ROOF
 CONTRIBUTION IN THE CALCULATIONS FOR THE ROOF/DECK
 DRAINS.
  
 7. SHT A-104 ROOF DRAIN CALCULATIONS. AREA "C" SCALES
 OUT TO BE ROUGHLY 15FT SHORTER THAN AREAS "D & E", BUT
 SHOWS MORE TOTAL AREA. PLEASE CLARIFY. SECTION 106.1.1.
 IS THERE MORE VERTICAL SF OR UPPER ROOF AREA?
  
 8. SHT A-104 AREAS "D & E" SCALE OUT TO BE
 APPROXIMATELY THE SAME LENGTH, BUT AREA "E" IS
 INDICATED AS ABOUT TWICE THE AREA. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 9. SHT A-104. AREA "F" SHOWS NO CALCULATIONS FOR THE
 PRIMARY AND SECONDARY ROOF DRAINS. PLEASE SHOW
 CALCULATIONS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE SQUARE FOOTAGE OF THE ROOF AREA,
 WITH 1/2 THE AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AS WELL AS THE AREA FROM THE UPPER ROOF THAT
 DRAINS ONTO THE ROOF FROM ABOVE.
  
 10. SHT A-104 CALCULATIONS ARE REQUIRED FOR THE OUTDOOR
 LIVING PATIO & DECK DRAINS. SHOW THE SQUARE FOOTAGE OF
 THE DECK AREA AND SHOW 1/2 AREA OF ALL VERTICAL WALLS
 AND INDICATE THE SQUARE FOOT AREA OF THE ROOFS THAT
 DRAIN ONTO THE DECK AREA FROM ABOVE. SECTIONS 1106 &
 1107 AND ALL SUBSECTIONS.
  
 11. SHT A-104 SHOW THE LOCATIONS FOR ALL SECONDARY
 DRAINAGE ON THE DECK. INDICATE ALL AREAS THAT DRAIN OFF
 THE SIDE OF THE BUILDING IF ANY. SECTIONS 106.1.2 &
 1107.
  
 12. SHT A-104 THE LOCATIONS OF THE DECK DRAINS IN THE
 OUTDOOR LIVING PATIO & DECK DRAINS ARE APPROXIMATELY
 6FT FROM THE SLIDING GLASS DOOR, BUT THE DISTANCE TO
 THE AREA WHERE THE OVERFLOW LEAVES THEPATIO AREA IS
 APPROXIMATELY 11FT. IS THERE ANY CONCERN THAT THE STORM
 WATER WILL ENTER THE UNIT BEFORE THE STORM WATER
 REACHES THE OVERFLOW AREA? PLEASE CLARIFY. SECTION
 106.1.2. (MORE INFORMATION REQUIRED). SECTION 1503.4.3
  
 13. SHT A-104 THERE ARE ABOUT FIVE PLANTER DRAINS THAT
 RECIEVE THE WATER OF THE VERTICAL WALL FROM THE ROOF
 AREA. WHEN INDICATING THE SQUARE FOOTAGE BEING DRAINED
 BY THESE PLANTER DRAINS, PLEASE SHOW 1/2 THE AREA OF
 THE VERTICAL WALLS INCLUDED IN THE TOTAL SQUARE
 FOOTAGE. SECTION 1106.4.
  
 14. SHT A-108 THE ROOF DRAINS DO NOT APPEAR TO BE
 LOCATED AT THE LOW POINT OF THE ROOF. THE LOW AREA FOR
 AREA"G" APPEARS TO BE IN THE ELEVATOR MACHINE ROOM.
 NO SLOPE INDICATION IS SHOWN FOR AREA "F" PLEASE
 CLARIFY. SECTION 106.1.1. ELEVATIONS SHALL BE SUBMITTED
 FOR ALL AREAS OF THE ROOF TO VERIFY IF THE ROOF DRAINS
 ARE IN THE LOWEST POINT OF THE ROOF.
  
 15. SHTS A-205 & A-206 SHOW THE SECONDARY DRAINS FOR
 ALL AREAS PER SECTION 1107.
  
 16. SHT A-206 SHOW COMPLIANCE FOR THE TOILET ROOMS.
 (337 & 338).
 ____W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ____URINAL
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 ____LAVS
 A.11-4.19.3 CLEAR FLOOR SPACE
 ____TOILET ROOMS
 A. 11-4.22.3 SHOW THE 5' TURNING AREA IN THE TOILET
 ROOM, ITS NOT REQUIRED IN STALL
  
 17. SHT A-907 FINISH SCHEDULE INDICATES PAINT ON GWB
 FOR THE ADCP TOILET ROOM, MEN'S TOILET ROOM & WOMEN'S
 TOILET ROOM. SECTION 1210.2 REQUIRES THE WALL WITHIN
 2FT OF WATER CLOSETS OR URINALS TO HAVE A "SMOOTH,
 HARD, NONABSORBENT" SURFACE. PAINTED GWB DOES NOT MEET
 THE "HARD" REQUIREMENT OF THE CODE SECTION. PLEASE SHOW
 COMPLIANCE.
  
 18. ALL CIVIL SHEETS ARE NOT SIGNED, SEALED OR DATED AS
 REQUIRED PER SECTION 106.1 AND FAC 61G15-23.002(2) & FS
 472.025. PLEASE SIGN, SEAL AND DATE ALL SHEETS.
  
 19. SHTS CS-1 & A-001A. THE PRINTED NAME OF THE PERSON
 SIGNING & SEALING THE DOCUMENT IS REQUIRED ON EACH
 SHEET. FAC 61G1-16.003, 61G1-16.004(6) & FS 481.2055.
  
 20. ALL CIVIL SHEETS SHALL BE SIGNED, SEALED &DATED
 PRIOR TO PLANS BEING ISSUED. THE DATE THE SEAL AND
 SIGNATURE ARE AFFIXED TO THE DOCUMENTS SHALL BE ENTERED
 ON THE PLANS, SPECIFICATIONS, REPORTS, OR OTHER
 DOCUMENTS IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL ENGINEER. FAC 61G15-23.002(1)(2) & FS
 471.025.
  
 21. SHT P0.1 PLUMBING LEGEND. ALL WATER LINES ARE SOLID
 LINES WITH NO DIFFERENCES. PLEASE CLARIFY. SECTION
 106.1.1.--PLUMBING SHEET INDEX DOES NOT INDICATE A
 6TH FLOOR. PLEASE CLARIFY.--SHTS P5.2.1, P5.2.2 &
 P5.3.1 WERE NOT SUBMITTED IN ONE SET OF PLANS.
  
 22. SHT P2.1.1 SHOWS SANITARY RISER #1 IN A SOLID WALL
 AND RISERS #5 & #8 IN COLUMNS. PER SECTION 1906.3
 CONDUITS AND PIPES EMBEDDED IN CONCRETE. CONDUITS,
 PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL TO
 CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, SECTION
 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE WITH
 APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. PLEASE
 SUBMIT APPROVAL FROM DESIGN ENGINEER. SLEEVES MAY BE
 REQUIRED. SECTION 305.
  
