2007-10-15 14:45:21THE LAKES AT PALM BEACH
 COMO BUILDING NO. 4
 FORMERLY: MIZNER LAKES
 OCT. 15, 2007
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07080072
 ADD:1596 VANDAN DR
 CONT: AVS CONSTRUCTION
 TEL: (954)655-5162
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT
 STATEMENT ---
 PLEASE DO
 NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)PLANS SUBMITTED AFTER JULY 1, 2007WILL BE
 REVIEWED UNDER THE 2004 BASE FLORIDA BUILDING CODE,
 BUILDING WITH 2007REVISIONS, WIND PROVISIONS. PLEASE
 CORRECT SHEET A-002 BUILDING NO. 4 DATA, THE WRONG YEAR
 CODE.
  
 3A) SHEET A-002 BUILDING DATA ALSO CORRECT THE HEIGHT
 AND AREA LIMITATIONS, AND THE REFERENCE TO TABLE 500
 PLEASE UPDATE TO THE 2004 NOMENCLATURE. PLEASE
 CORRELATE WITH THE LIFE SAFETY SHEET FOUND ON SHEET
 A-251- A-256.
  
 3B) SHEET A-002 INDICATES A MERCANTILE OR RETAIL
 OCCUPANCY? 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 4) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS. 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE
 A SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS
 ON A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 7) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY553.79(5) FLORIDA STATUTES TO
 THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT
 HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM
 AT (561) 805-6711 FOR FURTHER INFORMATION BEFORE THE
 PERMIT MAY BE ISSUED.
  
 8)W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY
 THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND
 633 FLORIDA STATUTE.
  
 10) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 11) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113
 OF THIS CHAPTER.
  
 12) CORRELATE PLANS IT APPEARS THAT ON THE CIVIL PLANS
 THE PROJECT NAME STILL INDICATES MIZNER LAKES AND NOT
 THE LAKES AT PALM BEACH, PLEASE CORRECT.
  
 13) SHEETS A-003- A004 INDICATE THE FAIR HOUSING
 GUIDELINES, PLEASE NOTE THAT THE FIRST FLOOR MERCANTILE
 OCCUPANCY WILL BE UNDER 2004 FBC CHAPTER 11 FLORIDA
 ACCESSIBILITY.
  
 14) SHEET A-102 & A-202 THE COVERED ENTRY LOADING SPACE
 BY THE FRONT ELEVATOR LOBBY # 100 INDICATES STAIRS BUT
 NO VERTICAL ACCESSIBILITYIN UNDER THE COVERED CANOPY.
 AGAIN
 11-2.2EQUIVALENT FACILITATION, YOU CAN?T DISCRIMINATE
 AGAINST TOUGHS WITH DISABILITIES
 REQUIRING THEM TO TAKE A ROUTE THAT IS NOT COVERED.
  
 15) SHEET A-102 & A-202 AND A-502 ALL INDICATE A
 SECURITY OFFICE AND A VALET STATION WITH
 WHAT APPEARS TO BE A COUNTER AND SLIDING GLASS WINDOWS,
 PLEASE PROVIDE A SECTION OF THIS AREA WITH THE COUNTER
 HEIGHT PROVIDED TO MEET FAIR HOUSING GUIDE LINES.
  
 16) SHEET A-102 & A-202 BOTH HAVE RAMPS:
 16A) BY THE CONDO UNITTH-1B THERE 2 ACCESSIBLE
 PARKING SPACES WITH A 5?-0? WIDE ACCESS AISLE, THIS
 AREA IS ALSO THE BOTTOM LANDING FOR TWO RAMPS, THE
 BOTTOM LANDING FOR RAMPS REQUIRES A 72? LANDING NOT A
 60? LANDING. 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON
 RAMPS SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF
 EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARANCE.
  
 16B) THE SAME TYPE SITUATION OCCURS AT CONDO UNIT TH-1A
 , THE BOTTOM LANDING FROM RAMPS IS ONLY 5?-0? NOT THE
 REQUIRED 72?. .(2) LANDINGS. ALL LANDINGS ON RAMPS
 SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL
 CLEARANCE.
  
 17) A-202 DOOR OR GATE G06 & G07 PLEASE PROVIDE
 MANUFACTURERS? INFORMATION ON HOW
 THESE UNITS WILL OPEN? 106.1.2* ADDITIONAL INFORMATION
 REQUIRED.
  
 18) A-201, THE HANDICAPPED RAMP IN THE UPPER RIGHT
 PORTION OF THE SHEET IS MISSING THE BOTTOM LANDING.
 .11-4.8.4(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT
 BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS
 THAN 72" OF STRAIGHT & LEVEL CLEARANCE.
  
 19) NOT USED.
  
 20) A-201 WHAT APPEARS TO BE RAMPS OR CURB CUTS THE
 BOTTOM LANDING IS 5?-0? WHERE :
 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT
 BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL CLEARANCE.
  
 21). NOT USED.
  
 22)1009.12 ACCESS TO ROOF.BUILDINGS FOUR STORIES OR
 MORE IN HEIGHT, EXCEPT THOSE WITH A ROOF SLOPE GREATER
 THAN 4:12, SHALL BE PROVIDED WITH A STAIRWAY TO THE
 ROOF. SUCH STAIRWAY SHALL BE MARKED AT STREET AND FLOOR
 LEVELS WITH A SIGN INDICATING THAT IT CONTINUES TO THE
 ROOF. WHERE ROOFS ARE USED FOR ROOF GARDENS OR FOR
 OTHER PURPOSES, STAIRWAYS SHALL BE PROVIDED AS REQUIRED
 FOR SUCH USE OR OCCUPANCY.
  
 23) SHEET A-201 G-05 DOES NOT HAVE A CURB CUT, THERE IS
 NO DESIGNATION FOR AN ACCESSIBLE PATH ACROSS THE ENTRY
 AREAS FOR BOTH ENTRIES INTO THE BUILDING BY VEHICLE AND
 THERE IS A
 CENTER AISLE THAT ALSO DOES NOT HAVE ACCESS ACROSS.
  
  
 24) HANDICAPPED PARKING SPACES IN THE GARAGE NEED TO
 COMPLY WITH 11-4.1.2(5)(B)IN PARKING STRUCTURES, ONE
 IN EVERY EIGHT ACCESSIBLE SPACES, BUT NOT LESS THAN
 ONE, SHALL BE ?VAN
 ACCESSIBLE? AND SHALL BE DESIGNED AS REQUIRED BY
 SECTION 11-4.6.3. THE VERTICAL CLEARANCE AT SUCH SPACES
 SHALL COMPLY WITH SECTION 11-4.6.5. ALL SUCH SPACES MAY
 BE GROUPED ON THE SAME LEVEL OF A PARKING STRUCTURE.
 WHEN SUCH SPACES ARE PROVIDED IN A PARKING STRUCTURE
 AND ONLY ONE IN EIGHT MEET THE HEIGHT REQUIREMENT OF
 SECTION 11-4.6.5, THEY SHALL BE DESIGNATED BY SECTION
 11.6.4.
  
 25) A-201 & A-703 BOTH INDICATE A GATE BENEATH THE
 STAIRWELL, AND A NOTE ON SHEET A-703 INDICATES THIS IS
 A MAINTENANCE GATE.ENCLOSURES UNDER STAIRWAYS.
 1019.1.5.
 THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES
 UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE
 PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION,
 OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY
 ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED
 USABLE SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE
 STAIR ENCLOSURE.
  
  
 26) SINCE THE LAST REVIEW UNDER PERMIT # 05091456,THE
 CONFIGURATION OF LOFT UNITS VERSES PASSAGE TO THE
 PARKING GARAGE WITH NO EXIT ACCESS CORRIDOR WAS BROUGHT
 TO THE ATTENTION OF THE BUILDING OFFICIAL. WE ARE
 SEEING MORE OF THIS TYPE DESIGN AND THE BUILDING
 OFFICIAL
 HAS RULED THAT THIS IS AN UNSAFE PRACTICE. THE
 OCCUPANTS LEAVE THE R-2 UNIT AND HAVE NO EXIT ACCESS
 CORRIDOR WHEN ENTERING THE PARKING GARAGE AREA.
 ALTHOUGH THE CODE DOESN'T QUOTE A
 SECTION, THAT AN EXIT ACCESS CORRIDOR IS REQUIRED THE
 BUILDING OFFICIAL IS USING THESE (2) CODE SECTIONS TO
 ENFORCE REQUIRING A EXIT ACCESS CORRIDOR TAKING THE
 OCCUPANT TO THE SAFETY OF AN EXIT. 103.6**
 REQUIREMENTS NOT COVERED BY THE CODE. ANY REQUIREMENTS
 NECESSARY
 FOR THE STRENGTH, STABILITY OR PROPER OPERATION OF
 EXITING OR PROPOSED BUILDING, STRUCTURE, ELECTRIC, GAS,
 MECHANICAL OR PLUMBING SYSTEM, OR FOR PUBLIC SAFETY,
 HEALTH AND GENERAL
 WELFARE , NOT SPECIFICALLY COVERED BY THIS OR OTHER
 TECHNICAL CODES, SHALL BE DETERMINED BY THE BUILDING
 OFFICIAL. IN ADDITION, OTHER REQUIREMENTS TO IMPLEMENT,
 CLARIFY OR SET PROCEDURES TO IMPLEMENT THIS CODE MAY BE
 SET IN WRITING BY THE BUILDING OFFICIAL AND BE
 POSTED ELECTRONICALLY FOR PUBLIC ACCESS. 1001.1.4 WHEN
 UNUSUALLY HAZARDOUS CONDITIONS EXIST, THE BUILDING
 OFFICIAL MAY REQUIRE ADDITIONAL MEANS OF EGRESS TO
 ASSURE THE SAFETY OF
 THE OCCUPANTS. 1016.1 CONSTRUCTION. CORRIDORS SHALL BE
 FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLE 1016.1 .
 THE CORRIDOR WALLS REQUIRED TO BE FIRE-RESISTANCE RATED
 SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS.
  
 27) SHEET A-201 THE CONDO ENTRY UNIT DOORS 133 & 134
 BOTH ARE MISSING AFIRE RATING ON THE DOOR SCHEDULE
 A-901. SEE TABLE 302.3.REQUIRING A 2HR WALLSS2 TO R2,
 OPENING PROTECTIVE?S
 715.3 1 ? HR OPENING PROTECTIVE?S.
  
 28) THIS WILL BE A COMMON NOTE FOR ALL R2 UNITS FOR
 WALL AND FLOOR SOUND INSULATION REQUIREMENTS. LEASE
 PLEASE PROVIDE THE STC RATINGS FOR WALLS AND FLOORS
 WHERE REQUIRED.
 SEE CODE SECTIONS BELOW.
  
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 29) SHEET A-202THE DOOR SCHEDULE THAT TIES TO DOORS
 111, 1132 & 115 CONDO ENTRY DOORS ARE NOT FIRE RATED.
 RS2 VS S2 TABLE 302.3.2 2HR WALLS 715.3 1 ? HR OPENING
 PROTECTIVE.
  
  
 30) SHEET A-203 DOOR # 208 DOOR TO STAIR# 4 NOT RATED,
 TABLE 715.3 OPENING PROTECTIVE
 < THAN 4STORIES 45 MINUTE DOOR.
  
 31) SHEET A-206 THE STAIR# 1 DOOR 302 IS MISSING FROM
 THE DOOR SCHEDULE, TABLE 715.3 OPENING PROTECTIVE 2HR
 SHAFT REQUIRES 1 ? HR OPENING PROTECTIVE.
  
 32) SHEET A-205 DOOR 342, 347,367 & 358 ALL INDICATE
 THE USE OF SLIDING GLASS DOORS ONTO
 PATIO DECKS, PLANS DO NOT INDICATE (3) ITEMS THAT ARE
 CONCERNS TO FAIR HOUSING REQUIREMENTS FOR SLIDING GLASS
 DOORS (SECONDARY DOORS) THAT LEAD ONTO A IMPERVIOUS
 SURFACE.
 A) PLEASE PROVIDE A DETAIL INDICATING THE BOTTOM TRACK
 HEIGHT IN RELATIONSHIP TO THE INTERIOR FINISH FLOOR AND
 THE FINISH FLOOR OF THE PATIO ON THE EXTERIOR.
 B) PLEASE PROVIDE THE CLEAR OPENING SIZE FOR THE 6?-2?
 SLIDING GLASS DOORS.
 C) PROVIDE DETAILS FOR THE LATCHING MECHANISM FOR THE
 SLIDING GLASS DOOR.
 PLEASE SEE PAGE 4.14 OF FAIR HOUSING MANUAL DETAIL FOR
 SLIDING GLASS DOORS AT CONCRETE LANDINGS.
  
 33A) SHEET A-205 & A-206BOTH INDICATE THE LOWER DECK
 AREA TO BE AT THE SAME GRADE AS THE INTERIOR CORRIDOR
 ELEVATION 23?-6?, PLANS INDICATE SLOPE BUT THERE IS NO
 PARAMETERS AS TO SLOPE?
  
 33B)PLANS INDICATE DECK DRAINS BUT THERE IS NO
 SECONDARY DRAINS THIS DECK IS NO DIFFERENT THAN A FLAT
 ROOF THAT REQUIRES SECONDARY DRAINAGE,SEE 1503.4 ROOF
 DRAINAGE AND 1503.4.3 OVERFLOW SCUPPERS. THE PROBLEM
 WITH THE USING OVERFLOW SCUPPERS THEY HAVE TO BE SET 2
 INCHES ABOVE THE ROOF DECK AT A MINIMUM, THERE WILL BE
 2? OF WATER POSSIBLY IN THE UNITS.
  
 34) POOL DECK DRAINS WILL BE PENETRATING A FIRE RATED
 FLOOR CEILING ASSEMBLY WITH THERE
 PIPE, PLEASE PROVIDE A RATED ASSEMBLY712.4HORIZONTAL
 ASSEMBLIES, PENETRATIONS OF A FLOOR, FLOOR/CEILING
 ASSEMBLY OR THE CEILING MEMBRANE OF A ROOF/CEILING
 ASSEMBLY SHALL BE PROTECTED IN ACCORDANCE WITH SECTION
 707
  
 35) NOTE)NOTE: SEE DEPARTMENT OF HEALTH [DOH] RULE
 64E-9, FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 514, FLORIDA STATUTES FOR SECURITY &
 REQUIRED FENCING. TO BE
 IN PLACE AT TIME OF BUILDING C.O.
  
 36) NOTE:13-412.1.ABCD.2.4.2 COVERS REQUIRED. SPAS AND
 HEATED SWIMMING POOLS
 SHALL BE EQUIPPED WITH A COVER DESIGNED TO MINIMIZE
 HEAT LOSS. TO BE IN PLACE AT
 TIME OF BUILDING C.O.
  
 37) PROVIDE EXITING SIGNAGE FOR POOL DECK.1006.1.1
 ILLUMINATION OF MEANS OF
 EGRESS SHALL BE PROVIDED IN ACCORDANCE WITH THIS
 SECTION FOR EVERY BUILDING AND STRUCTURE.FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT ACCESS SHALL INCLUDE
 ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS AND PASSAGEWAYS LEADING TO
 AN EXIT.FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS AND EXIT PASSAGEWAYS LEADING TO A
 PUBLIC WAY.
  
 38) SHEET A253 PLEASE REMOVE THE WORD TOWNHOUSE FROM
 THE PLANS THE LOFT UNITS ARE NOT A FEE SIMPLE PROPERTY,
 SEE DEFINITIONS 202 FOR TOWNHOUSE.
  
 39) SHEET A-206 CONDO UNIT C-5 HAS A BATHROOM AND
 BEDROOM THAT BACKS UP TO WHAT LOOKS LIKE EITHER A SHAFT
 OR POSSIBLY AN EXTERIOR WALL PLEASE CLARIFY THIS AREA,
 POSSIBLY A SECTION THROUGH SHOWING THE ELEVATIONS OF
 THE ADJOINING ROOF LINE. 106.1.2.ADDITIONAL INFORMATION
 REQUIRED.
  
 40) SHEET A208, THIS IS COMMON TO ALL SHEETS HAVING S1
 STORAGE ROOMS SIMILAR TO ROOM # 411 WILL REQUIRE A 3 HR
 WALL RATING WITH OPENING PROTECTIVE?S, PLANS DO NOT
 PROVIDE ANY WALL IDENTIFICATION TAGS.TABLE 302.3.2.
  
 41) 403- A.406 ELEVATIONS: 20A) ELEVATIONS, PLEASE
 PROVIDE THE POSITIVE AND NEGATIVE PRESSURES FOR ALL
 OPENINGS, INTERIOR AND END ZONES FOR ALL OPENINGS,
 INDICATE PRESSURES ON THE ELEVATIONS . DESIGN TO ASCE
 7-02.
  
 42) A650 INDICATES THE USE OF NON-COMBUSTIBLE MOLDINGS
 BY CARPENTER?CRETE, PLEASE PROVIDE
 INFORMATION ON THIS PRODUCT AS TO THE COMPOSITION OF
 THE MATERIAL AND FASTENING SYSTEM TO THEWALL.
 1404.1.1 ARCHITECTURAL TRIM ON BUILDINGS OF TYPE I, II
 AND IV CONSTRUCTION NOT MORE THAN THREE STORIES OR 40
 FT (12.2 M) HIGH MAY BE OF TYPE VI CONSTRUCTION, AND
 MAY BE OF TYPE VI
 CONSTRUCTION ON ALL BUILDINGS OF TYPE III, V AND VI
 CONSTRUCTION.TRIM SHALL BE SECURED TO THE WALL WITH
 METAL OR OTHER APPROVED BRACKETS OR FASTENERS.
  
 43) EXTERIOR ALUMINUM RAILINGS TO COMPLY WITH1607.1.1
 GUARDRAIL SYSTEMS SHALL BE DESIGNED AND CONSTRUCTED FOR
 A CONCENTRATED LOAD OF 200 LB (890 N) APPLIED AT ANY
 POINT AND IN ANY
 DIRECTION AT THE TOP OF THE GUARDRAIL.
  
 44)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
 45 )1606.1.4(1) IN WIND BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS UNLESS SUCH GLAZING IS
 IMPACT RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E
 1886 AND ASTM E 1996 OR MIAMI-DADE.1) GLAZED OPENINGS
 LOCATED WITHIN 30 FT OF GRADE SHALL MEET THE
 REQUIREMENTS OF LARGE MISSILE TEST.
  
