Plan Review Details - Permit 07080065
Plan Review Stops For Permit 07080065
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-29 Cont ID  
Sent By mjacobs Date 2008-01-29 Time 08:48 Rev Time 0.00
Received By mjacobs Date 2008-01-28 Time 15:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-24 Cont ID  
Sent By mjacobs Date 2007-12-24 Time 09:18 Rev Time 0.00
Received By mjacobs Date 2007-12-24 Time 06:47 Sent To  
Notes
2007-12-24 09:18:39 
 BUILDING PLAN REVIEW
 PERMIT: 07010426
 ADD: 4619 GEORGIA AVE.
 CONT: STONE IMAGE INC.
 TEL: (561)547-1177
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD -12/24/07
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 **THE ADDRESS ON THE APPLICAION WAS CHANGED TO 4619
 GEORGIA AVE HOWEVER, THE PLANS STILL SHOW THE ADDRESS
 AS ?604 BRADLEY STREET? CLARIFY.**
 NOTE:THIS PROJECT WAS SUBMITTED PREVIOUSLY UNDER
 APPLICATION #07010426 WITH THE ADDRESS AS 4619 GEORGIA
 AVE. THE SAME PROJECT IS NOW SUBMITTED WITH A NEW
 DIFFERENT APPLICATION #07080065 AND 604 BRADLEY ST AS
 THE ADDRESS. PLEASE RECTIFY THIS SITUATION WITH THE
 FRONT COUNTER WHEN RESUBMITTING.
 2)OK
 3) OK
 4) OK.
 5)OK
  
 **NEW**
 **SEE NOTE (A) BELOW.
 INDICATE ON THE DRAWINGS THE INTERIOR FINISHES OF THE
 NEW STRUCTURE. TOILET AND BATHING ROOM FLOORS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE THAT EXTENDS
 UPWARD ON TO THE WALLS AT LEAST 6 INCHES.WALL WITHIN
 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE THE SAME
 TYPE OF SURFACES MENTION ABOVE. FBC1210. NOTE: DRYWALL
 WITH PAINT IS NOT CONSIDERED A HARD SURFACE. INDICATE
 THE TYPE OF FINISH IN THE BATHROOM FROM THE FINISH
 FLOOR TO AT LEAST 4 FEET ABOVE.
  
 6)OK
  
 **NEW**
 **NO RESPONSE NOT ADDRESSED**
 A)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASE ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.INTERIOR WALL AND
 CEILING FINISH SHALL HAVE A FLAME SPREAD INDEX NOT
 GREATER THAN THAT SPECIFIED IN TABLE 803.5.
  
 B)OK,
 C)OK
 D)OK
  
 E)ROOFING PERMIT; ONLY CHECKED ITEMS APPLY (SEE
 POLICY)
  
 _XX___1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 _OK__2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY:
 MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF
 EACH ROOF TYPE
  
 _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 _XX_6.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected].

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-08 Cont ID  
Sent By mjacobs Date 2007-09-08 Time 07:42 Rev Time 0.00
Received By mjacobs Date 2007-09-07 Time 16:47 Sent To  
Notes
2007-09-07 17:56:54 
 BUILDING PLAN REVIEW
 PERMIT07080065
 ADD: 604 BRADLEY ST.
 CONT: STONE IMAGE INC.
 TEL: (561)547-1177
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 NOTE:THIS PROJECT WAS SUBMITTED PREVIOUSLY UNDER
 APPLICATION #07010426 WITH THE ADDRESS AS 4619 GEORGIA
 AVE. THE SAME PROJECT IS NOW SUBMITTED WITH A NEW
 DIFFERENT APPLICATION #07080065 AND 604 BRADLEY ST AS
 THE ADDRESS. PLEASE RECTIFY THIS SITUATION WITH THE
 FRONT COUNTER WHEN RESUBMITTING.
  
 2)OK
  
 3) OK
  
 4) OK.
  