 23. SHT P2.1.2 SHOWS SANITARY RISERS #13 & #14 IN A
 SOLID WALL AND RISERS #21 & #25 & #26 IN COLUMNS. PER
 SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SLEEVES
 MAY BE REQUIRED. SECTION 305.
  
 24. SHT P2.1.3 A CLEANOUT IS REQUIRED IN THE BUILDING
 STORM DRAIN TO SDR'S 1 & 2 AND AT THE JUNCTION OF THE
 STORM SEWER AT SDR 3. SECTION 1101.8.
  
 25. SHT P2.1.4 A CLEANOUT IS REQUIRED AT THE JUNCTION
 OF THE STORM SEWER AT SDR 4. SECTION 1101.8.
  
 26. SHT P2.1.5 TWO KEY NOTES #3 SHOWN. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 27. SHT P2.1.5 IDENTIFY ALL STRUCTURES. (CB-1, CB-2
 ETC). SECTION 106.1.2.
  
 28. SHT P2.1.5 CONDENSATE RISER #1&2 AND SANT. RISER #1
 ARE SHOWN IN A SOLID WALL. PER SECTION 1906.3 CONDUITS
 AND PIPES EMBEDDED IN CONCRETE. CONDUITS, PIPES AND
 SLEEVES OF ANY MATERIAL NOT HARMFUL TO CONCRETE AND
 WITHIN THE LIMITATIONS OF ACI 318, SECTION 6.3, ARE
 PERMITTED TO BE EMBEDDED IN CONCRETE WITH APPROVAL OF
 THE REGISTERED DESIGN PROFESSIONAL. PLEASE SUBMIT
 APPROVAL FROM DESIGN ENGINEER. SLEEVES MAY BE REQUIRED.
 SECTION 305.
  
 29. SHT P2.1.5 A CLEANOUT IS REQUIRED NEAR THE JUNCTION
 OF THE BUILDING STORM DRAIN AND THE BUILDING STORM
 SEWER. SECTION 1101.8.
  
 30. SHT P2.1.6 KEY NOTES #1 & #3 NOT FOUND. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 31. SHT P2.2.1 CONDENSATE RISER #1&2 AND SANT. RISER #1
 ARE SHOWN IN A SOLID WALL. PER SECTION 1906.3 CONDUITS
 AND PIPES EMBEDDED IN CONCRETE. CONDUITS, PIPES AND
 SLEEVES OF ANY MATERIAL NOT HARMFUL TO CONCRETE AND
 WITHIN THE LIMITATIONS OF ACI 318, SECTION 6.3, ARE
 PERMITTED TO BE EMBEDDED IN CONCRETE WITH APPROVAL OF
 THE REGISTERED DESIGN PROFESSIONAL. PLEASE SUBMIT
 APPROVAL FROM DESIGN ENGINEER. SLEEVES MAY BE REQUIRED.
 SECTION 305.
  
 32. SHT P2.2.1 SANITARY RISER #8 IS SHOWN IN A COLUMN.
 PER SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN
 CONCRETE. CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL
 NOT HARMFUL TO CONCRETE AND WITHIN THE LIMITATIONS OF
 ACI 318, SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN
 CONCRETE WITH APPROVAL OF THE REGISTERED DESIGN
 PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 33. SHT P2.2.2 THE MATCH LINE DOES NOT REFLECT THE
 PREVIOUS WEST SECTION MATCH LINES. PLEASE CORRLEATE
 MATCH LINES TO AVOID CONFUSION. SECTION 106.1.1.
  
 34. SHT P2.2.2 SANITARY RISERS #8, #21, #22 & #26 ARE
 SHOWN IN COLUMNS. PER SECTION 1906.3 CONDUITS AND PIPES
 EMBEDDED IN CONCRETE. CONDUITS, PIPES AND SLEEVES OF
 ANY MATERIAL NOT HARMFUL TO CONCRETE AND WITHIN THE
 LIMITATIONS OF ACI 318, SECTION 6.3, ARE PERMITTED TO
 BE EMBEDDED IN CONCRETE WITH APPROVAL OF THE REGISTERED
 DESIGN PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 35. SHT P2.2.2 SHOWS SANITARY RISERS #13 & #14 IN A
 SOLID WALL AND RISERS #21 & #25 & #26 IN COLUMNS. PER
 SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SLEEVES
 MAY BE REQUIRED. SECTION 305.
  
 36. SHT P2.2.2 SHOWS A MINI SUTDOR VENT. A RELEIF VENT
 IS REQUIRED PER SECTION 917.3.2. PLEASE SHOW ON THE
 FLOOR PLAN AND THE RISER DIAGRAM.
  
 37. SHT P2.3.1A RELIEF VENT IS REQUIRED FOR THE AIR
 ADMITTENCE VALVE AT THE PAVILLION SINK. SECTION
 917.3.2. PLEASE SHOW ON THE FLOOR PLAN AND THE RISER
 DIAGRAM.
  
 38. SHT P2.3.1 SANITARY RISER #6 SHOWS A BRANCH LINE
 RUNNING THRU A COLUMN. PER SECTION 1906.3 CONDUITS AND
 PIPES EMBEDDED IN CONCRETE. CONDUITS, PIPES AND SLEEVES
 OF ANY MATERIAL NOT HARMFUL TO CONCRETE AND WITHIN THE
 LIMITATIONS OF ACI 318, SECTION 6.3, ARE PERMITTED TO
 BE EMBEDDED IN CONCRETE WITH APPROVAL OF THE REGISTERED
 DESIGN PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 39. SHT P2.3.1 SANT. RISER #1 DESIGNATOR IS NOT
 LEGIBLE. SECTION 106.1.1.
  
 40. SHT P2.3.1 CONDENSATE RISER #1&2 AND SANT. RISER #1
 ARE SHOWN IN A SOLID WALL. PER SECTION 1906.3 CONDUITS
 AND PIPES EMBEDDED IN CONCRETE. CONDUITS, PIPES AND
 SLEEVES OF ANY MATERIAL NOT HARMFUL TO CONCRETE AND
 WITHIN THE LIMITATIONS OF ACI 318, SECTION 6.3, ARE
 PERMITTED TO BE EMBEDDED IN CONCRETE WITH APPROVAL OF
 THE REGISTERED DESIGN PROFESSIONAL. PLEASE SUBMIT
 APPROVAL FROM DESIGN ENGINEER. SLEEVES MAY BE REQUIRED.
 SECTION 305.
  
