Plan Review Details - Permit 07080045
Plan Review Stops For Permit 07080045
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-01-10 Cont ID  
Sent By mjacobs Date 2008-01-10 Time 08:57 Rev Time 0.00
Received By mjacobs Date 2008-01-10 Time 06:59 Sent To  
Notes
2008-01-10 09:11:02PROVISOR:
 SHOW THE ACCESSIBLE ROUTE TO THE UNIT MEET THE
 REQUIREMENTS OF SECTION 11-4.3.1
 **NEW** FBC 11-4.5.2 CHANGES IN LEVEL GREATER THAN ?
 INCH SHALL BE ACCOMPLISHED BY MEANS OF A RAMP THAT
 COMPLIES WITH SECTION 11-4.7 OR 11-4.8. SHOW
 COMPLIANCE. THIS IS REQUIRED DUE TO THE FACT THAT THERE
 ARE STEPS LEADING TO THE ENTRANCE OF THE ROOM. ALL
 RAMPS SHALL BE STABLE, FIRM, SLIP RESISTANT, AND SHALL
 COMPLY WITH SECTION 11-4.5.LANDINGS AT RAMPS SHALL
 MEET THE REQUIREMENTS OF 11-4.8.4 AND 11-4.13.6 SHOW IN
 DETAIL DRAWINGS HOW THESE REQUIREMENTS WILL BE
 ACCOMPLISHED.
 **(A) ALL LANDINGS ON RAMPS SHALL BE NOT LESS THAN 60
 INCHES CLEAR, AND THE BOTTOM OF EACH RAMP SHALL HAVE
 NOT LESS THAN 72 INCHES OF STRAIGHT AND LEVEL
 CLEARANCE. 11-4.8.4(2)
 **(B) IF A RAMP RUN HAS A RISE GREATER THAN 6 INCHES,
 THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES. THE
 INFORMATION ABOVE SHALL BE CLEARLY INDICATED ON THE
 DRAWINGS. THE DRAWINGS SUBMITTED DO NOT SHOW ALL THE
 REQUIREMENTS FOR THE RAMP CLEARLY. SUBMIT ELEVATION
 DRAWINGS SHOWING THE SLOPE AND RISE, CLEAR WIDTH,
 LANDINGS AND HANDRAILS WITH ALL REQUIRED DIMENSIONS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS O THIS CODE. 106.1.1**
 NOTE: IF THIS IS A TEMPORARY STURCTURE, IT SHALL
 CONFORM TO FBC. SEC 107. WHIC HAS A TIME LIMIT OF 180
 DAYS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-12-15 Cont ID  
Sent By mjacobs Date 2007-12-15 Time 16:07 Rev Time 0.00
Received By mjacobs Date 2007-12-15 Time 10:13 Sent To  
Notes
2007-12-15 16:07:39BUILDING PLAN REVIEW
 PERMIT: 07080045
 ADD: 1604 CLARE AVE
 CONT: BENITZ BUILDING LLC
 TEL: (561)659-4024
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 4TH
 ACTION: DENIED
 12/15/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)OK
  
 3)BEFORE THE MOCK-UP ROOMS CAN BE APPROVED, MORE
 INFORMATION SHALL BE SUBMITTED.
 **NOTED**SHEETS WERE REMOVED FROM PACKAGE.
 4)OK
 5)OK
 6) NOTE: IF THIS IS A TEMPORARY STURCTURE, IT SHALL
 CONFORM TO FBC. SEC 107. WHIC HAS A TIME LIMIT OF 180
 DAYS.
 **THE RESPONSE SHEET STATES THAT THE WORK ?TEMPORARY?
 WILL BE REMOVED FROM THE APPLICATION. DOES THIS MEAN
 THAT THE STRUCTURE WILL NOW BE ?PERMANENT??**
  
  
  
  
 7)OK
  
 **NO RRESPONSE NOT ADDRESSED**
 8)ADDITIONAL STRUCTURAL DETAIL ON THE FLOOR AND
 CEILING STUDS WILL ALSO BE REQUIRED, ALSO THE
 VENTILATION PER 1203 AND 1210 OF THE FBC. THE TYPE OF
 GLASS AT THE BATHROOM SHOWER FBC.2406/
 **NEW**
 SHOW THE ATTACHMENT DETAIL OF THE FLOOR JOIST TO THE
 EXISTING FLOOR INDICATING THE MATERIALS. THE HEADER AND
 SILL FRAMING DETAIL SHALL BE SHOWN ON THE DRAWINGS. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS AND OTHER DATA NECESSARY TO DESCRIBE
 THE CONSTRUCTION OR INSTALLATION OF THE PROJECT. WPB
 AMENDMENTS 106.1.2
 **(A)PROVIDE A NORTH, SOUTH, EAST AND WEST FRAMING
 ELEVATION OF THE STRUCTURE SHOWING EACH OPENING WITH
 THE FRAMING DETAILS.
  
 9) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 THERE MAY BE OTHER COMMENTS FOR ACCESSIBILITY AND FAIR
 HOUSING DEPENDING ON THE USE AND OCCUPANCY OF THE
 BUILDING.
  
 **NEW**
 10)OK.
  
 **NO RRESPONSE NOT ADDRESSED**
 11)SHOW THE ACCESSIBLE ROUTE TO THE UNIT MEET THE
 REQUIREMENTS OF SECTION 11-4.3.1
 **NEW** FBC 11-4.5.2 CHANGES IN LEVEL GREATER THAN ?
 INCH SHALL BE ACCOMPLISHED BY MEANS OF A RAMP THAT
 COMPLIES WITH SECTION 11-4.7 OR 11-4.8. SHOW
 COMPLIANCE. THIS IS REQUIRED DUE TO THE FACT THAT THERE
 ARE STEPS LEADING TO THE ENTRANCE OF THE ROOM. ALL
 RAMPS SHALL BE STABLE, FIRM, SLIP RESISTANT, AND SHALL
 COMPLY WITH SECTION 11-4.5.LANDINGS AT RAMPS SHALL
 MEET THE REQUIREMENTS OF 11-4.8.4 AND 11-4.13.6 SHOW IN
 DETAIL DRAWINGS HOW THESE REQUIREMENTS WILL BE
 ACCOMPLISHED.
 **(A) ALL LANDINGS ON RAMPS SHALL BE NOT LESS THAN 60
 INCHES CLEAR, AND THE BOTTOM OF EACH RAMP SHALL HAVE
 NOT LESS THAN 72 INCHES OF STRAIGHT AND LEVEL
 CLEARANCE. 11-4.8.4(2)
 **(B) IF A RAMP RUN HAS A RISE GREATER THAN 6 INCHES,
 THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES. THE
 INFORMATION ABOVE SHALL BE CLEARLY INDICATED ON THE
 DRAWINGS. THE DRAWINGS SUBMITTED DO NOT SHOW ALL THE
 REQUIREMENTS FOR THE RAMP CLEARLY. SUBMIT ELEVATION
 DRAWINGS SHOWING THE SLOPE AND RISE, CLEAR WIDTH,
 LANDINGS AND HANDRAILS WITH ALL REQUIRED DIMENSIONS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS O THIS CODE. 106.1.1**
  
 **NO RRESPONSE NOT ADDRESSED**
 12)SHOW ON THE ON THE DRAWINGS THE EXISTING BATHROOM
 FACILITIES. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. FBC 106.1.1.
 **(A) BATHROOMS, BATHING FACILITIES, OR SHOWER ROOMS
 REQUIRED TO BE ACCESSIBLE SHALL COMPLY WITH SECTION
 11-4.23 AND SHALL BE ON AN ACCESSIBLE ROUTE. THE CLEAR
 FLOOR SPACE AND TURNING SPACE SHALL BE INDICATED ON THE
 PLANS.
 **(B) SHOWER STALL SIZE AND CLEAR FLOOR SPACE SHALL
 COMPLY WITH FIGURE 35(A) OR FIGURE 35(B). A SEAT SHALL
 BE PROVIDED IN SHOWER STALLS 36 INCHES BY 36 INCHES AND
 SHALL BE AS SHOWN IN FIGURE 36.11-4.21.3
  
 **NO RRESPONSE NOT ADDRESSED**
 13)A DETAIL LETTER INDICATING THE USE/ OCCUPANCY AND
 PURPOSE OF THE STRUCTURE CAN ALSO SUBMITTED BY THE
 OWNER. THE LETTER SHALL BE CLEAR AND PRECISE STATING
 THAT THE SPACE IS ONLY USED AS A SHOW ROOM.
  
 **NEW**
 14)OK
  
 15)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS
 & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-11-28 Cont ID  
Sent By mjacobs Date 2007-11-28 Time 17:39 Rev Time 0.00
Received By mjacobs Date 2007-11-28 Time 11:31 Sent To  
Notes
2007-11-28 17:34:33 
 BUILDING PLAN REVIEW
 PERMIT: 07080045
 ADD: 1604 CLARE AVE
 CONT: BENITZ BUILDING LLC
 TEL: (561)659-4024
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD
 ACTION: DENIED
 11/28/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)OK
  
 3)BEFORE THE MOCK-UP ROOMS CAN BE APPROVED, MORE
 INFORMATION SHALL BE SUBMITTED.
 **NOTED**SHEETS WERE REMOVED FROM PACKAGE.
 4)OK
 5)OK
  
 6) NOTE: IF THIS IS A TEMPORARY STURCTURE, IT SHALL
 CONFORM TO FBC. SEC 107. WHIC HAS A TIME LIMIT OF 180
 DAYS.
  
 **NO RRESPONSE NOT ADDRESSED**
 7)A LEGEND WITH THE WALL DETAILS SHALL ALSO BE
 SUBMITTED, ALONG WITH THE WALL FINISHES COMPLYING WITH
 FBC SEC. 803/ 804 AND 805.
  
 **NO RRESPONSE NOT ADDRESSED**
 8)ADDITIONAL STRUCTURAL DETAIL ON THE FLOOR AND
 CEILING STUDS WILL ALSO BE REQUIRED, ALSO THE
 VENTILATION PER 1203 AND 1210 OF THE FBC. THE TYPE OF
 GLASS AT THE BATHROOM SHOWER FBC.2406/
 **NEW**
 SHOW THE ATTACHMENT DETAIL OF THE FLOOR JOIST TO THE
 EXISTING FLOOR INDICATING THE MATERIALS. THE HEADER AND
 SILL FRAMING DETAIL SHALL BE SHOWN ON THE DRAWINGS. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS AND OTHER DATA NECESSARY TO DESCRIBE
 THE CONSTRUCTION OR INSTALLATION OF THE PROJECT. WPB
 AMENDMENTS 106.1.2
  
 9) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 THERE MAY BE OTHER COMMENTS FOR ACCESSIBILITY AND FAIR
 HOUSING DEPENDING ON THE USE AND OCCUPANCY OF THE
 BUILDING.
  