 46) FL BLD CODE 1606.1.5: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTINGREPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED/ STOREFRONT
 B) WINDOWS OPERABLE
 C) MULLIONS
 D) EXTERIOR DOORS GLAZED, SLIDERS
 E) EXTERIOR LOUVERED DOORS
 F) DOORS STEEL
 G)EXTERIOR OVERHEAD DOORS
 H)HANDRAILS
 I) STORM SHUTTERS SHEET A-903 SEE NOTES ABOUT
 REQUIRED STORM SHUTTERS!!!
 J) TRUSS ANCHORS
 K) ROOFING ASSEMBLIES
 L) PRE-MANUFACTURED A/C STANDS
 M) STORM SHUTTERS
 N) EFIS SYSTEMS, NOTE FROM A-905
  
 47) NOTE)) AN INTERPRETATION FROM THE BUILDING OFFICIAL
 ON STORM SHUTTERS THAT ARE USED ON LARGE PROJECTS:
 QUESTION# 13) RECOGNIZING SUCH CONCERNS AS ABSENTEE
 OWNERS, OR CASES WHERE LONGER TIME AND EFFORT IS
 NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR
 IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR
 SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004 EDITION,
 PROVIDES THE ABILITY FOR THE BUILDING OFFICIAL TO
 IMPLEMENT REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF EXISTING BUILDINGS.
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE SAME PROPERTY,
 PRE-STORM PREPARATION PLANS MUST BE SUBMITTED BY THE
 PROPERTY OWNERS OR MANAGING AGENTS FOR REVIEW BY THE
 CONSTRUCTION SERVICES DEPARTMENT. ANY SUCH PLAN SHALL
 INCLUDE, AT A MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE SHUTTERS (SAID
 PARTIES MUST BE LOCATED WITHIN PALM BEACH COUNTY),
 TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND TOTAL TIME
 REQUIRED TO SECURE ALL OPENINGS. PROTECTION OF OPENINGS
 SHALL BE ACCOMPLISHED WITHIN TWELVE (12) HOURS OR LESS
 OF THE OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER
 SERVICE OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE BUILDING OFFICIAL
 TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN QUALITY, STRENGTH,
 EFFECTIVENESS, FIRE RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE PROVISION,
 ACCEPTANCE OF ALTERNATE MATERIALSAND METHODS MAY BE
 APPROVED ON A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO SUBSTANTIATE ANY CLAIM
 MADE REGARDING THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS APPROPRIATE
 FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES? NO, EXCEPT ON THE GROUND
 FLOOR. ON COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL, IMPACT RESISTANT
 GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE INSTALLED.
 PERMANENTLY AFFIXED PROTECTIVE DEVICES SHALL REQUIRE
 THE WRITTEN APPROVAL OF THE BUILDING OFFICIAL.
  
 48) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 48A) FL BLD CODE 2001 SECTION 1609.1.4, 1714.5
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC.,
 SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO
 FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.
  
 48B) PROVIDE ROOF PRESSURE ZONES FOR ZONES 4&5. SEE
 1609.1.1/ ASCE 7-02.
  
  
 49) SHEET A-650 SHOWS VARIOUS SUN SHADES, DETAIL 1& 5
 INDICATE THE USE OF CLOTH SUN SHADES, NOTE HOW YOU WILL
 MEET THE WIND REQUIREMENTS OF 3105.4.2.1 OR 3105.4.2.2.
 SHOP DRAWINGS MAY BE SUBMITTED AFTER PERMIT.
  
 50) PLEASE COMPLY WITH FIRE TREATED FABRIC FOR AWNINGS.
 3105.3.1FABRIC USED FOR AWNINGS OR FABRIC-COVERED
 FRAMES SHALL BE FLAME RESISTANT IN ACCORDANCE WITH NFPA
 701.
  
 51) SHEET A652 DETAIL# 06 PROVIDEPRODUCT TESTING
 REPORT FOR EXHAUST FAN AND PRE-MANUFACTURED CURB,
 PROVIDE THE +/- PRESSURES THIS ASSEMBLY HAS BEEN TESTED
 FOR.
 1609.6. 1.2 COMPONENTS & CLADDING.
  
 52) SHEET A-652 DETAILS 24 & 26 BOTH SHOW RAIN WATER
 LITER DETAILS, THESE ARE GOING TO BE PLACED IN 1 HR
 FIRE RATED CORRIDORS, BUT THERE IS ONLY 1 LAYER OF
 DRYWALL AROUND THE PIPE, PLEASE PROVIDE UL RATING OR
 SOME OTHER APPROVED AGENCY THAT THIS IS A 1 HR FIRE
 RATED SYSTEM. TABLE 1016.1.
  
 53)SHEETS A801-A801E ALL INDICATE A DOOR D-11 BUT NOT
 FOUND ON THE DOOR SCHEDULE
 A-903. PLEASE PROVIDE ADDITIONAL INFORMATION, 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 54) SHEET A801 TH1A UNITS (2STORY CONDOS) THE GROUND
 FLOOR OF THESE UNITS STILL HAVE TO COMPLY WITH FAIR
 HOUSING, DOOR D-1 IS A 2?-6? DOOR AND BY DEFINITION A
 USEABLE DOOR A NOMINAL 32? CLEAR.
  
 55) SHEET A801 TH1A UNITS THERE ARE DOORS ON THE FIRST
 FLOOR AND ALSO THE 2ND FLOOR LOFT PORTION OF THE UNIT
 THAT BOTH HAVE EXTERIOR DOORS LEADING TO BALCONIES AND
 DO NOT HAVE A DOOR IDENTIFICATION MARKER. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 56) SHEET A801B-E TH1B-E UNITS(2STORY CONDOS) THE
 GROUND FLOOR OF THESE UNITS STILL HAVE TO COMPLY WITH
 FAIR HOUSING, DOOR D-1 IS A 2?-6? DOOR AND BY
 DEFINITION A USEABLE DOOR A NOMINAL 32? CLEAR.
  
 57) SHEET A801B-E TH1B-E UNITS THERE ARE DOORS ON THE
 FIRST FLOOR AND ALSO THE 2ND FLOOR LOFT PORTION OF THE
 UNIT THAT BOTH HAVE EXTERIOR DOORS LEADING TO BALCONIES
 AND DO NOT HAVE A DOOR IDENTIFICATION MARKER. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 58) SHEET A802- A802C (2STORY CONDOS) THE GROUND FLOOR
 OF THESE UNITS STILL HAVE TO COMPLY WITH FAIR HOUSING,
 DOOR D-1 IS A 2?-6? DOOR AND BY DEFINITION A USEABLE
 DOOR A NOMINAL 32? CLEAR.
  
 59) SHEET A802-A802C THE DOORS ON THE FIRST FLOOR AND
 ALSO THE 2ND FLOOR LOFT PORTION OF THE UNIT THAT BOTH
 HAVE EXTERIOR DOORS LEADING TO BALCONIES AND DO NOT
 HAVE A DOOR IDENTIFICATION MARKER. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 60) SHEET A-803 FRONT ENTRY DOOR, AGAIN THIS DOOR IS
 NOT LISTED ON THE DOOR SCHEDULE, THIS FRONT ENTRY DOOR
 IS IN A FIRE RATED WALL BEING BETWEEN A S2 OCCUPANCY
 AND R2 OCCUPANCY, THIS DOOR WILL NEED A CLOSER AND
 LATCH AS WELL AS FIRE RATING, PLEASE SEE ANSI A117.1-
 98 DOOR CLEAR WIDTH 404.2.3 AND MINIMUM CLEARANCES SEE
 FIGURE 404.2.4.1(B)REQUIRES 12 INCHES WHERE BOTH A
 DOOR CLOSER AND LATCH ARE PROVIDED. ALSO FBC TABLE
 715.3, COMMON TO ALL UNITS.
  
 61) SHEET A-803A- A-803B BOTH ARE MISSING INFORMATION
 ON THE FRONT DOOR AS WELL AS THE SECONDARY DOOR LEADING
 TO THE BALCONY, PLEASE SEE COMMENT ABOVE NUMBER 60 ALSO
 RELATES, 106.1.2 ADDITIONAL INFORMATION REQUIRED. ALSO
 SEE TABLE 715.3.
  
 62)SHEET A-804A- A-804HTHE FRONT DOOR AND BALCONY
 DOORS DO NOT HAVE IDENTIFICATION TAGS INDICATING THEIR
 SIZE AND OR FIRE RATING. FAIR HOUSING ACCESSIBLE DOORS
 AND FBC TABLE 715.3.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 63) SHEET A-804D AT BEDROOM NUMBER 2 ON THE BALCONY
 THERE APPEARS TO BE A LINE INDICATING A CHANGE IN
 GRADE, 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 64) SHEET A-801 SERIES IS MISSING THE DIMENSION BETWEEN
 DOORS IN THE VESTIBULE, FAIR HOSING
 ANSI 4.13 MINIMUM SPACE BETWEEN DOORS IN SERIES 4?-0?
 PLUS DOOR WIDTH IF SWINGS IN.
 PROVIDE DIMENSION.
  
 65) SHEET A-805, A-806, A-807 & A-807A ALL NEED TO
 PROVIDE THE CLEAR OPENING WIDTH FOR THE 6?-0? SLIDING
 GLASS DOORS FOR SECONDARY DOORS MINIMUM OF 32? CLEAR,
 SEE FAIR HOUSING
 404.2.3 (B).
  
 66) SHEET A-903 DOOR NOTES, HURRICANE MISSILE IMPACT
 NOTES, FRENCH DOORS TO COMPLY WITH
 COMMENT 47 & 48A.
  
 67) SHEET A-903 BURGLAR INTRUSION NOTES (3), INDICATES
 THE USE OF PINS FOR EXTRA SECURITY DEVICES, SEE FAIR
 HOUSING SECONDARY EXTERIOR DOORS SLIDING GLASS DOORS
 PAGE 3.10-3.12 CLEAR WIDTH AND HARDWARE REQUIREMENTS
 AND RECOMMENDATIONS.
  
 68)SHEET A-903 BURGLAR INTRUSION NOTE NUMBER (7),
 INACTIVE LEAF OF A PAIR OF DOORS SHALL BE PROVIDED WITH
 MULTIPLE POINT LOCKS AS REQUIRED BY THE PRODUCT
 APPROVALS. AGAIN THESE LOCKS HAVE TO BE ABLE TO OPERATE
 FROM A WHEELCHAIR.ANSI A117.1-98, 404.2.7.
  
 69) SHEET S4.5 DETAIL SECTION 5-4.5 INDICATES USE OF
 5/8? EXTERIOR GRADE PLYWOOD PLEASE SEE
 TABLE 601 FOOTNOTE ( C ) (2) WHEN FIRE TREATED PLYWOOD
 CAN AND CAN NOT BE USED. THIS BUILDING IS CLASSIFIED AS
 A TYPE IB BUILDING.
  
 70) ?S? SHEETS THE SEAL IS NOT EMBOSSED TO WHERE IT IS
 LEGIBLE AND OR SOME SHEETS ARE NOT SEALED AT ALL. THE
 EMBOSSED SEAL SHALL BE LEGIBLE 61G15-23.002.
  
 71) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-14 Cont ID  
Sent By dpalmer Date 2007-09-14 Time 20:07 Rev Time 0.00
Received By dpalmer Date 2007-09-13 Time 14:41 Sent To  
Notes
2007-09-14 20:07:462007-09-14 20:07:46
  
 ** DENIED **
  
 LAKES AT PALM BEACH FORMERLY MIZNER LAKES. BUILDING
 #4.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-20
 ** SOME OF THE ABOVE ARE REFERENCED ON PLANS HOWEVER
 SOME REFERENCED ARE NO LONGER IN EFFECT.
 PLEASE SEE THAT ALL SHEETS CONTAIN THE RELEVANT CODES
 FOR DESIGN.
 FBC 106.1.2, 106.1.3, 110.1.2
  
 2) NOTE: PLEASE SEE THE DATE ON THE PLANS IN WHICH THE
 ENGINEERED SIGNED PLANS IS DATED BEFORE THEY WERE
 ISSUED. HOW IS THIS POSSIBLE?
 PLEASE SEE FLORIDA STATUTES471.025 AS THIS REQUIRES
 THE DESIGN PROFESSIONAL TO SIGN AND DATE EACH SHEET
 WHEN SIGNING, DATING AND SEALING SAID PLANS.
  
 3) NOTE: PLEASE SEE THE LANDSCAPE PLANS IN WHICH THE
 TITLE BLOCKS ARE MISSING REQUIRED LICENSE INFORMATION
 PER FLORIDA ADMINISTRATIVE CODE 61G1-16.004, AND FS
 481.219.
 ** PLEASE VERIFY WITH THE STATE BOARD OF LANDSCAPE
 ARCHITECTS WITH ANY CHANGES IN THE SEAL REQUIREMENTS TO
 THE NEW 2INCH SEAL.
 61G1-16.002, 61G10-11.010
 ** THIS IS REQUIRED FOR ALL LANDSCAPE SHEETS AND PLANS
 WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES/REVIEWER(S).
  
 4) NOTE: PLEASE BE SURE THE LIGHTING SHOWN ON THE
 LANDSCAPE SHEETS CORRELATE WITH THE LIGHTING ON THE
 ELECTRICAL PLANS.
 FBC 106.1.2 FOR COORDINATION.
  
 5) NOTE: PLEASE SEE THE ADDRESS ON THE PERMIT
 APPLICATION INDICATES 715 HANK AARON DR, HOWEVER THE
 ASSIGNED ADDRESS FOR THIS BUILDING #4 IS 1596 VANDAN
 DR.
 **PLEASE KNOW THERE ARE STILL SEVERAL SHEETS IN PLANS
 SETS WHICH REFLECT THE PREVIOUS PROJECT NAME OF MIZNER
 LAKES AND SHEETS WHICH NOW REFLECT LAKES AT PALM
 BEACH.
 ** PLEASE BE SURE TO COORDINATE SHEETS. (NOT A KAMM
 CONSULTING COMMENT)
  
 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED ARE IN NEED OF CORRECTIONS.
 PLEASE SEE THE ADDRESS AND BUILDING INFORMATION NEEDS
 TO MATCH WITH PLANS AND PROJECT. COVER SHEET CALLS FOR
 AN ADDRESS LOCATED IN MIAMI, CALLS FOR MIZNER LAKES,
 ETC.
 PLEASE SEE THE INFORMATION ON LIGHTING NEEDS TO
 CORRELATE WITH PLANS. PLEASE SEE THE SUMMARY SHEETS AND
 THE INPUT DATA REPORT DOES NOT CONTAIN ANY *EXTERIOR
 LIGHTING* ENTERED. HOW IS THIS POSSIBLE WHEN THE PLANS
 CONTAIN DOZENS OF EXTERIOR LIGHT FIXTURES?
 PLEASE SEE LANDSCAPE PLANS AND ELECTRICAL PLANS WHICH
 INDICATE LANDSCAPE LIGHTING FIXTURES.
 PLEASE ALSO SEE THE INFORMATION ON THE INPUT DATA
 REPORT FOR THE INTERIOR LIGHTING WHICH ALSO DOES NOT
 MATCH WITH PLANS. PLEASE SEE THERE ARE ONLY 1 OF EACH
 TYPE OF FIXTURE ENTERED WHICH IS NOT POSSIBLE. PLEASE
 COORDINATE ALL INFORMATION ON CALCULATIONS WITH PLANS.
 PLEASE SEE 13-415.1.A, 13-415.2, 13-415.2.ABC.1.3 ETC
  
 7) NOTE: PLEASE SEE THERE ARE A FEW AREAS ON PLANS
 WHICH SOME DEVICES FOR CONTROLS ON LIGHTING AS REQUIRED
 PER 13-415.1.ABC.1.1, .1.2 NEEDS ADDRESSING. PLEASE SEE
 METHODS OF CONTROLS FOR EXTERIOR LIGHTING. PLEASE SEE
 SOME ROOMS FOR EXAMPLE, CUSTODIAN CLOSET, WOMEN RR AND
 MEN RR ON E2.3.2 NEAR THE POOL DECK ACCESS DOORS.
 PLEASE KNOW AREA FOR RESTROOMS NEEDS TO PROVIDE DEVICES
 WHICH PROVIDE COVERAGE IN ALL AREAS FOR LIFE SAFETY AND
 EGRESS SAFETY.
  
 8) NOTE: PLEASE SEE SHEET A102, 101 ETC WHICH REFERENCE
 TO SEE A307 FOR DETAILS FOR FIRE PUMP ROOM HOWEVER THE
 307 SHEET DOES NOT PROVIDE ANY INFORMATION.
 PLEASE SEE THAT NO INFORMATION FOR THIS PUMP HOUSE
 ELECTRICAL FOR LIGHTING, SERVICE RECEPTACLES ETC COULD
 BE FOUND ON PLANS.
 PLEASE KNOW AS THIS IS A SEPARATE BUILDING PLEASE SEE
 225.31-225.39, 250.32.
 PLEASE SEE BATTERY BACK UP LIGHTING FIXTURES WILL BE
 REQUIRED IN THIS ROOM IN ADDITION TO NORMAL LIGHTING.
 PLEASE SEE 700.16, 700.12F ETC
 408.4, 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE PROVIDE THE INFORMATION ON PLANS FOR
 THE *EQUAL-POTENTIAL POOL GROUNDING GRID* AS REQUIRED
 PER 680.26.
 PLEASE KNOW EVEN THOUGH THE POOL IT SELF WILL BE UNDER
 SEPARATE PERMIT THE MAIN STRUCTURAL CONTENTS OF THE
 POOL WILL BE PART OF THE BUILDING AND WILL REQUIRE THIS
 GROUNDING.
  
 10) NOTE: PLEASE KNOW THAT THE PLANS WILL BE REQUIRED
 TO STATE *NO DUSK TO DAWN SWIMMING*. PLEASE KNOW IF ANY
 AFTER DISK SWIMMING WILL TAKE PLACE THE REQUIRED
 MINIMUM SIGNED, DATED AND SEALED PHOTO-METRICS WILL BE
 REQUIRED TO BE SUBMITTED TO PALM BEACH COUNTY HEALTH
 DEPARTMENT FOR REVIEW AND STAMPING. THESE WOULD BE
 REQUIRED TO BE SUBMITTED WITH BOTH THE BASE BUILDING
 PLANS AND ALONG WITH THE POOL PERMIT.
 AS MUCH OF THE ELECTRICAL CONDUITS, LIGHTING CONDUITS
 AND GROUNDING OF SYSTEMS IS PART OF THE BASE BUILDING;
 THESE PLANS WILL BE REQUIRED TO CONTAIN MUCH OF THIS
 INFORMATION.
 FBC 106.1.2, NEC 680
  
 11) NOTE: PLEASE SEE SHEET A-352 AND BE SURE THIS AND
 ANY OTHER ELECTRICAL REFLECTED ON OTHER SHEETS
 COORDINATE WITH THE ELECTRICAL PLANS.
 FBC 106.3.5.1.2
  
 12) NOTE: PLEASE SEE THE FS SHEETS WHICH REFLECT THE
 INCORRECT NFPA-20.
 THE STATE IS CURRENTLY UNDER THE 2003 NFPA-20
  
 13) NOTE: PLEASE PROVIDE ALL INFORMATION ON THE FIRE
 PUMPS AND MINIMUM FUEL BEING PROVIDED PER NFPA-20
 11.4.3.
 ** PLEASE SEE ALL OF CHAPTER 11.
  
 14) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS
 FOR FIRE PUMP, FIRE PUMP CONTROLLER AND FUEL
 TANKS.110.3, 90.7, NFPA-20 CHAPTER 10, 11 ETC. PLEASE
 KNOW MUCH OF THIS WILL ALSO BE REVIEWED BY THE
 MECHANICAL, BUILDING AND FIRE MARSHAL.
 **PLEASE BE SURE TO SEE ANY COMMENTS FROM FIRE MARSHAL
 WITH RESPECT TO BOTH BUILDINGS BEING FED FROM ONE FIRE
 PUMP AND LOCATION.
  
