 |
Plan Review Details - Permit 07080045
| Plan Review Stops For Permit 07080045 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-01-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-01-10 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-01-10 |
Time |
06:59 |
Sent To |
|
|
| Notes |
| 2008-01-10 09:11:02 | PROVISOR: | | | SHOW THE ACCESSIBLE ROUTE TO THE UNIT MEET THE | | | REQUIREMENTS OF SECTION 11-4.3.1 | | | **NEW** FBC 11-4.5.2 CHANGES IN LEVEL GREATER THAN ? | | | INCH SHALL BE ACCOMPLISHED BY MEANS OF A RAMP THAT | | | COMPLIES WITH SECTION 11-4.7 OR 11-4.8. SHOW | | | COMPLIANCE. THIS IS REQUIRED DUE TO THE FACT THAT THERE | | | ARE STEPS LEADING TO THE ENTRANCE OF THE ROOM. ALL | | | RAMPS SHALL BE STABLE, FIRM, SLIP RESISTANT, AND SHALL | | | COMPLY WITH SECTION 11-4.5.LANDINGS AT RAMPS SHALL | | | MEET THE REQUIREMENTS OF 11-4.8.4 AND 11-4.13.6 SHOW IN | | | DETAIL DRAWINGS HOW THESE REQUIREMENTS WILL BE | | | ACCOMPLISHED. | | | **(A) ALL LANDINGS ON RAMPS SHALL BE NOT LESS THAN 60 | | | INCHES CLEAR, AND THE BOTTOM OF EACH RAMP SHALL HAVE | | | NOT LESS THAN 72 INCHES OF STRAIGHT AND LEVEL | | | CLEARANCE. 11-4.8.4(2) | | | **(B) IF A RAMP RUN HAS A RISE GREATER THAN 6 INCHES, | | | THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES. THE | | | INFORMATION ABOVE SHALL BE CLEARLY INDICATED ON THE | | | DRAWINGS. THE DRAWINGS SUBMITTED DO NOT SHOW ALL THE | | | REQUIREMENTS FOR THE RAMP CLEARLY. SUBMIT ELEVATION | | | DRAWINGS SHOWING THE SLOPE AND RISE, CLEAR WIDTH, | | | LANDINGS AND HANDRAILS WITH ALL REQUIRED DIMENSIONS. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS O THIS CODE. 106.1.1** | | | NOTE: IF THIS IS A TEMPORARY STURCTURE, IT SHALL | | | CONFORM TO FBC. SEC 107. WHIC HAS A TIME LIMIT OF 180 | | | DAYS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-12-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-15 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-15 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2007-12-15 16:07:39 | BUILDING PLAN REVIEW | | | PERMIT: 07080045 | | | ADD: 1604 CLARE AVE | | | CONT: BENITZ BUILDING LLC | | | TEL: (561)659-4024 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 4TH | | | ACTION: DENIED | | | 12/15/07 | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)OK | | | | | | 3)BEFORE THE MOCK-UP ROOMS CAN BE APPROVED, MORE | | | INFORMATION SHALL BE SUBMITTED. | | | **NOTED**SHEETS WERE REMOVED FROM PACKAGE. | | | 4)OK | | | 5)OK | | | 6) NOTE: IF THIS IS A TEMPORARY STURCTURE, IT SHALL | | | CONFORM TO FBC. SEC 107. WHIC HAS A TIME LIMIT OF 180 | | | DAYS. | | | **THE RESPONSE SHEET STATES THAT THE WORK ?TEMPORARY? | | | WILL BE REMOVED FROM THE APPLICATION. DOES THIS MEAN | | | THAT THE STRUCTURE WILL NOW BE ?PERMANENT??** | | | | | | | | | | | | | | | 7)OK | | | | | | **NO RRESPONSE NOT ADDRESSED** | | | 8)ADDITIONAL STRUCTURAL DETAIL ON THE FLOOR AND | | | CEILING STUDS WILL ALSO BE REQUIRED, ALSO THE | | | VENTILATION PER 1203 AND 1210 OF THE FBC. THE TYPE OF | | | GLASS AT THE BATHROOM SHOWER FBC.2406/ | | | **NEW** | | | SHOW THE ATTACHMENT DETAIL OF THE FLOOR JOIST TO THE | | | EXISTING FLOOR INDICATING THE MATERIALS. THE HEADER AND | | | SILL FRAMING DETAIL SHALL BE SHOWN ON THE DRAWINGS. THE | | | BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS, | | | STRESS DIAGRAMS AND OTHER DATA NECESSARY TO DESCRIBE | | | THE CONSTRUCTION OR INSTALLATION OF THE PROJECT. WPB | | | AMENDMENTS 106.1.2 | | | **(A)PROVIDE A NORTH, SOUTH, EAST AND WEST FRAMING | | | ELEVATION OF THE STRUCTURE SHOWING EACH OPENING WITH | | | THE FRAMING DETAILS. | | | | | | 9) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | THERE MAY BE OTHER COMMENTS FOR ACCESSIBILITY AND FAIR | | | HOUSING DEPENDING ON THE USE AND OCCUPANCY OF THE | | | BUILDING. | | | | | | **NEW** | | | 10)OK. | | | | | | **NO RRESPONSE NOT ADDRESSED** | | | 11)SHOW THE ACCESSIBLE ROUTE TO THE UNIT MEET THE | | | REQUIREMENTS OF SECTION 11-4.3.1 | | | **NEW** FBC 11-4.5.2 CHANGES IN LEVEL GREATER THAN ? | | | INCH SHALL BE ACCOMPLISHED BY MEANS OF A RAMP THAT | | | COMPLIES WITH SECTION 11-4.7 OR 11-4.8. SHOW | | | COMPLIANCE. THIS IS REQUIRED DUE TO THE FACT THAT THERE | | | ARE STEPS LEADING TO THE ENTRANCE OF THE ROOM. ALL | | | RAMPS SHALL BE STABLE, FIRM, SLIP RESISTANT, AND SHALL | | | COMPLY WITH SECTION 11-4.5.LANDINGS AT RAMPS SHALL | | | MEET THE REQUIREMENTS OF 11-4.8.4 AND 11-4.13.6 SHOW IN | | | DETAIL DRAWINGS HOW THESE REQUIREMENTS WILL BE | | | ACCOMPLISHED. | | | **(A) ALL LANDINGS ON RAMPS SHALL BE NOT LESS THAN 60 | | | INCHES CLEAR, AND THE BOTTOM OF EACH RAMP SHALL HAVE | | | NOT LESS THAN 72 INCHES OF STRAIGHT AND LEVEL | | | CLEARANCE. 11-4.8.4(2) | | | **(B) IF A RAMP RUN HAS A RISE GREATER THAN 6 INCHES, | | | THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES. THE | | | INFORMATION ABOVE SHALL BE CLEARLY INDICATED ON THE | | | DRAWINGS. THE DRAWINGS SUBMITTED DO NOT SHOW ALL THE | | | REQUIREMENTS FOR THE RAMP CLEARLY. SUBMIT ELEVATION | | | DRAWINGS SHOWING THE SLOPE AND RISE, CLEAR WIDTH, | | | LANDINGS AND HANDRAILS WITH ALL REQUIRED DIMENSIONS. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS O THIS CODE. 106.1.1** | | | | | | **NO RRESPONSE NOT ADDRESSED** | | | 12)SHOW ON THE ON THE DRAWINGS THE EXISTING BATHROOM | | | FACILITIES. CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED. FBC 106.1.1. | | | **(A) BATHROOMS, BATHING FACILITIES, OR SHOWER ROOMS | | | REQUIRED TO BE ACCESSIBLE SHALL COMPLY WITH SECTION | | | 11-4.23 AND SHALL BE ON AN ACCESSIBLE ROUTE. THE CLEAR | | | FLOOR SPACE AND TURNING SPACE SHALL BE INDICATED ON THE | | | PLANS. | | | **(B) SHOWER STALL SIZE AND CLEAR FLOOR SPACE SHALL | | | COMPLY WITH FIGURE 35(A) OR FIGURE 35(B). A SEAT SHALL | | | BE PROVIDED IN SHOWER STALLS 36 INCHES BY 36 INCHES AND | | | SHALL BE AS SHOWN IN FIGURE 36.11-4.21.3 | | | | | | **NO RRESPONSE NOT ADDRESSED** | | | 13)A DETAIL LETTER INDICATING THE USE/ OCCUPANCY AND | | | PURPOSE OF THE STRUCTURE CAN ALSO SUBMITTED BY THE | | | OWNER. THE LETTER SHALL BE CLEAR AND PRECISE STATING | | | THAT THE SPACE IS ONLY USED AS A SHOW ROOM. | | | | | | **NEW** | | | 14)OK | | | | | | 15)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS | | | & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO | | | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR | | | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED | | | AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION | | | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS | | | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND | | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-11-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-11-28 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-11-28 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2007-11-28 17:34:33 | | | | BUILDING PLAN REVIEW | | | PERMIT: 07080045 | | | ADD: 1604 CLARE AVE | | | CONT: BENITZ BUILDING LLC | | | TEL: (561)659-4024 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 3RD | | | ACTION: DENIED | | | 11/28/07 | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)OK | | | | | | 3)BEFORE THE MOCK-UP ROOMS CAN BE APPROVED, MORE | | | INFORMATION SHALL BE SUBMITTED. | | | **NOTED**SHEETS WERE REMOVED FROM PACKAGE. | | | 4)OK | | | 5)OK | | | | | | 6) NOTE: IF THIS IS A TEMPORARY STURCTURE, IT SHALL | | | CONFORM TO FBC. SEC 107. WHIC HAS A TIME LIMIT OF 180 | | | DAYS. | | | | | | **NO RRESPONSE NOT ADDRESSED** | | | 7)A LEGEND WITH THE WALL DETAILS SHALL ALSO BE | | | SUBMITTED, ALONG WITH THE WALL FINISHES COMPLYING WITH | | | FBC SEC. 803/ 804 AND 805. | | | | | | **NO RRESPONSE NOT ADDRESSED** | | | 8)ADDITIONAL STRUCTURAL DETAIL ON THE FLOOR AND | | | CEILING STUDS WILL ALSO BE REQUIRED, ALSO THE | | | VENTILATION PER 1203 AND 1210 OF THE FBC. THE TYPE OF | | | GLASS AT THE BATHROOM SHOWER FBC.2406/ | | | **NEW** | | | SHOW THE ATTACHMENT DETAIL OF THE FLOOR JOIST TO THE | | | EXISTING FLOOR INDICATING THE MATERIALS. THE HEADER AND | | | SILL FRAMING DETAIL SHALL BE SHOWN ON THE DRAWINGS. THE | | | BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS, | | | STRESS DIAGRAMS AND OTHER DATA NECESSARY TO DESCRIBE | | | THE CONSTRUCTION OR INSTALLATION OF THE PROJECT. WPB | | | AMENDMENTS 106.1.2 | | | | | | 9) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | THERE MAY BE OTHER COMMENTS FOR ACCESSIBILITY AND FAIR | | | HOUSING DEPENDING ON THE USE AND OCCUPANCY OF THE | | | BUILDING. | | | | | | **NEW** | | | 10)OK. | | | | | | **NO RRESPONSE NOT ADDRESSED** | | | 11)SHOW THE ACCESSIBLE ROUTE TO THE UNIT MEET THE | | | REQUIREMENTS OF SECTION 11-4.3.1 | | | **NEW** FBC 11-4.5.2 CHANGES IN LEVEL GREATER THAN ? | | | INCH SHALL BE ACCOMPLISHED BY MEANS OF A RAMP THAT | | | COMPLIES WITH SECTION 11-4.7 OR 11-4.8. SHOW | | | COMPLIANCE. THIS IS REQUIRED DUE TO THE FACT THAT THERE | | | ARE STEPS LEADING TO THE ENTRANCE OF THE ROOM. ALL | | | RAMPS SHALL BE STABLE, FIRM, SLIP RESISTANT, AND SHALL | | | COMPLY WITH SECTION 11-4.5.LANDINGS AT RAMPS SHALL | | | MEET THE REQUIREMENTS OF 11-4.8.4 AND 11-4.13.6 SHOW IN | | | DETAIL DRAWINGS HOW THESE REQUIREMENTS WILL BE | | | ACCOMPLISHED | | | | | | **NO RRESPONSE NOT ADDRESSED** | | | 12)SHOW ON THE ON THE DRAWINGS THE EXISTING BATHROOM | | | FACILITIES. CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED. FBC 106.1.1. | | | | | | **NO RRESPONSE NOT ADDRESSED** | | | 13)A DETAIL LETTER INDICATING THE USE/ OCCUPANCY AND | | | PURPOSE OF THE STRUCTURE CAN ALSO SUBMITTED BY THE | | | OWNER. THE LETTER SHALL BE CLEAR AND PRECISE STATING | | | THAT THE SPACE IS ONLY USED AS A SHOW ROOM. | | | | | | **NEW** | | | 14)FBC 907.2.10.1 AN APPROVED SINGLE-STATION SMOKE | | | ALARM SHALL BE INSTALLED IN EVERY GUESTROOM AND EVERY | | | LIVING AREA AND SLEEPING ROOM WITHIN A GUEST SUITE. | | | | | | 15)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS | | | & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO | | | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR | | | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED | | | AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION | | | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS | | | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND | | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-10-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-10 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-10 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2007-10-10 17:31:07 | | | | | | | | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07080045 | | | ADD: 1604 CLARE AVE | | | CONT: BENITZ BUILDING LLC | | | TEL: (561)659-4024 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND | | | ACTION: DENIED | | | 10/10/07 | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)OK | | | | | | 3)BEFORE THE MOCK-UP ROOMS CAN BE APPROVED, MORE | | | INFORMATION SHALL BE SUBMITTED. | | | **NOTED** HOWEVER, ALL DRAWINGS SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BE SIGNED SEAL AND DATED BY THE | | | DESIGN PROFESSIONAL AS REQUIRED BY FLORIDA STATUTES 471 | | | AND 481. IF THE 11X17 SHEETS ARE SUBMITTED AS | | | ADDITIONAL INFORMATION, THEY SHALL BE SIGNED BY THE | | | PERSON RESPONSIBLE FOR THE DRAWINGS. | | | | | | 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD KEEPING: | | | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS | | | DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED | | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | | BUILDING PERMIT | | | . ------------------------------------- | | | ) NUMBER OF UNITS | | | ) NUMBER OF FLOORS | | | ) NUMBER OF BEDROOMS | | | ) NUMBER OF ROOMS | | | ) NUMBER OF BEDROOMS | | | ) SQ. FT. LIV SPACE/ FL | | | ) SQ. FT. FOOTPRINT | | | **NOTED, HOWEVER, ALL THE INFORMATION SHALL BE | | | INDICATED ON THE DRAWINGS** | | | | | | 5)OK | | | | | | 6)IF THIS IS A TEMPORARY STURCTURE, IT SHALL CONFORM | | | TO FBC. SEC 107. WHIC HAS A TIME LIMIT OF 180 DAYS. | | | **NO RESPONSE NOT ADDRESSED** | | | | | | 7)A LEGEND WITH THE WALL DETAILS SHALL ALSO BE | | | SUBMITTED, ALONG WITH THE WALL FINISHES COMPLYING WITH | | | FBC SEC. 803/ 804 AND 805. | | | **NO RESPONSE NOT ADDRESSED** | | | | | | 8)ADDITIONAL STRUCTURAL DETAIL ON THE FLOOR AND | | | CEILING STUDS WILL ALSO BE REQUIRED, ALSO THE | | | VENTILATION PER 1203 AND 1210 OF THE FBC. THE TYPE OF | | | GLASS AT THE BATHROOM SHOWER FBC.2406/ | | | **NEW** | | | SHOW THE ATTACHMENT DETAIL OF THE FLOOR JOIST TO THE | | | EXISTING FLOOR INDICATING THE MATERIALS. THE HEADER AND | | | SILL FRAMING DETAIL SHALL BE SHOWN ON THE DRAWINGS. THE | | | BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS, | | | STRESS DIAGRAMS AND OTHER DATA NECESSARY TO DESCRIBE | | | THE CONSTRUCTION OR INSTALLATION OF THE PROJECT. WPB | | | AMENDMENTS 106.1.2 | | | | | | 9) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | THERE MAY BE OTHER COMMENTS FOR ACCESSIBILITY AND FAIR | | | HOUSING DEPENDING ON THE USE AND OCCUPANCY OF THE | | | BUILDING. | | | | | | **NEW** | | | 10)THE FUNCTIONAL UNIT SHALL BE ACCESSIBLE AND SHALL | | | MEET THE REQUIREMENTS OF THE ACCESSIBILITY CODE. SINKS | | | SHALL MEET THE REQUIREMENTS OF SECTION 11-4.24. SHOWER | | | STALLS SHALL COMPLY WITH SECTION 11-4.21. A SHOWER | | | SPRAY UNIT WITH A HOSE AT LEAST 60 INCHES LONG THAT CAN | | | BE USED BOTH AS A FIXED SHOWER HEAD AND AS A HAND-HELD | | | SHOWER SHALL BE PROVIDED 11-4.20.6.11-4.26.1 GENERAL. | | | ALL HANDRAILS , GRAB BARS , AND TUB AND SHOWER SEATS | | | REQUIRED TO BE ACCESSIBLE BY SECTION 11-4.1 , 11-4.8 , | | | 11-4.9 , 11-4.16 , 11-4.17 , 11-4.20 OR 11-4.21 SHALL | | | COMPLY WITH SECTION 11-4.26 . | | | | | | 11)SHOW THE ACCESSIBLE ROUTE TO THE UNIT MEET THE | | | REQUIREMENTS OF SECTION 11-4.3.1 | | | | | | 12)SHOW ON THE ON THE DRAWINGS THE EXISTING BATHROOM | | | FACILITIES. CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED. FBC 106.1.1. | | | | | | 13)A DETAIL LETTER INDICATING THE USE/ OCCUPANCY AND | | | PURPOSE OF THE STRUCTURE CAN ALSO SUBMITTED BY THE | | | OWNER. THE LETTER SHALL BE CLEAR AND PRECISE STATING | | | THAT THE SPACE IS ONLY USED AS A SHOW ROOM. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-08-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-21 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-21 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2007-08-21 12:41:57 | BUILDING PLAN REVIEW | | | PERMIT: 07080045 | | | ADD: 1604 CLARE AVE | | | CONT: BENITZ BUILDING LLC | | | TEL: (561)659-4024 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)IF THERE IS A SPRINKLER SYSTEM IN THE BUILDING, THE | | | MODEL ROOMS SHALL BE PROTECTED WITH SPRINLERS. SHOW THE | | | SPRINKLER-HEADS SHALL BE INDICATED ON THE CEILING | | | PLAN. | | | | | | 3)BEFORE THE MOCK-UP ROOMS CAN BE APPROVED, MORE | | | INFORMATION SHALL BE SUBMITTED. | | | | | | 4)110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR | | | RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PROJECT IS DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED | | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT | | | . ------------------------------------- | | | ) NUMBER OF UNITS | | | ) NUMBER OF FLOORS | | | ) NUMBER OF BEDROOMS | | | ) NUMBER OF ROOMS | | | ) NUMBER OF BEDROOMS | | | ) SQ. FT. LIV SPACE/ FL | | | ) SQ. FT. FOOTPRINT | | | | | | 5)INDICATE IF THE MOCK-UP ROOMS WILL BE CONSTRUCTED | | | IN A NEW BUILDING OR A RENOVATED BUILDING. WILL THIS | | | PROJECT INVOLVED A CHANGE OF OCCUPANCY? IF SO SEE FBC | | | EXISTING CH.8. | | | | | | 6)IF THIS IS A TEMPORARY STURCTURE, IT SHALL CONFORM | | | TO FBC. SEC 107. WHIC HAS A TIME LIMIT OF 180 DAYS. | | | | | | 7)A LEGEND WITH THE WALL DETAILS SHALL ALSO BE | | | SUBMITTED, ALONG WITH THE WALL FINISHES COMPLYING WITH | | | FBC SEC. 803/ 804 AND 805. | | | | | | 8)ADDITIONAL STRUCTURAL DETAIL ON THE FLOOR AND | | | CEILING STUDS WILL ALSO BE REQUIRED, ALSO THE | | | VENTILATION PER 1203 AND 1210 OF THE FBC. THE TYPE OF | | | GLASS AT THE BATHROOM SHOWER FBC.2406/ | | | | | | 9) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | THERE MAY BE OTHER COMMENTS FOR ACCESSIBILITY AND FAIR | | | HOUSING DEPENDING ON THE USE AND OCCUPANCY OF THE | | | BUILDING. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2008-01-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-01-08 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-01-08 |
Time |
08:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-12-18 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-12-18 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2007-12-18 08:06:35 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR | | | DEVICES AND EQUIPMENT IN THE ADDED TOILET,106.3.5 | | | FBC.. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-11-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-11-29 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-11-29 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2007-11-29 11:29:22 | | | | PROVISO | | | | | | 907.2.10.1 WHERE REQUIRED. | | | SINGLE- OR MULTIPLE-STATION SMOKE ALARMS SHALL BE | | | INSTALLED IN THE LOCATIONS DESCRIBED IN SECTIONS | | | 907.2.10.1.1 THROUGH 907.2.10.1.3. | | | 907.2.10.1.1 GROUP R-1. | | | AN APPROVED SINGLE-STATION SMOKE ALARM SHALL BE | | | INSTALLED IN EVERY GUESTROOM AND EVERY LIVING AREA AND | | | SLEEPING ROOM WITHIN A GUEST SUITE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-11-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-11-20 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-11-20 |
Time |
07:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-03 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-03 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2007-10-03 16:29:02 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | ALL COMMENTS RELATE TO SHEET E-P, UNLESS OTHERWISE | | | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | | OTHERWISE NOTED. | | | | | | 1} PER 700.12(F)(4) THE BRANCH CIRCUIT FEEDING THE UNIT | | | EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT | | | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED | | | AHEAD OF ANY LOCAL SWITCHES. INDICATE SAME ON PLANS , | | | WITH CIRCUITS NUMBERED. | | | | | | 2} RECEPTACLE SPACING MUST COMPLY WITH 210.60 AND | | | LIGHTING PER 210.70(B), LOCATE SAME ON PLANS. | | | | | | 3} THE LOAD CALCULATION MUST BE PER 220.44. | | | | | | 4} INDICATE CONDUCTOR AND CONDUIT SIZES AND TYPE FOR | | | THE FEEDER TO THE SUB PANEL. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-08-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-08-28 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-08-28 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2007-08-28 12:33:03 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONE COMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE SCOPE OF WORK IS UNCLEAR. SUBMIT PLANS PER | | | 106.3.5.1.2 FBC. PANEL SCHEDULES, FLOOR PLANS, LOAD | | | CALCS, CIRCUIT NUMBERS PANEL DESIGNATIONS, EXIT AND | | | EMERGENCY LIGHTING, ETC. | | | | | | 2} AN ELECTRICALPERMIT FOR THIS BUILDING WAS RECENTLY | | | ISSUED, # 07070451, TO REPAIROR REPLACE FIXTURES. THE | | | STATED USE AT THAT TIME WAS WAREHOUSE.THE DESIGN | | | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF | | | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE | | | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE | | | PLAN. | | | | | | 3} DECLARE THE TYPE OF OCCUPANY AND USE PER SECTION | | | 306 | | | CHANGE OF OCCUPANCY | | | 306.1SCOPE. | | | CHANGE OF OCCUPANCY PROVISIONS APPLY WHERE THE ACTIVITY | | | IS CLASSIFIED AS A CHANGE OF OCCUPANCY AS DEFINED IN | | | CHAPTER 2. | | | 306.2APPLICATION. | | | CHANGES OF OCCUPANCY SHALL COMPLY WITH THE PROVISIONS | | | OF CHAPTER 8. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2008-01-10 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-10 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-01-10 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2008-01-10 14:10:33 | *****APPROVED***** | | | | | | | | | PLAN SHEETS A-S-1 AND E-P-2 STAMPED, INITIALED, AND | | | DATED |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-12-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-20 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-20 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2007-12-20 15:00:27 | *****PROVISO***** | | | | | | | | | PLANS WERE APPROVED AND STAMPED ON 11/27/07;HOWEVER | | | THE NEW SUBMITTED SHEETS TO BE FIRE-STAMPED WHEN THE | | | OTHER REVIEWERS HAVE BEEN ADDRESSED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-11-27 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-11-27 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-11-27 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2007-11-27 15:24:29 | PLANS APPROVED AND STAMPED ON THIS DATE. SEPARATE SHOP | | | DRAWINGS AND PERMIT REQUIRED FOR FIRE SPRINKLER | | | REMODEL. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-10-12 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-12 |
Time |
22:11 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-12 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2007-10-12 23:14:34 | *****DENIED***** | | | | | | | | | 01.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET (INCLUDING | | | CONSTRUCTION DOCUMENTS). | | | | | | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 03.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR | | | HINDER ACCESS TO OR EGRESS FROM THE SAID PROPERTY.ALL | | | EXIT COMPONENTS ARE TO BE MAINTAINED. | | | | | | 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 05. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 06.THE DOOR TO THE TEMPORARY STRUCTURE IS TO REMAIN | | | LOCKED DURING NON VIEWING TIMES. | | | | | | 07.SPECIFY THE HAZARD OF CONTENTS OF THE STRUCTURE AS | | | CLASSIFIED AS LOW, ORDINARY, OR HIGH. | | | | | | 08.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN | | | TERRMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 09.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF | | | CLASS I OR CLASS II. | | | | | | 10.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | FIRE SPRINKLER REMODEL.NFPA 13 - 2002 EDITION SHALL | | | BE REFERENCED.PLEASE BE ADVISED THAT SUB-PERMITS | | | SHALL NOT BE REVIEWED AND APPROVED BY THIS OFFICE UNTIL | | | SUCH TIME THAT THE MASTER PERMIT HAS BEEN ISSUED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-08-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-29 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-29 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2007-08-29 16:23:47 | *****DENIED***** | | | | | | | | | PLEASE BE ADVISED THATIN ORDER TO CONDUCT A COMPLETE | | | FIRE REVIEW MORE INFORMATION IS NEEDED (FOR INSTANCE): | | | | | | *THE USE AND OCCUPANCY OF THE BUILDING OF WHICH THE | | | MOCK-UP HOTEL ROOM IS TO BE LOCATED.*HOW WILL THE | | | SCOPE OF WORK IMPACT FIRE SPRINKLER/FIRE ALARM SYSTEM, | | | MEANS OF EGRESS, AND/OR ANY OTHER LIFE SAFETY | | | COMPONENTS PRESENTLY IN THE BUILDING*WHAT | | | BUILDING, FIRE, ELECTRICAL, PLUMBING, ETC., CODES WILL | | | THE STRUCTURE BE ERECTED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-01-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-04 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-04 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2008-01-04 11:06:46 | TO "BOB"#2 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-12-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-10 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-10 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2007-12-12 11:29:39 | TO "BOB"#15 | | 2007-12-10 15:44:22 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-11-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-15 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-15 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2007-11-19 10:00:11 | TO "BOB"#8 | | 2007-11-15 09:22:22 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-09-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-21 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-21 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2007-10-01 14:32:22 | TO "BOB"#10 | | 2007-09-21 16:54:56 | "WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-08-30 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-08-03 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2007-08-10 08:58:04 | TO BOB #13 | | 2007-08-03 13:53:26 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2008-01-08 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-01-08 |
Time |
16:29 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-01-08 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2008-01-08 16:35:18 | NO A/C PLAN SUBMITTED AT THIS TIME, ONLY BATHROOM AND | | | CLOTHES DRYER VENTS. | | | | | | *** PROVISO: PROVIDE FOR OUTSIDE AIR, PER 2004 FBC/M | | | 401.2. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2007-12-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-12 |
Time |
14:31 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-12-12 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2007-12-12 14:50:58 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) 401.5.1 INTAKE OPENINGS. | | | MECHANICAL AND GRAVITY OUTSIDE AIR INTAKE OPENINGS | | | SHALL BE LOCATED A MINIMUM OF 10 FEET FROM ANY | | | HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | | AND LOADING DOCKS, EXCEPT AS OTHERWISE SPECIFIED IN | | | THIS CODE. FRESH AIR INTAKES SHALL NOT BE LOCATED | | | CLOSER THAN 10 FEET (3048 MM) FROM ANY CHIMNEY OR VENT | | | OUTLET, OR SANITARY SEWER VENT OUTLET. | | | | | | 2) PLEASE SHOW OUTDOOR AIR CALCULATIONS, AND | | | INFORMATION REGARDING SUPPLY FAN, SEE 2004 FBC/M | | | 403.2. | | | | | | 3) THE NEW HANDICAPPED BATHROOM REQUIRES A EXHAUST FAN | | | ALSO, SEE 2004 FBC/M 402.3.1 AND NOTE #1 ABOVE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-11-29 |
Time |
15:12 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-11-29 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2007-11-29 15:36:51 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) AS THE UNIT WILL HAVE OPERATING BATHROOM AND | | | OPERATING ELECTRICAL APPLIANCES ,THE UNIT MUST BE | | | TREATED AS IF IT COULD BE OCCUPIED. AND MUST COMPLY | | | WITH THE FBC MECHANICAL. | | | | | | 2) PROVIDE MECHANICAL PLANS SHOWING BATHROOM EXHAUST, | | | CLOTHES DRYER EXHAUST, OUTDOOR VENTILATION, AND AIR | | | CONDITIONING. SHOW HOW THE EXHAUST AIR WILL BE | | | TRANSFERRED TO THE OUTDOORS AND HOW THE OUTDOOR AIR | | | WILL BE BROUGHT IN FROM THE OUTDOORS (NOT WITHIN | | | WAREHOUSE). PER 2004 FBC 106.3.5. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-08-13 |
Time |
11:55 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2007-08-13 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2007-08-13 11:57:32 | NO MECHANICAL PLANS SUBMITTED, AND NO | | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | | THIS TIME. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-01-11 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-01-11 |
Time |
15:17 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-12-18 |
Time |
06:03 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-12-18 |
Time |
06:03 |
Sent To |
|
|
| Notes |
| 2007-12-18 06:51:20 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED 4TH TIME: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. THE PREVIOUS PLAN REVIEW COMMENTS WERE ADDRESSED | | | HOWEVER WITH THE ADDITION OF THE NEW HANDICAP BATHROOM | | | THE FOLLOWING IS REQUIRED. | | | NOTE: THE REQUIRED FIXTURE CLEAR FLOOR SPACE AND | | | WHEELCHAIR TURNING SPACE SHALL ALSO BE INDICATED ON THE | | | FLOOR PLAN. | | | | | | **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH | | | THE FOLLOWING INFORMATION) | | | 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3 | | | HEIGHT. 17" TO 19". | | | 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C | | | 36" LONG. | | | 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" | | | HIGH. | | | 11-4.16.6 DISPENSERS. SEE FIGURE 29(B). | | | | | | | | | **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL | | | REQUIRED WITH THE FOLLOWING INFORMATION) | | | 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR | | | COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE | | | FIGURE 31) | | | 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND | | | A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE | | | 32) | | | 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO | | | PROTECT AGAINST CONTACT. | | | 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND | | | ELECTRONICALLY CONTROLLED ARE EXAMPLES. | | | 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F. | | | . | | | | | | **11-4.21 SHOWER STALLS (ELEVATION DETAIL REQUIRED WITH | | | THE FOLLOWING INFORMATION) | | | 11-4.21.2 SIZE AND CLEARANCES. (SEE FIGURES 35(A) OR | | | (B) AND FIGURES 57 (A) OR (B) | | | 11-4.21.3 SEAT. REQUIRED IN A 36" X 36" (17"-19" HIGH) | | | 11-4.21.4 GRAB BARS. REQUIRED (SEE FIGURE 37) 11-4.21.5 | | | CONTROLS. REQUIRED (SEE FIGURE 37) 11-4.21.7 CURBS. 36" | | | X 36" MAXIMUM 1/2" CURB (NO CURB REQUIRED IN MINIMUM | | | 30" X 60" STALLS) | | | | | | **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER | | | ROOMS. | | | 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE | | | SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR | | | SPACE (PER 11-4.2.3) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-12-05 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-12-05 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-12-05 |
Time |
13:26 |
Sent To |
PC |
|
| Notes |
| 2007-12-05 13:57:41 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 07 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED 3RD TIME: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | THE RESUBMITTED PLAN FOR PLUMBING PLAN REVIEW TO MEET | | | CODE COMPLIANCE. | | | | | | 1. FULL-OPEN VALVES SHALL BE INSTALLED IN THE | | | FOLLOWING LOCATIONS. PER *106.1, LOCATION OF FULL-OPEN | | | VALVES. | | | | | | A} ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE | | | ENTRANCE INTO THE STRUCTURE. | | | | | | B} ON THE WATER SUPPLY PIPE TO EVERY WATER HEATER. | | | | | | 2. WATER HAMMER ARRESTORS SHALL BE INSTALLED WHERE | | | QUICK CLOSING VALVES ARE UTILIZED. PLEASE PROVIDE WATER | | | HAMMER ARRESTORS FOR THE COLD AND HOT WATER ON THE | | | WASHING MACHINE. PER *604.9, WATER HAMMER. | | | | | | 3. CLEARLY IDENTIFY THE BACKFLOW PREVENTER AND WATER | | | METER ON THE RESUBMITAL. PER *106.1.1, INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | 4. THE WATER HEATER REQUIRES A PAN. PER *504.7, PAN | | | REQUIRED: PAN DRAIN FOR WATER HEATER MINIMUM DIAMETER | | | IS 3/4". PER 504.7.1, PAN SIZE AND DRAIN: PAN DRAIN | | | SHALL EXTEND TO THE EXTERIOR OF THE BUILDING AND | | | TERMINATE NOT LESS THAN 6" AND NOT MORE THAN 24" ABOVE | | | ADJACENT GROUND SURFACE. PER *504.7.2, PAN DRAIN | | | TERMINATION. | | | | | | 5. RELIEF VALVE REQUIRED FOR THE WATER HEATER. PER | | | *504.4, RELIEF VALVE: THE RELIEF VALVE SHALL DISCHARGE | | | FULL SIZE TO A SAFE PLACE OF DISPOSAL SUCH AS THE | | | HEATER PAN OR OUTSIDE THE BUILDING. PER *504.6.1, | | | DISCHARGE. | | | | | | 6. THERMAL EXPANSION CONTROL IS REQUIRED FOR THE WATER | | | HEATER. PER *607.3, THERMAL EXPANSION CONTROL AND | | | *607.3.2, BACKFLOW PREVENTION DEVICE OR CHECK VALVE. | | | | | | ********IMPORTANT INFORMATION******** | | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | | TRANSMITTAL LETTER INDICATING HOW EACH | | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. | | | NOTE: THERE IS ONLY ONE CORRECTED DRAWING | | | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS | | | EXAMINER FOR REFERENCE FOR THE | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-10-11 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-10-12 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-10-11 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2007-10-11 17:06:39 | DENIED 2ND TIME | | | REFERENCE: | | | ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA | | | ACCESSIBILITY CODE. | | | ** FLORIDA ADMINISTRATIVE CODE (FAC). | | | ** FLORIDA STATUTES (FS). | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, | | | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING | | | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT | | | MADE ON PREVIOUS REVIEWS. | | | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM | | | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. | | | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE | | | PREVIOUS REVIEW NOTES. | | | | | | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR | | | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS | | | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER | | | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. | | | | | | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL | | | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. | | | | | | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN | | | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW | | | COMMENT MAY HAVE BEEN FULLY ADDRESSED. | | | | | | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF | | | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. | | | | | | 1. **OK** | | | | | | 2. **NO/OK** A SANITARY RISER DIAGRAM WAS SUBMITTED AS | | | ASKED FOR (SEE NEW COMMENTS ON SANITARY RISER) BUT | | | HOWEVER NOT ALL OF THIS COMMENT WAS ADDRESSED. SUBMIT | | | PLANS PER FBC-2004 CHAPTER 1, THE CITY OF WEST PALM | | | BEACH AMENDMENTS, SECTION 106.3.5.1.3 PLUMBING 1 THRU | | | 13. | | | | | | NOTE: THE FOLLOWING IS REQUIRED ON THE RESUBMITTAL PER | | | SECTION 106.3.5.1.3, PLUMBING SUBSECTIONS, (3) WATER | | | SUPPLY PIPING, (5) WATER HEATERS, (8) BACKFLOW | | | PREVENTION, (10) LOCATION OF WATER SUPPLY LINE. PLEASE | | | SUBMIT AN ISOMETRIC WATER RISER DIAGRAM INDICATING PIPE | | | SIZES FOR HOT AND COLD WATER, VALVE LOCATIONS, WATER | | | HAMMER ARRESTOR LOCATIONS, BACKFLOW PREVENTOR LOCATION | | | ON RISER DIAGRAM AND FLOOR PLAN, WATER HEATER LOCATION | | | ON RISER DIAGRAM AND FLOOR PLAN. | | | | | | 3. **NO** NOTE: A THOROUGH REVIEW CAN'T BE DONE AT | | | THIS TIME BECAUSE OF ADDITIONAL INFORMATION REQUESTED | | | BY OTHER PLAN REVIEWERS IN REGUARD TO OCCUPANCY. | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW DUE TO NEW INFORMATION ON THE RESUBMITTAL. | | | THERE MAY BE OTHER COMMENTS FOR ACCESSIBILITY DEPENDING | | | ON THE USE AND OCCUPANCY OF THE BUILDING. | | | NOTE: PLEASE REFERENCE THE NEW COMMENTS ON | | | ACCESSIBILITY. | | | | | | **THE FOLLOWING ARE NEW COMMENTS: | | | | | | 4. SHEET A-S FLOOR PLAN AND SHEET ID-503 100% | | | CONSTRUCTION DOCUMENTS INDICATE A SHOWER BUT THE | | | SANITARY ISOMETRIC RISER DIAGRAM IS INDICATING A TUB. | | | PER FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON | | | CONSTRUCTION | | | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL | | | BE OF SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE | | | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, | | | AS DETERMINED BY THE | | | BUILDING OFFICIAL. PLEASE CORRELATE THE RISER DIAGRAM | | | ON THE RESUBMITTAL. | | | | | | 5. PLEASE INDICATE ON THE RESUBMITTED FLOOR PLAN WHERE | | | THE FUTURE WATER CLOSET AND LAVATORY ARE LOCATED ON | | | SHEET E-P SANITARY RISER PER FBC-2004 CHAPTER 1, | | | SECTION 106.1.1 AND SHOULDN'T THEY BE IDENTIFIED AS | | | TEMPORARY AS THE PERMIT APPLICATION STATES. NOTE: IF | | | THE FIXTURES WERE TO REMAIN FUTURE THEY WOULD NEED TO | | | BE CAPPED OR PLUGGED PER FBC-2004 W/05 & 06 REV. | | | PLUMBING, SECTION 704.5. PLEASE CLARIFY THIS ON THE | | | RESUBMITTAL. | | | | | | 6. SHEET E-P SANITARY RISER: PLEASE SIZE THE FUTURE | | | WATER CLOSET AND LAV PER FBC-2004 CHAPTER 1,PLUMBING | | | SECTION 106.3.5.1.3 AND CLEARLY INDICATE A TRAP FOR THE | | | LAV PER FB-2004 W/05 & 06 REV. SECTION 1002.1. | | | | | | 7. PER FBC-2004 WITH 05 & 06 REV.PLUMBING, THE | | | FOLLOWING IS REQUIRED FOR THE CLEANOUT FOR THE WASHING | | | MACHINE. | | | (A) 708.7 MINIMUM SIZE. CLEANOUTS SHALL | | | BE THE SAME NOMINAL SIZE AS THE PIPE | | | THEY SERVE UP TO 4 INCHES (102MM) | | | NOTE: CLEANOUT FOR WASHING MACHINE SHALL BE 3 INCH. | | | CLEARLY INDICATE THIS ON THE RESUBMITTAL. | | | (B) 708.9 ACCESS. ACCESS SHALL BE | | | PROVIDED TO ALL CLEANOUTS. | | | NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED | | | AT 4' A.F.F. CLEARLY INDICATE THIS ON THE RESUBMITTAL. | | | | | | 8. THE RESUBMITTAL IS INDICATINGTHE MOCK-UP UNIT AS | | | BEING FUNCTIONAL. NOTE: UNIT SHALL BE ACCESSIBLE PER | | | THE FOLLOWING FBC-2004 WITH 06 REVISIONS CHAPTER 11, | | | FLORIDA ACCESSIBILITY CODE. | | | NOTE: CLEAR FLOOR SPACE SHALL BE INDICATED ON THE | | | RESUBMITTED FLOOR PLAN. | | | | | | **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH | | | THE FOLLOWING INFORMATION) | | | 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3 | | | HEIGHT. 17" TO 19". | | | 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C | | | 36" LONG. | | | 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" | | | HIGH. | | | 11-4.16.6 DISPENSERS. SEE FIGURE 29(B). | | | | | | **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL | | | REQUIRED WITH THE FOLLOWING INFORMATION) | | | 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR | | | COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE | | | FIGURE 31) | | | 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND | | | A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE | | | 32) | | | 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO | | | PROTECT AGAINST CONTACT. | | | 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND | | | ELECTRONICALLY CONTROLLED ARE EXAMPLES. | | | 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F. | | | | | | **11-4.21 SHOWER STALLS (ELEVATION DETAIL REQUIRED WITH | | | THE FOLLOWING INFORMATION) | | | 11-4.21.2 SIZE AND CLEARANCES. (SEE FIGURES 35(A) OR | | | (B) AND FIGURES 57 (A) OR (B). | | | 11-4.21.3 SEAT. REQUIRED IN A 36" X 36" (17"-19" | | | HIGH). | | | 11-4.21.4 GRAB BARS. REQUIRED (SEE FIGURE 37). | | | 11-4.21.5 CONTROLS. REQUIRED (SEE FIGURE 37). 11-4.21.7 | | | CURBS. 36" X 36" MAXIMUM 1/2" CURB (NO CURB REQUIRED IN | | | MINIMUM 30" X 60" STALLS). | | | | | | **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE | | | FOLLOWING INFORMATION) | | | 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR | | | COUNTER. | | | 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE, | | | AND 19" DEEP. | | | 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP. | | | 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR | | | SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE | | | SINK. | | | 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO | | | PROTECT AGAINST CONTACT. | | | 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR | | | ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS. | | | | | | **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER | | | ROOMS. | | | 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR | | | SPACE (CLEARLY INDICATE ON FLOOR PLAN) | | | 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE | | | SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR | | | SPACE (PER 11-4.2.3) (CLEARLY INDICATE ON FLOOR PLAN) | | | | | | ********IMPORTANT INFORMATION******** | | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | | TRANSMITTAL LETTER INDICATING HOW EACH | | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. | | | NOTE: THERE IS ONLY ONE CORRECTED DRAWING | | | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS | | | EXAMINER FOR REFERENCE FOR THE | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-08-30 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-08-30 |
Time |
13:14 |
Sent To |
PC |
|
| Notes |
| 2007-08-30 13:38:50 | DENIED | | | REFERENCE: | | | ** FBC-2004 PLUMBING. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | 1. THE SCOPE OF WORK FOR THIS PROPOSED "MOCK UP OF A | | | HOTEL ROOM INCLUDING BATHROOM" IS UNCLEAR. IS THIS | | | GOING TO BE A WOKING MOCK UP? PLEASE CLARIFY THIS ON | | | THE RESUBMITTAL. | | | | | | 2. SUBMIT PLANS PER FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS, SECTION 106.3.5.1.3 | | | PLUMBING 1 THROUGH 13. | | | | | | 3. NOTE: A THOROUGH REVIEW CAN'T BE DONE AT THIS TIME | | | BECAUSE OF ADDITIONAL INFORMATION REQUESTED BY OTHER | | | PLAN REVIEWERS IN REGUARD TO OCCUPANCY. ADDITIONAL | | | COMMENTS MAY APPEAR THAT WERE NOT PART OF THIS REVIEW | | | DUE TO NEW INFORMATION ON THE THE RESUBMITTAL. THERE | | | MAY BE OTHER COMMENTS FOR ACCESSIBILITY DEPENDING ON | | | THE USE AND OCCUPANCY OF THE BUILDING. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-08-13 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-08-13 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2007-08-13 17:12:06 | RESEARCH AND DEVELOPMENT OF MOCK-UP HOTEL SUITE IS A | | | PERMITTED USE IN INDUSTRIAL ZONING DESIGNATIONS. | | | | | | *VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | | IMPROVEMENT VALUE. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |