| Plan Review Stops For Permit 07080065 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-01-29 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-01-28 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-12-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-24 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-24 |
Time |
06:47 |
Sent To |
|
|
| Notes |
| 2007-12-24 09:18:39 | | | | BUILDING PLAN REVIEW | | | PERMIT: 07010426 | | | ADD: 4619 GEORGIA AVE. | | | CONT: STONE IMAGE INC. | | | TEL: (561)547-1177 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 3RD -12/24/07 | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | **THE ADDRESS ON THE APPLICAION WAS CHANGED TO 4619 | | | GEORGIA AVE HOWEVER, THE PLANS STILL SHOW THE ADDRESS | | | AS ?604 BRADLEY STREET? CLARIFY.** | | | NOTE:THIS PROJECT WAS SUBMITTED PREVIOUSLY UNDER | | | APPLICATION #07010426 WITH THE ADDRESS AS 4619 GEORGIA | | | AVE. THE SAME PROJECT IS NOW SUBMITTED WITH A NEW | | | DIFFERENT APPLICATION #07080065 AND 604 BRADLEY ST AS | | | THE ADDRESS. PLEASE RECTIFY THIS SITUATION WITH THE | | | FRONT COUNTER WHEN RESUBMITTING. | | | 2)OK | | | 3) OK | | | 4) OK. | | | 5)OK | | | | | | **NEW** | | | **SEE NOTE (A) BELOW. | | | INDICATE ON THE DRAWINGS THE INTERIOR FINISHES OF THE | | | NEW STRUCTURE. TOILET AND BATHING ROOM FLOORS SHALL | | | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE THAT EXTENDS | | | UPWARD ON TO THE WALLS AT LEAST 6 INCHES.WALL WITHIN | | | 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE THE SAME | | | TYPE OF SURFACES MENTION ABOVE. FBC1210. NOTE: DRYWALL | | | WITH PAINT IS NOT CONSIDERED A HARD SURFACE. INDICATE | | | THE TYPE OF FINISH IN THE BATHROOM FROM THE FINISH | | | FLOOR TO AT LEAST 4 FEET ABOVE. | | | | | | 6)OK | | | | | | **NEW** | | | **NO RESPONSE NOT ADDRESSED** | | | A)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION; | | | PROVIDE INFORMATION BASE ON INTERIOR FINISH | | | REQUIREMENTS BASED ON OCCUPANCY.INTERIOR WALL AND | | | CEILING FINISH SHALL HAVE A FLAME SPREAD INDEX NOT | | | GREATER THAN THAT SPECIFIED IN TABLE 803.5. | | | | | | B)OK, | | | C)OK | | | D)OK | | | | | | E)ROOFING PERMIT; ONLY CHECKED ITEMS APPLY (SEE | | | POLICY) | | | | | | _XX___1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH | | | THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. | | | | | | _OK__2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING | | | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY: | | | MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF | | | EACH ROOF TYPE | | | | | | _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | REQUIRED IN ADDITION TO THE EVALUATION REPORT | | | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG | | | | | | _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED | | | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER | | | IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. | | | | | | _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED | | | FASTENING FOR CORNER AND PERIMETER ZONES. | | | | | | _XX_6.)SEE PRODUCT LIMITATION #7.CALCULATIONS | | | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF | | | CONSULTANT REQUIRED FOR ENHANCED FASTENING. | | | | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected]. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-08 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-08 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-07 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2007-09-07 17:56:54 | | | | BUILDING PLAN REVIEW | | | PERMIT07080065 | | | ADD: 604 BRADLEY ST. | | | CONT: STONE IMAGE INC. | | | TEL: (561)547-1177 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 3RD | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | NOTE:THIS PROJECT WAS SUBMITTED PREVIOUSLY UNDER | | | APPLICATION #07010426 WITH THE ADDRESS AS 4619 GEORGIA | | | AVE. THE SAME PROJECT IS NOW SUBMITTED WITH A NEW | | | DIFFERENT APPLICATION #07080065 AND 604 BRADLEY ST AS | | | THE ADDRESS. PLEASE RECTIFY THIS SITUATION WITH THE | | | FRONT COUNTER WHEN RESUBMITTING. | | | | | | 2)OK | | | | | | 3) OK | | | | | | 4) OK. | | | | | | 5)FBC. 1203.4.2.1 ROOMS CONTAINING BATHTUBS, SHOWERS, | | | SPAS AND SIMILAR BATHING FIXTURES SHALL BE MECHANICALLY | | | VENTILATED IN ACCORDANCE WITH THE FLORIDA BUILDING | | | CODE, MECHANICAL. | | | **NEW** | | | INDICATE ON THE DRAWINGS THE INTERIOR FINISHES OF THE | | | NEW STRUCTURE. TOILET AND BATHING ROOM FLOORS SHALL | | | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE THAT EXTENDS | | | UPWARD ON TO THE WALLS AT LEAST 6 INCHES.WALL WITHIN | | | 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE THE SAME | | | TYPE OF SURFACES MENTION ABOVE. FBC1210. NOTE: DRYWALL | | | WITH PAINT IS NOT CONSIDERED A HARD SURFACE. INDICATE | | | THE TYPE OF FINISH IN THE BATHROOM FROM THE FINISH | | | FLOOR TO AT LEAST 4 FEET ABOVE. | | | | | | 6)OK | | | | | | **NEW** | | | A)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION; | | | PROVIDE INFORMATION BASE ON INTERIOR FINISH | | | REQUIREMENTS BASED ON OCCUPANCY.INTERIOR WALL AND | | | CEILING FINISH SHALL HAVE A FLAME SPREAD INDEX NOT | | | GREATER THAN THAT SPECIFIED IN TABLE 803.5. | | | B)ON SHEET A-2 DETAIL #1 SHOW THE PLYWOOD FASTENERS | | | AS 8D RING SHANK NAILS, HOWEVER IN THE TABLE WITH THE | | | SIZE, SPACING AND TYPE OF NAILS HAS 8D PLANE SHANK | | | NAILS. WOOD STRUCTURAL PANEL SHEATHING SHALL BE | | | FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS. | | | CLARIFY. | | | | | | C)SHOW THE ACCESSIBLE ROUTE TO THE NEW BUILDING. | | | 11-4.1.3(1) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING | | | WITH 11-4.3 SHALL CONNECT ACCESSIBLE BUILDING OR | | | FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND | | | ELEMENTS WITHIN THE BUILDING OR FACILITY. | | | | | | D)11-4.1.3(3) GROUND & FLOOR SURFACES ALONG | | | ACCESSIBLE ROUTES & IN ACCESSIBLE ROOMS & SPACES SHALL | | | COMPLY WITH 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE) A | | | STATIC COEFFICIENT OF FRICTION OF 0.6 IS RECOMMENDED | | | FOR ACCESSIBLE ROUTES AND 0.8 FOR RAMPS. | | | | | | E)ROOFING PERMIT; ONLY CHECKED ITEMS APPLY | | | | | | _XX___1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH | | | THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. | | | | | | _XX__2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING | | | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY: | | | MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF | | | EACH ROOF TYPE | | | | | | _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | REQUIRED IN ADDITION TO THE EVALUATION REPORT | | | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG | | | | | | _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED | | | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER | | | IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. | | | | | | _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED | | | FASTENING FOR CORNER AND PERIMETER ZONES. | | | | | | ____6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH | | | METHOD OF ATTACHMENT YOU ARE USING. | | | | | | _XX_7.)SEE PRODUCT LIMITATION #7.CALCULATIONS | | | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF | | | CONSULTANT REQUIRED FOR ENHANCED FASTENING. | | | | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected]. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-03-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-18 |
Time |
18:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-18 |
Time |
18:28 |
Sent To |
|
|
| Notes |
| 2008-03-12 18:29:43 | PAST ON 1/18/08, ENTERED IN COMPUTER 3/12 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-12-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-11 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-11 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2007-12-11 17:06:29 | **** DENIED 2ND REVIEW **** | | | | | | ** AS STATED ON PREVIOUS REVIEW, PLEASE SEE PERMIT # | | | 07010426 IS STILL ACTIVE. | | | | | | 1) NOTE: PLEASE SEE THE NEW LOAD SHOWN ON SHEET A-1 IS | | | SHOWN AS 1.86 AMPS, HOWEVER THE NEW LOAD SHOWN ON SHEET | | | A-2 IS 7.5AMPS. | | | PLEASE ADJUST LOAD CALCULATIONS TO SHOW NEW LOADS BEING | | | ADDED TO EXISTING PER 220.87 | | | | | | 2) NOTE: PLEASE SEE THE *EQUIPMENT GROUNDING CONDUCTOR* | | | SHOWN FROM EXISTING PANEL TO NEW MAIN AT DETACHED | | | BUILDING AND FROM DISCONNECT TO PANEL IS SHOWN WITH A | | | CONDUCTOR SIZE WHICH IS NOT STANDARD PER AWG (AMERICAN | | | WIRE GAUGE) OR 310.16. | | | PLEASE KNOW THE MINIMUM SIZE NEEDS TO BE #10 PER | | | 250.122, 310.16. | | | PLEASE KNOW THIS IS AN ITEM WHICH COULD BE *REDLINED* | | | ON PLANS. | | | PLEASE ADDRESS COMMENT #1 ABOVE. | | | | | | ** PLEASE CALL IF ALL OTHER COMMENTS AND ALL OTHER | | | TRADES PASS REVIEWS. A *PROVISO* MAY BE SET IN PLACE | | | FOR PERMIT ISSUANCE. THIS IS ONLY IF ALL OTHER TRADES | | | PASS THEIR REVIEWS. IF THERE ARE COMMENTS FOR ANY OTHER | | | TRADES AND PLANS ARE GOING BACK FOR CORRECTIONS, PLEASE | | | ADDRESS COMMENT #1 AT THIS TIME. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-08-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-29 |
Time |
19:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-29 |
Time |
19:00 |
Sent To |
|
|
| Notes |
| 2007-08-29 19:00:31 | ** DENIED ** | | | | | | 1) NOTE: PLEASE SEE TWO REVIEWS WERE DONE UNDER PERMIT | | | NUMBER 07010426 WHICH IS STILL AN ACTIVE PERMIT. IT IS | | | COMPLETELY UNCLEAR WHY A NEW PERMIT APPLICATION FOR THE | | | SAME SCOPE OF WORK IS BEING SUBMITTED WHEN THE OTHER | | | PERMIT APPLICATION IS STILL ACTIVE. | | | | | | ** PLEASE SEE SOME COMMENTS FROM THE REVIEWS DONE UNDER | | | THE PERMIT # ABOVE IS STILL IN NEED OF ADDRESSING. | | | | | | 2) NOTE: PLEASE COMPLETE RISER WITH ALL FEEDERS AND | | | GROUNDING CONDUCTORS TO THE DETACHED STRUCTURE. | | | 310.16,240.4,215.5, ETC. | | | | | | 3) NOTE: PLEASE SEE MISSING THE REQUIRED GROUNDING | | | ELECTRODE SYSTEM AT THE DETACHED STRUCTURE PER 250.32, | | | 250.50. | | | | | | 4) NOTE: PLEASE SEE THE MISSING OVER CURRENT PROTECTION | | | IN THE EXISTING 150AMP RATED PANEL WHICH IS FEEDING THE | | | NEW SUB PANEL. | | | THERE ARE TOO MANY SECTIONS TO NOTE WHICH REQUIRES | | | THIS. | | | NEC 2005. | | | | | | 5) NOTE: PLEASE SEE THE PANELS DO NOT SUPPLY THE | | | INFORMATION NEEDED FOR REVIEW OF LOADS, EXISTING AND | | | NEW, THE CONDUCTORS ETC WHICH IS NOT COMPLETE. | | | FBC 106.3.5.1.2 | | | NEC 215.5,240.4,310.16,2 | | | | | | 6) NOTE: PLEASE SEE ONLY ONE SET OF PLANS FOR ALL ITEMS | | | WAS SUBMITTED. | | | ONLY ONE SURVEY, | | | ONLY ONE PLAN, | | | ONLY ONE LANDSCAPE PLAN. | | | PLEASE SUBMIT TWO COPIES OF ALL DOCUMENTS AS REQUIRED | | | PER FBC 106.1.1, 106.1.2 | | | | | | 7) NOTE: PLEASE SEE THE SIGNATURE ON THE SURVEY IS A | | | *RUBBER-STAMP* WHICH IS NOT PERMITTED PER FS 472.025. | | | MUST BE AN ORIGINAL SIGNATURE. | | | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY | | | ANY OTHER TRADE. | | | | | | 8) NOTE: PLEASE SEE THE SEAL ON THE LANDSCAPE ARCHITECT | | | PLANS IS NOT VALID UNDER THE REQUIREMENTS FROM THE | | | STATE AND FLORIDA ADMINISTRATIVE CODE, FAC 61G1-16.002. | | | (2INCH MIN SEAL). | | | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY | | | ANY OTHER TRADE. | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-02-13 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-02-13 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-13 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2008-02-13 17:09:50 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED;PLAN SHEET A-1 STAMPED, INITIALED, AND | | | DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-12-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-28 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-28 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2007-12-28 14:36:57 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS (OF 6) TAKEN FROM THE PREVIOUS | | | FIRE PLAN REVIEW COMMENT STILL NEED TO BE ADDRESSED: | | | | | | 1.THE PERMIT NUMBER REGISTERS THE ADDRESS LOCATION AS | | | 4619 GEORGIA AVENUE AND NOT AS 604 BRADLEY STREET AS | | | INDICATED ON THE APPLICATION OR ON THE SUBMITTED PLAN | | | SHEETS. | | | | | | 2.IF THE PROJECTED WORK SITE IS ADDRESSED ON BRADLEY | | | STREET,THE NUMERICAL ADDRESS SHALL BE AN ODD NUMBER | | | SINCE IT IT IS ON THE NORTH SIDE OF THE STREET. | | | | | | 6.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR | | | THIS STRUCTURE IN TERMS OF CLASS A, CLASS B, OR CLASS | | | C. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-10-02 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-02 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-02 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2007-10-02 11:34:35 | *****DENIED***** | | | | | | | | | 1.THE PERMIT NUMBER REGISTERS THE ADDRESS LOCATION AS | | | 4619 GEORGIA AVENUE AND NOT AS 604 BRADLEY STREET AS | | | INDICATED ON THE APPLICATION OR ON THE SUBMITTED PLAN | | | SHEETS. | | | | | | 2.IF THE PROJECTED WORK SITE IS ADDRESSED ON BRADLEY | | | STREET,THE NUMERICAL ADDRESS SHALL BE AN ODD NUMBER | | | SINCE IT IT IS ON THE NORTH SIDE OF THE STREET. | | | | | | 3.ON SHEET A-1,INCLUDE EAST, WEST, NORTH, AND SOUTH | | | TO THE APPROPIATE EXTERIOR ELEVATIONS IN ADDITION TO | | | WHAT IS LISTED. | | | | | | 4.ON SHEET A-1 UNDER THE FLOOR PLAN LAYOUT, INSERT | | | "NFPA 101," IN FRONT OF LIFE SAFETY CODE TO PREVENT | | | CONFUSION WITH NFPA-70 (NEC). | | | | | | 5.ON SHEET A-1 IN THE ELECTRICAL NOTES, REFERENCES | | | ARE MADE TO SMOKE DETECTORS, BEDROOMS, AND SLEEPING | | | AREAS.ARE THESE REFERENCES RELEVANT TO THIS SCOPE OF | | | WORK? | | | | | | 6.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR | | | THIS STRUCTURE IN TERMS OF CLASS A, CLASS B, OR CLASS | | | C. | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2009-05-20 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-05-20 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-05-19 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2009-05-20 11:42:35 | IN ZONING BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-03-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-12 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-12 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2008-03-12 15:13:24 | TO "COMM" BD#57 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-17 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-17 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2008-01-17 09:22:34 | TO "COMM" BD#51 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-12-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-07 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-07 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2007-12-07 10:00:51 | TO "COMM" BD#51 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-10-02 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-02 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-06 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2007-08-29 14:34:18 | TO "COMM" BD#21 | | 2007-08-06 15:02:22 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
P |
Date |
2009-05-21 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-05-21 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-05-21 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2009-05-21 09:45:38 | ***LANDSCAPE APPROVED WITH 'PROVISO'*** | | | | | | MULCH TO BE USED IN PLANT BEDS AND AT BASE OF TREES (3' | | | DIAMETER) ONLY. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2008-02-11 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-02-11 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-02-11 |
Time |
15:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-12-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-12-22 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-12-22 |
Time |
09:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-09-02 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-09-02 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2007-09-02 10:37:46 | REVIEW #: 1 | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC | | | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. THIS SCOPE OF WORK WAS PREVIOUSLY APPLIED FOR UNDER | | | PERMIT # 07010426. WHY HAS IT BEEN REAPPLIED UNDER A | | | NEW PERMIT APPLICATION? THIS SHOULD EITHER BE | | | RESUBMITTED UNDER THE PREVIOUS APPLICATION OR THE | | | PREVIOUS APPLICATIN SHOULD BE VOIDED. PLEASE | | | COMMUNICATE THE INTENTIONS TO THIS OFFICE SO THE PROPER | | | STEPS IN PROCEEDING MAY BE DETERMINED. | | | | | | 2. SHOW RATE OF MECHANICAL VENTILATION FOR TOILET ROOM | | | IN ACCORDANCE WITH FBC,M TABLE 403.3. | | | | | | 3. SHOW MEANS OF SUPPLY AIR OR MAKE-UP AIR FOR THE | | | EXHAUST FAN PER FBC,M 403.1. | | | | | | 4. SHOW LOCATION OF EXHAUST OUTLET AND OUTDOOR AIR | | | INTAKE WHICH ARE BOTH TO BE IN COMPLIANCE WITH FBC,M | | | 401.5 AND 401.6. | | | | | | 5. PROVIDE EQUIPMENT SCHEDULE FOR EXHAUST FAN TO BE | | | INSTALLED AND SHOW SIZE OF EXHAUST DUCT TO BE USED PER | | | FBC 106.3.5.1.4. | | | | | | 6. A MECHANICAL PERMIT IS REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-02-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-13 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-13 |
