Plan Review Details - Permit 07080044
Plan Review Stops For Permit 07080044
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.77
Received By jwitmer Date 2008-01-24 Time 12:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-08 Cont ID  
Sent By jjohnsto Date 2007-11-08 Time 11:06 Rev Time 2.00
Received By jjohnsto Date 2007-11-08 Time 11:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-14 Cont ID  
Sent By jwitmer Date 2007-09-14 Time 08:02 Rev Time 1.55
Received By jwitmer Date 2007-09-13 Time 15:04 Sent To  
Notes
2007-09-13 16:55:56BUILDING PLAN REVIEW
 PERMIT: 07080044
 ADD: 4300 N FLAGLER DR
 CONT: S L PLOTA CO. LLC
 TEL: (727)709-4373
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)CONTRACTOR S. L. PLOTO CO., LLC NEEDS TO NOTIFY
 DBPR OF CHANGE IN ADDRESS FROM WHAT IS CURRENTLY ON
 STATE WEB SITE.
  
 4) DIGITAL DESIGN & DRAFTING 1 SET OF PLANS HAS BEEN
 FORWARDED TO THE STATE OF FLORIDA TO INVESTIGATOR JACK
 BEAMISH FLORIDA BOARD OF PROFESSIONAL ENGINEERS FOR
 ADVERTISING AS DESIGN PROFESSIONALS WITHOUT LICENSURE.
 MR BEMISH REQUESTED THE PLANS FROM THIS PERMIT FOR
 ADDITIONAL INFORMATION ON THE CASE # 2007049814 AN
 ONGOING INVESTIGATION. FL STATUTE 471.
  
 5) SHEET # 1 INDICATES WHAT APPEARS TO BE A OVERHEAD
 DOOR TO BE FILLEDIN BY OTHERS? WHO IS PICKING UP THIS
 WORK THAT IS NOT UNDER THIS PERMIT?
  
 6)SHEET # 2 ONLY PROVIDES A PORTION OF THE REQUIRED
 WIND INFORMATION PLEASE COMPLETE: 2004 FL. BLD CODE
 1603.1.4 THE FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY 3)-
 WIND EXPOSURE
 4)- - COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 7) SHEET# 2 INDICATES THE BASE OF THE EXHAUST DUCTS
 SITTING ON A 3'-0" X3'-0" FOUNDATION WITH 3"X3'X1/4"
 STEEL ANGLES. ARE THE STEEL ANGLES
 FASTENED TO THE EXHAUST DUCT, ?
  
 8) SHEET # 2 ALSO INDICATES 2 OF 3 3/16" STEEL CABLES
 TO BE SPACED AT 120 DEGREES APART. THE 2 THAT ARE
 ILLUSTRATED WILL BE TIED BACK TO THE ROOFING SYSTEM,
 WHERE IS THE THIRD CABLE TO BE TERMINATED? 106.1.2*
 ADDITIONAL INFORMATION REQUIRED.
  
 9)SHEET # 2 INDICATES THERE WILL BE (2)24" EXHAUST
 DUCTS THAT RUN 6'-0" ABOVE THE ROOF, WILL THE INTAKE
 DUCTS ALSO TERMINATE ABOVE THE ROOF?
 IT APPEARS THEY ALSOMAY REQUIRE FOUNDATIONS? P[LANS
 ARE NOT CLEAR IN THIS MANNER?
  
 10)HOW OFTEN WILL THE 24" EXHAUST DUCT BE BRACED BACK
 TO THE BUILDING WITH THE 3"X3"X1/4" STEEL ANGLES.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-31 Cont ID  
Sent By btrobaug Date 2007-10-31 Time 13:55 Rev Time 0.00
Received By btrobaug Date 2007-10-31 Time 09:18 Sent To  
Notes
2007-10-31 13:54:51 
  
  
  
 PROVISO
  
 IF SPRAY APPLICATION OPERATIONS ARE CONFINED TO AN
 ENCLOSED SPRAY BOOTH OR ROOM, ANY ELECTRICAL WIRING OR
 UTILIZATION EQUIPMENT LOCATED WITHIN 3 FT (915 MM) OF
 ANY OPENING SHALL BE SUITABLE FOR CLASS I, DIVISION 2;
 CLASSI , ZONE2;OR CLASS II, DIVISION 2 LOCATIONS,
 WHICHEVER IS APPLICABLE

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By btrobaug Date 2007-09-17 Time 10:40 Rev Time 0.00
Received By btrobaug Date 2007-09-17 Time 08:27 Sent To  
Notes
2007-09-17 09:30:07 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ELECTRICAL CONTRACTOR SIGNED ON THE APPLICATION
 IS BANVILLE BARRETT. THE NOTE PROVIDED WITH THE PLANS
 INDICATES "DAVCO ELECTRIC" IS THE INTENDED CONTRACTOR.
 PLEASE CLARIFY, REMOVE BANVILLE FROM THE APPLICATION,
 OR REMOVE THE NOTE.
  
 2} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS,
 CONDUIT AND CONDUCTOR SIZE AND TYPE, AND THE LOCATION
 FOR EQUIPMENT BEING WIRED UNDER THIS PERMIT. FBC
 106.3.5.1.2 AS AMENDED.
  
 3} SEE MECHANICAL AND BUILDING COMMENTS REGARDING
 ENGINEERING AND CONTRACTORS INFORMATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-02-12 Cont ID  
Sent By mawillia Date 2008-02-12 Time 12:20 Rev Time 0.00
Received By mawillia Date 2008-02-12 Time 11:19 Sent To B
Notes
2008-02-12 12:12:11*****APPROVED*****
  
 PLAN SHEETS FP 1.00, 1, 2, AND E1.0 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-02 Cont ID  
Sent By mwennerg Date 2007-11-02 Time 14:37 Rev Time 0.00
Received By mwennerg Date 2007-11-02 Time 14:37 Sent To  
Notes
2007-11-02 14:55:23***DENIED***
  
 IT DOES NOT APPEAR THAT ALL OF THE PREVIOUS FIRE REVIEW
 COMMENTS HAVE BEEN ADEQUATELY ADDRESSED.
  
 1) THERE IS STILL CONFLICTING ADDRESS INFORMATION ON
 SHEETS. CORRELATE ALL SHEETS TO ILLUSTRATE CORRECT
 ADDRESS .
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SUPPRESSION SYSTEM. SHEET 2 INDICATES A SELF CONTAINED
 SUPPRESSION SYSTEM. FP 1.00 INDICATES FIRE SPRINKLER
 COVERAGE. THE FIRE SPRINKLER WORK WOULD HAVE TO BE
 EXTENDED FROM THE EXISTING BUILDING SYSTEM. PLEASE
 CLARIFY INFORMATION.
  
 3) THERE APPEARS TO BE AN EXIT DOOR THAT WOULD BE
 OBSTRUCTED. OTHER SHEETS SHOW AN EXISTING EXTERIOR WALL
 WITH NO DOOR.
  
 4) PROVIDE DISTANCE OF EQUIPMENT TO WALL AND INDICATE
 FIRE RATING FOR EXISTING DOOR.
  
 5) SEE COMMENT 3.
  
 6) INCLUDE ADOPTED EDITIONS WHEN REFERENCING NFPA
 101,2003, NFPA 33,2003 AND NFPA 17, 2002 IF
 APPLICABLE.
  
 7) GROUNDING AND BONDING NOTE HAS BEEN ADDED TO PLANS.
 PLEASE SHOW DETAIL.
  
 NEW COMMENT:
  
 1) E1.0 INDICATE THE REMOVEL OF FIRE ALARM DEVICE. WILL
 IT BE RELOCATED?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-02 Cont ID  
Sent By mawillia Date 2007-10-02 Time 09:38 Rev Time 0.00
Received By mawillia Date 2007-10-01 Time 17:25 Sent To  
Notes
2007-10-01 17:51:42*****DENIED*****
  
  
 1.THE PROJECT NAME AND ADDRESS ON SHEET 1 IS
 INCORRECT.THE ACTUAL ADDRESS OF THE PROJECT SITE
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2.SEPARATE PLANS AND PERMIT REQUIRED FOR THE PAINT
 BOOTH FIRE SUPPRESSION SYSTEM.
  
 3.THE PROPOSED EQUIPMENT APPEARS TO BE PLACED IN
 FRONT OF AN EXIT DOOR.WILL THIS DOOR CONTINUE TO BE A
 MEANS OF EGRESS?
  
 4.PROVIDE THE DISTANCE OF THE EQUIPMENT TO THE WALL
 AND INDICATE THE FIRE RATING FOR THE EXISTING DOOR.
  
 5.ON SHEET 1, A DOOR IS SHOWN LEADING TO THE PROPOSED
 SPRAY BOOTH WHEREAS ON SHEET 2, AN EXISTING EXTERIOR
 WALL IS SHOWN.PLEASE CLARIFY.
  
 6.ON SHEET 2, THE APPROPIATE EDITION OF THE CODES TO
 BE REFERENCED ARE: NFPA 101- 2003,NFPA 33 - 2003, AND
 NFPA 17 - 2002.
  
 7.PLEASE INDICATE THE SEPARATION DISTANCE BETWEEN THE
 INTAKE AND EXHAUST DUCTS.2004 FBC/M 502.7.3.6
  
 8.ILLUSTRATE REQUIRED GROUNDING AND BONDING FOR THE
 BOOTH OR ADD TO NOTES THAT THE BOOTH WILL BE PROPERLY
 GROUNDED AND BONDED.
  
 9.IF TO BE USED, PROVIDE PRODUCT APPROVAL RATING AND
 SIZE OF SAFETY STORAGE CABINET AND/OR LOCATION OF THE
 STORAGE AREA.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-01 Cont ID  
Sent By adarroug Date 2008-10-01 Time 16:46 Rev Time 0.00
Received By adarroug Date 2008-10-01 Time 16:46 Sent To FIRE
Notes
2008-10-01 16:46:57TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-15 Cont ID  
Sent By adarroug Date 2008-01-15 Time 14:45 Rev Time 0.00
Received By adarroug Date 2008-01-15 Time 14:45 Sent To  
Notes
2008-01-15 14:45:22TO "COMM" BD#47

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 11:52 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 11:52 Sent To  
Notes
2007-10-29 08:39:05TO "COMM" BD#41
2007-10-11 11:52:53WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-01 Cont ID  
Sent By mawillia Date 2007-10-01 Time 17:25 Rev Time 0.00
Received By mawillia Date 2007-08-03 Time 08:44 Sent To  
Notes
2007-08-24 08:44:48TO "COMM" BD#2
2007-08-03 13:28:25WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-16 Cont ID  
Sent By rregueir Date 2007-11-16 Time 14:07 Rev Time 0.00
Received By rregueir Date 2007-11-13 Time 17:39 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-23 Cont ID  
Sent By rregueir Date 2007-08-23 Time 18:38 Rev Time 0.00
Received By rregueir Date 2007-08-23 Time 18:09 Sent To  
Notes
2007-08-23 18:37:57REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE SITE PLAN SHOWING LOCATION OF INTAKE AND
 EXHAUST OPENINGS IN RELATION TO PROPERTY LINES,
 ADJACENT BUILDINGS AND OPENINGS INTO THIS BUILDING PER
 FBC,M 401.5 AND FBC,M 502.7.3.6.
  
 2. THIS PERMIT APPLICATION WAS ERRONEOUSLY PROCESSED AS
 A MISCELANEOUS PERMIT RATHER THAN A SPRAY BOOTH PERMIT.
 AS A RESULT, A REQUIRED FIRE PLAN REVIEW SURCHARGE OF
 10% OF THE PERMIT FEE HAS BEEN ADDED. THIS FEE MUST BE
 PAID AT TIME OF RESUBMITTAL.
  
 3. WHAT IS THE SOURCE OF MAKE UP AIR FOR THE EXHAUST
 FAN IN THE MIXING ROOM? SHOW COMPLIANCE WITH FBC,M
 502.9.5.4.
  
 4. PROVIDE WIND LOAD CALCULATIONS SHOWING OUTDOOR
 EQUIPMENT AND DUCT RISERS SECURED TO MEET MINIMUM 140
 MPH WIND LOADS IN ACCORDANCE WITH FBC,M 301.13 AND FBC
 SEC.1609. SEE FBC 106.1.2.
  
 5. PROVIDE DETAIL SHOWING MATERIALS AND FASTENERS TO BE
 USED FOR SUPPORTS FOR RISER DUCTS. ALSO SHOW MAXIMUM
 SPACING OF SUPPORTS AND METHOD OF ATTACHMENT TO
 BUILDING STRUCTURE WHICH MEETS WIND LOAD REQUIREMENTS
 AS STATED IN COMMENT #4.
  
 6. THE ROOF VIEW ON PG.2 SHOWS TWO 14X28 INTAKE DUCTS
 ATTACHED TO TWO 24 INCH DIA. EXHAUST DUCTS. PLEASE
 CLARIFY. FBC 106.1.1.
  
 7. THIS SYSTEM HAS BEEN DESIGNED BY DIGITAL DESIGN &
 DRAFTING. THIS IS NOT A LICENSED ENGINEERING BUSINESS
 UNDER THE REQUIREMENTS OF F.S. 471. JF SHANNON, P.E.
 STATES ON PLANS THAT HE HAS REVIEWED PLANS FOR CODE
 COMPLIANCE AND FOUND THEM TO BE COMPLIANT, INDICATING
 HE HAS PROVIDED PLAN REVIEW SERICES AND IS NOT THE
 DESIGNER OF RECORD. THERE IS ALSO A NOTE ON THE PLAN
 STATING "NOTIFY DIGITAL DESIGN & DRAFTING OF ANY
 DESCREPANCY BEFORE PROCEEDING WITH CONSTRUCTION." WHICH
 AGAIN INDICATES THEY ARE RESPONSIBLE FOR THE SYSTEM
 DESIGN.
  
 ONE SET OF THESE PLANS IS BEING RETAINED BY THIS OFFICE
 FOR POSSIBLE INVESTIGATION BY THE STATE OF FLORIDA FOR
 ENGINEERING SERVICES PROVIDED WITHOUT A LICENSE IN
 VIOLATION OF FS 471.003.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2008-01-18 Cont ID  
Sent By jroach Date 2008-01-18 Time 15:07 Rev Time 0.00
Received By jroach Date 2008-01-18 Time 15:05 Sent To  
Notes
2008-01-18 15:07:36***PROVISO***
  
 EXISTING LANDSCAPING SHALL NOT BE ALTERED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-11-07 Cont ID  
Sent By jroach Date 2007-11-07 Time 20:35 Rev Time 0.00
Received By jroach Date 2007-11-07 Time 20:35 Sent To  
Notes
2007-11-07 20:38:58***FAILED***
  
 1) REPEAT COMMENT - MINOR AMENDMENT TO THE RYBOVICH
 COMMERCIAL MARINE PLANNED DEVELOPMENT (CMPD) SHALL BE
 SUBMITTED TO, AND APPROVED BY, THE PLANNING DEPARTMENT
 PRIOR TO ISSUANCE OF THE BUILDING PERMIT (PREFERRED
 THAT THIS BE DONE BEFORE RESUBMITTAL OF THE PERMIT
 APPLICATION).NO MINOR AMENDMENT WAS
 SUBMITTED/APPROVED FOR THE INSTALLATION OF THE PAINT
 BOOTH.A REVISED SITE PLAN, LANDSCAPE PLAN, AND
 ELEVATIONS SHALL BE SUBMITTED AS PART OF THE MINOR
 AMENDMENT.
  
 2) REPEAT COMMENT - IT APPEARS THAT THE LOCATION OF THE
 PROPOSED EXHAUST WILL CONFLICT WITH EXISTING
 LANDSCAPING ON THE SITE. REVISED LANDSCAPE PLANS
 SHOWING THE LOCATION OF THE EXHAUST AND THE
 MODIFICATIONS TO THE LANDSCAPING SHALL BE PROVIDED.
 WHEN DIMENSIONED ON THE SITE PLAN, THE EXHAUST DUCTS
 AND MECHANICAL SYSTEMS, AS WELL AS THE FENCE SCREENING,
 WILL INTERFERE WITH AN EXISTING LANDSCAPE ISLAND.NO
 REVISED LANDSCAPE PLAN WAS PROVIDED.
  
 3) AT LEAST TWO (2) COPIES OF ANY SUBMITTED PLANS SHALL
 BE PROVIDED.ONLY ONE (1) COPY OF THE MARINA SITE PLAN
 WAS PROVIDED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-30 Cont ID  
Sent By jroach Date 2007-08-30 Time 11:23 Rev Time 0.00
Received By jroach Date 2007-08-30 Time 11:23 Sent To  
Notes
2007-08-30 12:10:07***FAILED***
  
 1) MINOR AMENDMENT TO THE RYBOVICH COMMERCIAL MARINE
 PLANNED DEVELOPMENT (CMPD) SHALL BE SUBMITTED TO, AND
 APPROVED BY, THE PLANNING DEPARTMENT PRIOR TO ISSUANCE
 OF THE BUILDING PERMIT (PREFERRED THAT THIS BE DONE
 BEFORE RESUBMITTAL OF THE PERMIT APPLICATION).
  
 2) IT APPEARS THAT THE LOCATION OF THE PROPOSED EXHAUST
 WILL CONFLICT WITH EXISTING LANDSCAPING ON THE SITE.
 REVISED LANDSCAPE PLANS SHOWING THE LOCATION OF THE
 EXHAUST AND THE MODIFICATIONS TO THE LANDSCAPING SHALL
 BE PROVIDED.
  
 3) PLANS SHALL CLEARLY INDICATE THAT ALL EXTERIOR
 COMPONENTS WILL BE PAINTED TO MATCH THE EXTERIOR OF THE
 BUILDING.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.