 15) NOTE: PLEASE SEE PLANS ARE MISSING COMPLETED
 PHOTO-METRICS FOR ALL EGRESS PATHS UNDER NORMAL AND
 EMERGENCY. PLEASE KNOW AS THE GARAGE INDICATES THE
 LEVELS UNDER EMERGENCY THIS DOES NOT NEED TO SHOW THE
 NORMAL.
 PLEASE SEE STAIRS WHICH DO NOT INDICATE ANY LEVELS. FAC
 61G15-33.004
 NFPA-101 7.8.1.3, 7.9.2.2
  
 16) NOTE: PLEASE CLARIFY HOW PHOTO-METRIC LEVELS WERE
 SUBMITTED FOR POOL DECK AREA UNDER EMERGENCY WHEN THE
 FIXTURES ON PLANS DO NOT INDICATE BATTERY BACK UP?
 COULD NOT LOCATE THESE? PLEASE SEE E2.3.1
 LS 101 7.8 AND 7.9
  
 17) NOTE: PLEASE SEE THERE ARE FIXTURE DESIGNATIONS ON
 PLANS WHICH DO NOT CORRELATE WITH THE LIGHTING FIXTURE
 LEGEND. PLEASE SEE GARAGE FIXTURES FOR EXAMPLE ON
 PHOTO-METRICS SEEM TO INDICATE A *G* NEXT TO THE
 FIXTURES, BUT THE LEGEND INDICATES WALL SCONCE
 FIXTURES? THIS IS THE SAME FOR WHAT APPEARS TO BE EXIT
 LIGHTS IN STAIRS. PLEASE SEE E2.1.1. THESE SEEM TO BE
 SOME KIND OF MISPRINT.
 PLEASE SEE SAME SHEET E2.1.1 WHICH INDICATES A NOTE #8
 IN THE UPPER LEFT HAND CORNER STAIRS , YET THE NOT
 LEGEND DOES NOT CONTAIN AND NOTE #8.
 PLEASE BE SURE TO SEE THE LIGHTING PLANS AND COORDINATE
 THE FIXTURES ON LIGHTING PLANS WITH THAT OF THE
 FIXTURES ON THE PHOTO-METRIC SHEETS SUBMITTED. PLEASE
 COORDINATE. FBC106.1.2
  
 18) NOTE: PLEASE SEE SOME STAIRS ON LOWER LEVEL/FIRST
 FLOOR DO NOT INDICATE THE FIXTURE IDENTIFICATION AND
 SOME CIRCUITS. E2.1.1
  
 19) NOTE: PLEASE SEE PHOTO-METRICS FOR THIRD FLOOR EAST
 WHICH DOES NOT INDICATE TABLES FOR AVERAGE LEVELS. FBC
 106.3.5.1.2, 106.1.2
 SAME CODE SECTIONS AS NOTED ABOVE FOR LS.
  
 20) NOTE: PLEASE SEE STAIR AREAS ON E1.3.1 WHICH
 REQUIRES 10FT/CANDLES UNDER NORMAL AND 1FT CANDLE UNDER
 EMERGENCY.
 PLEASE PROVIDE LEVELS.
 FAC 61G15-33.004, LS 101 7.8.1.3, 7.9.2.2
  
 21) NOTE: PLEASE SEE NOTE #5 ON SHEET E2.1.1 WHICH
 CONTAINS A NOTE FOR RATING THE J-BOX AT 500LBS? PLEASE
 CLARIFY THIS? WHAT TYPE OF FIXTURE/EQUIPMENT WILL BE
 PLACED ON THIS?
 FBC 106.1.2
  
 22) NOTE: PLEASE PROVIDE INFORMATION FOR FAIL SAFE
 OPERATION OF DEVICES FOR ACCESS GATES, DOORS, AND
 PERSONNEL GATES.
 PLEASE SEE LS 101 7.2.1.5, 7.2.1.5.4, 7.2.1.6.2 ETC **
 PLEASE SEE FIRE MARSHAL REVIEW COMMENTS.
  
 23) NOTE: PLEASE CLARIFY MINIMUM LIGHTING LEVELS IN
 ELEVATOR PITS PER 620.24.
 PLEASE SEE COMMENTARY PROVIDED IN THE NEC FOR STANDARDS
 FROM THE ELEVATOR SAFETY CODE.
 PLEASE BE SURE TO CONTACT OR SEE ANY STATE ELEVATOR
 CODES WHICH ACTUALLY MAY BE MORE RESTRICTIVE FOR
 LIGHTING LEVELS.
 ? ASME A17.1-2004, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.*
  
 24) NOTE: PLEASE PROVIDE INFORMATION FOR EMERGENCY SHUT
 OFF OF SPA PER 680.41.
 THE DEVICE AS SHOWN DOES NOT PROVIDE LOCATION AND EM
 SHUT OFF INFORMATION.
  
 25) NOTE: PLEASE KNOW AS THE TIMERS AS SHOWN IN MOST
 ELECTRICAL ROOMS DO NOT MEET 110.26D, PLEASE PROVIDE A
 DIFFERENT WAY FOR CONTROLLING LIGHTING.
 PLEASE SEE13-415.1.ABC.1.1 EXCEPT *C*.
  
 26) NOTE: PLEASE CLARIFY WHERE THE LIGHTING IS LOCATED
 IN THE ELEVATOR EQUIPMENT ROOM ABOVE THE ELEVATOR
 MOTORS. PLEASE KNOW AS PER INFORMATION FROM THE STATE
 ELEVATOR CODE, THIS AREA WILL REQUIRE ADDITIONAL
 LIGHTING. THIS IS NOT IN THE NEC OR LS CODE, HOWEVER IT
 MAY BE OF INTEREST TO PLACE ON PLANS AT THIS TIME.
 PLEASE VERIFY WITH THE STATE.
 FBC 106.3.5.1.2, 106.1.2
 NO CHANGES ARE REQUIRED TO PLANS AND THIS NOTE IS FOR
 INFORMATIONAL PURPOSE.
  
 27) NOTE: PLEASE PROVIDE DISCONNECT DETAILS FOR ROOF
 TOP EQUIPMENT FOR SELECTIVE MECHANICAL AND OTHER
 EQUIPMENT.
 PLEASE SEE MECHANICAL REVIEW COMMENTS FOR POSSIBLE
 LOCATIONS AND INFORMATION NEEDED.
 440.11, 422.30 ETC THIS CAN BE A TYPICAL DETAIL FOR ANY
 EQUIPMENT WHICH IS MULTIPLE OF THE SAME USE ETC. FBC
 106.1.2
  
 28) NOTE: PLEASE SEE NEC 210.12 AS ARC FAULT PROTECTION
 IS REQUIRED FOR ALL OUTLETS IN SLEEPING ROOMS. PLEASE
 SEE THE SMOKE ALARMS IN BEDROOMS WHICH INDICATE AFCI
 PROTECTION ARE CIRCUITED TO A CIRCUIT IN THE PANEL
 SCHEDULE WHICH DOES NOT CONTAIN AFCI BREAKER. (KITCHEN)
 ETC.
 THIS IS TYPICAL OF ALL UNITS. C1.11, C2.11, C3.11 ETC.
  
 29) NOTE: PLEASE SEE E4.1.1 UNIT C-3 FOR CIRCUIT #26
 WHICH ON PANEL SCHEDULE MENTIONS HALF BATH, BUT ON
 PLANS ALSO FEED MASTER BEDROOM LIGHTING CIRCUIT. PLEASE
 SEE NO AFCI PROTECTION.
 408.4, 210.12
  
 30) NOTE: PLEASE SEE UNIT C-S E4.1.1 WHICH SHOWS NOOK
 RECEPTACLE IN DOOR WAY.
  
 31) NOTE: PLEASE SEE 210.4B FOR BRANCH CIRCUITS FEEDING
 SAME DEVICE/YOKE WITH MORE THAN ONE CIRCUIT.(REQUIRES
 2-POLE BREAKER.
 THIS IS TYPICAL OF ALL UNITS AND PANEL SCHEDULES.
  
 32) NOTE: PLEASE SEE UNIT C-1 MASTER BEDROOM DOORWAY TO
 BATHROOM WHICH CONTAINS THE RECEPTACLE WHICH SHOULD BE
 ON WALL IN DOOR WAY.
 PLEASE RELOCATE AND ADJUST.
  
 33) NOTE: PLEASE SEE C-5 4.1.1 MISSING DINING ROOM WALL
 RECEPTACLE PER 210.52
 PLEASE BE SURE TO CIRCUIT PER 210.52B1, 210.11C1,
 220.53
  
 34) NOTE: PLEASE SEE C-5, 4.1.2 BEDROOM #1 WHICH IS
 MISSING RECEPTACLE PER 2FT OF WALL PER 210.52
  
 35) NOTE: PLEASE SEE TH2 FOR MISSING RECEPTACLE FOR 2FT
 OR MORE OF WALL IN KITCHEN. THIS IS THE SAME FOR TH1
 ALSO.
  
 36) NOTE: PLEASE SEE DINING AREA IN TH3 FOR CIRCUITING
 OF RECEPTACLE WHICH IS SHOWN ON LIVING ROOM CIRCUIT.
 210.52B1
  
 37) NOTE: PLEASE SEE TH2 FOR MISSING DINING AREA PER
 210.52B1, 210.11C1, 220.53.
  
 38) NOTE: PLEASE SEE TH3 FOR MISSING RECEPTACLE
 REQUIRED WITHIN 6FT OF OPENING ON WALL SPACE. (DEN).
  
 39) NOTE: PLEASE SEE NFPA-72FOR DEFINITIONS OF SMOKE
 DETECTION DEVICES.
 PLANS INDICATE ALL DEVICES IN UNITS AS *SMOKE
 DETECTORS* AND NOT * SMOKE ALARMS*.
 PLEASE KNOW IF THESE ARE DEVICES WHICH DETECT AND SOUND
 AN ALARM.
 PLEASE ADJUST PLANS.
 PLEASE ALSO BE SURE ALL SMOKE ALARMS ARE MOUNTED ON
 WALL LEADING TO THE FLOOR ABOVE. A NOTE IS LOCATED FOR
 THIS HOWEVER THE NOTE COULD ALSO BE READ TO MOUNT THIS
 UNIT ON WALL ON THE UPPER LEVEL.
 PLEASE ADJUST NOTE.
 NFPA-7211.5.1.1, 11.8.3
  
 40) NOTE: PLEASE SUBMIT WORST CASE VOLTAGE DROP
 CALCULATIONS FOR FEEDER(S) AND BRANCH CIRCUIT(S) PER
 13-413.1ABC.1
  
 41) NOTE: PLEASE SEE THE PANEL SCHEDULES FOR UNITS
 WHICH CONTAINS (??) ON SCHEDULE BEFORE LINE FOR
 *LARGEST A/C LOAD*.
 FBC 106.1.2
  
 42) NOTE: PLEASE BE SURE THE ARCHITECT AND STRUCTURAL
 ENGINEER OBTAINS THE BUS-WAY/DUCT CURBING DETAIL AND
 PLACES ON THEIR RESPECTIVE SHEETS.
 THIS AHJ HAS HAD SEVERAL NOT INSTALLED AND CONSTRUCTED
 CORRECTLY AS THE DETAIL WAS NOT ON THE A AND S SHEETS
 FOR THE BUILDING CONTRACTOR.
 THIS IS NOT AN ITEM TO CONSTRUCT AFTER INSTALLATION OF
 BUS-WAY.
 106.1.2
  
 43) NOTE: PLEASE SEE MSB-9 WHICH INDICATES A 200AMP
 BREAKER FEEDING PANEL L1HC WHICH IS ONLY A 125AMP
 PANEL.
 PLEASE ADJUST. 240, 408 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 44) NOTE: PLEASE CLARIFY WHERE ALL CONTINUOUS LOADS ARE
 SHOWN AT 125%.
 215.3, 230.42 ETC
 FBC 106.1.2
  
 45) NOTE: PLEASE PROVIDE INFORMATION ON MAINS FOR MSB,
 SBA AND MC1A. PLEASE VERIFY MANUAL MEANS OF DISCONNECT
 RATED FOR THE LOAD SERVED PER 230.76, 230.79
  
 46) NOTE: PLEASE SEE RISER INDICATING ALL UNITS ONLY
 SEEMS TO INDICATE 114 UNITS YET PLANS INCLUDING OTHER
 TRADES MENTIONS 120 UNITS?
 PLEASE CORRELATE AND ADJUST ALL PLANS AS NEED.
 FBC 106.3.5.1.2
  
 47) NOTE: PLEASE SEE MC 1,3,4,5,6 AND 7 WHICH ALL
 CONTAIN A NOTE #1 IN A CIRCLE AT THE LOWER LEFT HAND
 SIDE OF SCHEDULE, HOWEVER NO NOTE #1 COULD BE LOCATED
 ON THIS SHEET.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY CERTAINLY AFFECT THE ELECTRICAL
 PLANS AND/OR DESIGN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-14 07:01:352007-09-14 07:01:35
  
 REVIEW IN PROGRESS
2007-09-13 19:35:482007-09-13 20:01:33
  
 REVIEW STOPPED, TO CONTIUE ON 9/14
2007-09-13 14:41:482007-09-13 14:41:48
  
 IN ELEC FOR REVIEW, 1-SET ONLY OF EACH ARCHITECTURAL
 AND MEP.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-09-19 Cont ID  
Sent By rchokshi Date 2007-09-19 Time 14:36 Rev Time 0.00
Received By rchokshi Date 2007-09-19 Time 14:36 Sent To  
Notes
2007-09-19 14:36:54***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 PLEASE PROVIDE LATEST REVISED DRAWINGSAS YOU
 SUBMITTED FOR SITE / STORM WATER PERMIT #07040152.
 JUST TO LET YOU KNOW A HEAD OF TIME THATWE NEED FOR
 ENG REVIEWSTORM WATER CALS, POLLUTION PREVENTION
 PLANS, CITY STANDARDS SHOWN ON CIVIL DRAWINGS ETC, ETC.
 SO, PLEASE PROVIDE SEPARATE SET OF CIVIL DRAWINGS.WE
 ARE ASKING YOU TO INCLUDE THE FOLLOWING WHEN YOU SUBMIT
 CIVIL DRAWINGS FOR ENGINEERING REVIEW, SO WE CAN
 EXPEDITE OUR ENG REVIEW PROCESS.
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON CIVIL DRAWING THE SITE PLAN SHOWING
 STREETS/ROADS AROUND THE SITE WITH NORTH ARROW.
 3.PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 5. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, PLEASE SHOW IN YOUR STORM WATER CALS
 THAT HOW DID YOU DETERMINE THE FIRST FLOOR
 ELEVATION??.
 6. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT,
 LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE
 THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED
 IN STORM WATER QUALITY CALCULATIONS.
 7.PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES,PLEASE SHOW HOW DID YOU DETERMINE
 THE LENGTH OF THE EXFILTRATION TRENCH?? PLEASE SHOW DRY
 DETENTION/WET DETENTION AREAS IN STORM WATER CALS.
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 9. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
 10. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 11. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-08 Cont ID  
Sent By mawillia Date 2007-11-08 Time 21:48 Rev Time 0.00
Received By mawillia Date 2007-11-08 Time 11:02 Sent To  
Notes
2007-11-09 02:01:35*****DENIED*****
  
 PLEASE BE ADVISED THAT THIS BUILDING AND/OR PHASE SHALL
 STAND UPON ITS OWN MERITS ( I.E. WATER SUPPLY, FIRE
 ALARM SYSTEM, FIRE SPRINKLER SYSTEM).
  
 01.FIRE HYDRANTS TO BE OPERATIONAL BEFORE, DURING,
 AND AFTER CONSTRUCTION.
  
 02.A TEMPORARY STANDPIPE IS REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 03.THE CONSTRUCTION AND PROTECTION OF OF THE
 STRUCTURE'S PARKING GARAGE AS WELL AS THE CONTROL OF
 HAZARDS SHALL COMPLY WITH NFPA 88A.
  
 04.WHAT IS THE VERTICAL CLEARANCE AT THE POINT OF
 VEHICLE ENTRY?
  
 05.BASED UPON NFPA 72 - 2002 EDITION - EXPLAIN
 CRITERIA FOR THE USE OF THE CEILING MOUNTED FIRE ALARM
 HORN/STROBE COMBO DEVICE IN THE PARKING GARAGE AS SHOWN
 ON A-251 AND A-252 SHEETS.
  
 06.WHAT IS THE EXIT AISLE CLEARANCE BETWEEN THE
 EXTERIOR REAR WALL OF THE CONDO UNITS AND THE VEHICLE
 PARKING SPACES?BE ADVISED THAT DURING ITS SWING, ANY
 DOOR IN A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN
 ONE-HALF THE WIDTH OF THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, OR PASSAGEWAY.
  
 07.ON SHEET A-251, IT APPEARS THAT THE SWING OF THE
 DOOR IS AGAINST THE PATH OF EGRESS IN STAIR #2 AND
 STAIR #4.
  
 08.PLEASE EXPLAIN EXIT LIGHTS SHOWN IN THE CONDO
 UNITS AT GRADE LEVEL.THESE LIGHTS ARE SHOWN ON SHEET
 A-251 BUT NOT SHOWN ON SHEET A-350.THE MEANS OF
 EGRESS SHALL NOT BE FROM AN AREA TO A MORE HAZARDOUS
 AREA (PARKING GARAGE).
  
 09.IN THE LIFE SAFETY SHEETS, CLARIFY THE USE OF
 SMOKE DETECTORS OR SMOKE ALARMS IN THE CONDO UNITS.BE
 ADVISED THAT SMOKE DETECTORS ARE TIED INTO THE
 BUILDING'S FIRE ALARM SYSTEM, WHEREAS SMOKE ALARMS
 ALERT THE OCCUPANTS OF THE DWELLING UNIT ONLY.
  
 10.ON SHEETS A-251 AND A-252,SOME PATHS OF EGRESS
 ARE ILLUSTRATED PASSING THRU PARKING SPACES AND OTHER
 CHANGES IN ELEVATION.
  
 11.ON SHEET A-251, THE FIRE ALARM CONTROL PANEL SHOWN
 IN THE MECHANICLA ROOM.PROVIDE CRITERIA THAT THIS
 ARRANGEMENT IS ACCEPTABLE AS PER NFPA 72 - 2002
 EDITION.
  
 12.POST/DISPLAY THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS VANDAN
 DRIVE.AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL
 BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 STROKE.
  
 13.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE ALUMINUM
 RAILINGS.
  
 14. ELEVATORS SHALL BE PROVIDED WITH FIRE FIGHTER
 SERVICE IN ACCORDANCE WITH ASMEA17.1
  
 15.WARNING SIGNS (DO NOT USE IN THE EVENT OF A FIRE)
 SHALL BE REQUIRED IN THE ELEVATOR LOBBIES.
  
 16.STAIRWELL IDENTIFICATION SIGNS REQUIRED.THE
 SIGNAGE SHALL IDENTIFY FLOOR LEVEL, STAIR NUMBER, AND
 TERMINUS TOP AND BOTTOM.
  
 17.FIRE DOORS AND FIRE WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 18.ON SHEET A-901 (IN REFERENCE TO DOOR REMARK #2),
 HOW IS RE-ENTRY ACCOMPLISHED DURING NORMAL OPERATION.
  
 19.ON SHEET FA2.1.2, NO FIRE ALARM DEVICE IS SHOWN IN
 THE TRANSFORMER ROOM.PROVIDE CRITERIA THAT THIS
 ARRANGEMENT IS ACEPTABLE AS PER NFPA 72 - 2002
 EDITION.
  
 20.THE FIRE ALARM CONTROL PANEL IS SHOWN IN THE MAIN
 ELECTRICAL ROOM ON SHEET FA2.2.2, BUT ON SHEET A-251 IT
 IS SHOWN IN THE MECHANICAL ROOM.
  
 21.ON SHEET FS0.1 IN GENERAL NOTE # 1 AND # 12,THE
 2003 EDITION OF NFPA 20 SHALL BE REFERENCED (NOT
 1999).
  
 22.ON SHEET FS0.1, CLARIFY NOTE 16 TO READ:KNOX
 LOCKING CAPS REQUIRED FOR THE FIRE DEPARTMENT
 CONNECTIONS.
  
 23.ON SHEET FS0.3 IN THE LAYOUT OF THE FIRE DEPARMENT
 CONNECTION, CLARIFY NOTE TO READ:KNOX LOCKING CAPS
 REQUIRED FOR THE FIRE DEPARTMENT CONNECTIONS.
  
 24.NO FIRE SPRINKLER COVERAGE ILLUSTRATED FOR ROOMS
 124 THRU 127, EVEN THOUGH SHEET FS2.1.2 REFERENCES
 SHEET FS2.2.1 FOR THE SPRINKLER COVERAGE IN THOSE
 ROOMS.
  
 25.SHOW THE LOCATION OF THE KNOX BOX (USUALLY AT THE
 MAIN ENTRANCE AREA).FOR APPLICATIONS, CONTACT WEST
 PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-11-29 Cont ID  
Sent By kstevens Date 2007-11-29 Time 14:49 Rev Time 0.00
Received By kstevens Date 2007-11-29 Time 14:49 Sent To  
Notes
2007-11-29 14:52:11DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT P6.1.5 A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT
 THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - INDICATE ALL CUT SECTIONS DOWNSTREAM
 OF THE REGULATOR FOR THE GAS WATER HEATERS. FINAL DROP
 LENGTH NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. - SIZE OF PIPE
 SHOWS 1-1/4" REDUCING TO 1" THEN BACK TO 1-1/4". PLEASE
 CLARIFY.--ALSO SHOW THE MATERIAL TYPE OF THE
 VENTING FROM THE REGULATORS. (MATERIAL SHALL BE NON
 COMBUSTABLE).
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - ALSO SHOW THE TOTAL
 DISTANCE FROM THE REGULATOR TO THE MOST REMOTE OUTLET
 DOWNSTREAM OF THE REGULATOR FOR THE GAS WATER HEATERS.
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - PLEASE SUBMIT AN
 APPROVED TABLE FOR 7"W.C. OR INDICATE 1/2PSI DOWNSTREAM
 OF THE REGULATOR. FBC-2004 FUEL GAS HAS NO 7" W.C.
 TABLES TO VERIFY PIPE SIZES.
  
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. SUBMIT MANUF. SPECIFICATION SHEETS FOR THE GAS
 REGULATORS. INDICATE MODEL NUMBER FOR EACH REGULATOR.
 --A UNION IS REQUIRED NEXT TO THE REGULATOR NOT AT
 THE END OF A RUN. (SEE GAS WATER HEATERS & HVAC SYSTEM
 REGULATORS).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected] .
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2007-11-08 Cont ID  
Sent By mawillia Date 2007-11-08 Time 21:50 Rev Time 0.00
Received By mawillia Date 2007-08-02 Time 14:59 Sent To  
Notes
2007-08-28 15:04:54TO "COMM" BD#34/PLANS ON RACK 4 ROLLS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-25 Cont ID  
Sent By rregueir Date 2007-09-25 Time 13:46 Rev Time 0.00
Received By rregueir Date 2007-09-21 Time 08:15 Sent To  
Notes
2007-09-21 14:37:53REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PERMIT APPLICATION INDICATES AN ADDRESS ON HANK
 AARON DRIVE, BUT PLANS SHOW AN ADDRESS ON VANDAN DRIVE.
 ENERGY CALCULATIONS SHOW AN ADDRESS OF BUILDING 4.
 PLEASE SHOW CORRECT ADDRESS ON ALL 3 LOCATIONS. FBC
 106.1.3
  
 2. M0.1: OUTSIDE AIR AND EXHAUST AIR CALCULATIONS,
 INCORRECT CODES AND REFERENCE STANDARDS ARE CITED.
 REFERENCE THE CORRECT STANDARDS WHICH ARE IN EFFECT AT
 TIME OF PERMIT APPLICATION SUCH AS FBC,M 2004 TABLE
 403.3 AND ASHRAE 62.1-2004. SEE FBC,M CH.15. ALSO, THE
 VENTILATION SYSTEMS SHALL BE DESIGNED BY EITHER FBC,M
 TABLE 403.3 OR ASHRAE 62.1-2004. SELECT AND DECLARE ONE
 METHOD OR THE OTHER TO BE USED AS ALLOWED BY FBC,M
 403.4.
  
 3. M0.2 PROVISIONS (A): IF THERE ARE CONFLICTS BETWEEN
 ANY OF THE LISTED CODES OR STANDARDS AND THE ONES
 CURRENTLY ADOPTED BY THE STATE OF FLORIDA, THE
 CURRENTLY ADOPTED CODE SHALL PREVAIL.
  
 4. M0.2 PROVISIONS (B): DUCT SMOKE DETECTORS SHALL BE
 INSTALLED IN THE SUPPLY DUCT OF ANY SYSTEM WITH A
 DESIGN CAPACITY EXCEEDING 2000 CFM, NOT JUST THOSE WITH
 COMMON PLENUMS. FBC,M 606.2.1
  
 5. M0.2 PROVISIONS (D): ALL THERMOSTATS WITHIN DWELLING
 UNITS SHALL BE AT A MAXIMUM HEIGHT OF 48" PROVIDED
 THERE IS AN UNOBSTRUCTED FORWARD APPROACH IN ACCORDANCE
 WITH FBC CH.11 PART B SECTION 5, REQUIREMENT 5.
  
 6. EXTERIOR WALL LOUVERS ARE CLASSIFIED AS PANEL WALLS
 PER FAC RULE 9B-72. AS SUCH, THEY ARE SUBJECT TO THE
 FLORIDA PRODUCT APPROVAL SYSTEM. PROVIDE PRODUCT
 APPROVALS FOR ALL WALL LOUVERS TO BE USED ON THIS
 PROJECT. FOR MORE INFORMATION ON THE FLORIDA PRODUCT
 APPROVAL SYSTEM PLEASE VISIT: WWW.FLORIDABUILDING.ORG
  
 7. M2.1.1 THROUGH M2.2.2: PROVIDE C.O. DETECTION SYSTEM
 SUBMITTAL WITH INSTALLATION INSTRUCTIONS TO FACILITATE
 A THOROUGH REVIEW OF THE GARAGE VENTILATION SYSTEM. FBC
 106.1.2 AND FBC,M 304.1
  
 8. M2.1.1 THROUGH M2.2.2: SUPPLY FANS COULD NOT BE
 LOCATED ANYWHERE IN THE GARAGE OR ON EQUIPMENT
 SCHEDULE. SUPPLY FANS ARE INDICATED IN GARAGE
 VENTILATION SEQUENCE ON PG M0.1. PLEASE CONFIRM
 SEQUENCE NEEDED TO PROVIDE MINIMUM VENTILATION RATES.
 SEE FBC,M 403.1 AND SEC.404.
  
 9. M2.2.1 AND M2.2.2: IF DRYER EXHAUST RISERS ARE OPEN
 AT THE BOTTOM WITH A GRILL, AS INDICATED ON PG M5.1,
 THE OPENINGS SHALL BE PROTECTED WITH FIRE AND SMOKE
 DAMPERS IN ACCORDANCE WITH FBC,M 607.5.5.1.
  
 10. M2.2.1 AND M2.2.2: DRYER EXHAUST RISER DUCTS WHICH
 ARE OPEN AT THE BOTTOM ARE FUNCTIONING IN ONE OF THE
 TWO FOLLOWING PROHIBITED CONDITIONS:
 A) GARAGE EXHAUST; IN THIS CASE FBC,M 504.1 REQUIRES
 DRYER EXHAUST SYSTEMS TO BE INDEPENDENT OF ALL OTHER
 SYSTEMS.
 B) MAKE-UP AIR FOR DRYER FANS; IN THIS CASE FBC,M
 401.5.1 REQUIRES INTAKE OPENINGS AT LEAST 10' FROM
 ALLEYS, STREETS OR PARKING LOTS. ALSO, MAKE-UP OR
 TRANSFER AIR CAN NOT BE DRAWN FROM DISSIMILAR
 OCCUPANCIES PER FBC,M 403.2.1(1).
  
 11. M2.2.2: MAINTENANCE OFFICE 219, THERE ARE NO
 PROVISIONS FOR AIR CONDITIONING OR VENTILATION OF THI
 SPACE SHOWN ON PLANS. PLEASE SHOW HOW VENTILATION IS TO
 BE PROVIDED IN ACCORDANCE WITH FBC,M TABLE 403.3 AS
 WELL AS THE SIZE OF EF-1 EXHAUST DUCT. ALSO, CONNECTING
 OFFICES AND SIMILAR USES THAT ARE ACCESSORY TO THE
 GARAGE SHALL BE MAINTAINED AT A POSITIVE PRESSURE PER
 FBC,M 404.3. SHOW ENOUGH OUTDOOR AIR TO PROVIDE THE
 REQUIRED VENTILATION FOR THE OCCUPANCY, MAKE-UP AIR FOR
 THE BATH FAN AND CREATE A POSITIVE PRESSURE IN THE
 SPACE.
  
 12. M2.3.1 THROUGH M2.6.2: ALL RTU RISER DUCT
 PENETRATIONS OF SHAFT ENCLOSURES SHALL BE PROTECTED BY
 FIRE AND SMOKE DAMPERS PER FBC,M 607.5.5.1. SHOW HOW
 SMOKE DAMPERS ARE TO BE ACTUATED IN ACCORDANCE WITH
 FBC,M 607.3.2.1.
  
 13. M2.3.1 THROUGH M2.6.2: ALL DUCT PENETRATIONS OF
 CORRIDOR WALLS BY RTU DUCTS SHALL BE PROTECTED BY FIRE
 AND SMOKE DAMPERS PER FBC,M 607.5 AND 607.5.4. SHOW HOW
 SMOKE DAMPERS ARE TO BE ACTUATED IN ACCORDANCE WITH
 FBC,M 607.5.4.1.
  
 14. M2.3.1 AND ALL FLOORS: RISERS PAU-1 AND PAU-2 AS
 SHOWN ON FLOOR PLAN DOES NOT CORRESPOND WITH ANY RISERS
 ON THE RISER DETAILS ON PG M5.1. IS THIS SUPPOSED TO BE
 RISERS RTU-1 AND RTU-2? PLEASE COORDINATE FLOOR PLANS
 AND RISER PLANS.
  
 15. M2.3.1 THROUGH M2.6.2: RTU-1 CALLS FOR 8630 CFM ON
 FLOOR PLAN. RTU-1 ON EQUIPMENT SCHEDULE (M6.1) CALLS
 FOR 8500 CFM. PLEASE SHOW CORRELATION BETWEEN FLOOR
 PLAN AND SCHEDULE. FBC 106.1.1.
  
 16. M2.3.2: SUPPLY DROPS IN CORRIDOR ARE MISSING SIZE
 AND CFM DESIGNATIONS. PLEASE CORRECT AND RESUBMIT. FBC
 106.3.5.1.4.THE CFM TOTALS FOR RTU-2 COULD NOT BE
 VERIFIED DUE TO MISSING INFORMATION. PLEASE VERIFY CFM
 ON FLOOR PLAN MATCHES THAT ON EQUIPMENT SCHEDULE ONCE
 MISSING INFORMATION IS PROVIDED.
  
 17. M2.3.2: RESIDENT STORAGE A/C CLOSET (313A), WHAT IS
 THE SOURCE OF R/A FOR HP-7? ROOM 313A COULD NOT BE
 FOUND ON DOOR SCHEDULE TO CHECK FOR GRILL OR LOUVERED
 DOOR. NOTE: 313A IS A PLENUM AND ALL MATERIALS USED
 SHALL BE APPROPRIATE FOR THAT APPLICATION. SEE FBC,M
 602.2.1 AND FBC,M 603.8-603.9. DOOR SHALL BE OF
 NON-COMBUSTIBLE MATERIALS OR MEET THE 25/50 RATING AS
 REQUIRED BY THIS CODE. THIS APPLIES TO ALL DOORS USED
 IN PLENUM CLOSETS IN ALL AREAS.
  
 18. M2.3.2: RESIDENT STORAGE A/C CLOSET (313A), HP-7
 DOES NOT APPEAR ON EQUIPMENT SCHEDULE. IS THIS SUPPOSED
 TO BE AHU-7? PLEASE COORDINATE FLOOR PLANS WITH
 SCHEDULES.
  
 19. M2.4.2: THE 8X6 O.A. DUCT FOR AHU-7 IS PENETRATING
 A 3-HOUR WALL BETWEEN STORAGE AND EXERCISE ROOMS, AS
 SHOWN ON A-254. SHOW OPENING PROTECTIVES IN ACCORDANCE
 WITH FBC,M 607.5. A MINIMUM 3-HOUR FIRE DAMPER IS
 REQUIRED AT THIS LOCATION PER FBC,M TABLE 607.3.1.
  
 20. M2.4.2: PG A-105 SHOWS HP-7 IN RESIDENT STORAGE 411
 TO BE IN A CLOSET (411A). THIS DOES NOT MATCH M2.4.2
 FLOOR PLAN, WHICH SHOWS AHU-7 IN A CAGE. COORDINATE
 PLANS, SHOWING COMPLIANCE WITH ALL PLENUM, SERVICE
 ACCESS AND R/A REQUIREMENTS AS STATED IN COMMENT 17.
 NOTE: ROOM 411 IN ITS ENTIRETY WILL BE CONSIDERED A
 PLENUM UNLESS THE 8X6 O.A. DUCT TIES INTO A DUCTED
 RETURN OR THE CLOSET SHOWN ON A-105 IS USED AS THE
 PLENUM.
  
 21. M2.4.2: FITNESS ROOM, AHU-9 APPEARS TO BE IN SOME
 KIND OF ENCLOSURE WITH NO OPENINGS FOR R/A OR SERVICE.
 SHOW SOURCE OF RETURN AIR FOR AHU-9. BALANCED RETURN IS
 REQUIRED PER FBC,M 601.4. ALSO, SHOW MEANS OF SERVICE
 ACCESS AS REQUIRED BY FBC,M SEC.306.
  
 22. M2.4.2: THERE IS NO SOURCE OF CONDENSER WATER SHOWN
 FOR AHU-7 OR AHU-9. PLEASE CLARIFY. FBC106.1.1
  
 23. M2.5.2: THE 8X6 O.A. DUCT FOR AHU-7 IS PENETRATING
 A 3-HOUR WALL BETWEEN STORAGE (511) AND OFFICE
 (RESIDENTS' CONFERENCE CENTER 533) AS SHOWN ON A-255.
 SHOW OPENING PROTECTIVES IN ACCORDANCE WITH FBC,M
 607.5. A MINIMUM 3-HOUR FIRE DAMPER IS REQUIRED AT THIS
 LOCATION PER FBC,M TABLE 607.3.1.
  
 24. M2.5.2: OFFICE, AHU-9 APPEARS TO BE IN SOME KIND OF
 ENCLOSURE WITH NO OPENINGS FOR R/A OR SERVICE. SHOW
 SOURCE OF RETURN AIR FOR AHU-9. BALANCED RETURN IS
 REQUIRED PER FBC,M 601.4. ALSO, SHOW MEANS OF SERVICE
 ACCESS AS REQUIRED BY FBC,M SEC.306.
  
 25. M2.5.2: THERE IS NO SOURCE OF CONDENSER WATER SHOWN
 FOR AHU-9. PLEASE CLARIFY. FBC106.1.1
  
 26. M2.5.2: FOR STORAGE ROOM 511, SEE COMMENT #20 AND
 SHOW COMPLIANCE WITH THE SAME. COORDINATE MECHANICAL
 FLOOR PLAN WITH PG A-106.
  
 27. M2.6.1 AND M2.6.2: PLAN INDICATES IN ONE LOCATION
 THAT THESE PAGES ARE TYPICAL FOR FLOORS 5 THRU 7, AND
 IN ANOTHER INDICATE FLOORS 6 AND 7. THESE PAGES APPEAR
 TO BE FOR FLOORS 6 AND 7 SINCE THERE ARE SEPARATE PAGES
 FOR THE 5TH FLOOR WHICH IS NOT TYPICAL. PLEASE CORRECT
 PAGE TITLES AND CLARIFY. FBC 106.1.3.
  
 28. M2.6.2: FOR STORAGE ROOM 611 AND 711, SEE COMMENT
 #20 AND SHOW COMPLIANCE WITH THE SAME. COORDINATE
 MECHANICAL FLOOR PLAN WITH PG A-107.
  
 29. M2.7.1: CONDENSER WATER LINE SIZES ON ROOF PLAN DO
 NOT MATCH THOSE ON RISERS AS SHOWN ON M5.2.1. EXAMPLE:
 RISER DIAGRAM SHOWS 3" LINES FEEDINGCWR-1 (2 1/2")
 AND CWR-2 (2"), BUT ROOF PLAN SHOWS A 4" LINE FEEDING
 BOTH RISERS WITH THE 4" LINES CONTINUING TO CWR-2.
 PLEASE COORDINATE DRAWINGS.
  
 30. M2.7.2: CONDENSER WATER LINE SIZES ON ROOF PLAN DO
 NOT MATCH THOSE ON RISER DIAGRAMS AS SHOWN ON M5.2.1
 AND M2.5.2. EXAMPLE: CWR-10 ON ROOF PLAN SHOWS 2 1/2"
 LINES BUT RISER DIAGRAM SHOWS 2" LINES. PLEASE
 COORDINATE DRAWINGS.
  
 31. M 2.7.2: TX-21 RISER TERMINATES IN OR UNDER THE
 ELEVATOR MACHINE ROOM. MECHANICAL EXHAUST SHALL BE
 DISCHARGED TO THE OUTDOORS PER FBC,M 501.2.
  
 32. M2.7.2: AC BOILER, THIS DOES NOT APPEAR ON ANY
 MECHANICAL EQUIPMENT SCHEDULES OR IN PLUMBING PLANS
 OTHER THAN THE GAS ISOMENTRIC DIAGRAM. SHOW THE TOTAL
 BTU/H OF ALL GAS APPLIANCES IN THE BOILER ROOM (SEE
 COMMENT #56 REGARDING SIZE OF BOILER), SIZE AND
 LOCATION OF VENTING, AMOUNT OF COMBUSTION AIR REQUIRED,
 METHOD USED TO CALCULATE COMBUSTION AIR (FBC,FG 304.6)
 AND FREE AREA ASSOCIATED WITH ALL LOUVERS AND GRILLS
 USED FOR COMBUSTION AIR (FBC,FG 304.10).
  
 33. M2.7.1 AND 2.7.2: VERIFY THAT OARTU'S HAVE
 SUFFICIENT CLEARANCE FOR SERVICE AND VENTILATION
 RELATED TO POTENTIAL OBSTRUCTIONS SUCH AS MANSARD ROOF
 STRUCTURES AND MECHANICAL SCREEN WALLS. FBC,M 306.1
  
 34. M4.1 - 4.3: SOME SUPPLY FLEX DROPS ARE MISSING
 INFORMATION SUCH AS DUCT SIZE, CFM AND GRILL SIZE.
 PLEASE PROVIDE ALL MISSING INFORMATION ON APARTMENT
 FLOOR PLANS. IF A SUPPLY DROP CFM FALLS OUTSIDE THE CFM
 RANGE OF THE FLEX DUCT SCHEDULE AS SHOWN ON M6.1,
 EITHER REVISE THE SCHEDULE TO SHOW THE SIZE TO BE USED
 OR SHOW ALL DUCT SIZES ON FLOOR PLANS. SHOWING ALL FLEX
 DUCT SIZES ON FLOOR PLANS WOULD BE BENEFICIAL DURING
 THE INSPECTION PROCESS.
  
 35. M4.1 - 4.3: SEVERAL BRANCH AND TRANSFER RECTANGULAR
 DUCTS ARE MISSING SIZES FOR SUPPLY AND RETURN. PLEASE
 PROVIDE ALL MISSING INFORMATION. FBC 106.1.1 AND FBC
 106.3.5.1.4
  
 36. M4.1 - 4.3: SOME R/A TRANSFER DUCTS, ESPECIALLY IN
 THE MASTER SUITES ARE NOT DESIGNED TO MEET THE BALANCED
 RETURN EXCEPTIONS UNDER FBC,M 601.4. IF TRANSFERS AND
 JUMPERS ARE NOT DESIGNED TO MEET THESE EXCEPTIONS, A
 FIELD TEST WILL BE REQUIRED AAT FINAL INSPECTION TO
 VERIFY PRESSURE DIFFERENTIALS ACROSS CLOSED BEDROOM
 DOORS DO NOT EXCEED 0.01" W.C. IN ACCORDANCE WITH THIS
 SECTION.
  