 41. SHT P2.3.1 SHOW THE LOCATION OF CONDENSATE RISER
 1/2. SECTION 106.1.2.
  
 42. SHT P2.3.1 SANITARY RISER #9 BRANCH LINE RUNNING
 THRU A COLUMN. PER SECTION 1906.3 CONDUITS AND PIPES
 EMBEDDED IN CONCRETE. CONDUITS, PIPES AND SLEEVES OF
 ANY MATERIAL NOT HARMFUL TO CONCRETE AND WITHIN THE
 LIMITATIONS OF ACI 318, SECTION 6.3, ARE PERMITTED TO
 BE EMBEDDED IN CONCRETE WITH APPROVAL OF THE REGISTERED
 DESIGN PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 43. SHT P2.3.1. SANITARY RISER #6 BRANCH LINE RUNNING
 THRU A COLUMN. PER SECTION 1906.3 CONDUITS AND PIPES
 EMBEDDED IN CONCRETE. CONDUITS, PIPES AND SLEEVES OF
 ANY MATERIAL NOT HARMFUL TO CONCRETE AND WITHIN THE
 LIMITATIONS OF ACI 318, SECTION 6.3, ARE PERMITTED TO
 BE EMBEDDED IN CONCRETE WITH APPROVAL OF THE REGISTERED
 DESIGN PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 44. SHT P2.3.2 THE TITLE BLOCK READS DRAINAGE PLAN 2ND
 FLOOR, BUT THE PAGE TITLE INDICATEDS 3RD FLOOR. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 45. SHT P2.3.2 SDR 10 & ODR SDR 10 ARE SHOWN IN A
 COLUMN. PER SECTION 1906.3 CONDUITS AND PIPES EMBEDDED
 IN CONCRETE. CONDUITS, PIPES AND SLEEVES OF ANY
 MATERIAL NOT HARMFUL TO CONCRETE AND WITHIN THE
 LIMITATIONS OF ACI 318, SECTION 6.3, ARE PERMITTED TO
 BE EMBEDDED IN CONCRETE WITH APPROVAL OF THE REGISTERED
 DESIGN PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 46. SHT P2.3.2SANITARY RISERS 16, 19, 20 & 25 SHOW
 BRANCH LINES RUNNING THRU COLUMNS. PER SECTION 1906.3
 CONDUITS AND PIPES EMBEDDED IN CONCRETE. CONDUITS,
 PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL TO
 CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, SECTION
 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE WITH
 APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. PLEASE
 SUBMIT APPROVAL FROM DESIGN ENGINEER. SLEEVES MAY BE
 REQUIRED. SECTION 305.
  
 47. SHT P2.3.2 REQUIRED SECONDARY DRAINS/SCUPPERS ARE
 NOT SHOWN. SECTION 1107. PLEASE SHOW THE LOCATION OF
 REQUIRED SECONDARY DRAINS OR OVERFLOW SCUPPERS AND
 INDICATE THE SQUARE FOOTAGE BEING DRAINED BY EACH
 DRAIN/SCUPPER.
  
 48. SHT P2.3.1E FOUR PLANTERS HAVE VERTICAL
 CONTRIBUTION NOT INDICATED IN THE CALCULATIONS. PLEASE
 SHOW ALL SQUARE FOOTAGE DRAINED BY THE PLANTER DRAINS.
 TABLE 1106.3.
  
 49. SHT P2.3.1E THE DISTANCE FROM THE DECK DRAINS IN
 THE PATIO TO THE SLIDING GLASS DOORS TO EACH UNIT US
 ABOUT 1/2 THE DISTANCE TO THE OVERFLOW LINE OUT OF THE
 PATIO AREA. IS THERE ANY CONCERN THAT THE STORM WATER
 WILL ENTER THE UNIT BEFORE OVERFLOWING OFF THE PATIO IF
 THERE IS A BLOCKAGE IN THE MAIN DECK DRAIN? PLEASE
 CLARIFY. SECTION 106.1.2.
  
 50. SHT P2.3.2E REQUIRED SECONDARY DRAINS/SCUPPERS ARE
 NOT SHOWN. SECTION 1107. PLEASE SHOW THE LOCATION OF
 REQUIRED SECONDARY DRAINS OR OVERFLOW SCUPPERS AND
 INDICATE THE SQUARE FOOTAGE BEING DRAINED BY EACH
 DRAIN/SCUPPER.
  
 51. SHT P2.4.1 SHOW THE RISER NUMBER FOR THE SANITARY
 RISERS AT THE SHOWER, LAV, W/C PORTION OF THE MASTER
 BATH, C-2 UNIT (414), & THE TUB, W/C, LAV BATH C-2 UNIT
 (415). SECTION 106.1.2.
  
 52. SHT P2.4.1 WEST SECTION DRAINAGE PLAN? (SAME AS SHT
 P2.4.2). PLEASE CLARIFY. SECTION 106.1.1.
  
 53. SHT P2.4.2 SHT TITLE STATES 4TH - 6TH FLOORS, BUT
 5TH FLOOR & 6TH - 7TH FLOORS SUBMITTED ALSO. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 54. SHT P2.4.2 SHOW THE PIPING FOR TWO RISERS #8.
 SECTION 106.1.2.
  
 55. SHT P2.4.2 INDICATE THE RISER NUMBER FOR THE MOP
 SINK SANITARY. SECTION 106.1.2
  
 56. SHT P2.4.2 SANITARY RISER #13 IS SHOWN IN A SOLID
 WALL. PER SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN
 CONCRETE. CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL
 NOT HARMFUL TO CONCRETE AND WITHIN THE LIMITATIONS OF
 ACI 318, SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN
 CONCRETE WITH APPROVAL OF THE REGISTERED DESIGN
 PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 57. SHT P2.4.2 SANITARY RISER NUMBERS 16,19 & 20 ARE
 NOT SHOWN IN THE SAME LOCATION ON THE FLOOR BELOW,
 (P2.3.2), AT THE TUB BATHS. ARE THE RISERS OFFSET? IF
 SO SHOW ON THE FLOOR PLAN AND THE RISER DIAGRAMS.
 SECTION 106.1.1.
  
 58. SHT P2.4.2 SHOW THE RISER NUMBER FOR THE
 LAV/JACUZZI RISER IN THE C-2E UNIT, (425). SECTION
 106.1.1.
  
 59. SHT P2.4.2 RISER DIAGRAM 23 IS NOT INDICATED FOR
 EACH RISER, (3). PLEASE INDICATE ALL RISER NUMBERS.
 SECTION 106.1.2.
  
 60. SHT P2.5.1 SANITARY RISER NUMBER IS NOT INDICATED
 FOR THE W/M STACK BY STAIR #3. PLEASE IDENTIFY. SECTION
 106.1.2.
  
 61. SHT P2.5.2 SANITARY RISERS 10 & 13, CONDENSATE
 RISER 11, AND RISER 9 WITH PLAN NOTE NUMBER 3 ARE
 EITHER IN A SOLID WALL OR PASSING THRU A COLUMN. PER
 SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SLEEVES
 MAY BE REQUIRED. SECTION 305.
  
 62. SHT P2.5.2 INDICATE THE RISER NUMBER FOR THE MOP
 SINK. SECTION 105.1.2.
  
 63. SHTS P2.5.1 & P2.5.2 INDICATED TYPICAL 5TH FLOOR.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 64. SHT P2.6.2 SANITARY RISERS 10 & 13, CONDENSATE
 RISER 11, AND RISER 9 WITH PLAN NOTE NUMBER 3 ARE
 EITHER IN A SOLID WALL OR PASSING THRU A COLUMN. PER
 SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SLEEVES
 MAY BE REQUIRED. SECTION 305.
  