Time |
11:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-12-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-19 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-19 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2007-12-19 16:04:21 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. THE ADDRESS ON THE APPLICATION AND PLANS, (604 | | | BRADLEY ST.), DOES NOT REFLECT THE ADDRESS FOR THE PCN | | | NUMBER AND ADDRESS ON OUR SYSTEM. PLEASE CLARIFY. | | | SECTION 105.3. (SEE ADDRESSING STOP DATED 01-17-2007 ON | | | PERMIT NUMBER 07010426). INDICATE THE CORRECT ADDRESS | | | ON THE APPLICATION AND ON THE PLANS. | | | ****NO RESPONSE. THE ADDRESS WAS CORRECTED ON THE | | | APPLICATION, BUT NOT ON THE PLANS. | | | | | | 2. OK PERMIT NUMBER 07010426 VOIDED. | | | | | | 3. OK | | | | | | 4. THE SURVEY SHEET REQUIRES THE SIGNED SEAL TO BE | | | DATED WHEN THE SEAL AND SIGNATURE ARE AFFIXED TO THE | | | DOCUMENT. FS 472.025. ALSO SEE ELECTRICAL REVIEW | | | COMMENT #7CONCERNING STAMPED SIGNATURES WHICH ARE NOT | | | APPROVED. | | | ****NO RESPONSE NOT ADDRESSED | | | | | | 5. SUBMIT A MINIMUM OF 2 SETS OF PLANS. LOOSE LANDSCAPE | | | AND SURVEY PLANS ARE NOT APPROVED. COMPLETE BOUND SETS | | | OF PLANS REQUIRED. SECTIONS 106.1 & 106.1.3. ****NO | | | RESPONSE, NOT ADDRESSED. | | | | | | 6. OK | | | 7. OK | | | 8. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-17 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-17 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2007-09-17 11:03:26 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. THE ADDRESS ON THE APPLICATION AND PLANS, (604 | | | BRADLEY ST.), DOES NOT REFLECT THE ADDRESS FOR THE PCN | | | NUMBER AND ADDRESS ON OUR SYSTEM. PLEASE CLARIFY. | | | SECTION 105.3. (SEE ADDRESSING STOP DATED 01-17-2007 ON | | | PERMIT NUMBER 07010426). INDICATE THE CORRECT ADDRESS | | | ON THE APPLICATION AND ON THE PLANS. | | | | | | 2. PLEASE EXPLAIN WHY THERE ARE TWO PERMITS APPLIED FOR | | | THE SAME PROJECT. PLEASE SUBMIT A LETTER INDICATING | | | THAT THE PREVIOUS APPLICATION BE VOIDED OR CLOSED TO | | | AVOID CONFUSION IN THE FUTURE. (SEE PERMIT NUMBER | | | 07010426). | | | | | | 3. THE LANDSCAPE PLANS SEAL IS NOT APPROVED. SEE FAC | | | 61G1-16.002 & FS 481.2055. SEAL TO BE APPROX. 2" IN | | | DIAMETER. | | | | | | 4. THE SURVEY SHEET REQUIRES THE SIGNED SEAL TO BE | | | DATED WHEN THE SEAL AND SIGNATURE ARE AFFIXED TO THE | | | DOCUMENT. FS 472.025. ALSO SEE ELECTRICAL REVIEW | | | COMMENT #7CONCERNING STAMPED SIGNATURES WHICH ARE NOT | | | APPROVED. | | | | | | 5. SUBMIT A MINIMUM OF 2 SETS OF PLANS. LOOSE LANDSCAPE | | | AND SURVEY PLANS ARE NOT APPROVED. COMPLETE BOUND SETS | | | OF PLANS REQUIRED. SECTIONS 106.1 & 106.1.3. | | | | | | 6. SHT A-1 SANITARY PLUMBING RISER DIAGRAM. THE | | | DRINKING FOUNTAIN IS NOT SHOWN ON THE RISER DIAGRAM. | | | SECTION 301.3.--ONLY THE FIXTURES WITHIN THE TOILET | | | ROOM SHALL CONNECT TO THE WET- VENTED HORIZONTAL BRANCH | | | DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. THE MOP SINK AND DRINKING | | | FOUNTAIN SHALL CONNECT DOWNSTREAM OF THE TOILET ROOM | | | FIXTURES. SECTION 909.1 (SEE RED LINE EXAMPLE ON ONE | | | SET OF PLAN TO CORRECT VIOLATION).--SHOW ALL PIPE | | | SIZES ON SANT. RISER DIAGRAM. TABLES 709.1, 710.1(1) & | | | 710.1(2). | | | | | | 7.SHT A-1 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR | | | W/C | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | ___FOR LAV | | | A. 11-4.19.2 CLEARANCES - 29" REQD. - 28" INDICATED | | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | | | | | 8. SHT A-1 DETAIL SHOWS THE W/C 1'6" "MIN" OFF THE WALL | | | TO THE CENTERLINE OF THE FIXTURE. THE 1'6" MEASUREMENT | | | IS AN ABSOLUTE MEASURMENT. PLEASE DELETE THE REFERENCE | | | TO "MINIMUM" . SECTION 11-3.1.--W/C AND LAV ARE TO | | | BE A MINIMUM OF 30" CENTERLINE OF FIXTURE TO CENTERLINE | | | OF FIXTURE, NOT 18" AS SHOWN ON THE DETAIL PLEASE | | | CORRECT DETAIL. SECTION 405.3.1 & FIGURE 504.3.1.-- | | | ACCESSIBLE LAVS SHALL BE A MINIMUM OF 15" OFF THE WALL | | | TO THE CENTERLINE OF THE FIXTURE TO BE CENTERED IN THE | | | 30" OF THE 30"X48" CLEAR FLOOR SPACE. PLEASE INDICATE | | | ON DETAIL. SECTION 11-4.19.3. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2008-03-14 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-03-14 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2008-03-14 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2008-03-14 13:36:19 | PER ERIC SCHNEIDER, PRINCIPAL PLANNER. | | | | | | NOTE - A PERMIT IS REQUIRED FOR THE IRRIGATION SYSTEM. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2008-01-22 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-01-22 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2008-01-22 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2008-01-22 17:42:43 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1. A SITE PLAN WAS NOT PROVIDED WITH THIS SUBMITTAL | | | PACKET. | | | 2. THE SURVEY SHOWING THE PROPOSED STRUCTURE DOES NOT | | | MATCH THE LANDSCAPE PLAN. | | | 3. ALL PLANS SHALL SHOW THE SAME BUILDING | | | CONFIGURATION.PLEASE NOTE THAT STAFF PREFERS THE | | | BUILDING CONFIGURATION SHOWN ON THE LANDSCAPE PLAN. | | | 4. PLEASE NOTE THAT DEPENDING ON THE ORIENTATION OF THE | | | BUILDING, ELEVATIONS MAY NEED TO BE REVISED TO MATCH | | | THE PROPOSED ORIENTATION. | | | | | | COMMENTS/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. | | 2008-01-22 10:57:47 | IN ZONING FOR REVIEW.ADQ. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-12-12 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2007-12-12 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2007-12-12 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2007-12-12 15:26:13 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1.SITE PLAN AND SURVEY DO NOT MATCH THE LANDSCAPE | | | PLAN.SITE PLAN SHALL BE REVISED TO SHOW THE | | | CONDITIONS SHOWN ON THE LANDSCAPE PLAN (BUILDING | | | LAYOUT). | | | | | | COMMENTS/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-13 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2007-09-13 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2007-08-30 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2007-09-13 15:40:45 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1.GROUND COVER OF A MINIMUM RADIUS OF 5 FEET SHALL BE | | | PROVIDED AROUND THE TREE SOUTH OF THE PROPOSED BUILDING | | | STRUCTURE. | | | | | | 2.A MINIMUM 5 FOOT GROUND COVER BUFFER STRIP SHALL BE | | | PROVIDED ALONG THE REMAINING EAST PROPERTY LINE (WITHIN | | | THE VISIBILITY TRIANGLE). | | | | | | COMMENTS/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. | | 2007-09-04 11:21:50 | CALLED LANDSCAPE ARCHITECT AND LEFT A MESSAGE. | | | LANDSCAPE ARCHITECT NEEDS TO COME IN AND MAKE | | | CORRECTION ON LANDSCAPE PLANS.WAITING FOR RESPONSE. | | | ADQ. |
|
|