 **NEW**
 10)OK.
  
 **NO RRESPONSE NOT ADDRESSED**
 11)SHOW THE ACCESSIBLE ROUTE TO THE UNIT MEET THE
 REQUIREMENTS OF SECTION 11-4.3.1
 **NEW** FBC 11-4.5.2 CHANGES IN LEVEL GREATER THAN ?
 INCH SHALL BE ACCOMPLISHED BY MEANS OF A RAMP THAT
 COMPLIES WITH SECTION 11-4.7 OR 11-4.8. SHOW
 COMPLIANCE. THIS IS REQUIRED DUE TO THE FACT THAT THERE
 ARE STEPS LEADING TO THE ENTRANCE OF THE ROOM. ALL
 RAMPS SHALL BE STABLE, FIRM, SLIP RESISTANT, AND SHALL
 COMPLY WITH SECTION 11-4.5.LANDINGS AT RAMPS SHALL
 MEET THE REQUIREMENTS OF 11-4.8.4 AND 11-4.13.6 SHOW IN
 DETAIL DRAWINGS HOW THESE REQUIREMENTS WILL BE
 ACCOMPLISHED
  
 **NO RRESPONSE NOT ADDRESSED**
 12)SHOW ON THE ON THE DRAWINGS THE EXISTING BATHROOM
 FACILITIES. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. FBC 106.1.1.
  
 **NO RRESPONSE NOT ADDRESSED**
 13)A DETAIL LETTER INDICATING THE USE/ OCCUPANCY AND
 PURPOSE OF THE STRUCTURE CAN ALSO SUBMITTED BY THE
 OWNER. THE LETTER SHALL BE CLEAR AND PRECISE STATING
 THAT THE SPACE IS ONLY USED AS A SHOW ROOM.
  
 **NEW**
 14)FBC 907.2.10.1 AN APPROVED SINGLE-STATION SMOKE
 ALARM SHALL BE INSTALLED IN EVERY GUESTROOM AND EVERY
 LIVING AREA AND SLEEPING ROOM WITHIN A GUEST SUITE.
  
 15)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS
 & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-10 Cont ID  
Sent By mjacobs Date 2007-10-10 Time 17:31 Rev Time 0.00
Received By mawillia Date 2007-10-10 Time 11:44 Sent To  
Notes
2007-10-10 17:31:07 
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07080045
 ADD: 1604 CLARE AVE
 CONT: BENITZ BUILDING LLC
 TEL: (561)659-4024
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 10/10/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)OK
  
 3)BEFORE THE MOCK-UP ROOMS CAN BE APPROVED, MORE
 INFORMATION SHALL BE SUBMITTED.
 **NOTED** HOWEVER, ALL DRAWINGS SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BE SIGNED SEAL AND DATED BY THE
 DESIGN PROFESSIONAL AS REQUIRED BY FLORIDA STATUTES 471
 AND 481. IF THE 11X17 SHEETS ARE SUBMITTED AS
 ADDITIONAL INFORMATION, THEY SHALL BE SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DRAWINGS.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 . -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF BEDROOMS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
 **NOTED, HOWEVER, ALL THE INFORMATION SHALL BE
 INDICATED ON THE DRAWINGS**
  
 5)OK
  
 6)IF THIS IS A TEMPORARY STURCTURE, IT SHALL CONFORM
 TO FBC. SEC 107. WHIC HAS A TIME LIMIT OF 180 DAYS.
 **NO RESPONSE NOT ADDRESSED**
  
 7)A LEGEND WITH THE WALL DETAILS SHALL ALSO BE
 SUBMITTED, ALONG WITH THE WALL FINISHES COMPLYING WITH
 FBC SEC. 803/ 804 AND 805.
 **NO RESPONSE NOT ADDRESSED**
  
 8)ADDITIONAL STRUCTURAL DETAIL ON THE FLOOR AND
 CEILING STUDS WILL ALSO BE REQUIRED, ALSO THE
 VENTILATION PER 1203 AND 1210 OF THE FBC. THE TYPE OF
 GLASS AT THE BATHROOM SHOWER FBC.2406/
 **NEW**
 SHOW THE ATTACHMENT DETAIL OF THE FLOOR JOIST TO THE
 EXISTING FLOOR INDICATING THE MATERIALS. THE HEADER AND
 SILL FRAMING DETAIL SHALL BE SHOWN ON THE DRAWINGS. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS AND OTHER DATA NECESSARY TO DESCRIBE
 THE CONSTRUCTION OR INSTALLATION OF THE PROJECT. WPB
 AMENDMENTS 106.1.2
  
 9) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 THERE MAY BE OTHER COMMENTS FOR ACCESSIBILITY AND FAIR
 HOUSING DEPENDING ON THE USE AND OCCUPANCY OF THE
 BUILDING.
  
 **NEW**
 10)THE FUNCTIONAL UNIT SHALL BE ACCESSIBLE AND SHALL
 MEET THE REQUIREMENTS OF THE ACCESSIBILITY CODE. SINKS
 SHALL MEET THE REQUIREMENTS OF SECTION 11-4.24. SHOWER
 STALLS SHALL COMPLY WITH SECTION 11-4.21. A SHOWER
 SPRAY UNIT WITH A HOSE AT LEAST 60 INCHES LONG THAT CAN
 BE USED BOTH AS A FIXED SHOWER HEAD AND AS A HAND-HELD
 SHOWER SHALL BE PROVIDED 11-4.20.6.11-4.26.1 GENERAL.
 ALL HANDRAILS , GRAB BARS , AND TUB AND SHOWER SEATS
 REQUIRED TO BE ACCESSIBLE BY SECTION 11-4.1 , 11-4.8 ,
 11-4.9 , 11-4.16 , 11-4.17 , 11-4.20 OR 11-4.21 SHALL
 COMPLY WITH SECTION 11-4.26 .
  
 11)SHOW THE ACCESSIBLE ROUTE TO THE UNIT MEET THE
 REQUIREMENTS OF SECTION 11-4.3.1
  
 12)SHOW ON THE ON THE DRAWINGS THE EXISTING BATHROOM
 FACILITIES. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. FBC 106.1.1.
  
 13)A DETAIL LETTER INDICATING THE USE/ OCCUPANCY AND
 PURPOSE OF THE STRUCTURE CAN ALSO SUBMITTED BY THE
 OWNER. THE LETTER SHALL BE CLEAR AND PRECISE STATING
 THAT THE SPACE IS ONLY USED AS A SHOW ROOM.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-21 Cont ID  
Sent By mjacobs Date 2007-08-21 Time 12:42 Rev Time 0.00
Received By mjacobs Date 2007-08-21 Time 08:38 Sent To  
Notes
2007-08-21 12:41:57BUILDING PLAN REVIEW
 PERMIT: 07080045
 ADD: 1604 CLARE AVE
 CONT: BENITZ BUILDING LLC
 TEL: (561)659-4024
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)IF THERE IS A SPRINKLER SYSTEM IN THE BUILDING, THE
 MODEL ROOMS SHALL BE PROTECTED WITH SPRINLERS. SHOW THE
 SPRINKLER-HEADS SHALL BE INDICATED ON THE CEILING
 PLAN.
  
 3)BEFORE THE MOCK-UP ROOMS CAN BE APPROVED, MORE
 INFORMATION SHALL BE SUBMITTED.
  
 4)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT
 . -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF BEDROOMS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
  
 5)INDICATE IF THE MOCK-UP ROOMS WILL BE CONSTRUCTED
 IN A NEW BUILDING OR A RENOVATED BUILDING. WILL THIS
 PROJECT INVOLVED A CHANGE OF OCCUPANCY? IF SO SEE FBC
 EXISTING CH.8.
  
 6)IF THIS IS A TEMPORARY STURCTURE, IT SHALL CONFORM
 TO FBC. SEC 107. WHIC HAS A TIME LIMIT OF 180 DAYS.
  
 7)A LEGEND WITH THE WALL DETAILS SHALL ALSO BE
 SUBMITTED, ALONG WITH THE WALL FINISHES COMPLYING WITH
 FBC SEC. 803/ 804 AND 805.
  
 8)ADDITIONAL STRUCTURAL DETAIL ON THE FLOOR AND
 CEILING STUDS WILL ALSO BE REQUIRED, ALSO THE
 VENTILATION PER 1203 AND 1210 OF THE FBC. THE TYPE OF
 GLASS AT THE BATHROOM SHOWER FBC.2406/
  
 9) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 THERE MAY BE OTHER COMMENTS FOR ACCESSIBILITY AND FAIR
 HOUSING DEPENDING ON THE USE AND OCCUPANCY OF THE
 BUILDING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-01-08 Cont ID  
Sent By btrobaug Date 2008-01-08 Time 09:01 Rev Time 0.00
Received By btrobaug Date 2008-01-08 Time 08:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-12-18 Cont ID  
Sent By btrobaug Date 2007-12-18 Time 08:06 Rev Time 0.00
Received By btrobaug Date 2007-12-18 Time 07:19 Sent To  
Notes
2007-12-18 08:06:35 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES AND EQUIPMENT IN THE ADDED TOILET,106.3.5
 FBC..
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-11-29 Cont ID  
Sent By btrobaug Date 2007-11-29 Time 11:48 Rev Time 0.00
Received By btrobaug Date 2007-11-29 Time 11:27 Sent To  
Notes
2007-11-29 11:29:22 
 PROVISO
  
 907.2.10.1 WHERE REQUIRED.
 SINGLE- OR MULTIPLE-STATION SMOKE ALARMS SHALL BE
 INSTALLED IN THE LOCATIONS DESCRIBED IN SECTIONS
 907.2.10.1.1 THROUGH 907.2.10.1.3.
 907.2.10.1.1 GROUP R-1.
 AN APPROVED SINGLE-STATION SMOKE ALARM SHALL BE
 INSTALLED IN EVERY GUESTROOM AND EVERY LIVING AREA AND
 SLEEPING ROOM WITHIN A GUEST SUITE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-11-20 Cont ID  
Sent By btrobaug Date 2007-11-20 Time 08:03 Rev Time 0.00
Received By btrobaug Date 2007-11-20 Time 07:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-03 Cont ID  
Sent By btrobaug Date 2007-10-03 Time 16:29 Rev Time 0.00
Received By btrobaug Date 2007-10-03 Time 12:45 Sent To  
Notes
2007-10-03 16:29:02 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET E-P, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} PER 700.12(F)(4) THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES. INDICATE SAME ON PLANS ,
 WITH CIRCUITS NUMBERED.
  
 2} RECEPTACLE SPACING MUST COMPLY WITH 210.60 AND
 LIGHTING PER 210.70(B), LOCATE SAME ON PLANS.
  
 3} THE LOAD CALCULATION MUST BE PER 220.44.
  
 4} INDICATE CONDUCTOR AND CONDUIT SIZES AND TYPE FOR
 THE FEEDER TO THE SUB PANEL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-28 Cont ID  
Sent By btrobaug Date 2007-08-28 Time 13:04 Rev Time 0.00
Received By btrobaug Date 2007-08-28 Time 06:49 Sent To  
Notes
2007-08-28 12:33:03 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONE COMPLIANT WITH THE FOLLOWING:
  
 1} THE SCOPE OF WORK IS UNCLEAR. SUBMIT PLANS PER
 106.3.5.1.2 FBC. PANEL SCHEDULES, FLOOR PLANS, LOAD
 CALCS, CIRCUIT NUMBERS PANEL DESIGNATIONS, EXIT AND
 EMERGENCY LIGHTING, ETC.
  
 2} AN ELECTRICALPERMIT FOR THIS BUILDING WAS RECENTLY
 ISSUED, # 07070451, TO REPAIROR REPLACE FIXTURES. THE
 STATED USE AT THAT TIME WAS WAREHOUSE.THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 3} DECLARE THE TYPE OF OCCUPANY AND USE PER SECTION
 306
 CHANGE OF OCCUPANCY
 306.1SCOPE.
 CHANGE OF OCCUPANCY PROVISIONS APPLY WHERE THE ACTIVITY
 IS CLASSIFIED AS A CHANGE OF OCCUPANCY AS DEFINED IN
 CHAPTER 2.
 306.2APPLICATION.
 CHANGES OF OCCUPANCY SHALL COMPLY WITH THE PROVISIONS
 OF CHAPTER 8.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-01-10 Cont ID  
Sent By mawillia Date 2008-01-10 Time 14:11 Rev Time 0.00
Received By mawillia Date 2008-01-10 Time 14:01 Sent To  
Notes
2008-01-10 14:10:33*****APPROVED*****
  
  
 PLAN SHEETS A-S-1 AND E-P-2 STAMPED, INITIALED, AND
 DATED

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-12-20 Cont ID  
Sent By mawillia Date 2007-12-20 Time 15:03 Rev Time 0.00
Received By mawillia Date 2007-12-20 Time 14:52 Sent To  
Notes
2007-12-20 15:00:27*****PROVISO*****
  
  
 PLANS WERE APPROVED AND STAMPED ON 11/27/07;HOWEVER
 THE NEW SUBMITTED SHEETS TO BE FIRE-STAMPED WHEN THE
 OTHER REVIEWERS HAVE BEEN ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-27 Cont ID  
Sent By mwennerg Date 2007-11-27 Time 15:18 Rev Time 0.00
Received By mwennerg Date 2007-11-27 Time 15:18 Sent To  
Notes
2007-11-27 15:24:29PLANS APPROVED AND STAMPED ON THIS DATE. SEPARATE SHOP
 DRAWINGS AND PERMIT REQUIRED FOR FIRE SPRINKLER
 REMODEL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-10-12 Cont ID  
Sent By mawillia Date 2007-10-12 Time 22:11 Rev Time 0.00
Received By mawillia Date 2007-10-12 Time 18:20 Sent To  
Notes
2007-10-12 23:14:34*****DENIED*****
  
  
 01.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET (INCLUDING
 CONSTRUCTION DOCUMENTS).
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER ACCESS TO OR EGRESS FROM THE SAID PROPERTY.ALL
 EXIT COMPONENTS ARE TO BE MAINTAINED.
  
 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 05. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 06.THE DOOR TO THE TEMPORARY STRUCTURE IS TO REMAIN
 LOCKED DURING NON VIEWING TIMES.
  
 07.SPECIFY THE HAZARD OF CONTENTS OF THE STRUCTURE AS
 CLASSIFIED AS LOW, ORDINARY, OR HIGH.
  
 08.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERRMS OF CLASS A, CLASS B, OR CLASS C.
  
 09.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF
 CLASS I OR CLASS II.
  