 5)FBC. 1203.4.2.1 ROOMS CONTAINING BATHTUBS, SHOWERS,
 SPAS AND SIMILAR BATHING FIXTURES SHALL BE MECHANICALLY
 VENTILATED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, MECHANICAL.
 **NEW**
 INDICATE ON THE DRAWINGS THE INTERIOR FINISHES OF THE
 NEW STRUCTURE. TOILET AND BATHING ROOM FLOORS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE THAT EXTENDS
 UPWARD ON TO THE WALLS AT LEAST 6 INCHES.WALL WITHIN
 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE THE SAME
 TYPE OF SURFACES MENTION ABOVE. FBC1210. NOTE: DRYWALL
 WITH PAINT IS NOT CONSIDERED A HARD SURFACE. INDICATE
 THE TYPE OF FINISH IN THE BATHROOM FROM THE FINISH
 FLOOR TO AT LEAST 4 FEET ABOVE.
  
 6)OK
  
 **NEW**
 A)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASE ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.INTERIOR WALL AND
 CEILING FINISH SHALL HAVE A FLAME SPREAD INDEX NOT
 GREATER THAN THAT SPECIFIED IN TABLE 803.5.
 B)ON SHEET A-2 DETAIL #1 SHOW THE PLYWOOD FASTENERS
 AS 8D RING SHANK NAILS, HOWEVER IN THE TABLE WITH THE
 SIZE, SPACING AND TYPE OF NAILS HAS 8D PLANE SHANK
 NAILS. WOOD STRUCTURAL PANEL SHEATHING SHALL BE
 FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS.
 CLARIFY.
  
 C)SHOW THE ACCESSIBLE ROUTE TO THE NEW BUILDING.
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING
 WITH 11-4.3 SHALL CONNECT ACCESSIBLE BUILDING OR
 FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND
 ELEMENTS WITHIN THE BUILDING OR FACILITY.
  
 D)11-4.1.3(3) GROUND & FLOOR SURFACES ALONG
 ACCESSIBLE ROUTES & IN ACCESSIBLE ROOMS & SPACES SHALL
 COMPLY WITH 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE) A
 STATIC COEFFICIENT OF FRICTION OF 0.6 IS RECOMMENDED
 FOR ACCESSIBLE ROUTES AND 0.8 FOR RAMPS.
  
 E)ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 _XX___1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 _XX__2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY:
 MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF
 EACH ROOF TYPE
  
 _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 ____6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.
  
 _XX_7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected].

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-03-12 Cont ID  
Sent By dpalmer Date 2008-01-18 Time 18:29 Rev Time 0.00
Received By dpalmer Date 2008-01-18 Time 18:28 Sent To  
Notes
2008-03-12 18:29:43PAST ON 1/18/08, ENTERED IN COMPUTER 3/12

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-11 Cont ID  
Sent By dpalmer Date 2007-12-11 Time 17:06 Rev Time 0.00
Received By dpalmer Date 2007-12-11 Time 16:55 Sent To  
Notes
2007-12-11 17:06:29**** DENIED 2ND REVIEW ****
  
 ** AS STATED ON PREVIOUS REVIEW, PLEASE SEE PERMIT #
 07010426 IS STILL ACTIVE.
  
 1) NOTE: PLEASE SEE THE NEW LOAD SHOWN ON SHEET A-1 IS
 SHOWN AS 1.86 AMPS, HOWEVER THE NEW LOAD SHOWN ON SHEET
 A-2 IS 7.5AMPS.
 PLEASE ADJUST LOAD CALCULATIONS TO SHOW NEW LOADS BEING
 ADDED TO EXISTING PER 220.87
  
 2) NOTE: PLEASE SEE THE *EQUIPMENT GROUNDING CONDUCTOR*
 SHOWN FROM EXISTING PANEL TO NEW MAIN AT DETACHED
 BUILDING AND FROM DISCONNECT TO PANEL IS SHOWN WITH A
 CONDUCTOR SIZE WHICH IS NOT STANDARD PER AWG (AMERICAN
 WIRE GAUGE) OR 310.16.
 PLEASE KNOW THE MINIMUM SIZE NEEDS TO BE #10 PER
 250.122, 310.16.
 PLEASE KNOW THIS IS AN ITEM WHICH COULD BE *REDLINED*
 ON PLANS.
 PLEASE ADDRESS COMMENT #1 ABOVE.
  
 ** PLEASE CALL IF ALL OTHER COMMENTS AND ALL OTHER
 TRADES PASS REVIEWS. A *PROVISO* MAY BE SET IN PLACE
 FOR PERMIT ISSUANCE. THIS IS ONLY IF ALL OTHER TRADES
 PASS THEIR REVIEWS. IF THERE ARE COMMENTS FOR ANY OTHER
 TRADES AND PLANS ARE GOING BACK FOR CORRECTIONS, PLEASE
 ADDRESS COMMENT #1 AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-29 Cont ID  
Sent By dpalmer Date 2007-08-29 Time 19:00 Rev Time 0.00
Received By dpalmer Date 2007-08-29 Time 19:00 Sent To  
Notes
2007-08-29 19:00:31** DENIED **
  
 1) NOTE: PLEASE SEE TWO REVIEWS WERE DONE UNDER PERMIT
 NUMBER 07010426 WHICH IS STILL AN ACTIVE PERMIT. IT IS
 COMPLETELY UNCLEAR WHY A NEW PERMIT APPLICATION FOR THE
 SAME SCOPE OF WORK IS BEING SUBMITTED WHEN THE OTHER
 PERMIT APPLICATION IS STILL ACTIVE.
  
 ** PLEASE SEE SOME COMMENTS FROM THE REVIEWS DONE UNDER
 THE PERMIT # ABOVE IS STILL IN NEED OF ADDRESSING.
  
 2) NOTE: PLEASE COMPLETE RISER WITH ALL FEEDERS AND
 GROUNDING CONDUCTORS TO THE DETACHED STRUCTURE.
 310.16,240.4,215.5, ETC.
  
 3) NOTE: PLEASE SEE MISSING THE REQUIRED GROUNDING
 ELECTRODE SYSTEM AT THE DETACHED STRUCTURE PER 250.32,
 250.50.
  
 4) NOTE: PLEASE SEE THE MISSING OVER CURRENT PROTECTION
 IN THE EXISTING 150AMP RATED PANEL WHICH IS FEEDING THE
 NEW SUB PANEL.
 THERE ARE TOO MANY SECTIONS TO NOTE WHICH REQUIRES
 THIS.
 NEC 2005.
  
 5) NOTE: PLEASE SEE THE PANELS DO NOT SUPPLY THE
 INFORMATION NEEDED FOR REVIEW OF LOADS, EXISTING AND
 NEW, THE CONDUCTORS ETC WHICH IS NOT COMPLETE.
 FBC 106.3.5.1.2
 NEC 215.5,240.4,310.16,2
  
 6) NOTE: PLEASE SEE ONLY ONE SET OF PLANS FOR ALL ITEMS
 WAS SUBMITTED.
 ONLY ONE SURVEY,
 ONLY ONE PLAN,
 ONLY ONE LANDSCAPE PLAN.
 PLEASE SUBMIT TWO COPIES OF ALL DOCUMENTS AS REQUIRED
 PER FBC 106.1.1, 106.1.2
  
 7) NOTE: PLEASE SEE THE SIGNATURE ON THE SURVEY IS A
 *RUBBER-STAMP* WHICH IS NOT PERMITTED PER FS 472.025.
 MUST BE AN ORIGINAL SIGNATURE.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 8) NOTE: PLEASE SEE THE SEAL ON THE LANDSCAPE ARCHITECT
 PLANS IS NOT VALID UNDER THE REQUIREMENTS FROM THE
 STATE AND FLORIDA ADMINISTRATIVE CODE, FAC 61G1-16.002.
 (2INCH MIN SEAL).
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-02-13 Cont ID  
Sent By mawillia Date 2008-02-13 Time 17:18 Rev Time 0.00
Received By mawillia Date 2008-02-13 Time 16:52 Sent To  
Notes
2008-02-13 17:09:50*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEET A-1 STAMPED, INITIALED, AND
 DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-12-28 Cont ID  
Sent By mawillia Date 2007-12-28 Time 14:48 Rev Time 0.00
Received By mawillia Date 2007-12-28 Time 14:30 Sent To  
Notes
2007-12-28 14:36:57*****DENIED*****
  
 THE FOLLOWING COMMENTS (OF 6) TAKEN FROM THE PREVIOUS
 FIRE PLAN REVIEW COMMENT STILL NEED TO BE ADDRESSED:
  
 1.THE PERMIT NUMBER REGISTERS THE ADDRESS LOCATION AS
 4619 GEORGIA AVENUE AND NOT AS 604 BRADLEY STREET AS
 INDICATED ON THE APPLICATION OR ON THE SUBMITTED PLAN
 SHEETS.
  
 2.IF THE PROJECTED WORK SITE IS ADDRESSED ON BRADLEY
 STREET,THE NUMERICAL ADDRESS SHALL BE AN ODD NUMBER
 SINCE IT IT IS ON THE NORTH SIDE OF THE STREET.
  
 6.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR
 THIS STRUCTURE IN TERMS OF CLASS A, CLASS B, OR CLASS
 C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-02 Cont ID  
Sent By mawillia Date 2007-10-02 Time 12:49 Rev Time 0.00
Received By mawillia Date 2007-10-02 Time 11:31 Sent To  
Notes
2007-10-02 11:34:35*****DENIED*****
  
  
 1.THE PERMIT NUMBER REGISTERS THE ADDRESS LOCATION AS
 4619 GEORGIA AVENUE AND NOT AS 604 BRADLEY STREET AS
 INDICATED ON THE APPLICATION OR ON THE SUBMITTED PLAN
 SHEETS.
  
 2.IF THE PROJECTED WORK SITE IS ADDRESSED ON BRADLEY
 STREET,THE NUMERICAL ADDRESS SHALL BE AN ODD NUMBER
 SINCE IT IT IS ON THE NORTH SIDE OF THE STREET.
  
 3.ON SHEET A-1,INCLUDE EAST, WEST, NORTH, AND SOUTH
 TO THE APPROPIATE EXTERIOR ELEVATIONS IN ADDITION TO
 WHAT IS LISTED.
  
 4.ON SHEET A-1 UNDER THE FLOOR PLAN LAYOUT, INSERT
 "NFPA 101," IN FRONT OF LIFE SAFETY CODE TO PREVENT
 CONFUSION WITH NFPA-70 (NEC).
  
 5.ON SHEET A-1 IN THE ELECTRICAL NOTES, REFERENCES
 ARE MADE TO SMOKE DETECTORS, BEDROOMS, AND SLEEPING
 AREAS.ARE THESE REFERENCES RELEVANT TO THIS SCOPE OF
 WORK?
  
 6.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR
 THIS STRUCTURE IN TERMS OF CLASS A, CLASS B, OR CLASS
 C.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-05-20 Cont ID  
Sent By lmartine Date 2009-05-20 Time 11:42 Rev Time 0.00
Received By lmartine Date 2009-05-19 Time 11:41 Sent To  
Notes
2009-05-20 11:42:35IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-12 Cont ID  
Sent By adarroug Date 2008-03-12 Time 15:10 Rev Time 0.00
Received By adarroug Date 2008-03-12 Time 15:10 Sent To  
Notes
2008-03-12 15:13:24TO "COMM" BD#57

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-17 Cont ID  
Sent By adarroug Date 2008-01-17 Time 09:19 Rev Time 0.00
Received By adarroug Date 2008-01-17 Time 09:19 Sent To  
Notes
2008-01-17 09:22:34TO "COMM" BD#51

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 09:58 Rev Time 0.00
Received By adarroug Date 2007-12-07 Time 09:58 Sent To  
Notes
2007-12-07 10:00:51TO "COMM" BD#51

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-02 Cont ID  
Sent By mawillia Date 2007-10-02 Time 11:31 Rev Time 0.00
Received By mawillia Date 2007-08-06 Time 15:00 Sent To  
Notes
2007-08-29 14:34:18TO "COMM" BD#21
2007-08-06 15:02:22WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-05-21 Cont ID  
Sent By rkussner Date 2009-05-21 Time 09:43 Rev Time 0.00
Received By rkussner Date 2009-05-21 Time 09:43 Sent To  
Notes
2009-05-21 09:45:38***LANDSCAPE APPROVED WITH 'PROVISO'***
  
 MULCH TO BE USED IN PLANT BEDS AND AT BASE OF TREES (3'
 DIAMETER) ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-11 Cont ID  
Sent By rregueir Date 2008-02-11 Time 15:59 Rev Time 0.00
Received By rregueir Date 2008-02-11 Time 15:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-22 Cont ID  
Sent By rregueir Date 2007-12-22 Time 09:41 Rev Time 0.00
Received By rregueir Date 2007-12-22 Time 09:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-02 Cont ID  
Sent By rregueir Date 2007-09-02 Time 10:37 Rev Time 0.00
Received By rregueir Date 2007-09-02 Time 10:15 Sent To  
Notes
2007-09-02 10:37:46REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THIS SCOPE OF WORK WAS PREVIOUSLY APPLIED FOR UNDER
 PERMIT # 07010426. WHY HAS IT BEEN REAPPLIED UNDER A
 NEW PERMIT APPLICATION? THIS SHOULD EITHER BE
 RESUBMITTED UNDER THE PREVIOUS APPLICATION OR THE
 PREVIOUS APPLICATIN SHOULD BE VOIDED. PLEASE
 COMMUNICATE THE INTENTIONS TO THIS OFFICE SO THE PROPER
 STEPS IN PROCEEDING MAY BE DETERMINED.
  
 2. SHOW RATE OF MECHANICAL VENTILATION FOR TOILET ROOM
 IN ACCORDANCE WITH FBC,M TABLE 403.3.
  
 3. SHOW MEANS OF SUPPLY AIR OR MAKE-UP AIR FOR THE
 EXHAUST FAN PER FBC,M 403.1.
  
 4. SHOW LOCATION OF EXHAUST OUTLET AND OUTDOOR AIR
 INTAKE WHICH ARE BOTH TO BE IN COMPLIANCE WITH FBC,M
 401.5 AND 401.6.
  
 5. PROVIDE EQUIPMENT SCHEDULE FOR EXHAUST FAN TO BE
 INSTALLED AND SHOW SIZE OF EXHAUST DUCT TO BE USED PER
 FBC 106.3.5.1.4.
  
 6. A MECHANICAL PERMIT IS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-02-13 Cont ID  
Sent By kstevens Date 2008-02-13 Time 11:13 Rev Time 0.00
Received By kstevens Date 2008-02-13 Time 11:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-19 Cont ID  
Sent By kstevens Date 2007-12-19 Time 16:00 Rev Time 0.00
Received By kstevens Date 2007-12-19 Time 16:00 Sent To  
Notes
2007-12-19 16:04:21DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. THE ADDRESS ON THE APPLICATION AND PLANS, (604
 BRADLEY ST.), DOES NOT REFLECT THE ADDRESS FOR THE PCN
 NUMBER AND ADDRESS ON OUR SYSTEM. PLEASE CLARIFY.
 SECTION 105.3. (SEE ADDRESSING STOP DATED 01-17-2007 ON
 PERMIT NUMBER 07010426). INDICATE THE CORRECT ADDRESS
 ON THE APPLICATION AND ON THE PLANS.
 ****NO RESPONSE. THE ADDRESS WAS CORRECTED ON THE
 APPLICATION, BUT NOT ON THE PLANS.
  
 2. OK PERMIT NUMBER 07010426 VOIDED.
  
 3. OK
  
 4. THE SURVEY SHEET REQUIRES THE SIGNED SEAL TO BE
 DATED WHEN THE SEAL AND SIGNATURE ARE AFFIXED TO THE
 DOCUMENT. FS 472.025. ALSO SEE ELECTRICAL REVIEW
 COMMENT #7CONCERNING STAMPED SIGNATURES WHICH ARE NOT
 APPROVED.
 ****NO RESPONSE NOT ADDRESSED
  
 5. SUBMIT A MINIMUM OF 2 SETS OF PLANS. LOOSE LANDSCAPE
 AND SURVEY PLANS ARE NOT APPROVED. COMPLETE BOUND SETS
 OF PLANS REQUIRED. SECTIONS 106.1 & 106.1.3. ****NO
 RESPONSE, NOT ADDRESSED.
  
 6. OK
 7. OK
 8. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By kstevens Date 2007-09-17 Time 10:09 Rev Time 0.00
Received By kstevens Date 2007-09-17 Time 10:09 Sent To  
Notes
2007-09-17 11:03:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE ADDRESS ON THE APPLICATION AND PLANS, (604
 BRADLEY ST.), DOES NOT REFLECT THE ADDRESS FOR THE PCN
 NUMBER AND ADDRESS ON OUR SYSTEM. PLEASE CLARIFY.
 SECTION 105.3. (SEE ADDRESSING STOP DATED 01-17-2007 ON
 PERMIT NUMBER 07010426). INDICATE THE CORRECT ADDRESS
 ON THE APPLICATION AND ON THE PLANS.
  
 2. PLEASE EXPLAIN WHY THERE ARE TWO PERMITS APPLIED FOR
 THE SAME PROJECT. PLEASE SUBMIT A LETTER INDICATING
 THAT THE PREVIOUS APPLICATION BE VOIDED OR CLOSED TO
 AVOID CONFUSION IN THE FUTURE. (SEE PERMIT NUMBER
 07010426).
  
 3. THE LANDSCAPE PLANS SEAL IS NOT APPROVED. SEE FAC
 61G1-16.002 & FS 481.2055. SEAL TO BE APPROX. 2" IN
 DIAMETER.
  
 4. THE SURVEY SHEET REQUIRES THE SIGNED SEAL TO BE
 DATED WHEN THE SEAL AND SIGNATURE ARE AFFIXED TO THE
 DOCUMENT. FS 472.025. ALSO SEE ELECTRICAL REVIEW
 COMMENT #7CONCERNING STAMPED SIGNATURES WHICH ARE NOT
 APPROVED.
  
 5. SUBMIT A MINIMUM OF 2 SETS OF PLANS. LOOSE LANDSCAPE
 AND SURVEY PLANS ARE NOT APPROVED. COMPLETE BOUND SETS
 OF PLANS REQUIRED. SECTIONS 106.1 & 106.1.3.
  
 6. SHT A-1 SANITARY PLUMBING RISER DIAGRAM. THE
 DRINKING FOUNTAIN IS NOT SHOWN ON THE RISER DIAGRAM.
 SECTION 301.3.--ONLY THE FIXTURES WITHIN THE TOILET
 ROOM SHALL CONNECT TO THE WET- VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. THE MOP SINK AND DRINKING
 FOUNTAIN SHALL CONNECT DOWNSTREAM OF THE TOILET ROOM
 FIXTURES. SECTION 909.1 (SEE RED LINE EXAMPLE ON ONE
 SET OF PLAN TO CORRECT VIOLATION).--SHOW ALL PIPE
 SIZES ON SANT. RISER DIAGRAM. TABLES 709.1, 710.1(1) &
 710.1(2).
  
 7.SHT A-1 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR
 W/C
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ___FOR LAV
 A. 11-4.19.2 CLEARANCES - 29" REQD. - 28" INDICATED
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
  
 8. SHT A-1 DETAIL SHOWS THE W/C 1'6" "MIN" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE. THE 1'6" MEASUREMENT
 IS AN ABSOLUTE MEASURMENT. PLEASE DELETE THE REFERENCE
 TO "MINIMUM" . SECTION 11-3.1.--W/C AND LAV ARE TO
 BE A MINIMUM OF 30" CENTERLINE OF FIXTURE TO CENTERLINE
 OF FIXTURE, NOT 18" AS SHOWN ON THE DETAIL PLEASE
 CORRECT DETAIL. SECTION 405.3.1 & FIGURE 504.3.1.--
 ACCESSIBLE LAVS SHALL BE A MINIMUM OF 15" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE TO BE CENTERED IN THE
 30" OF THE 30"X48" CLEAR FLOOR SPACE. PLEASE INDICATE
 ON DETAIL. SECTION 11-4.19.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-03-14 Cont ID  
Sent By adavila Date 2008-03-14 Time 13:36 Rev Time 0.00
Received By adavila Date 2008-03-14 Time 13:36 Sent To  
Notes
2008-03-14 13:36:19PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 NOTE - A PERMIT IS REQUIRED FOR THE IRRIGATION SYSTEM.

Review Stop Z ZONING
Rev No 3 Status F Date 2008-01-22 Cont ID  
Sent By adavila Date 2008-01-22 Time 17:42 Rev Time 0.00
Received By adavila Date 2008-01-22 Time 10:57 Sent To  
Notes
2008-01-22 17:42:43PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. A SITE PLAN WAS NOT PROVIDED WITH THIS SUBMITTAL
 PACKET.
 2. THE SURVEY SHOWING THE PROPOSED STRUCTURE DOES NOT
 MATCH THE LANDSCAPE PLAN.
 3. ALL PLANS SHALL SHOW THE SAME BUILDING
 CONFIGURATION.PLEASE NOTE THAT STAFF PREFERS THE
 BUILDING CONFIGURATION SHOWN ON THE LANDSCAPE PLAN.
 4. PLEASE NOTE THAT DEPENDING ON THE ORIENTATION OF THE
 BUILDING, ELEVATIONS MAY NEED TO BE REVISED TO MATCH
 THE PROPOSED ORIENTATION.
  
 COMMENTS/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
2008-01-22 10:57:47IN ZONING FOR REVIEW.ADQ.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-12-12 Cont ID  
Sent By adavila Date 2007-12-12 Time 15:10 Rev Time 0.00
Received By adavila Date 2007-12-12 Time 11:22 Sent To  
Notes
2007-12-12 15:26:13PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.SITE PLAN AND SURVEY DO NOT MATCH THE LANDSCAPE
 PLAN.SITE PLAN SHALL BE REVISED TO SHOW THE
 CONDITIONS SHOWN ON THE LANDSCAPE PLAN (BUILDING
 LAYOUT).
  
 COMMENTS/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-13 Cont ID  
Sent By adavila Date 2007-09-13 Time 16:19 Rev Time 0.00
Received By adavila Date 2007-08-30 Time 11:21 Sent To  
Notes
2007-09-13 15:40:45PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.GROUND COVER OF A MINIMUM RADIUS OF 5 FEET SHALL BE
 PROVIDED AROUND THE TREE SOUTH OF THE PROPOSED BUILDING
 STRUCTURE.
  
 2.A MINIMUM 5 FOOT GROUND COVER BUFFER STRIP SHALL BE
 PROVIDED ALONG THE REMAINING EAST PROPERTY LINE (WITHIN
 THE VISIBILITY TRIANGLE).
  
 COMMENTS/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
2007-09-04 11:21:50CALLED LANDSCAPE ARCHITECT AND LEFT A MESSAGE.
 LANDSCAPE ARCHITECT NEEDS TO COME IN AND MAKE
 CORRECTION ON LANDSCAPE PLANS.WAITING FOR RESPONSE.
 ADQ.