 37. M4.1: UNIT C3, FLOOR PLAN DOES NOT SHOW OUTDOOR AIR
 DUCT PENETRATION FROM CORRIDOR AS SHOWN ON M2.4.2.
 PLEASE COORDINATE DRAWINGS. ALSO, SEE COMMENT # 13
 REGARDING DUCT PENETRATIONS OF CORRIDOR WALLS. THIS
 APPLIES TO ALL UNIT FLOOR PLANS.
  
 38. M4.1, M4.2, M5.1: BATH AND DRYER EXHAUST DUCTS
 WHICH ENTER A SHAFT AND UTILIZE A SUBDUCT SYSTEM ARE
 EXEMPT FROM FIRE DAMPERS UNDER THE EXCEPTIONS LISTED IN
 FBC,M 607.5.5.1. HOWEVER, THEY ARE NOT EXEMPT FROM
 SMOKE DAMPERS WHICH ARE REQUIRED BY THIS SECTION. NOTE:
 SMOKE DAMPERS SHALL NOT BE INSTALLED IN CLOTHES DRYER
 EXHAUST DUCTS PER FBC,M 504.2. ALSO, AN INLINE
 BACKDRAFT DAMPER IS ALSO PROHIBITED UNDER THIS SECTION.
 SEE ALSO COMMENTS #9 AND #10.
  
 39. M4.1, M4.2, M5.1: BATH EXHAUST SUBDUCT SYSTEM
 REQUIRES A CONTINUOUS AIRFLOW UPWARD TO THE OUTSIDE IF
 THE FIRE DAMPER EXCEPTION IS TO BE CLAIMED UNDER FBC,M
 607.5.5.1 (1.1). THIS WOULD REQUIRE A FAN ON THE ROOF
 ABOVE THE SUBDUCT SYSTEM WHICH WOUDL RUN CONTINUOUSLY,
 EVEN UNDER EMERGENCY CONDITIONS.
  
 40. M4.1 AND M4.2: MECHANICAL FLOOR PLANS SHOW RETURNS
 DUCTED TO A/C CLOSETS WHICH ARE BEING USED AS PLENUMS
 (SOME WITH SOLID DOORS). FLOOR PLAN ON A-803 (FOR
 EXAMPLE) SHOWS A/C CLOSETS WITH 7'8" CEILINGS, WHICH
 WOULD NOT ALLOW FOR THE DUCTED RETURN TO GET BACK TO
 THE A/C UNIT, AND BIFOLD DOORS. IS THE R/A TO BE DUCTED
 TO THE CLOSET OR THROUGH BIFOLD LOVER DOORS? MECHANICAL
 AND ARCHITECTURAL PLANS ARE IN CONFLICT. PLEASE
 CLARIFY. NOTE: SEE COMMENT #17 REGARDING A/C CLOSET
 DOORS.
  
 41. M4.2 AND M4.3: TH1, 2 AND 3 ALL SHOW DRYER EXHAUST
 DUCTS TO BE 5 INCH ROUND. THIS WOULD NOT CONFORM TO
 MOST DRYER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
 THIS CAN NOT BE VERIFIED AS INSTALLATION INSTRUCTIONS
 WERE NOT PROVIDED. CLOTHES DRYERS SHALL BE EXHAUSTED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS IN
 ACCORDANCE WITH FBC,M 504.1. PROVIDE DRYER
 MANUFACTURER'S INSRUCTIONS TO DEMONSTRATE THAT THE
 EXHAUST AS SHOWN ON PLANS IS IN COMPLIANCE.
  
 42. M4.2: TH3, PLAN SHOWS 12X8 DUCT DOWN FROM 2ND FLOOR
 TO KITCHEN. THE RISER DUCT IS SHOWN IN THE EXACT SAME
 LOCATION AS A CONCRETE COLUMN. SEE PG A-808. THERE IS A
 CHASE WITHIN THE UNIT DESIGNED FOR THIS RISER DUCT
 MAKING THE 2-HOUR RATED ENCLOSURE IN THE PARKING GARAGE
 UNNECESSARY, ASIDE FROM THE FACT THAT IT IS IN CONFLICT
 WITH A STRUCTURAL COLUMN. PLEASE COORDINATE MECHANICAL
 PLANS WITH ARCHITECTURAL PLANS.
  
 43. M4.3: TH1, MECHANICAL FLOOR PLAN SHOWS A/C DUCT
 DESIGNED TO THE LAUNDRY ROOM INSTEAD OF THE A/C CLOSET.
 SEE PG A-801 FOR APARTMENT LAYOUT. COORDINATE
 MECHANICAL AND ARCHITECTURAL FLOOR PLANS. THE DUCT
 SYSTEM CANNOT BE REVIEWED FOR CODE COMPLIANCE AT THIS
 TIME UNTIL THE DUCT SYSTEM MATCHES FLOOR PLANS. ALSO,
 IF A/C UNIT IS TO BE LOCATED IN KITCHEN, PLEASE SEE
 FBC,M 407.1 REGARDING RETURN AIR INTAKE LOCATIONS.
  
 44. M4.3: TH2, THERE IS NO SUPPLY DUCT GOING TO A/C
 CLOSET. SUPPLY DUCT ONLY GOES FROM 2ND FLOOR DOWN TO
 1ST FLOOR, WITH NO SOURCE OF SUPPLY AIR. PLEASE
 CLARIFY.
  
 45. M4.1 THROUGH M4.3: NO INFORMATION COULD BE FOUND ON
 PLANS REGARDING VENTILATION FOR UNITS. SHOW COMPLIANCE
 WITH FBC,M SEC.402 OR TABLE 403.3. ALSO, SHOW HOW UNITS
 ARE TO BE PRESSURIZED WITH RESPECT TO THE OUTDOORS IN
 ACCORDANCE WITH FBC 13-409.1.ABC.2.
  
 46. M4.4: IF LOWER AND UPPER LOBBY AREAS ARE DEEMED TO
 BE AN ATRIUM RATHER THAN A MEZZANINE DURING BUILDING
 PLAN REVIEW, SMOKE CONTROL SHALL BE REQUIRED PER FBC
 SEC. 404.
  
 47. M4.4: MECHANICAL FLOOR PLAN ON 2ND FLOOR SHOWS THE
 SUPPLY RISER GOING DOWN THROUGH THE CORNER OF A
 CONCRETE BLOCK WALL TO THE FIRST FLOOR. THE FLOOR PLAN
 OR A-301 SHOWS A CHASE IN THE A/C CLOSET (PROBABLY FOR
 A/C DUCT) AND THE DOOR TO THE A/C CLOSET IS SHOWN WHERE
 THE RETURN WALL GRILL IS LOCATED. PLEASE COORDINATE
 PLANS. ALSO, LIFE SAFETY PLAN A-252 SHOWS THE
 MECHANICAL ROOM WALL AS 2-HOUR RATED. SHOW OPENING
 PROTECTIVES AT ALL DUCT PENETRATIONS OF RATED
 ASSEMBLIES (VERTICAL AND HORIZONTAL) IN ACCORDANCE WITH
 FBC,M 607.5.
  
 48. M4.4: WHAT IS THE PURPOSE OF THE ACCESS PANELS IN
 THE 2-HOUR RATED ENCLOSURES? IF THIS IS THE LOCATION OF
 SUPPLY FANS, PLEASE SHOW THE FANS ON THE PLANS. FBC
 106.1.1 AND FBC 106.3.5.1.4. NOTE: 60X30 SAR'S WOULD
 INDICATE THAT THESE ARE SUPPLY DUCTS.
  
 49. M4.4: M4.4: EF-1 IN TOILET ROOM 124 SHALL BE
 INTERLOCKED TO RUN WITH AHU-6 TO ENSURE ALL AIR
 SUPPLIED TO THAT SPACE IS EXHAUSTED IN ACCORDANCE WITH
 FBC,M 403.2.1(3). PROVISIONS SHALL ALSO BE MADE TO
 ASSURE THAT BOTH THE AHU AND THE EF ARE RUNNING
 WHENEVER THE SPACE IS OCCUPIED IN ACCORDANCE WITH FBC,M
 401.3 (UNLESS BOTH ARE SET TO RUN CONTINUOUS).
  
 50. M5.1: PLAN SHOWS ROOF CURBS FOR RTU 1 AND 2 USED
 FOR SUPPLY DUCT. IF SO, CURBS SHALL BE LINED WITH MIN.
 R-8, UL-181 APPROVED DUCT MATERIAL IN ACCORDANCE WITH
 FBC TABLE 13-410.1.ABC.2.2 AND FBC,M 604.13. IF THIS IS
 A LISTED SYSTEM, PROVIDE SUBMITTAL.
  
 51. M5.1: M5.1: ALL DUCT PENETRATIONS OF SHAFT FOR RTU
 1 AND 2 SHALL BE PROTECTED BY FIRE AND SMOKE DAMPERS
 PER FBC,M 607.5.5.1. SEE COMMENT #13.
  
 52. M5.1: TOILET EXHAUST RISER PENETRATIONS REQUIRE
 SMOKE DAMPERS AND ROOFTOP EXHAUST FANS TO RUN
 CONTINUOUS UNDER ALL CONDITIONS PER FBC,M 607.5.5.1.
 SEE COMMENT #38 AMD #39.
  
 53. M5.1: DRYER EXHAUST RISERS ARE NOT EXEMPT FROM
 SMOKE DAMPER REQUIREMENTS. SEE COMMENT #9 AND #38.
  
 54. M5.2.1: COORDINATE PIPE SIZES WITH THOSE SHOWN ON
 ROOF PLAN (M2.7.1, M2.7.2) AND WATER FLOW DIAGRAM
 (M5.3). ALSO, SHOW ALL PIPE SIZES, INCLUDING BRANCHES
 FOR AHU'S 2,5,6,14.
  
 55. M5.2.2: COORDINATE PIPE SIZES WITH THOSE SHOWN ON
 ROOF PLAN (M2.7.1, M2.7.2) AND WATER FLOW DIAGRAM
 (M5.3). ALSO, SHOW ALL PIPE SIZES, INCLUDING BRANCHES
 FOR AHU'S 10,11,12.
  
 56. M5.3: DIAGRAM ON THIS PAGE SHOWS AC BOILER TO BE
 600,000 BTU/H BUT PLUMBING PLAN SHOWS THE BOILER AT
 200,000 BTU/H. PLEASE CLARIFY. PROVIDE SUBMITTAL FOR
 THE BOILER AND ALL EQUIPMENT SHOWN ON THIS PAGE. FBC
 106.1.2.
  
 57. M5.3: COORDINATE PIPE SIZES WITH THOSE SHOWN ON
 ROOF PLAN (M2.7.1, M2.7.2) AND RISER DIAGRAMS (M5.2.1,
 M5.2.2).
  
 58. M5.3: TOWER NOTES, NOTE #2, PROVIDE DETAIL AND WIND
 LOAD CALCULATIONS FOR THIS INSTALLATION. FBC,M 301.13,
 FBC, CH.16 AND FCB 106.1.2.
  
 59. M6.1: EF-3, 4 POOL TOILET AND POOL EQUIPMENT ROOMS
 COULD NOT BE LOCATED ON MECHANICAL PLANS. PROVIDE
 MISSING INFORMATION. FBC 106.1.1
  
 60. M6.1: SHOW LOCATION OF EF-7 AND FIRE PUMP ROOM ON
 PLANS. ELECTRICAL PLAN INDICATES FIRE PUMPS ARE DIESEL
 OPERATED. PROVIDE INFORMATION ON FUEL STORAGE MEANS,
 LOCATION AND QUANTITIES AS WELL AS LOCATION AND DETAILS
 OF ALL FUEL DELIVERY AND REFUELING LINES. PROVIDE
 SUBMITTALS FOR ALL LISTED EQUIPMENT USED FOR FUEL
 STORAGE AND DELIVERY. STATIONARY COMBUSTION ENGINES
 SHALL COMPLY WITH NFPA 37-02 AND FUEL STORAGE SHALL
 COMPLY WITH NFPA 30-00.
  
 61. M6.1: HEAT PUMP SCHEDULE, NOTE INDICATES HONEYWELL
 "T-87" THERMOSTAT. THIS TYPE OF THERMOSTAT IS NOT
 PROGRAMMABLE AS CALLED FOR ON PG M0.2 AUTOMATIC
 TEMPERATURE CONTROLS NOTE (A). THERMOSTATS SHALL COMPLY
 WITH FBC 13-407.1.ABC.2.4.1.
  
 62. M6.1: PROVIDE SUBMITTALS FOR ALL LISTED MECHANICAL
 EQUIPMENT TO BE USED ON THIS PROJECT. FBC 106.1.3
  
 63. M6.1: WATER SOURCE HEAT PUMPS SHALL HAVE
 TWO-POSITION AUTOMATIC VALVES INTERLOCKED TO SHUT OFF
 WATER FLOW WHEN THE COMPRESSOR IS OFF IN ACCORDANCE
 WITH FBC 13-411.1.ABC.1.4.
  
 64. M7.1: ROOFTOP CLEARANCE SCHEDULE, THE INCORRECT
 CODE YEAR AND CODE SECTION ARE REFERENCED. THE CORRECT
 YEAR/SECTION ARE AS FOLLOWS: FBC 2004 TABLE 1509.7.
  
 65. M7.1: INSULATED DUCT THRU ROOF DETAIL, THIS DETAIL
 DOES NOT MAKE SENSE AS THE NOTES POINT TO STRUCTURAL
 STEEL COMPONENTS WHERE NONE EXIST. THE DETAIL ALSO
 INDICATES PENETRATION OF AN EXISTING ROOF DECK. THIS IS
 NEW CONSTRUCTION. NOTHING IS EXISTING. ALSO, IF
 FLASHING AND DUCT ARE TO BE WELDED, PLEASE PROVIDE
 ADDDITIONAL INFO, SUCH AS METHOD OF WELDING AND
 REQUIRED THICKNESS OF SHEET METAL FOR EACH.
  
 66. M7.1: CLOSED CIRCUIT COOLER DETAIL, WHERE VIBRATION
 ISOLATION IS EMPLOYED, AN APPROVED MEANS OF
 SUPPLEMENTAL RESTRAINT SHALL BE USED TO ACCOMPLISH
 SUPPORT AND RESTRAINT IN ACCORDANCE WITH FBC,M 301.10.
 ALSO, SHOW COMPLIANCE WITH FBC,M 301.13 FOR WIND
 RESISTANCE.
  
 67. M7.1: HEAT PUMP DETAIL, THERE IS ANOTHER DETAIL FOR
 THIS SAME INSTALLATION ON M7.3, BUT THE DETAILS DO NOT
 MATCH. PLEASE CHOOSE ONE METHOD AND REMOVE THE OTHER
 FROM PLANS TO AVOID CONFLICT. FBC 106.1.1.
  
 68. M7.2: DUCT SUPPORT DETAIL, THERE IS ANOTHER DETAIL
 FOR THIS SAME INSTALLATION ON M7.3, BUT THE DETAILS DO
 NOT MATCH. PLEASE CHOOSE ONE METHOD AND REMOVE THE
 OTHER FROM PLANS TO AVOID CONFLICT. FBC 106.1.1. NOTE:
 COMPLIANCE WITH FBC,M 301.13 AND FBC TABLE 1509.7 IS
 REQUIRED.
  
 69. M7.3: SHOW HOW AIR SEPARATOR AND EXPANSION TANK ARE
 TO BE SECURED TO STRUCTURE IN A MANNER THAT MEETS WIND
 LOAD REQUIREMENTS OF FBC,M 301.13 AND FBC CH.16.
  
 70. M7.2 AND 7.3: FIRE DAMPERS, SMOKE DAMPERS AND
 COMBINATION FIRE/SMOKE DAMPERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S
 INSTALLATION INSTRUCTIONS PER FBC,M 607.2. WHERE
 CONFLICTS BETWEEN DETAIL ON PLANS AND MANUFACTURER'S
 INSTRUCTIONS OCCUR, THE MANUFACTURER'S INSTRUCTIONS
 SHALL GOVERN.
  
 71. M7.3:THERE ARE TWO DETAILS FOR VERTICAL PIPE FLOOR
 PENETRATIONS ON THIS PAGE. WHICH IS TO BE USED? PROVIDE
 MANUFACTURER AND LISTING FOR ALL THROUGH-PENETRATION
 FIRESTOP SYSTEMS TO BE USED AT RATED ASSEMBLIES. FBC
 SEC.712
  
 72. M7.3: ROOF MOUNTED EF DETAIL HAS A NOTE FOR
 STRUCTURAL ENGINEER TO DETERMINE AND VERIFY ATTACHMENT
 DETAILS FOR REQUIRED WIND LOADS. NO SUCH INFORMATION
 COULD BE FOUND IN STRUCTURAL PLANS. FBC 301.13
  
 73. M7.4: GARAGE EF 14-16 MOUNTING DETAIL DOES NOT SHOW
 HOW FANS, SLEEVES OR SOUND ATTENUATION BOXES ARE TO BE
 SECURED TO STRUCTURE. PROVIDE SUFFICIENT DETAIL AND
 EQUIPMENT SUBMITTALS. FBC 106.1.2
  
 74. M7.4: GARAGE EF 8-13, SHOW HOW FANS ARE TO BE
 SECURED TO STRUCTURE TO MEET WIND LOAD REQUIREMENTS PER
 FBC,M 301.13 AND CLEARANCE REQUIREMENTS OF FBC TABLE
 1509.7. ALSO PROVIDE SUBMITTAL FOR FLEXIBLE DUCT
 CONNECTIONS, SHOWING SUITABLILITY FOR OUTDOOR USE.
  
 75. GARAGE EF 17-18, SHOW HOW FANS ARE TO BE SECURED TO
 STRUCTURE TO MEET WIND LOAD REQUIREMENTS PER FBC,M
 301.13. PROVIDE SUBMITTAL SHOWING PENTHOUSE TYPE FAN
 HOUSING SUITABLE FOR USE IN 140 MPH WIND ZONE. FBC
 CH.16
  
 76. M7.4: VERTICAL HP DETAIL, SHOW MEANS OF AUXILIARY
 DRAIN PROTECTION PER FBC,M 307.2.3.
  
 77. M7.4: TOILET AND DRYER EXHAUST DETAILS, VERIFY
 SIZES OF WALL CAPS CORRESPOND WITH THOSE SHOWN ON FLOOR
 PLANS. BE SURE TO VERIFY DRYER EXHAUST SIZES ARE IN
 COMPLIANCE WITH DRYER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. SEE COMMENT #41.
  
 78. M7.4: DUCT SMOKE DETECTORS SHALL BE CONNECTED TO
 THE BUILDING FIRE ALARM SYSTEM PER FBC,M 606.4.1.
  
 ENERGY CALCULATIONS:
  
 79. OUTDOOR AIR QUANTITIES SHOWN ON SIZING SUMMARY DO
 NOT MATCH THOSE GIVEN ON PG M0.1. THESE VALUES SHOULD
 CORRESPOND. EXAMPLE: EXERCISE ROOM ON SCHEDULE CALLS
 FOR 150 CFM O.A. WHILE THE SUMMARY SHOWS 120 CFM O.A.
 PLEASE SHOW CORRELATION BETWEEN DESIGN ON PLANS AND
 CALCULATIONS USED FOR SIZING OF EQUIPMENT.
  
 80. COIL SIZING/ COOLING CAPACITY SHOWN ON SIZING
 SUMMARY DO NOT MATCH THOSE GIVEN ON PG M6.1. EXAMPLE 1:
 APT C2 ON SCHEDULE SHOWS 23.83 MBH AND APT C2 ON
 SUMMARY SHOWS 28.8 MBH.THIS UNIT LOOKS TO BE
 SIGNIFICANTLY UNDERSIZED BASED ON THE SIZING
 SUMMARY/COOLING LOADS. PLEASE CLARIFY.
 EXAMPLE 2: SUMMARY FOR AHU-OFFICES CALLS FOR SENSIBLE
 COIL LOAD OF 11.3 MBH WHILE ON SCHEDULE AHU-4 SHOWS
 16.87 MBH. HVAC SYSTEMS AND EQUIPMENT SHALL BE SIZED TO
 PROVIDE NO MORE THAN THE SPACE AND SYSTEM LOADS
 CALCULATED IN ACCORDANCE WITH FBC 13-407.1.ABC.1.
 PLEASE SHOW EQUIPMENT TO BE SIZED ACCORDINGLY.
  
 81. SYSTEM REPORT COMPLIANCE: SYSTEM SIZES AS SHOWN ON
 REPORT DO NOT CORRESPOND WITH SYSTEMS IN THE SYSTEM
 SIZING SUMMARY. GROUPING OF SYSTEMS WILL INCREASE THE
 SIZE OF THE SYSTEM IN THE REPORT WILL DISTORT THE
 ALLOWED EFFICIENCY CRITERIA WHICH WOULD PROVIDE UNDUE
 TRADE-OFF CREDIT FOR EFFICIENCY OF THE COOLING SYSTEMS.
 EXAMPLE: SYSTEM 1 IS LISTED FOR ALL TOWNHOMES AS ONE
 "WATER COOLED >240,000 BTU/H" UNIT. THE TOWNHOMES ARE
 EACH COOLED BY INDIVIDUAL UNITS AND WOULD BE
 CATEGORIZED AS "WATER COOLED 17,000 TO <135,000 BTU/H"
 IN ACCORDANCE WITH FBC TABLE 13-407.1.ABC.3.2B. THIS
 TABLE GIVES A MINIMUM EFFICIENCY CRITERIA OF 12.00 EER.
 "SYSTEMS" SHOULD CORRESPOND WITH "ZONES" IN THE INPUT
 DATA REPORT. FOR GUIDANCE AS TO WHAT ACTUALLY
 CONSTITUTES A ZONE, PLEASE SEE FBC 13-407.1.ABC.2.2.1.
  
 82. INPUT DATA REPORT: BUILDING ENVELOPE COMPONENTS AS
 SHOWN ON THE INPUT DATE REPORT DO NOT CORRESPOND WITH
 THE TYPE OF CONSTRUCTION SHOWN ON PLANS. EXAMPLE:
 REPORT SHOWS THE ROOF TO BE INSULATED WITH R-19 BATTS.
 DETAILS ON A-652 INDICATE THE ROOF INSULATED WITH RIGID
 BOARD TO A VALUE OF R-14 IN A BUILT-UP ROOF SYSTEM.
 ALSO, NO INFORMATION COULD BE FOUND REGARDING TYPE OR
 R-VALUE OF INSULATION TO BE USED IN THE MANSARD ROOF
 SECTIONS WHICH ARE ABOVE CONDITIONED SPACES. NO
 INFORMATION COULD BE FOUND IN ARCHITECTURAL PLANS OR
 DETAILS SHOWING 1.36" INSULATION AT EXTERIOR WALLS AS
 INDICATED ON THE REPORT. PLEASE CLARIFY ON PLANS AND
 PROVIDE CORRESPONDING INFORMATION ON CALCULATIONS.
  
 83. WHAT IS THE R-VALUE OF THE 3RD FLOOR FLOOR/CEILING
 ASSEMBLY BETWEEN THE PARKING GARAGE AND THE 3RD FLOOR
 APARTMENTS? THIS INFORMATION IS NOT SHOWN ON PLANS OR
 IN THE REPORT. ALSO, PLEASE EXPLAIN HOW AN 8"
 LIGHTWEIGHT CONCRETE BLOCK WITH 1.36" INSULATION SYSTEM
 IS TO BE USED FOR THE FLOOR IN THE LOBBY AS INDICATED
 IN THE REPORT.
  
 84. ENERGY CALCULATIONS SHOW A "PLANT" CHILLER AT 390
 TONS. THERE IS NO CHILLER SHOWN AS PART OF THIS SYSTEM.
 ALSO, THE CLOSED CIRCUIT COOLERS AND A/C BOILER WERE
 OMITTED FROM THE CALCULATIONS. PLEASE CORRECT AND
 RESUBMIT.
  
 85. STAIR AND ELEVATOR SHAFT VENTS SHALL BE EQUIPPED
 WITH MOTORIZED DAMPERS THAT ARE CAPABLE OF BEING
 AUTOMATICALLY CLOSED DURING NORMAL BUILDING OPERATION
 AND ARE INTERLOCKED TO OPEN AS REQUIRED BY FIRE AND
 SMOKE DETECTION SYSTEMS. FBC 13-409.1.ABC.3.1
  
 86. MECHANICAL SYSTEMS SHALL BE DESIGNED TO ASSURE THAT
 BUILDINGS ARE PRESSURIZED WITH RESPECT TO OUTDOORS.
 PROVIDE AIR BALANCE SCHEDULE(S) SHOWING COMPLIANCE FOR
 ALL ZONES/FLOORS. FBC 13-409.1.ABC.2
  
 87. SHOW SHUTOFF DAMPER CONTROLS FOR O.A. SUPPLY AND
 EXHAUST SYSTEMS AS REQUIRED BY FBC 13-409.1.ABC.3.3.
  
 88. DEMONSTRATE COMPLIANCE WITH FBC 13-406.1.ABC.1.1
 FOR AIR INFILTRATION AT EXTERIOR DOORS AND WINDOWS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-06 Cont ID  
Sent By kstevens Date 2007-10-06 Time 14:01 Rev Time 0.00
Received By kstevens Date 2007-09-22 Time 18:08 Sent To  
Notes
2007-10-06 16:49:08DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB MUNICIPAL CODE
  
 1. ALL ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT IS REQUIRED IN THE TITLE
 BLOCK OF EACH SHEET. FAC 61G1-16.004(6) & FS 481.2055.
 PLEASE SHOW PRINTED NAME IN TITLE BLOCK OF EACH SHEET.
  
 2. SHT A-002 BUILDING #4 DATA. THE BUILDING CODE
 EDITION IS SHOWN AS 2001 FBC. THE CODE IN EFFECT IS THE
 FBC-2004. PLEASE CORRECT CODE REFERENCE.
  
 3. SHT A-200 BUILDING #4 DATA. ONE INTENDED USE
 ACCESSORY OCCUPANCY IS INDICATED AS MERCANTILE RETAIL
 AREA. PLEASE INDICATE THE LOCATION OF THE RETAIL AREA.
 SECTION 106.1.1.
  
 4. SHT A-003 DETAIL E. THE CLEAR FLOOR SPACE FOR THE
 LAV IS NOT SHOWN. PLEASE SHOW CLEAR FLOOR SPACE AS
 INDICATED ON PAGE 7.47.
  
 5. SHT A-0003A DETAILS A & B. THE WATER CLOSET CAN NOT
 BE IN THE CLEAR FLOOR SPACE REQUIRED FOR THE LAV,
 (DETAIL A), OR SHOWER, (DETAIL B). PLEASE SHOW
 COMPLIANCE WITH THE CLEAR FLOOR SPACE REQUIREMENTS.
  
 6. SHT A-104 ROOF DRAIN CALCULATIONS. NO MENTION OF THE
 CONTRIBUTION FROM THE ROOF AREA ABOVE DRAINING ONTO THE
 ROOF AREAS. SECTION 1106.3. PLEASE SHOW THE UPPER ROOF
 CONTRIBUTION IN THE CALCULATIONS FOR THE ROOF/DECK
 DRAINS.
  
 7. SHT A-104 ROOF DRAIN CALCULATIONS. AREA "C" SCALES
 OUT TO BE ROUGHLY 15FT SHORTER THAN AREAS "D & E", BUT
 SHOWS MORE TOTAL AREA. PLEASE CLARIFY. SECTION 106.1.1.
 IS THERE MORE VERTICAL SF OR UPPER ROOF AREA?
  
 8. SHT A-104 AREAS "D & E" SCALE OUT TO BE
 APPROXIMATELY THE SAME LENGTH, BUT AREA "E" IS
 INDICATED AS ABOUT TWICE THE AREA. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 9. SHT A-104. AREA "F" SHOWS NO CALCULATIONS FOR THE
 PRIMARY AND SECONDARY ROOF DRAINS. PLEASE SHOW
 CALCULATIONS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE SQUARE FOOTAGE OF THE ROOF AREA,
 WITH 1/2 THE AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AS WELL AS THE AREA FROM THE UPPER ROOF THAT
 DRAINS ONTO THE ROOF FROM ABOVE.
  
 10. SHT A-104 CALCULATIONS ARE REQUIRED FOR THE OUTDOOR
 LIVING PATIO & DECK DRAINS. SHOW THE SQUARE FOOTAGE OF
 THE DECK AREA AND SHOW 1/2 AREA OF ALL VERTICAL WALLS
 AND INDICATE THE SQUARE FOOT AREA OF THE ROOFS THAT
 DRAIN ONTO THE DECK AREA FROM ABOVE. SECTIONS 1106 &
 1107 AND ALL SUBSECTIONS.
  
 11. SHT A-104 SHOW THE LOCATIONS FOR ALL SECONDARY
 DRAINAGE ON THE DECK. INDICATE ALL AREAS THAT DRAIN OFF
 THE SIDE OF THE BUILDING IF ANY.
  
 12. SHT A-104 THE LOCATIONS OF THE DECK DRAINS IN THE
 OUTDOOR LIVING PATIO & DECK DRAINS ARE APPROXIMATELY
 6FT FROM THE SLIDING GLASS DOOR, BUT THE DISTANCE TO
 THE AREA WHERE THE OVERFLOW LEAVES THEPATIO AREA IS
 APPROXIMATELY 11FT. IS THERE ANY CONCERN THAT THE STORM
 WATER WILL ENTER THE UNIT BEFORE THE STORM WATER
 REACHES THE OVERFLOW AREA? PLEASE CLARIFY. SECTION
 106.1.2. (MORE INFORMATION REQUIRED).
  
 13. SHT A-104 THERE ARE ABOUT FIVE PLANTER DRAINS THAT
 RECIEVE THE WATER OF THE VERTICAL WALL FROM THE ROOF
 AREA. WHEN INDICATING THE SQUARE FOOTAGE BEING DRAINED
 BY THESE PLANTER DRAINS, PLEASE SHOW 1/2 THE AREA OF
 THE VERTICAL WALLS INCLUDED IN THE TOTAL SQUARE
 FOOTAGE. SECTION 1106.4.
  
 14. SHT A-108 THE ROOF DRAINS DO NOT APPEAR TO BE
 LOCATED AT THE LOW POINT OF THE ROOF. THE LOW AREA FOR
 AREA"G" APPEARS TO BE IN THE ELEVATOR MACHINE ROOM.
 NO SLOPE INDICATION IS SHOWN FOR AREA "F" PLEASE
 CLARIFY. SECTION 106.1.1. ELEVATIONS SHALL BE SUBMITTED
 FOR ALL AREAS OF THE ROOF TO VERIFY IF THE ROOF DRAINS
 ARE IN THE LOWEST POINT OF THE ROOF.
  
 15. SHTS A-205 & A-206 SHOW THE SECONDARY DRAINS FOR
 ALL AREAS PER SECTION 1107.
  
 16. SHT A-206 SHOW COMPLIANCE FOR THE TOILET ROOMS.
 (337 & 338).
 ____W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ____URINAL
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 ____LAVS
 A.11-4.19.3 CLEAR FLOOR SPACE
 ____TOILET ROOMS
 A. 11-4.22.3 SHOW THE 5' TURNING AREA IN THE TOILET
 ROOM, ITS NOT REQUIRED IN STALL
  
 17. SHT A-907 FINISH SCHEDULE INDICATES PAINT ON GWB
 FOR THE ADCP TOILET ROOM, MEN'S TOILET ROOM & WOMEN'S
 TOILET ROOM. SECTION 1210.2 REQUIRES THE WALL WITHIN
 2FT OF WATER CLOSETS OR URINALS TO HAVE A "SMOOTH,
 HARD, NONABSORBENT" SURFACE. PAINTED GWB DOES NOT MEET
 THE "HARD" REQUIREMENT OF THE CODE SECTION. PLEASE SHOW
 COMPLIANCE.
  
 18. ALL CIVIL SHEETS ARE NOT SIGNED, SEALED OR DATED AS
 REQUIRED PER SECTION 106.1 AND FAC 61G15-23.002(2) & FS
 472.025. PLEASE SIGN, SEAL AND DATE ALL SHEETS.
  
 19. SHTS CS-2 & A-001B. THE PRINTED NAME OF THE PERSON
 SIGNING & SEALING THE DOCUMENT IS REQUIRED ON EACH
 SHEET. FAC 61G1-16.004(6) & FS 481.2055.
  
 20. ALL ENGINEERED SHEETS SHALL BE DATED PRIOR TO PLANS
 BEING ISSUED. THE DATE THE SEAL AND SIGNATURE ARE
 AFFIXED TO THE DOCUMENTS SHALL BE ENTERED ON THE PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. FAC
 61G15-23.002(1)(2) & FS 471.025.
  
 21. SHT P0.1 PLUMBING LEGEND. ALL WATER LINES ARE SOLID
 LINES WITH NO DIFFERENCES. PLEASE CLARIFY. SECTION
 106.1.1.
  
 22. SHT P2.1.1 KEY NOTES 1 & 3. PLEASE INDICATE THE
 SYSTEM FOR THESE LINES. (STORM, CONDENSATE)? SECTION
 106.1.1.
  
 23. SHT P2.1.1 SHOW THE CLEANOUTS REQUIRED IN THE STORM
 DRAINAGE LINES PER SECTION 1101.8.
  
 24. SHT P2.1.1 INDICATE THE UNIT NUMBERS FOR EACH
 TOWNHOUSE UNIT. SECTION 106.1.2.
  
 25. SHT P2.1.1 INDICATE THE RISER NUMBERS FOR EACH
 TOWNHOUSE UNIT. (TH3(A), TH3(B), TH3(C) ETC). SECTION
 106.1.2.
  
 26. SHT P2.1.1 RISER DESIGNATION FOR CONDENSATE RISER
 IS NOT LEGIBLE. SECTION 106.1.1. PLEASE MAKE SURE ALL
 RISERS ARE LEGIBLE.
  
 27. SHT P2.1.1 8" POOL DRAIN & 4" JACUZZI SPA DRAIN
 SHALL CONNECT TO THE STORM, NOT THE SANITARY. PLEASE
 SHOW DRAINS CONNECTING TO STORM.
  
 28. SHT P2.1.1 SHOW ALL RISER NUMBERS FOR THE STORM
 RISERS. (RWL-1, RWL-2 OR SD-1, SD-2 ETC). SECTION
 106.1.1.
  
 29. SHT P2.1.1A CONDENSATE RISER IS INDICATED AS 1/2"
 RISER. PLEASE CLARIFY. SECTION 106.1.1.
  
 30. SHT P2.1.1 CONDENSATE RISER #1&2 AND SANT. RISER #1
 ARE SHOWN IN A STEM WALL. SECTION 1906.3 CONDUITS AND
 PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER.
  
 31. SHT P2.1.1 IDENTIFY THE SYSTEM SHOWN TO THE RIGHT
 OF CATCH BASIN #2 INDICATED BY THE NOTE "UP TO 2ND
 FLOOR". SECTION 106.1.1.
  
 32. SHT P2.1.2 SHOW ALL RISER NUMBERS FOR THE STORM
 RISERS. (RWL-1, RWL-2 OR SD-1, SD-2 ETC). SECTION
 106.1.2.
  
 33. SHT P2.1.2 SANT. RISER #8 IS SHOWN IN COLUMN AND
 UNDER THE SHEAR WALL. SECTION 1906.3 CONDUITS AND PIPES
 EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED.
  
 34, SHT P2.1.2 THE SANITARY BUILDING DRAIN IS SHOWN IN
 AND UNDER COLUMNS. SECTION 1906.3 CONDUITS AND PIPES
 EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED.
  
 35. SHT P2.1.2 SANITARY RISERS 21 & 25 ARE SHOWN IN
 COLUMNS. SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN
 CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED.
  
 36. SHT P2.1.2 CLEANOUTS ARE REQUIRED IN THE STORM
 STYTEM PER SECTION 1101.8. PLEASE SHOW ON FLOOR PLAN TO
 REFLECT THE RISER DIAGRAM.
  
 37. SHT P2.1.2 THE WASH MACHINE IS INDICATED BEYOND THE
 LAV IN "TH" UNIT BETWEEN SANT. RISERS 22 & 25. ALSO
 SHOWN ON THE RISER DIAGRAM. PLEASE CLARIFY AS THE W/M
 SEEMS TO BE LOCATED BY KITCHEN, NOT IN THE CLOSET NEXT
 TO THE POWDER ROOM. SECTION 106.1.1.
  
 38. SHT P2.1.2 CONDENSATE RISER 17/18 IS SHOWN
 CONNECTING TO THE STORM LINE. PLEASE CLARIFY.
 CONDENSATE SHALL DISCHARGE OUTSIDE THE BUILDING
 SEPARATELY.
  
 39. SHT P2.1.2 CONDENSATE FITTING SHALL GUIDE WASTE IN
 THE DIRECTION OF FLOW. SECTION 706.3. SEE FITTING NEAR
 SANT. RISER 26. CORRECT FITTING TO GUIDE WASTE IN THE
 DIRECTION OF FLOW.
  
 40. SHT P2.1.2 THE CONDENSATE LINE APPEARS TO RUN THRU
 CATCH BASIN #3. PLEASE CLAIRFY. SECTION 106.1.1.
  
 41. SHT P2.1.2 NO KEY NOTES 1, 2 OR 3 INDICATED ON
 SHEET. PLEASE INDICATE WHAT ITEMS (1)(2)(3) REPRESENT.
 IDENTIFY SYSTEMS FOR KEY NOTES 1 & 3. SECTION 106.1.2.
  
 42. SHT P2.1.2 INDICATE THE UNIT NUMBER FOR EACH
 TOWNHOUSE UNIT. SECTION 106.1.2.
  
 43. SHT P2.2.1 SANT. RISER #5 IS SHOWN IN A COLUMN.
 SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED.
  
 44. SHT P2.2.1 INDICATE THE UNIT NUMBER FOR EACH
 TOWNHOUSE UNIT. SECTION 106.1.2.
  
 45. SHT P2.2.1 INDICATE THE RISER NUMBERS FOR THE
 TOWNHOUSES. (TH3(A)(B)(C) OR (D). SECTION 106.1.2.
  
 46. SHT P2.2.1 INDICATE STORM RISER NUMBERS. (RWL-1,
 RWL-2 OR SD-1, SD-2 ETC). SECTION 106.1.2.
  
 47. SHT P2.2.1 THE SANITARY RISER UP TO 3RD FLOOR SINK
 SHALL NOT DRAIN THROUGH THE HORIZONTAL WET VENT OF THE
 BATHROOM FIXTURES. SECTION 909.1. THE SINK SHALL
 DISCHARGE DOWNSTREAM OF THE BATHROOM GROUP.
  
 48. SHT P2.2.2 THE SHEET IDENTIFICATION INDICATES 2ND
 FLOOR "SOUTH". ALL PREVIOUS SHEETS ARE IDENTIFIED AS
 "EAST" OR "WEST" PLEASE CLARIFY. SECTION 106.1.1.
  
 49. SHT P2.2.2 SANT. RISER #23 IS NOT SHOWN ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1. PLEASE
 SHOW THE LOCATION OF SANT. RISER #23.
  
 50. SHT P2.2.2 CONDENSATE RISER 17/18IS NOT SHOWN ON
 THE FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1. PLEASE
 SHOW THE LOCATION OF COND. RISER 17/18.
  
 51. SHT P2.2.2 SANT. RISERS 21 & 25 ARE NOT SHOWN ON
 THE FLOOR PLAN. ARE THEY RUN IN THE COLUMNS? IF SO
 PLEASE COMPLY WITH SECTION 1906.3. IF NOT SHOW THE
 LOCATION OF THE RISERS. SECTIONS 106.1.2 & 106.1.1.
  
 52. SHT P2.2.2 SANT. RISER 15 AND RISER DESIGNATION ARE
 NOT SHOWN ON THE FLOOR PLAN. PLEASE CLARIFY. SECTION
 106.1.1. PLEASE SHOW THE LOCATION OF SANT. RISER 15.
  
 53. SHT P2.2.2 INDICATE STORM RISER NUMBERS FOR EACH
 RISER. (RWL-1, RWL-2 OR SD-1, SD-2 ETC). SECTION
 106.1.2.
  
 54. SHT P2.2.2 IDENTIFY THE SYSTEM WITH THE "OD LINE
 DOWN/UP". SECTION 106.1.2.
  
 55. SHT P2.3.1 THE CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINAGE ON SHT A-104 AREAS "A" THRU "E"
 DO NOT REFLECT WHAT IS SHOWN ON THE ROOF PLANS FOR
 THOSE AREAS. PLEASE CLARIFY. RECHECK THE TOTAL SQUARE
 FOOTAGE BEING DRAINED IN EACH AREA. SECTION 1106 &
 TABLE 1106.3.
  
 56. SHT P2.3.1 SHOW THE LOCATION OF ALL REQUIRED
 SECONDARY DRAINS FOR THE DECK AREA. SECTION 1107 WITH
 ALL SUBSECTIONS & TABLES.
  
 57. SHT P2.3.1 A RELIEF VENT IS REQUIRED FOR THE AIR
 ADMITTENCE VALVE AT THE PAVILLION SINK. SECTION
 917.3.2. PLEASE SHOW ON THE FLOOR PLAN AND THE RISER
 DIAGRAM.
  
 58. SHT P2.3.1 SUBMIT THE INVERT ELEVATIONS FOR THE
 STORM PIPING FOR THE ROOFS OF RETAIL UNITS AND AT THE
 POINT WHERE THEY TURN DOWN TO THE FLOOR BELOW. SECTION
 106.1.2. ALSO INCLUDE THE ELEVATION OF THE PARKING
 GARAGE BELOW THE PIPING.
  
 59. SHT P2.3.1 IDENTIFY AND SHOW THE SQUARE FOOTAGE
 BEING DRAINED BY ALL DRAINS. SECTIONS 106.1.1, 1106
 WITH ALL SUBSECTIONS & TABLES.
  
 60. SHT P2.3.1 IDENTIFY SYSTEM & PIPING IN THE POOL
 EQUIPMENT ROOM. (SHOWN AS DD ON SHT A-205). SECTION
 106.1.2.
  
 61. SHT P2.3.1 THE SQUARE FOOTAGE FOR THE PATIOS
 OUTSIDE THE CONDO UNITS DOES NOT APPEAR TO BE CORRECT.
 (EXAMPLE THE DRAIN BY UNIT C-5A 320 SHOWS DD 900 SF.
 SCALING SHOWS APPROX 1,015 SF NOT COUNTING 1/2 VERTICAL
 WALLS TO ROOF LEVEL PLUS THE UPPER ROOF CONTRIBUTION
 DRAINING ONTO THE PATIO AREA. PLEASE CLARIFY. SECTION
 1106.3 & TABEL 1106.3.
  
 62. SHT P2.3.1 THE RISER BY STAIR #3 IS NOT LEGIBLE.
 SECTION 106.1.1. PLEASE CLARIFY.
  
 63. SHT P2.3.1 EXTRA RISER INDICATORS ARE SHOWN ON
 RISER 2, (2) (BY W/C & LAV),RISER 3, (1) (BY LAV) &
 RISER 4, (1) (BY LAV). PLEASE INDICATE WHAT THE RISERS
 ARE INDICATED FOR. SECTION 106.1.1.
  
 64. SHT P2.3.1 THERE ARE 2 SANITARY LINES THRU COLUMNS.
 UNITS C-2 (317)(319). SECTION 301.2 & SECTION 1906.3
 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED.
  
 65. SHT P2.3.2 SANT RISER 13 SHOWS A FLOOR DRAIN UNDER
 THE ROOF IN WHAT APPEARS TO BE OUTSIDE THE BUILDING.
 MORE INFORMATION IS REQUIRED. PLEASE INDICATE WHAT WILL
 BE DRAINED. SECTION 106.1.2.
  
 66. SHT P2.3.2 IDENTIFY ALL DRAINS IN THE DECK AREA AND
 SHOW THE SQUARE FOOTAGE BEING DRAINED BY EACH DRAIN.
 SECTION 106.1.2.
  
 67. SHT P2.3.2 NO SQUARE FOOTAGE IS SHOWN FOR AREA "F"
 OF THE LOWER ROOF AREA. PLEASE SUBMIT CALCULATIONS FOR
 THE DRAINS OF AREA "F" SHOWING THE SQUARE FOOTAGE OF
 THE ROOF AREA, 1/2 AREA OF VERTICAL WALLS INCULDING
 PARAPETS, AND ROOF AREAS THAT DRAIN ONTO THE ROOF FROM
 ABOVE IN THE CALCULATION. SECTION 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES.
  
 68. SHT P2.3.2 THE WASTE ARMS TO THE LAVS IN UNITS C-1,
 (326), & C-1, (332), ARE NOT SHOWN AT THE FIXTURE.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 69. SHT P2.3.2 ONLY ONE RISER 20 SHOWN AT THE W/M,
 WHEREAS TWO RISERS ARE SHOWN ON THE RISER DIAGRAM.
 SECTION 106.1.1. PLEASE HAVE THE FLOOR PLAN AND RISER
 DIAGRAM REFLECT.
  
 70. SHT P2.3.2 THE SANITARY RISER NUMBER FOR THE DOUBLE
 LAV IN UNIT C1B (315) IS MISSING. SECTION 106.1.1.
 PLEASE INDICATE RISER NUMBER.
  
 71. SHT P2.4.1 THE SANITARY RISER NUMBER IS MISSING
 BEHIND THE TUB IN UNIT C-4 (418). SECTION 106.1.1.
 PLEASE INDICATE RISER NUMBER.
  
 72. SHT P2.4.1 INDICATE THE STORM RISER NUMBERS FOR
 EACH STORM RISER. SECTION 106.1.2.
  
 73. SHT P2.4.1 SANITARY LINES ARE SHOWN RUNNING THRU
 COLUMNS. SECTION 301.2 & SECTION 1906.3 CONDUITS AND
 PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED.
  
 74. SHT P2.4.2SANITARY RISER 13 SHOWS A FLOOR DRAIN
 THAT APPEARS TO BE OUTSIDE THE BUILDING. MORE
 INFORMATION IS REQUIRED. PLEASE INDICATE WHAT WILL BE
 DRAINED. SECTION 106.1.2.
  
 75. SHT P2.4.2 SHEET IDENTIFICATION IS SHOWN AS 4TH
 FLOOR "SOUTH" PREVIOUS SHEETS WERE INDICATED AS "EAST"
 & "WEST". PLEASE CLARIFY. SECTION 106.1.1.
  
 76. SHT P2.4.2 THE WASTE ARM FOR THE LAV IS NOT SHOWN
 AT THE FIXTURE IN UNIT C1 (430). PLEASE CLARIFY.
 SECTION 106.1.1.
  
 77. SHT P2.4.2 INDICATE THE STORM RISER NUMBERS FOR
 EACH STORM RISER. SECTION 106.1.2.
  
 78. SHT P2.5.1 SHOW THE RISER NUMBERS FOR THE
 CONDENSATE RISERS. SECTION 106.1.2.
  
 79. SHT P2.5.1 SHOW THE STORM RISER NUMBERS FOR EACH
 STORM RISER. SECTION 106.1.2.
  
 80. SHT P2.5.2 SANITARY RISER 13 SHOWS A FLOOR DRAIN
 THAT APPEARS TO BE OUTSIDE THE BUILDING. MORE
 INFORMATION IS REQUIRED. PLEASE INDICATE WHAT WILL BE
 DRAINED. SECTION 106.1.2.
  
 81. SHT P2.5.2 INDICATE THE STORM RISER NUMBERS FOR
 EACH STORM RISER. SECTION 106.1.2.
  
 82. SHT P2.5.2 THE SANITARY RISER NUMBER FOR RISER
 BEHIND THE LAV IN UNIT C1 (524) IS MISSING. PLEASE SHOW
 RISER NUMBER. SECTION 106.1.1.
  
 83. SHT P2.6.1 INDICATE THE STORM RISER NUMBERS FOR
 EACH STORM RISER. SECTION 106.1.2.
  
 84. SHT P2.6.2 INDICATE THE STORM RISER NUMBERS FOR
 EACH STORM RISER. SECTION 106.1.2.
  
 85. SHT P2.6.2 THE WASTE ARM IS NOT SHOWN AT THE LAV
 FIXTURE IN UNIT C1 (730). PLEASE CLARIFY. SECTION
 106.1.1.
  
 86. SHT P2.6.2 SANITARY RISER 13 SHOWS A FLOOR DRAIN
 THAT APPEARS TO BE OUTSIDE THE BUILDING. MORE
 INFORMATION IS REQUIRED. PLEASE INDICATE WHAT WILL BE
 DRAINED. SECTION 106.1.2.
  
 87. SHT P2.6.2 THE SANITARY RISER NUMBER IS MISSING BY
 THE LAV IN UNIT C1 (724). PLEASE SHOW RISER NUMBER.
 SECTION 106.1.2.
  
 88. SHT P2.7.1 ROOF DRAINS DO NOT APPEAR TO BE LOCATED
 AT THE LOW POINT OF THE ROOF. PLEASE SUBMIT ELEVATIONS
 AT DIFFERENT AREAS OF THE ROOF SHOWING THE LOW POINTS
 AND THE HIGH POINTS OF THE ROOF TO VERIFY PROPER
 DRAINAGE TO THE ROOF DRAINS. SECTION 106.1.2.
  
 89. SHT P2.7.2 ROOF DRAINS DO NOT APPEAR TO BE LOCATED
 AT THE LOW POINT OF THE ROOF. PLEASE SUBMIT ELEVATIONS
 AT DIFFERENT AREAS OF THE ROOF SHOWING THE LOW POINTS
 AND THE HIGH POINTS OF THE ROOF TO VERIFY PROPER
 DRAINAGE TO THE ROOF DRAINS. SECTION 106.1.2.
  
 90.SHT P2.7.2 SANITARY RISER VTR #14 SHALL NOT BE
 LOCATED IN THE STAIRWELL. NFPA 101 SECTION
 7.1.3.2.1(6). PLEASE OFFSET OUT OF STAIRWELL.
  
 91. SHT P2.7.2 SANITARY RISER VTR #17 IS SHOWN UNDER
 CCC-3. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS FOR
 THIS UNIT TO MAKE SURE THERE IS NO AIR INTAKE OR OTHER
 REQUIREMENTS PROHIBITING THE VENT FROM BEING UNDER THIS
 UNIT. SECTION 106.1.2.
  
 92. SHT P2.7.2 ROOF AREA "F" SHOWS NO SLOPE TO DRAIN.
 PLEASE INDICATE SLOPE TO ROOF DRAIN. SECTION 106.1.2.
  
 93. SHT P2.7.2 ROOF AREA "G" ROOF DRAIN AND OD NOT
 LABELED. PLEASE INDICATE WHICH IS THE ROOF DRAIN AND
 WHICH IS THE OD. SECTION 106.1.1.
  
 94. SHT P2.7.2 PLAN NOTES (1) DOES NOT SHOW PIPING TO
 THE ROOF DRAIN. PLEASE CLAIRFY AS NOTE INDICATES
 PIPING. SECTION 106.1.1.
  
 95. SHT P2.7.2 PLAN NOTES (3) &(4). MORE INFORMATION IS
 REQUIRED. WHAT DRAINS FROM CCC-1, CCC-2 & CCC-3. IF THE
 DRAINAGE IS CONDENSATE, THEN IT SHALL NOT DRAIN INTO
 THE SANITARY SYSTEM. ARTICLE III SECTION 90-125(5)--
 PLEASE INDICATE WHAT DRAINS FROM THE UNITS AND IF IT
 SHALL INDEED DRAIN INTO THE SANITARY SYSTEM, THEN
 SUBMIT A DETAIL SHOWING HOW STORM WATER WILL NOT DRAIN
 INTO THE FUNNEL DRAIN. SECTION 106.1.2.
  
 96. SHT P3.1.2 INDICATE THE MATERIAL USED FOR THE 3"
 UNDERGROUND WATER SERVICE TO THE PUMP ROOM. MATERIAL
 SHALL COMPLY WITH TABLE 605.3 AND SECTION 605.3.
  
 97. SHT P3.2.1 SHOWS THE HOT & COLD WATER LINES THRU A
 COLUMN. SLEEVES MAY BE REQUIRED, AND PER SECTION 1906.3
 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED.
  
 98. SHT P3.2.2 WATER RISER 13 IS SHOWN THRU A COLUMN.
 SLEEVES MAY BE REQUIRED. PER SECTION 1906.3 CONDUITS
 AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED.
  
 99. SHT P3.2.2 WATER RISER 23 DOES NOT SHOW A
 CONNECTION TO THE WATER MAIN. SECTION 106.1.2. PLEASE
 INDICATE WHERE THE RISER CONNECTS TO THE WATER MAIN.
  
 100. SHT P3.3.2 WATER RISER 11 SHOWS 2 SLEEVES FOR HOT
 & COLD WATER, BUT THE GAS PIPING ALSO IS INDICATED AS
 RUNNING ALONG SIDE OF THE WATER.PLEASE CLARIFY.
 SECTION 106.1.1.
  
 101. SHT P3.3.2 WATER RISER 23, (HOT RECIRCULATION),
 SHOWS 2 SLEEVES. PLEASE CLARIFY. SECTION 106.1.1.
  
 102. SHT P3.4.2 WATER RISER 11 SHOWS 2 SLEEVES FOR HOT
 & COLD WATER, BUT THE GAS PIPING ALSO IS INDICATED AS
 RUNNING ALONG SIDE OF THE WATER.PLEASE CLARIFY.
 SECTION 106.1.1.
  
 103. SHT P3.4.2 THE COLD WATER RISER LINE FOR THE CHUTE
 WASHDOWN APPEARS TO BE LOCATED OUTSIDE THE BUILDING.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 104. SHT P3.5.2 WATER RISER 11 SHOWS 2 SLEEVES FOR HOT
 & COLD WATER, BUT THE GAS PIPING ALSO IS INDICATED AS
 RUNNING ALONG SIDE OF THE WATER.PLEASE CLARIFY.
 SECTION 106.1.1.
  
 105. SHT P3.5.2 THE COLD WATER RISERLINE FOR THE
 CHUTE WASHDOWN APPEARS TO BE LOCATED OUTSIDE THE
 BUILDING. PLEASE CLARIFY. SECTION 106.1.1.
  
 106. SHT P3.6.1 THE WATER RISER DESIGNATIONS HAVE
 CHANGED. PLEASE CORRELATE THE RISER DIAGRAMS WITH OTHER
 SHEETS. SECTION 106.1.1.
  
 107. SHT P3.6.2 THE WATER RISER DESIGNATIONS HAVE
 CHANGED. PLEASE CORRELATE THE RISER DIAGRAMS WITH OTHER
 SHEETS. SECTION 106.1.1.
  
 108. SHT P3.6.2 THE COLD WATER RISER LINE FOR THE CHUTE
 WASHDOWN APPEARS TO BE LOCATED OUTSIDE THE BUILDING.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 109. SHT P3.7.2 THE COLD WATER RISER LINE FOR THE CHUTE
 WASHDOWN APPEARS TO BE LOCATED OUTSIDE THE BUILDING.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 110. SHT 3.7.2 NOTE INDICATES HOT WATER "UP TO" WATER
 HEATERS, BUT FROM THE HOT RISER DIAGRAM, IT APPEARS
 THAT IT SHOULD READ HOT WATER "DOWN FROM" THE WATER
 HEATERS. PLEASE CLARIFY. SECTION 106.1.1.
  
 111. SHT P3.7.2WATER RISER 11 SHOWS 2 SLEEVES FOR HOT
 & COLD WATER, BUT THE GAS PIPING ALSO IS INDICATED AS
 RUNNING ALONG SIDE OF THE WATER.PLEASE CLARIFY.
 SECTION 106.1.1.
  
 112. SHT P3.8.1 THE WATER SUPPLY ROOF PLAN EAST SECTION
 SHOWS NO WATER. PLEASE CLARIFY. SECTION 106.1.1. PLEASE
 INDICATE WHERE THE WATER IS LOCATED.
  
 113. SHT P3.8.2 NOTE BY THE WATER HEATER ROOM ABOVE
 G.W.H. - 1 IS NOT LEGIBLE. SECTION 106.1.1. PLEASE MAKE
 ALL INFORMATION LEGIBLE.
  
 114. SHT P4.1.1 UNIT "C2" NO COLD WATER SUPPLY TO
 KITCHEN SINK IS SHOWN. SECTION 106.1.1. PLEASE SHOW
 COLD WATER SUPPLY.
  
 115. SHT P4.1.1 UNIT "C2 MIRRORED" NO COLD WATER SUPPLY
 TO KITCHEN SINK IS SHOWN. SECTION 106.1.1. PLEASE SHOW
 COLD WATER SUPPLY.
  
 116. SHT P4.1.1 3RD FLOOR TOILET ROOMS. THE DRINKING
 FOUNTAIN WATER SUPPLY IS SHOWN CONNECTING TO THE HOT
 WATER. PLEASE CLARIFY. SECTION 106.1.1.
  
 117. SHT P4.1.2 THE HOT & COLD WATER DESIGNATIONS ARE
 NOT SHOWN. PLEASE INDICATE HOT & COLD WATER LINES.
 SECTION 106.1.1.
  
 118. SHT P4.1.3 THE HOT & COLD WATER DESIGNATIONS ARE
 NOT SHOWN. PLEASE INDICATE HOT & COLD WATER LINES.
 SECTION 106.1.1.
  
 119. SHT P4.1.5 NO WATER RISER DIAGRAMS FOR THE TPICAL
 UNIT "TH3" HAS BEEN SUBMITTED. PLEASE SUBMIT THE WATE
 RISER DIAGRAM. SECTION 106.3.5.1.3(3)(10)(13).
  
 120. SHT P5.1.1 THE SANITARY RISER ISOMETRIC DOES NOT
 REFLECT THE FLOOR PLAN IN FIVE AREAS. SECTION 1-6.1.1.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
  
 121. SHT P5.1.1 THE WASH MACHINE SHALL CONNECT TO A
 BRANCH DRAIN A MINIMUM 3" IN DIAMETER. SECTION 406.3.
 2" SHOWN PLEASE CORRECT.
  
 122. SHT P5.1.1 VARIOUS NOTES INDICATE VENT TO CONNECT
 TO THE NEAREST RISER ABOVE. PLEASE INDICATE WHICH RISER
 EACH VENT WILL CONNECT TO AND MAKE SURE THE RISER
 INDICATED REFLECTS THE VENT FROM BELOW CONNECTING TO
 THAT RISER. TABLE 916.1.--(ONE VENT STATES "CONNECT
 TO 2" VENT AT RISER #12 ABOVE". RISER #12 DOES NOT SHOW
 THE VENT CONNECTING FROM BELOW). PLEASE CLARIFY.
  
 123. SHT P5.1.2 THE SANITARY RISER DOES NOT REFLECT THE
 FLOOR PLAN IN APPROXIMATELY 17 PLACES. SECTION 106.1.1.
 PLEASE RECHECK THE RISER DIAGRAM AND MAKE SURE IT
 REFLECTS THE FLOOR PLAN.
  
 124. SHT P5.1.2 RISER #8 SHOW THE EXTENDED RUN TO THE
 BASE OF THE RISER TO REFLECT THE FLOOR PLAN. SECTION
 106.1.1.
  
 125. SHT P5.1.2 THE WASH MACHINES SHALL CONNECT TO A
 BRANCH DRAIN A MINIMUM OF 3" IN DIAMETER. SECTION
 406.3. PLEASE CHANGE PIPE SIZE.
  
 126. SHT P5.1.2 THE DRAINAGE FIXTURE UNITS FOR A 4"
 FLOOR DRAIN IS 6DFU, NOT 2DFU AS SHOWN. TABLE 709.2.
 PLEASE CORRECT FIXTURE UNITS FOR ALL FLOOR DRAINS PER
 TABLE AND RECHECK THE FIXTURE UNITS AS THEY ACCUMULATE
 IN THE SYSTEM.
  
 127. SHT P5.1.2NO FLOOR PLAN PIPING IS SHOWN FOR THE
 TOWNHOUSE UNITS. SECTION 106.1.2. PLEASE PROVIDE THE
 FLOOR PLAN PIPING FOR UNITS. SECTION
 105.35.1.3(1)(2)(3)(4)(5)(10).
  
 128. SHT P5.1.2 INDICATE WHERE ALL VENTS CONNECT ABOVE
 THE UNITS. WILL THEY VENT THRU ROOF OR CONNECT TO A
 VENT STACK ABOVE? SECTION 106.1.2. IF THEY CONNECT TO A
 RISER ABOVE, PLEASE INDICATE WHICH RISER AND THE RISER
 SHALL REFLECT THE VENT CONNECTION.
  
 129. SHT P5.1.3 ALL RISERS. INDICATE THE FLOOR LEVELS
 ON THE RISERS. SECTION 106.1.2.
  
 130. SHT P5.1.3 RISER DIAGRAM #2 DOES NOT REFLECT THE
 FLOOR PLAN DOWNSTREAM OF THE SHOWER ON LEVELS 4 THRU 7
 AND AT THE BASE OF THE STACK, (4" 40 DFU). SECTION
 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS
 THE PIPING ON THE FLOOR PLAN.
  
 131. SHT P5.1.3 RISER DIAGRAM #3 DOES NOT REFLECT THE
 FLOOR PLAN AT THE BASE OF ONE KITCHEN SINK STACK AND
 THE KITCHEN SINK ARE ON THE RISER BY THE WASH MACHINES.
 SECTION 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM
 REFLECTS THE PIPING ON THE FLOOR PLAN.
  
 132. SHT P5.1.3 RISER DIAGRAM #4 DOES NOT REFLECT THE
 FLOOR PLAN . THE LAV SHALL CONNECT PRIOR TO THE SHOWER
 3RD FLOOR AT JACUZZI BATHROOM. DOWNSTREAM OF THE BASE
 OF THE TUB BATH STACK DOES NOT REFLECT THE FLOOR PLAN.
 VENTS ARE REQUIRED FOR THE LAVS BY THE WATER CLOSET IN
 THE JACUZZI BATH. SECTIONS 106.1.1 & 901.2.1. PLEASE
 MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE
 FLOOR PLAN.
  
 133. SHT P5.1.3 RISER DIAGRAMS #5 AND #7 DO NOT REFLECT
 THE FLOOR PLAN AT THE KITCHEN SINK. SECTION 106.1.1.
 PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING
 ON THE FLOOR PLAN.
  
 134. SHT P5.1.3 RISER DIAGRAM #6 DOES NOT REFLECT THE
 FLOOR PLAN AT THE TUB BATH 3RD FLOOR, AND FOR THE LAV
 ARM IN THE TUB BATH AT THE END OF THE RISER ALL FLOORS
 AND AT THE OFFSET DOWNSTREAM OF THE JACUZZI/LAV RISER.
 SECTION 1-6.1.1. PLEASE MAKE SURE THE RISER DIAGRAM
 REFLECTS THE PIPING ON THE FLOOR PLAN.
  
 135. SHT P5.1.3 RISER DIAGRAM #8 DOES NOT REFLECT THE
 FLOOR PLAN. WASH MACHINE RISERS TO CONNECT PRIOR TO
 JACUZZI/LAV RISER, AND THE LAV ARM IN THE LAST TUB BATH
 ON THE 3RD FLOOR. SECTION 106.1.1. PLEASE MAKE SURE THE
 RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR PLAN.
  
 136. SHTS P5.1.3, P5.1.4 & P5.1.5 PLEASE INDICATE THE
 FLOOR LEVELS ON ALL RISER DIAGRAMS. SECTION 106.1.2.
  
 137. SHT P5.1.4 RISER DIAGRAM #9 KITCHEN SINK ARMS DO
 NOT REFLECT THE FLOOR PLAN. SECTION 106.1.1. PLEASE
 MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE
 FLOOR PLAN.
  
 138. SHT P5.1.4 RISER DIAGRAM #12 DOES NOT REFLECT THE
 FLOOR PLAN WHERE THE SHOWER BATH BRANCH CONNECTS TO THE
 BUILDING DRAIN. SECTION 106.1.1. PLEASE MAKE SURE THE
 RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR PLAN.
  
 139. SHT P5.1.4 RISER DIAGRAM #13 TOTAL DFUS ARE 25,
 NOT 10 AS SHOWN. TABLE 709.2. PLEASE SHOW CORRECT
 DFUS.
  
 140. SHT P5.1.4 RISER DIAGRAM 16/20 DOES NOT REFLECT
 THE FLOOR PLAN AT THE WASH MACHINE BRANCH LINE, NOR AT
 THE WATER CLOSET/ LAV PIPING DOWNSTREAM OF THE DOUBLE
 LAV ON THE THIRD FLOOR.--THE JACUZZI TUB IS NOT
 IDENTIFIED ON THE THIRD FLOOR.--PLEASE INDICATE THE
 SYMBOL USED FOR THE DRAIN DOWNSTREAM OF CCC-1. SYMBOL
 NOT SHOWN ON THE PLUMBING LEGEND.--DRAIN FOR CCC-2
 INDICATED AS 3" 4" PLEASE CLARIFY. SECTIONS 106.1.2 &
 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS
 THE PIPING ON THE FLOOR PLAN.
  
 141. SHT P5.1.5 RISER DIAGRAM #18 DOES NOT REFLECT THE
 FLOOR PLAN AT THE BASE OF BOTH WASH MACHINES RISERS.
 THE FLOOR PLAN SHOWS THE LAUNDRY BOX BETWEEN THE
 RISERS. PLEASE CLARIFY. SECTION 106.1.1. PLEASE MAKE
 SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR
 PLAN.
  
 142. SHT P5.1.5 RISER DIAGRAM #19 DOES NOT REFLECT THE
 FLOOR PLAN AT THE BASE OF THE WASH MACHINE RISERS FOR
 THE OFFSETS AND THE LAUNDRY BOX SHOWN BETWEEN THE
 RISERS. NOR DOES IT REFLECT THE FLOOR PLAN WHERE THE
 BRANCH CONNECTION FOR THE JACUZZI TUB/LAV TO DRAIN LINE
 AS WELL AS THE LAV ARM IN THE SHOWER BATH. SECTION
 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS
 THE PIPING ON THE FLOOR PLAN.
  
 143. SHT P5.1.5 RISER DIAGRAM #21 DOES NOT REFLECT THE
 FLOOR PLAN AT THE BRANCH LINE TO THE
 KITCHEN/LAV/JACUZZI & AT THE WASH MACHINE RISERS WHERE
 THEY CONNECT TO THE DRAIN LINE. SECTION 106.1.1. PLEASE
 MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE
 FLOOR PLAN.
  
 144. SHT P5.1.5 RISER DIAGRAM #25 DOES NOT REFLECT THE
 FLOOR PLAN AT THE BASE OF THE WASH MACHINE STACK, OFF
 SET NOT SHOWN AND JACUZZI TUB IS NOT LEFT OF STACK.
 SECTION 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM
 REFLECTS THE PIPING ON THE FLOOR PLAN.
  
 145. SHT P5.1.5 RISER DIAGRAM #26 DOES NOT REFLECT THE
 FLOOR PLAN AT THE WASH MACHINE STACK BASE, (LAUNDRY BOX
 SHOWN BETWEEN THE W/M STACKS), AND AT THE LAV ARM IN
 THE TUB BATH ALL FLOORS.--A DRY HORIZONTAL VENT IS
 SHOWN UPSTREAM OF THE W/C AT THE BASE OF THE W/C STACK.
 SECTION 106.1.1. DRY HORIZONTAL VENTS ARE NOT APPROVED.
 PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING
 ON THE FLOOR PLAN AND MEETS CODE REQUIREMENTS. SECTION
 905.3.
  
 146. SHT P5.1.6 SANT RISERS TH3A, TH3B, TH3C & TH3D DO
 NOT REFLECT THE FLOOR PLANS. THE WASH MACHINE SHALL
 CONNECT TO A BRANCH LINE A MINIMUM 3" IN DIAMETER PER
 SECTION 406.3. SECTION 106.1.1. PLEASE MAKE SURE THE
 RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR PLAN.
  
 147. SHT P5.2.1 ALL CONDENSATE RISER VENTS SHOW "TO
 NEAREST SANT. VENT". THIS IS NOT APPROVED. VENTS FOR
 CONDENSATE SHALL TERMINATE SEPARATELY FROM THE SANITARY
 VENTS.THESE ARE TWO SEPARATE SYSTEMS AND SHALL NOT BE
 CROSS CONNECTED.--UNABLE TO REVIEW THE MOST
 UPSTREAM SECTION OF THE RISER UPSTREAM OF RD #1 AT THE
 BASE OF THE CONDENSATE RISER #1. THE INFORMATION IS NOT
 ACCESSIBLE AS THE PLANS DO NOT OPEN UP TO SHOW THAT
 INFORMATION.--THE STORM/CONDENSATE RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN IN MANY AREAS. SECTION
 106.1.2 & SECTION 106.1.1. PLEASE MAKE SURE THE RISER
 DIAGRAM REFLECTS THE PIPING ON THE FLOOR PLAN.
  
 148. SHT P5.2.2 STORM/CONDENSATE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 106.1.1. PLEASE MAKE
 SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR
 PLAN.
  
 149. SHT P5.2.3STORM/CONDENSATE RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. SECTION 106.1.1. PLEASE
 MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE
 FLOOR PLAN.
  
 150. SHT P6.1.1 RISER DOES NOT REFLECT THE FLOOR PLAN.
 SHOW ALL OFFSETS, CONNECTIONS TO MAINS ETC TO REFLECT
 THE FLOOR PLAN.--2 COLD LINES FROM PUMP ROOM AND
 AROUND THE 2ND FLOOR SHOWN ON THE FLOOR PLAN ARE NOT ON
 THE RISER DIAGRAM. SECTION 106.1.1. PLEASE MAKE SURE
 THE RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR
 PLAN. --RPZV BACKFLOW SHALL BE LOCATED AS CLOSE TO
 THE METER AS POSSIBLE ON PRIVATE PROPERTY.
  
 151. SHT P6.1.2 RISER DOES NOT REFLECT THE FLOOR PLAN
 WHERE SOME RISERS OR DROPS CONNECT TO THE MAIN, AT
 OFFSETS AND AT THE TOP OF RISER 23.--CHECK VALVES
 ARE NOT REQUIRED AT THE BASE OF THE DROPS. (HOW CAN
 RISERS BE DRAINED IF REQUIRED FOR SERVICE)?SECTION
 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS
 THE PIPING ON THE FLOOR PLAN.
  
 152. SHT P6.1.3 UNIT "C1" WATER HAMMER ARRESTOR IS
 REQUIRED AT THE COLD WATER TO THE WASH MACHINE. SECTION
 604.9.
  
 153. SHT P6.1.3 TYPICAL UNITS C2, C2 MIRRORED, C3, C3A,
 C4, & C5DO NOT REFLECT THE FLOOR PLAN. SECTION
 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS
 THE PIPING ON THE FLOOR PLAN.
  
 154. SHT P6.1.3 IN UNIT "C3", A WATER HAMMER ARRESTOR
 IS REQUIRED AT THE ICE MAKER. SECTION 604.9.
  
 155. SHT P6.1.3 3RD FLOOR TOILET ROOMS DO NOT REFLECT
 THE FLOOR PLAN. SECTION 106.1.1. PLEASE MAKE SURE THE
 RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR PLAN.
  
 156. SHT P6.1.3 TYPICAL UNIT "TH3" A WATER RISER
 DIAGRAM REQUIRED. SECTION 106.3.5.1.3(3)(10)(13).
  
 157. SHT P6.1.4 ALL UNITS. SUBMIT FLOOR PLANS FOR THESE
 UNITS. SECTION 106.1.2--THE RISERS SHALL REFLECT
 THE FLOOR PLANS SUBMITTED.--SOME RISERS MISSING
 WATER HAMMER ARRESTORS AT DISHWASHERS OR ICE MAKERS.
 SECTION 604.9.
  
 158. SHT P6.1.5 A SEPARATE GAS PERMIT IS REQUIRED.
 SUBMIT THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - INDICATE ALL CUT SECTIONS DOWNSTREAM
 OF THE REGULATOR FOR THE GAS WATER HEATERS. FINAL DROP
 LENGTH NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. - SIZE OF PIPE
 SHOWS 1-1/4" REDUCING TO 1" THEN BACK TO 1-1/4". PLEASE
 CLARIFY.--ALSO SHOW THE MATERIAL TYPE OF THE
 VENTING FROM THE REGULATORS. (MATERIAL SHALL BE NON
 COMBUSTABLE).
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - ALSO SHOW THE TOTAL
 DISTANCE FROM THE REGULATOR TO THE MOST REMOTE OUTLET
 DOWNSTREAM OF THE REGULATOR FOR THE GAS WATER HEATERS.
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - PLEASE SUBMIT AN
 APPROVED TABLE FOR 7"W.C. OR INDICATE 1/2PSI DOWNSTREAM
 OF THE REGULATOR. FBC-2004 FUEL GAS HAS NO 7" W.C.
 TABLES TO VERIFY PIPE SIZES.
  
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. SUBMIT MANUF. SPECIFICATION SHEETS FOR THE GAS
 REGULATORS. INDICATE MODEL NUMBER FOR EACH REGULATOR.
 --A UNION IS REQUIRED NEXT TO THE REGULATOR NOT AT
 THE END OF A RUN. (SEE GAS WATER HEATERS & HVAC SYSTEM
 REGULATORS).
  
 159. SHT P9.1.1 ROOFTOP EQUIPMENT. CONDENSATION
 CONNECTION DETAIL INDICATES A LINE TO DISCHARGE THAT
 RUNS BELOW THE ROOF & CONNECTS TO NEAREST CATCH BASIN,
 BUT SHT P2.7.2 SHOWS RTU-2 DISCHARGING TO NEAREST ROOF
 DRAIN. PLEASE CORRELATE DETAIL AND ROOF PLAN. SECTION
 106.1.1.
  
 160. THERE IS A MOP SINK INDICATED IN ROOM 339 THAT HAS
 NO SANITARY OR WATER PIPING SHOWN. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 161. SHT A-001B INDEX OF DRAWINGS VOL II INDICATES
 IRRIGATION PLANS. NO IRRIGATION PLANS FOUND. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 162. ENERGY CALCULATION INDICATE HEAT PUMPS FOR THE
 WATER HEATERS UNDER THE WATER HEATER COMPLIANCE AND FOR
 THE INPUT DATA REPORT. PLANS INDICATE GAS WATER
 HEATERS. PLEASE CORRELATE PLANS AND ENERGY
 CALCULATIONS. SECTION 106.1.1.
  
 163. THE PLANS DO NOT APPEAR TO BE 100% COMPLETE AT
 THIS TIME. MORE COMMENTS MAY FOLLOW WHEN PLANS ARE
 COMPLETE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-05 Cont ID  
Sent By eschneid Date 2007-09-05 Time 19:05 Rev Time 0.00
Received By eschneid Date 2007-09-05 Time 19:05 Sent To  
Notes
2007-09-05 19:06:31FAILED
  
 RESPOND TO COMMENTS IN WRITING.
  
 1) PER ORDINANCE NO. 3914-05, PRIOR TO THE ISSUANCE OF
 THE FIRST BUILDING PERMIT, THE APPLICANT/OWNER SHALL:
 A) RECORD PUBLIC ACCESS EASEMENTS FOR ROADWAYS AND
 ADJACENT SIDEWALKS THROUGHOUT THE SITE.THIS MAY BE
 DONE ON A PLAT OR SEPARATE INSTRUMENT.
 B) RECORD A RESTRICTIVE DEED OR COVENANT PREVENTING THE
 GATING OF ANY OF THE ROADWAYS IN THE MIZNER LAKES RPD.
 C) RECORD A MAINTENANCE AGREEMENT FOR THE PAVERS AND
 LANDSCAPING IN THE HANK AARON DRIVE TRAFFIC OVAL.
 D) RECORD A MAINTENANCE AGREEMENT FOR THE LAKE PATH AND
 LANDSCAPING ADJACENT TO THE MIZNER LAKES RPD.
  
 2) PLEASE NOTE THAT THE MINOR AMENDMENT SUBMITTED TO
 REVISE THE APPROVED PLANS TO MATCH THE BUILDING PERMIT
 PLANS HAS NOT BEEN APPROVED AS THE SUBMITTED LANDSCAPE
 PLANS DID NOT MATCH THE ENGINEERING AND SITE PLANS.
 NOTE THAT THE LANDSCAPE PLANS SUBMITTED WITH THIS
 PERMIT DO MATCH THE OTHER PLANS.THIS PERMIT WILL NOT
 BE APPROVED UNTIL THE MINOR AMENDMENT IS APPROVED.
  
 3) THE PARKING SPACE DETAILS FROM CIVIL PLANS SHEET
 C-18 (SUBMITTED WITH PERMIT NO. 07040152) SHALL BE
 INCLUDED ON THE SITE PLAN.
  
 4) IS THE SPACE IN THE NORTHWEST CORNER OF THE GARAGE A
 LOADING ZONE OR A PARKING SPACE?IT IS LABELED
 DIFFERENTLY ON DIFFERENT SHEETS. [REPEAT COMMENT]
  
 5) PROVIDE WRITTEN VERIFICATION FROM THE CITY'S
 ENGINEERING SERVICES AND PARKING DEPARTMENTS THAT THE
 CITY RECOGNIZES THE SAME NUMBER OF PARALLEL PARKING
 SPACES ON HANK AARON DRIVE AS SHOWN ON THE SUBMITTED
 PLANS.PROVIDE THE DIMENSIONS OF THE SPACES ON THE
 PLANS.THESE SPACES ARE TO BE INSTALLED/MAINTAINED
 MEETING THE MINIMUM CITY REQUIREMENTS. [REPEAT
 COMMENT]
  
 6) THE WATER FEATURE SHOWN ON THE PLANS APPROVED BY
 ORDINANCE NO. 3914-05 IS SHOWN AS A PUMP HOUSE ON THE
 SUBMITTED PLANS.WHILE STAFF PREFERS TO SEE A
 COMMUNITY AMENITY AT THIS LOCATION, A MINOR AMENDMENT
 APPROVAL IS REQUIRED FOR THE NEW LAYOUT.THE PUMP
 HOUSE NEEDS TO BE SCREENED BY A HEDGE ON ALL SIDES.
 [REPEAT COMMENT]
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.