 65. SHT P2.6.2 INDICATE THE RISER NUMBER FOR THE MOP
 SINK. SECTION 105.1.2.
  
 66. SHT P2.7.1 ROOF DRAINS DO NOT APPEAR TO BE LOCATED
 AT THE LOW POINT OF THE ROOF. PLEASE SUBMIT ELEVATIONS
 AT DIFFERENT AREAS OF THE ROOF SHOWING THE LOW POINTS
 AND THE HIGH POINTS OF THE ROOF TO VERIFY PROPER
 DRAINAGE TO THE ROOF DRAINS. SECTION 106.1.2. THE
 PRIMARY AND SECONDARY ROOF DRAINS APPEAR TO BE IN LINE,
 BUT NOT NEXT TO EACH OTHER BEFORE OFFSETTING IN
 DIFFERENT DIRECTIONS. THE FLOORS BELOW SHOW THE PRIMARY
 AND SECONDARY RISERS NEXT TO EACH OTHER ON EACH FLOOR
 PLAN. PLEASE CORRELATE THE ROOF DRAIN AND OFFSETS WITH
 THE FLOOR PLANS BELOW. SECTION 106.1.1.
  
 67. SHT P2.7.2 ROOF DRAINS DO NOT APPEAR TO BE LOCATED
 AT THE LOW POINT OF THE ROOF. PLEASE SUBMIT ELEVATIONS
 AT DIFFERENT AREAS OF THE ROOF SHOWING THE LOW POINTS
 AND THE HIGH POINTS OF THE ROOF TO VERIFY PROPER
 DRAINAGE TO THE ROOF DRAINS. SECTION 106.1.2. THE
 PRIMARY AND SECONDARY ROOF DRAINS APPEAR TO BE IN LINE,
 BUT NOT NEXT TO EACH OTHER BEFORE OFFSETTING IN
 DIFFERENT DIRECTIONS. THE FLOORS BELOW SHOW THE PRIMARY
 AND SECONDARY RISERS NEXT TO EACH OTHER ON EACH FLOOR
 PLAN. PLEASE CORRELATE THE ROOF DRAIN AND OFFSETS WITH
 THE FLOOR PLANS BELOW. SECTION 106.1.1.
  
 68. SHT P2.7.2 THE DRAINS FOR CCC-1, CCC-2, & CCC-3 THE
 MAXIMUM DISTANCE FROM THE TRAP TO THE VENT IS 12. ALL
 THREE EXCEED THIS LIMIT. TABLE 906.1.
  
 69. SHT P2.7.2 SHOW THE VENT THRU ROOF LOCATION FOR ALL
 SANITARY RISER DIAGRAMS AND FOR THE CONDENSATE VENT
 THRU THE ROOF. SECTION 106.1.2.
  
 70. SHT P2.7.2 ONE ROOF AREA "?" SHOWS NO SLOPE TO
 DRAIN. PLEASE INDICATE SLOPE TO ROOF DRAIN. SECTION
 106.1.2.
  
 71. SHT P2.7.2 ONE ROOF AREA "?" ROOF DRAIN AND OD NOT
 LABELED. PLEASE INDICATE WHICH IS THE ROOF DRAIN AND
 WHICH IS THE OD. SECTION 106.1.1.
  
 72. SHT P2.7.2 PLAN NOTES (3) &(4). MORE INFORMATION IS
 REQUIRED. WHAT DRAINS FROM CCC-1, CCC-2 & CCC-3. IF THE
 DRAINAGE IS CONDENSATE, THEN IT SHALL NOT DRAIN INTO
 THE SANITARY SYSTEM. ARTICLE III SECTION 90-125(5)--
 PLEASE INDICATE WHAT DRAINS FROM THE UNITS AND IF IT
 SHALL INDEED DRAIN INTO THE SANITARY SYSTEM, THEN
 SUBMIT A DETAIL SHOWING HOW STORM WATER WILL NOT DRAIN
 INTO THE FUNNEL DRAIN. SECTION 106.1.2.
  
 73. SHT P3.1.2 IDENTIFY THE GAS PIPING TO REFLECT THE
 PIPING LEGEND ON SHT P0.1.
  
 74. SHT P3.1.2 INDICATE THE MATERIAL USED FOR THE 3"
 UNDERGROUND WATER SERVICE TO THE PUMP ROOM. MATERIAL
 SHALL COMPLY WITH TABLE 605.3 AND SECTION 605.3.
  
 75. SHT P3.2.1 SHOWS THE HOT & COLD WATER LINES THRU A
 COLUMN. SLEEVES MAY BE REQUIRED, AND PER SECTION 1906.3
 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED.
  
 76. SHT P3.2.1 IDENTYFY ALL PIPING SYSTEMS, HOT, COLD &
 GAS LINES. UNABLE TO VERIFY CODE COMPLIANCE UNTIL ALL
 LINES ARE IDENTIFIED. SECTION 106.1.2.
  
 77 SHT P3.2.1 HAS A NOTE THAT STATES "SEE RETAIL WATER
 SUPPL RISER ON SHT P7.1". SHT P7.1 NOT SUBMITTED, NOR
 IS IT INDICATED ON THE PLUMBING SHEET INDEX SHT P0.1.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 78. SHT P3.2.2 IDENTYFY ALL PIPING SYSTEMS, HOT, COLD &
 GAS LINES. UNABLE TO VERIFY CODE COMPLIANCE UNTIL ALL
 LINES ARE IDENTIFIED. SECTION 106.1.2.
  
 79. SHT P3.2.2 WATER RISER 13 IS SHOWN THRU A COLUMN.
 PER SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN
 CONCRETE. CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL
 NOT HARMFUL TO CONCRETE AND WITHIN THE LIMITATIONS OF
 ACI 318, SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN
 CONCRETE WITH APPROVAL OF THE REGISTERED DESIGN
 PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SECTION 305.3 SLEEVES MAY BE REQUIRED.
  
 80. SHT P3.2.2 WATER RISER 23 DOES NOT SHOW A
 CONNECTION TO THE WATER MAIN. SECTION 106.1.2. PLEASE
 INDICATE WHERE THE RISER CONNECTS TO THE WATER MAIN.
  
 81. SHT P3.3.1 TWO SHEETS WITH THE SAME NUMBER AND SAME
 INFORMATION SUBMITTED.DELETE ONE. SECTION 106.1.1.
  
 82.SHT P3.3.2 SHOWS RISER 11 IN A COLUMN. PER SECTION
 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED. ALSO THE RISER STARTED
 OUT WITH 3 SLEEVES FOR COLD WATER, GAS & HOT WATER.
  
 83. SHT P3.4.2 SHOWS RISER 11 IN A COLUMN. PER SECTION
 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED. ALSO THE RISER STARTED
 OUT WITH 3 SLEEVES FOR COLD WATER, GAS & HOT WATER.
  
 84. SHT P3.5.2 SHOWS RISER 11 IN A COLUMN. PER SECTION
 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED. ALSO THE RISER STARTED
 OUT WITH 3 SLEEVES FOR COLD WATER, GAS & HOT WATER.
  
 85. SHT P3.6.2 SHOWS RISER 11 IN A COLUMN. PER SECTION
 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED. ALSO THE RISER STARTED
 OUT WITH 3 SLEEVES FOR COLD WATER, GAS & HOT WATER.
  
 86. SHT P3.6.2 OFFSET FOR RISER 23 NOT SHOWN ON THE
 FLOOR PLAN. SECTION 106.1.2.
  
 87. SHT P3.7.2 RISER 11 STARTED OUT WITH 3 SLEEVES FOR
 COLD WATER, GAS & HOT WATER, BUT NOW SHOWS 2. CLARIFY &
 CORRELATE. SECTION 106.1.1.
  
 88. SHT 3.7.2 NOTE INDICATES HOT WATER "UP TO" WATER
 HEATERS, BUT FROM THE HOT RISER DIAGRAM, IT APPEARS
 THAT IT SHOULD READ HOT WATER "DOWN FROM" THE WATER
 HEATERS. PLEASE CLARIFY. SECTION 106.1.1.
  
 89. SHT P3.8.1 THE WATER SUPPLY ROOF PLAN EAST SECTION
 SHOWS NO WATER. PLEASE CLARIFY. SECTION 106.1.1. PLEASE
 INDICATE WHERE THE WATER IS LOCATED.
  
 90. SHT P3.8.2 PRV SET AT 7"W.C. SUBMIT THE TABLE FOR
 THE GAS PRESSURE AT 7" W.C. AS THE MINIMUM PRESSURE
 TABLE IN FBC-2004 FUEL GAS IS .5PSI.
  
 91. SHT P3.8.2 IDENTIFY WHAT THE GAS LINE THAT CONNECTS
 TO THE RISER AND IS ROUTED TO THE AREA BY THE
 CIRCULATION PUMP FOR THE RECIRCULATION OF HOT WATER.
 WHERE IS THE HVAC SYSTEM W/H (200KBTUH MAX) AS THE GAS
 APPLIANCE IS NOT SHOWN ON THE FLOOR PLAN. SECTION
 106.1.2.
  
 92. SHT P3.8.2 NOTE STATES, "GAS, CW AND RECIRC. PIPING
 DOWN", WHEN IT IS ACTUALLY FEEDING UP TO THE ROOF.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 93. SHT P4.1.1 WATER SUPPLY PLANS FOR UNITS C1, C1A &
 CAB. WATER HAMMER ARRESTORS ARE REQUIRED FOR BOTH THE
 HOT & COLD WATER AT THE WASH MACHINE. SECTION 604.9.
  
 94. SHT P4.1.6 WATER SUPPLY PLANS FOR UNITS TH2, & TH2A
 THE WATER HAMMER ARRESTORS ARE REQUIRED AT THE WASH
 MACHINES BY SECTIONS 604.9.
  
 95. SHT P4.1.7WATER SUPPLY PLANS FOR UNITS TH2B, &
 TH2C THE WATER HAMMER ARRESTORS ARE REQUIRED AT THE
 WASH MACHINES BY SECTIONS 604.9.--ALSO SHOW THE
 PIPING TO THE W/C 2ND FLOOR OF TH2B & THE W/C IN TH2C
 IS NOT LOCATED WHERE THE WATER LINE IS SHOWN. PLEASE
 CLARIFY. IF THE FLOOR PLAN IS DIFFERENT, THAN THE WATER
 RISER DIAGRAM CAN NOT BE TYPICAL AND A SEPARATE
 ISOMETRIC RISER DIAGRAM IS REQUIRED.SECTIONS 106.1.1
 & 106.3.5.1.3.
  
 96. SHT P5.1.1 THE SANITARY RISER ISOMETRIC DOES NOT
 REFLECT THE FLOOR PLAN AT THE BASE OF SANITARY RISERS
 11 & 25. PLEASE CORRELATE. SECTION 106.1.1.
  
 97. SHT P5.1.1 SANITARY RISER 27 DOES NOT REFLECT THE
 FLOOR PLAN AT THE 2ND FLOOR TOILET ROOM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 98. SHT P5.1.1 EXPLAIN THE HORIZONTAL BRANCH LINE FROM
 SANITARY RISER 17 TO SANITARY RISER 13. SECTION
 106.1.1.
  
 99. SHT P5.1.1 THE VENTING DOES NOT REFLECT THE FLOOR
 PLAN BY RISERS 17 & 20. PLEASE CORRELATE. SECTION
 106.1.1.
  
 100. SHT P5.1.1 THE WASH MACHINE PIPING AND W/M BOX
 LOCATION DOES NOT REFLECT THE FLOOR PLAN BY SANITARY
 RISERS 17 & 22. PLEASE CORRELATE. SECTION 106.1.1.
  
 101. SHT P5.1.1 THE OFFSET SHOWN ON THE FLOOR PLAN AT
 THE TOP OF THE RISER TO THE 2ND FLOOR FIXTURES IN UNIT
 TH2B IS NOT REFLECTED ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 102. SHT P5.1.1 EXPLAIN THE BRANCH LINE & CLEANOUT PAST
 RISER 26 ON THE RISER DIAGRAM.THIS IS NOT SHOWN ON
 THE FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 103. SHT P5.1.2 THE SANITARY DRAINAGE ISOMETRIC DOES
 NOT REFLECT THE FLOOR PLAN AT THE VENTING, WASH MACHINE
 BOX & OFFSET ON THE SECOND FLOOR FOR TH2. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 104. SHT P5.1.2 THE BUILDING DRAIN CLEANOUT IS MISSING
 UPSTREAM OF TH2 AS INDICATED ON THE FLOOR PLAN. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 105. SHT P5.1.2 THE UNIT TH1D THE LAUNDRY BOX AND
 OFFSET AT THE TOP OF THE RISER TO THE 2ND FLOOR DOES
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 106. SHT P5.1.2THE CLEANOUT UPSTREAM OF UNIT TH1D IS
 NOT SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 107. SHT P5.1.2THE RISER UPSTREAM OF UNIT TH1D DOES
 NOT REFLECT THE FLOOR PLAN. THE OFFSET IS NOT SHOWN &
 NO SANT PLUMBING FOR THE POOL ELECTRICAL ROOM FLOOR
 DRAIN. PLEASE CORRELATE. SECTION 106.1.
  
 108. SHT P5.1.2THE BUILDING SANT. DRAIN JUNCTION BY
 THE 6" 160 DFU & 6" 495 DFU DOES NOT REFLECT YTHE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 106.1.
  
 109. SHT P5.1.2 THE CLEANOUT IS MISSING UPSTREAM OF
 RISER JUST UPSTREAM OF UNITS TH1D AND IS SHOWN
 DOWNSTREAM OF SANT. RISER 5 ON THE FLOOR PLAN BUT
 UPSTREAM OF SANT. RISER 5 ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.
  
 110. SHT P5.1.2 DOES NOT REFLECT THE FLOOR PLAN AT THE
 WASH MACHINE BOX AND AT THE TOP OF THE RISER TO THE 2ND
 FLOOR. PLEASE CORRELATE. SECTION 106.1.
  
 111. SHT P5.1.2 SANITARY RISER 8 BRANCH LINE DOES NOT
 REFLECT THE FLOOR PLAN AS IT DOES NOT INDICATE THE
 LOCATION IN RESPECT TO RISERS 6 & 7. PLEASE CORRELATE.
 SECTION 106.1.
  
 112. SHT P5.1.3 SANITARY RISERS 12 & 13 VENT SHALL
 CONNECT TO THE DRAINAGE STACK. SECTION 903.4
  
 113. SHT P5.1.3 SANITARY RISER 4 DOES NOT REFLECT THE
 FLOOR PLAN WHERE THE LAV STACK CONNECTS TO THE DRAIN
 LINE, (PRIOR TO MASTER BATH), AND AT THE LAV IN THE TUB
 BATH AS WELL AS AT THE BASE OF THE RISER TO LAV AT THE
 3RD FLOOR. PLEASE CORRELATE. SECTION 106.1.
  
 114. SHT P5.1.3 SANITARY RISER 6 DOES NOT REFLECT THE
 FLOOR PLAN FOR THE 3RD FLOOR TUB BATHAT THE LAV.
 PLEASE CORRELATE. SECTION 106.1.
  
 115. SHT P5.1.3 SANITARY RISER 8 DOES NOT REFLECT THE
 FLOOR PLAN WHERE THE WASH MACHINE BRANCH LINES CONNECT
 TO THE BUILDING DRAIN LINE AND ONLY ONE BRANCH LINE IS
 SHOWN WHERE THERE ARE TWO BRANCH LINES ON THE FLOOR
 PLAN. ALSO WHERE THE DOUBLE LAV BRANCH LINE CONNECTS TO
 BLDG DRAIN. PLEASE CORRELATE. SECTION 106.1.
  
 116. SHT ??? SHEET BETWEEN P5.1.3 & P5.1.5 IS MISSING
 THE TITLE BLOCK INFORMATION AND PAGE NUMBER. PLEASE
 CLARIFY AND MAKE SURE THE TITLE BLOCK AND SHEET NUMBER
 ARE INDICATED. (SHOWN AS P5.1.4 ON SECOND SET OF
 PLANS).
  
 117. SHT P5.1.4SANITARY RISER 9, MINIMUM 3" REQUIRED
 TO THE WASH MACHINE. SECTION 406.3.--CLEANOUT PAST
 THE WATER CLOSET IS NOT SHOWN ON THE FLOOR PLAN.--
 THE VENT SHALL CONNECT TO THE DRAINAGE STACK AT THE TUB
 BATH RISER. SECTION 903.4.--THE FLOOR DRAIN FOR THE
 WATER HEATER ROOM IS SHOWN ON THE 5TH, 6TH & 7TH FLOORS
 ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.
  
 118. SHT P5.1.4 SANITARY RISER 13 DOES NOT REFLECT THE
 FLOOR PLAN ON THE SECOND FLOOR. PLEASE CORRELATE.
 SECTION 106.1.
  
 119. SHT P5.1.4 SANITARY RISER 15 DOES NOT REFLECT THE
 OFFSET SHOWN ON FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.
  
 120. SHT P5.1.4 SANITARY RISER 16/20 DOES NOT REFLECT
 THE FLOOR PLAN AT EITHER WASH MACHINE BRANCH LINES &
 WHERE THE LAV FOR THE TUB BATH CONNECTS TO THE STACK.
 ALSO THE DRAIN LINE FOR THE CCC UNITS DOES NOT REFLECT
 THE FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.
  
 121 SHT P5.1.4 SANITARY RISER 17 DOES NOT REFLECT THE
 FLOOR PLAN AT OFFSETS PRIOR TO STACK AND STACK FOR
 JACUZZ I/LAV IS NOT SHOWN ON THE FLOOR PLAN. PLEASE
 CORRELATE. SECTION 106.1.
  
 122. SHT P5.1.5 RISER DIAGRAM #18 DOES NOT REFLECT THE
 FLOOR PLAN AT THE BASE OF BOTH WASH MACHINES RISERS.
 THE FLOOR PLAN SHOWS THE LAUNDRY BOX BETWEEN THE
 RISERS. PLEASE CLARIFY. SECTION 106.1.1. PLEASE MAKE
 SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR
 PLAN.
  
 123. SHT P5.1.5 RISER DIAGRAM #19 DOES NOT REFLECT THE
 FLOOR PLAN AT THE BASE OF THE WASH MACHINE RISERS FOR
 THE OFFSETS AND THE LAUNDRY BOX SHOWN BETWEEN THE
 RISERS. NOR DOES IT REFLECT THE FLOOR PLAN WHERE THE
 BRANCH CONNECTION FOR THE JACUZZI TUB/LAV TO DRAIN LINE
 AS WELL AS THE LAV ARM IN THE SHOWER BATH. SECTION
 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS
 THE PIPING ON THE FLOOR PLAN.
  
 124. SHT P5.1.5 RISER DIAGRAM #21 DOES NOT REFLECT THE
 FLOOR PLAN AT THE BRANCH LINE TO THE
 KITCHEN/LAV/JACUZZI & AT THE WASH MACHINE RISERS WHERE
 THEY CONNECT TO THE DRAIN LINE. SECTION 106.1.1. PLEASE
 MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE
 FLOOR PLAN.
  
 125. SHT P5.1.5 RISER DIAGRAM #25 DOES NOT REFLECT THE
 FLOOR PLAN AT THE BASE OF THE WASH MACHINE STACK, OFF
 SET NOT SHOWN AND JACUZZI TUB IS NOT LEFT OF STACK.
 SECTION 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM
 REFLECTS THE PIPING ON THE FLOOR PLAN.
  
 126. SHT P5.1.5 RISER DIAGRAM #26 DOES NOT REFLECT THE
 FLOOR PLAN AT THE WASH MACHINE STACK BASE, (LAUNDRY BOX
 SHOWN BETWEEN THE W/M STACKS), AND AT THE LAV ARM IN
 THE TUB BATH ALL FLOORS.--A DRY HORIZONTAL VENT IS
 SHOWN UPSTREAM OF THE W/C AT THE BASE OF THE W/C STACK.
 SECTION 106.1.1. DRY HORIZONTAL VENTS ARE NOT APPROVED.
 PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING
 ON THE FLOOR PLAN AND MEETS CODE REQUIREMENTS. SECTION
 905.3.
  
 127. SHT P6.1.1 RISER DOES NOT REFLECT THE FLOOR PLAN.
 SHOW ALL OFFSETS, CONNECTIONS TO MAINS ETC TO REFLECT
 THE FLOOR PLAN.--2 COLD LINES FROM PUMP ROOM AND
 AROUND THE 2ND FLOOR SHOWN ON THE FLOOR PLAN ARE NOT ON
 THE RISER DIAGRAM. THERE IS NO SUPPLY TO THE MOP SINK
 RISER, NOR IS THERE SUPPLY TO THE TOILET ROOM. ALL "TH"
 UNITS SHOW CONNECTING TO A SECOND WATER MAIN. WATER
 PIPING TO WATER HEATER ON THE 3RD FLOOR AND RELATED
 PIPING DOES NOT REFLECT THE FLOOR PLAN. PIPING AT THE
 BASE OF SOME RISERS DOES NOT REFLECT THE FLOOR PLAN.
 ALSO THE COLD WATER ISO FOR THE POOL SUPPLY LINE DOES
 NOT REFLECT THE FLOOR PLAN.PLEASE MAKE SURE THE RISER
 DIAGRAM REFLECTS THE PIPING ON THE FLOOR PLAN. --RPZV
 BACKFLOW SHALL BE LOCATED AS CLOSE TO THE METER AS
 POSSIBLE ON PRIVATE PROPERTY. PLEASE CORRELATE. SECTION
 106.1.
  
 128. SHT P6.1.2 RISER DOES NOT REFLECT THE FLOOR PLAN
 WHERE SOME RISERS OR DROPS CONNECT TO THE MAIN, AT
 OFFSETS AND AT THE TOP OF RISER 23.--CHECK VALVES
 ARE NOT REQUIRED AT THE BASE OF THE DROPS. (HOW CAN
 RISERS BE DRAINED IF REQUIRED FOR SERVICE)?SECTION
 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS
 THE PIPING ON THE FLOOR PLAN. THE MOP SINK& TOILET
 ROOM PIPING IS NOT SHOWN. "TH" UNITS DO NOT CONNECT TO
 THE MAIN AS SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.
  
 129. SHT P6.1.5 A SEPARATE GAS PERMIT IS REQUIRED.
 SUBMIT THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - INDICATE ALL CUT SECTIONS DOWNSTREAM
 OF THE REGULATOR FOR THE GAS WATER HEATERS. FINAL DROP
 LENGTH NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. - SIZE OF PIPE
 SHOWS 1-1/4" REDUCING TO 1" THEN BACK TO 1-1/4". PLEASE
 CLARIFY.--ALSO SHOW THE MATERIAL TYPE OF THE
 VENTING FROM THE REGULATORS. (MATERIAL SHALL BE NON
 COMBUSTABLE).
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - ALSO SHOW THE TOTAL
 DISTANCE FROM THE REGULATOR TO THE MOST REMOTE OUTLET
 DOWNSTREAM OF THE REGULATOR FOR THE GAS WATER HEATERS.
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - PLEASE SUBMIT AN
 APPROVED TABLE FOR 7"W.C. OR INDICATE 1/2PSI DOWNSTREAM
 OF THE REGULATOR. FBC-2004 FUEL GAS HAS NO 7" W.C.
 TABLES TO VERIFY PIPE SIZES.
  
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. SUBMIT MANUF. SPECIFICATION SHEETS FOR THE GAS
 REGULATORS. INDICATE MODEL NUMBER FOR EACH REGULATOR.
 --A UNION IS REQUIRED NEXT TO THE REGULATOR NOT AT
 THE END OF A RUN. (SEE GAS WATER HEATERS & HVAC SYSTEM
 REGULATORS).
  
 130. SHT P6.1.4 ISOMETRIC WATER RISER DIAGRAM FOR UNITS
 C1, C1A & C1B REQUIRE A WATER HAMMER ARRESTOR FOR THE
 DISH WASHER & FOR BOTH THE HOT & COLD AT THE WASH
 MACHINE. SECTION 604.9.
  
 131. SHT P6.1.4 ISOMETRIC WATER RISER DIAGRAMS FOR
 UNITS C2, C2C, C2F & C2D REQUIRE A WATER HAMMER
 ARRESTOR FOR THE DISH WASHER. 604.9.
  
 132. SHT P6.1.4 ISOMETRIC WATER RISER DIAGRAM FOR UNITS
 C3 REQUIRES A WATER HAMMER ARRESTOR FOR THE DISH WASHER
 & THE ICE MAKER. 604.9.
  
 133. SHT P6.1.4 ISOMETRIC WATER RISER DIAGRAM FOR UNITS
 C5A REQUIRES A WATER HAMMER ARRESTOR FOR THE ICE MAKER.
 604.9.
  
 134. SHT P6.1.4 ISOMETRIC WATER RISER DIAGRAMS FOR
 UNITS TH1, TH1A, TH1B, TH1C, TH1D & TH1E REQUIRE A
 WATER HAMMER ARRESTOR FOR THE ICE MAKER PER SECTION
 604.9 AND DO NOT REFLECT THE FLOOR PLAN WHERE THE
 JACUZZI CONNECTS TO THE WATER MAIN LINES. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 135. SHT P6.1.4 ISOMETRIC WATER RISER DIAGRAMS FOR
 UNITS TH2, TH2A, TH2B & TH2C REQUIRE THE WATER HAMMER
 ARRESTORS TO BE LOCATED AT THE WASH MACHINE. SECTION
 604.9.
  
 136. SHT P6.1.4 SUBMIT A FLOOR PLAN FOR THE 3RD FLOOR
 RESTROOMS THAT SHOWS THE WATER PIPING IN PLAN VIEW THAT
 WILL REFLECT THE RISER DIAGRAM. IDENTIFY THE HOT AND
 COLD WATER LINES. SECTION 106.3.5.1.3.
  
 137.SHT P5.2.1 ALL OFFSETS AT THE ROOF LEVEL DO NOT
 REFLECT THE OFFSETS SHOWN ON THE ROOF PLAN. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 138. SHT P5.2.1 RISER SDR2 DECK DRAIN, (FD-4), THE TRAP
 AND TRAP PRIMER IS NOT REQUIRED ON THE STORM DRAINAGE.
 PLEASE DELETE.
  
 139. SHT P5.2.1 SDR 5 OFFSETS AT THE ROOF,MINIMUM 5"
 PIPE REQUIRED OR MINIMUM SLOPE 2%.PLEASE SHOW ON THE
 PLANS. TABLE 1106.3.
  
 140. SHT P5.2.1 SDR'S 6, 7, 8, 9, 10, 11, 13 & 14
 OFFSETS AT THE ROOF, MINIMUM 5" PIPE REQUIRED OR
 MINIMUM 4% SLOPE. PLEASE SHOW ON THE PLANS. TABLE
 1106.3.
  
 141. SHT P5.2.1 SDR 12 OFFSET AT THE ROOF, MINIMUM 5"
 PIPE REQUIRED OR MINIMUM 2% SLOPE. PLEASE SHOW ON THE
 PLANS. TABLE 1106.3.
  
 142. SHT P5.2.1 SDR 15 OFFSET AT THE ROOF, MINIMUM 6"
 PIPE REQUIRED OR MINIMUM 4% SLOPE. PLEASE SHOW ON THE
 PLANS. TABLE 1106.3.
  
 142. SHT P5.2.1 SDR'S 10 & 15 FD-4 IS NOT SHOWN ABOVE
 THE THIRD FLOOR BT ON THE 2ND FLOOR ON THE FLOOR PLAN.
 THE RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 143. SHT P5.2.1 THE GCO IS SHOWN UPSTREAM OF SDR 13 ON
 THE FLOOR PLAN BUT IS SHOWN DOWNSTREAM ON THE RISER
 DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1.
  
 144. SHT P5.2.2 SHOW ALL PIPE SIZES PER TABLE 1106.3.
  
 145. SHT P5.2.2 CLEANOUTS REQUIRED BY SECTION 1101.8
 SHALL BE SHOWN TO REFLECT THE FLOOR PLAN. (SOME ARE
 MISSING). PLEASE CORRELATE. SECTION 106.1.1.
  
 146. SHT P5.2.2 RECHECK THE ADDITION ON DDR 1 & DDR 7
 AND CORRECT ALL SQUARE FOOTAGE FOR THOSE RISERS AND ALL
 PIPING DOWNSTREAM. TABLE 1106.3.
  
 147. SHT P5.2.2MINIMUM 5" PIPE REQUIRED FOR DD
 2,500SF ON RISERS DDR-2 & DDR-3. TABLE 1106.3.
  
 148. SHT P5.2.2 MINIMUM 5" PIPE REQUIRED FOR 1750SF,
 (4" SHOWN), ON RISER DDR-5. TABLE 1106.3.
  
 149. SHT P5.2.2 ALL PIPING DOWNSTREAM OF THE LAST CATCH
 BASIN SHALL SLOPE IN A UNIFORM SLOPE OF 1/4"/FT. PLEASE
 SHOW ON THE PLANS. SECTION 704.1.
  
 150. SHT P9.1.1 ROOF TOP EQUIPMENT. CONDENSATION
 CONNECTION DETAIL INDICATES A LINE TO DISCHARGE THAT
 RUNS BELOW THE ROOF & CONNECTS TO NEAREST CATCH BASIN,
 BUT SHT P2.7.2 SHOWS RTU-2 DISCHARGING TO NEAREST ROOF
 DRAIN. PLEASE CORRELATE DETAIL AND ROOF PLAN. SECTION
 106.1.1.
  
 151. THERE IS A MOP SINK INDICATED IN ROOM 339 THAT HAS
 NO WATER PIPING SHOWN. PLEASE CLARIFY. SECTION
 106.1.1.
  
 152. ALL LANDSCAPE PLANS THE FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK OF ALL SHEETS. THE SEAL FOR EACH SHEET IS
 NOT APPROVED AS IT IS REQUIRED TO BE APPROX. 2" IN
 DIAMETER. FAC 61G1-16.002, 61G1-16.004(2) & FS
 481.305.
  
 153. SHTS IR-1 THRU IR-12 THE FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK OF ALL SHEETS. THE SEAL FOR EACH SHEET IS
 NOT APPROVED AS IT IS REQUIRED TO BE APPROX. 2" IN
 DIAMETER.--SUBMIT ONLY THE IRRIGATION SHEETS FOR
 BUILDING 5 IN THE PLANS FOR BUILDING 5.--INDICATE
 THE WATER SOURCE FOR THE IRRIGATION AND SHOW RPZV
 BACKFLOW LOCATION. SHOW THE CONTROLLER LOCATION AND THE
 RAIN SENSOR LOCATION ON THE PLANS. FAC 61G1-16.002,
 61G1-16.004(2) & FS 481.305.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-05 Cont ID  
Sent By eschneid Date 2007-09-05 Time 18:59 Rev Time 0.00
Received By eschneid Date 2007-09-05 Time 18:59 Sent To  
Notes
2007-09-05 19:01:11FAILED
  
 RESPOND TO ALL COMMENTS IN WRITING.
  
 1) PER ORDINANCE NO. 3914-05, PRIOR TO THE ISSUANCE OF
 THE FIRST BUILDING PERMIT, THE APPLICANT/OWNER SHALL:
 A) RECORD PUBLIC ACCESS EASEMENTS FOR ROADWAYS AND
 ADJACENT SIDEWALKS THROUGHOUT THE SITE.THIS MAY BE
 DONE ON A PLAT OR SEPARATE INSTRUMENT.
 B) RECORD A RESTRICTIVE DEED OR COVENANT PREVENTING THE
 GATING OF ANY OF THE ROADWAYS IN THE MIZNER LAKES RPD.
  
 C) RECORD A MAINTENANCE AGREEMENT FOR THE PAVERS AND
 LANDSCAPING IN THE HANK AARON DRIVE TRAFFIC OVAL.
 D) RECORD A MAINTENANCE AGREEMENT FOR THE LAKE PATH AND
 LANDSCAPING ADJACENT TO THE MIZNER LAKES RPD.[REPEAT
 COMMENT]
  
 2) PLEASE NOTE THAT THE MINOR AMENDMENT SUBMITTED TO
 REVISE THE APPROVED PLANS TO MATCH THE BUILDING PERMIT
 PLANS HAS NOT BEEN APPROVED AS THE SUBMITTED LANDSCAPE
 PLANS DID NOT MATCH THE ENGINEERING AND SITE PLANS.
 NOTE THAT THE LANDSCAPE PLANS SUBMITTED WITH THIS
 PERMIT DO MATCH THE OTHER PLANS.THIS PERMIT WILL NOT
 BE APPROVED UNTIL THE MINOR AMENDMENT IS APPROVED.
  
 3) THE PARKING SPACE DETAILS FROM CIVIL PLANS SHEET
 C-18 (SUBMITTED WITH PERMIT NO. 07040152) SHALL BE
 INCLUDED ON THE SITE PLAN.
  
 4) IS THE SPACE IN THE NORTHWEST CORNER OF THE GARAGE A
 LOADING ZONE OR A PARKING SPACE?IT IS LABELED
 DIFFERENTLY ON DIFFERENT SHEETS. [REPEAT COMMENT]
  
 5) PROVIDE THE DIMENSION, ON THE PLAN, OF THE LOADING
 SPACE AND CORRECTLY LABEL THE PASSENGER DROP OFF ON THE
 NORTHWEST CORNER OF THE BUILDING ON ALL PLANS.
  
 6) PROVIDE WRITTEN VERIFICATION FROM THE CITY'S
 ENGINEERING SERVICES AND PARKING DEPARTMENTS THAT THE
 CITY RECOGNIZES THE SAME NUMBER OF PARALLEL PARKING
 SPACES ON HANK AARON DRIVE AS SHOWN ON THE SUBMITTED
 PLANS.PROVIDE THE DIMENSIONS OF THE SPACES ON THE
 PLANS.THESE SPACES ARE TO BE INSTALLED/MAINTAINED
 MEETING THE MINIMUM CITY REQUIREMENTS. [REPEAT
 COMMENT]
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.