 10.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SPRINKLER REMODEL.NFPA 13 - 2002 EDITION SHALL
 BE REFERENCED.PLEASE BE ADVISED THAT SUB-PERMITS
 SHALL NOT BE REVIEWED AND APPROVED BY THIS OFFICE UNTIL
 SUCH TIME THAT THE MASTER PERMIT HAS BEEN ISSUED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-08-29 Cont ID  
Sent By mawillia Date 2007-08-29 Time 16:23 Rev Time 0.00
Received By mawillia Date 2007-08-29 Time 15:50 Sent To  
Notes
2007-08-29 16:23:47*****DENIED*****
  
  
 PLEASE BE ADVISED THATIN ORDER TO CONDUCT A COMPLETE
 FIRE REVIEW MORE INFORMATION IS NEEDED (FOR INSTANCE):
  
 *THE USE AND OCCUPANCY OF THE BUILDING OF WHICH THE
 MOCK-UP HOTEL ROOM IS TO BE LOCATED.*HOW WILL THE
 SCOPE OF WORK IMPACT FIRE SPRINKLER/FIRE ALARM SYSTEM,
 MEANS OF EGRESS, AND/OR ANY OTHER LIFE SAFETY
 COMPONENTS PRESENTLY IN THE BUILDING*WHAT
 BUILDING, FIRE, ELECTRICAL, PLUMBING, ETC., CODES WILL
 THE STRUCTURE BE ERECTED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-04 Cont ID  
Sent By shill Date 2008-01-04 Time 11:04 Rev Time 0.00
Received By shill Date 2008-01-04 Time 11:04 Sent To  
Notes
2008-01-04 11:06:46TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 15:44 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 15:44 Sent To  
Notes
2007-12-12 11:29:39TO "BOB"#15
2007-12-10 15:44:22WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 09:22 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 09:22 Sent To  
Notes
2007-11-19 10:00:11TO "BOB"#8
2007-11-15 09:22:22WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-21 Cont ID  
Sent By adarroug Date 2007-09-21 Time 16:54 Rev Time 0.00
Received By adarroug Date 2007-09-21 Time 16:54 Sent To  
Notes
2007-10-01 14:32:22TO "BOB"#10
2007-09-21 16:54:56"WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-30 Cont ID  
Sent By mperson Date 2007-08-30 Time 15:01 Rev Time 0.00
Received By mperson Date 2007-08-03 Time 13:52 Sent To  
Notes
2007-08-10 08:58:04TO BOB #13
2007-08-03 13:53:26WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-01-08 Cont ID  
Sent By tgordon Date 2008-01-08 Time 16:29 Rev Time 0.30
Received By tgordon Date 2008-01-08 Time 16:29 Sent To  
Notes
2008-01-08 16:35:18NO A/C PLAN SUBMITTED AT THIS TIME, ONLY BATHROOM AND
 CLOTHES DRYER VENTS.
  
 *** PROVISO: PROVIDE FOR OUTSIDE AIR, PER 2004 FBC/M
 401.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-12-12 Cont ID  
Sent By tgordon Date 2007-12-12 Time 14:31 Rev Time 0.30
Received By tgordon Date 2007-12-12 Time 14:31 Sent To  
Notes
2007-12-12 14:50:58PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) 401.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTSIDE AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET FROM ANY
 HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS, EXCEPT AS OTHERWISE SPECIFIED IN
 THIS CODE. FRESH AIR INTAKES SHALL NOT BE LOCATED
 CLOSER THAN 10 FEET (3048 MM) FROM ANY CHIMNEY OR VENT
 OUTLET, OR SANITARY SEWER VENT OUTLET.
  
 2) PLEASE SHOW OUTDOOR AIR CALCULATIONS, AND
 INFORMATION REGARDING SUPPLY FAN, SEE 2004 FBC/M
 403.2.
  
 3) THE NEW HANDICAPPED BATHROOM REQUIRES A EXHAUST FAN
 ALSO, SEE 2004 FBC/M 402.3.1 AND NOTE #1 ABOVE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-29 Cont ID  
Sent By tgordon Date 2007-11-29 Time 15:12 Rev Time 0.30
Received By tgordon Date 2007-11-29 Time 15:12 Sent To  
Notes
2007-11-29 15:36:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS THE UNIT WILL HAVE OPERATING BATHROOM AND
 OPERATING ELECTRICAL APPLIANCES ,THE UNIT MUST BE
 TREATED AS IF IT COULD BE OCCUPIED. AND MUST COMPLY
 WITH THE FBC MECHANICAL.
  
 2) PROVIDE MECHANICAL PLANS SHOWING BATHROOM EXHAUST,
 CLOTHES DRYER EXHAUST, OUTDOOR VENTILATION, AND AIR
 CONDITIONING. SHOW HOW THE EXHAUST AIR WILL BE
 TRANSFERRED TO THE OUTDOORS AND HOW THE OUTDOOR AIR
 WILL BE BROUGHT IN FROM THE OUTDOORS (NOT WITHIN
 WAREHOUSE). PER 2004 FBC 106.3.5.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-08-13 Cont ID  
Sent By tgordon Date 2007-08-13 Time 11:55 Rev Time 0.15
Received By tgordon Date 2007-08-13 Time 11:55 Sent To  
Notes
2007-08-13 11:57:32NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-01-11 Cont ID  
Sent By mperson Date 2008-01-11 Time 15:17 Rev Time 0.00
Received By mperson Date 2008-01-11 Time 15:17 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-12-18 Cont ID  
Sent By mperson Date 2007-12-18 Time 06:03 Rev Time 0.00
Received By mperson Date 2007-12-18 Time 06:03 Sent To  
Notes
2007-12-18 06:51:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 4TH TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE PREVIOUS PLAN REVIEW COMMENTS WERE ADDRESSED
 HOWEVER WITH THE ADDITION OF THE NEW HANDICAP BATHROOM
 THE FOLLOWING IS REQUIRED.
 NOTE: THE REQUIRED FIXTURE CLEAR FLOOR SPACE AND
 WHEELCHAIR TURNING SPACE SHALL ALSO BE INDICATED ON THE
 FLOOR PLAN.
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
 .
  
 **11-4.21 SHOWER STALLS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.21.2 SIZE AND CLEARANCES. (SEE FIGURES 35(A) OR
 (B) AND FIGURES 57 (A) OR (B)
 11-4.21.3 SEAT. REQUIRED IN A 36" X 36" (17"-19" HIGH)
 11-4.21.4 GRAB BARS. REQUIRED (SEE FIGURE 37) 11-4.21.5
 CONTROLS. REQUIRED (SEE FIGURE 37) 11-4.21.7 CURBS. 36"
 X 36" MAXIMUM 1/2" CURB (NO CURB REQUIRED IN MINIMUM
 30" X 60" STALLS)
  
 **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER
 ROOMS.
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-12-05 Cont ID  
Sent By mperson Date 2007-12-05 Time 13:26 Rev Time 0.00
Received By mperson Date 2007-12-05 Time 13:26 Sent To PC
Notes
2007-12-05 13:57:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 07 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 3RD TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 THE RESUBMITTED PLAN FOR PLUMBING PLAN REVIEW TO MEET
 CODE COMPLIANCE.
  
 1. FULL-OPEN VALVES SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS. PER *106.1, LOCATION OF FULL-OPEN
 VALVES.
  
 A} ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE
 ENTRANCE INTO THE STRUCTURE.
  
 B} ON THE WATER SUPPLY PIPE TO EVERY WATER HEATER.
  
 2. WATER HAMMER ARRESTORS SHALL BE INSTALLED WHERE
 QUICK CLOSING VALVES ARE UTILIZED. PLEASE PROVIDE WATER
 HAMMER ARRESTORS FOR THE COLD AND HOT WATER ON THE
 WASHING MACHINE. PER *604.9, WATER HAMMER.
  
 3. CLEARLY IDENTIFY THE BACKFLOW PREVENTER AND WATER
 METER ON THE RESUBMITAL. PER *106.1.1, INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. THE WATER HEATER REQUIRES A PAN. PER *504.7, PAN
 REQUIRED: PAN DRAIN FOR WATER HEATER MINIMUM DIAMETER
 IS 3/4". PER 504.7.1, PAN SIZE AND DRAIN: PAN DRAIN
 SHALL EXTEND TO THE EXTERIOR OF THE BUILDING AND
 TERMINATE NOT LESS THAN 6" AND NOT MORE THAN 24" ABOVE
 ADJACENT GROUND SURFACE. PER *504.7.2, PAN DRAIN
 TERMINATION.
  
 5. RELIEF VALVE REQUIRED FOR THE WATER HEATER. PER
 *504.4, RELIEF VALVE: THE RELIEF VALVE SHALL DISCHARGE
 FULL SIZE TO A SAFE PLACE OF DISPOSAL SUCH AS THE
 HEATER PAN OR OUTSIDE THE BUILDING. PER *504.6.1,
 DISCHARGE.
  
 6. THERMAL EXPANSION CONTROL IS REQUIRED FOR THE WATER
 HEATER. PER *607.3, THERMAL EXPANSION CONTROL AND
 *607.3.2, BACKFLOW PREVENTION DEVICE OR CHECK VALVE.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-10-11 Cont ID  
Sent By mperson Date 2007-10-12 Time 10:26 Rev Time 0.00
Received By mperson Date 2007-10-11 Time 10:26 Sent To  
Notes
2007-10-11 17:06:39DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **NO/OK** A SANITARY RISER DIAGRAM WAS SUBMITTED AS
 ASKED FOR (SEE NEW COMMENTS ON SANITARY RISER) BUT
 HOWEVER NOT ALL OF THIS COMMENT WAS ADDRESSED. SUBMIT
 PLANS PER FBC-2004 CHAPTER 1, THE CITY OF WEST PALM
 BEACH AMENDMENTS, SECTION 106.3.5.1.3 PLUMBING 1 THRU
 13.
  
 NOTE: THE FOLLOWING IS REQUIRED ON THE RESUBMITTAL PER
 SECTION 106.3.5.1.3, PLUMBING SUBSECTIONS, (3) WATER
 SUPPLY PIPING, (5) WATER HEATERS, (8) BACKFLOW
 PREVENTION, (10) LOCATION OF WATER SUPPLY LINE. PLEASE
 SUBMIT AN ISOMETRIC WATER RISER DIAGRAM INDICATING PIPE
 SIZES FOR HOT AND COLD WATER, VALVE LOCATIONS, WATER
 HAMMER ARRESTOR LOCATIONS, BACKFLOW PREVENTOR LOCATION
 ON RISER DIAGRAM AND FLOOR PLAN, WATER HEATER LOCATION
 ON RISER DIAGRAM AND FLOOR PLAN.
  
 3. **NO** NOTE: A THOROUGH REVIEW CAN'T BE DONE AT
 THIS TIME BECAUSE OF ADDITIONAL INFORMATION REQUESTED
 BY OTHER PLAN REVIEWERS IN REGUARD TO OCCUPANCY.
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW DUE TO NEW INFORMATION ON THE RESUBMITTAL.
 THERE MAY BE OTHER COMMENTS FOR ACCESSIBILITY DEPENDING
 ON THE USE AND OCCUPANCY OF THE BUILDING.
 NOTE: PLEASE REFERENCE THE NEW COMMENTS ON
 ACCESSIBILITY.
  
 **THE FOLLOWING ARE NEW COMMENTS:
  
 4. SHEET A-S FLOOR PLAN AND SHEET ID-503 100%
 CONSTRUCTION DOCUMENTS INDICATE A SHOWER BUT THE
 SANITARY ISOMETRIC RISER DIAGRAM IS INDICATING A TUB.
 PER FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL. PLEASE CORRELATE THE RISER DIAGRAM
 ON THE RESUBMITTAL.
  
 5. PLEASE INDICATE ON THE RESUBMITTED FLOOR PLAN WHERE
 THE FUTURE WATER CLOSET AND LAVATORY ARE LOCATED ON
 SHEET E-P SANITARY RISER PER FBC-2004 CHAPTER 1,
 SECTION 106.1.1 AND SHOULDN'T THEY BE IDENTIFIED AS
 TEMPORARY AS THE PERMIT APPLICATION STATES. NOTE: IF
 THE FIXTURES WERE TO REMAIN FUTURE THEY WOULD NEED TO
 BE CAPPED OR PLUGGED PER FBC-2004 W/05 & 06 REV.
 PLUMBING, SECTION 704.5. PLEASE CLARIFY THIS ON THE
 RESUBMITTAL.
  
 6. SHEET E-P SANITARY RISER: PLEASE SIZE THE FUTURE
 WATER CLOSET AND LAV PER FBC-2004 CHAPTER 1,PLUMBING
 SECTION 106.3.5.1.3 AND CLEARLY INDICATE A TRAP FOR THE
 LAV PER FB-2004 W/05 & 06 REV. SECTION 1002.1.
  
 7. PER FBC-2004 WITH 05 & 06 REV.PLUMBING, THE
 FOLLOWING IS REQUIRED FOR THE CLEANOUT FOR THE WASHING
 MACHINE.
 (A) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR WASHING MACHINE SHALL BE 3 INCH.
 CLEARLY INDICATE THIS ON THE RESUBMITTAL.
 (B) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED
 AT 4' A.F.F. CLEARLY INDICATE THIS ON THE RESUBMITTAL.
  
 8. THE RESUBMITTAL IS INDICATINGTHE MOCK-UP UNIT AS
 BEING FUNCTIONAL. NOTE: UNIT SHALL BE ACCESSIBLE PER
 THE FOLLOWING FBC-2004 WITH 06 REVISIONS CHAPTER 11,
 FLORIDA ACCESSIBILITY CODE.
 NOTE: CLEAR FLOOR SPACE SHALL BE INDICATED ON THE
 RESUBMITTED FLOOR PLAN.
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 **11-4.21 SHOWER STALLS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.21.2 SIZE AND CLEARANCES. (SEE FIGURES 35(A) OR
 (B) AND FIGURES 57 (A) OR (B).
 11-4.21.3 SEAT. REQUIRED IN A 36" X 36" (17"-19"
 HIGH).
 11-4.21.4 GRAB BARS. REQUIRED (SEE FIGURE 37).
 11-4.21.5 CONTROLS. REQUIRED (SEE FIGURE 37). 11-4.21.7
 CURBS. 36" X 36" MAXIMUM 1/2" CURB (NO CURB REQUIRED IN
 MINIMUM 30" X 60" STALLS).
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER
 ROOMS.
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE (CLEARLY INDICATE ON FLOOR PLAN)
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3) (CLEARLY INDICATE ON FLOOR PLAN)
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-08-30 Cont ID  
Sent By mperson Date 2007-08-30 Time 13:14 Rev Time 0.00
Received By mperson Date 2007-08-30 Time 13:14 Sent To PC
Notes
2007-08-30 13:38:50DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. THE SCOPE OF WORK FOR THIS PROPOSED "MOCK UP OF A
 HOTEL ROOM INCLUDING BATHROOM" IS UNCLEAR. IS THIS
 GOING TO BE A WOKING MOCK UP? PLEASE CLARIFY THIS ON
 THE RESUBMITTAL.
  
 2. SUBMIT PLANS PER FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS, SECTION 106.3.5.1.3
 PLUMBING 1 THROUGH 13.
  
 3. NOTE: A THOROUGH REVIEW CAN'T BE DONE AT THIS TIME
 BECAUSE OF ADDITIONAL INFORMATION REQUESTED BY OTHER
 PLAN REVIEWERS IN REGUARD TO OCCUPANCY. ADDITIONAL
 COMMENTS MAY APPEAR THAT WERE NOT PART OF THIS REVIEW
 DUE TO NEW INFORMATION ON THE THE RESUBMITTAL. THERE
 MAY BE OTHER COMMENTS FOR ACCESSIBILITY DEPENDING ON
 THE USE AND OCCUPANCY OF THE BUILDING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-13 Cont ID  
Sent By choops Date 2007-08-13 Time 17:11 Rev Time 0.00
Received By choops Date 2007-08-13 Time 17:11 Sent To  
Notes
2007-08-13 17:12:06RESEARCH AND DEVELOPMENT OF MOCK-UP HOTEL SUITE IS A
 PERMITTED USE IN INDUSTRIAL ZONING DESIGNATIONS.
  
 *VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved