Plan Review Details - Permit 07080030
Plan Review Stops For Permit 07080030
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-14 Cont ID  
Sent By shill Date 2008-01-14 Time 08:48 Rev Time 0.00
Received By shill Date 2008-01-14 Time 08:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-12-27 Cont ID  
Sent By shill Date 2007-12-27 Time 17:06 Rev Time 0.00
Received By shill Date 2007-12-27 Time 17:06 Sent To  
Notes
2007-12-27 17:08:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.FS481, ALL DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS.ONE WAS A PHOTOCOPY.PLEASE PROVIDE
 TWO COLLATED IDENTICAL ORIGINAL SETS OF PERMIT
 DOCUMENTS.
  
 2.PLEASE PROVIDE TWO COLLATED SETS FOR PERMIT
 ISSUANCE.YOU MAY REMOVE THE COPY OF THE ISSUED PERMIT
 WHICH YOU PROVIDED FOR REFERENCE.THE OTHER DOCUMENTS
 SHOULD BE IN TWO IDENTICAL SETS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-11 Cont ID  
Sent By shill Date 2007-12-11 Time 09:29 Rev Time 0.00
Received By shill Date 2007-12-11 Time 09:28 Sent To  
Notes
2007-12-11 09:32:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)PROVIDE ANCHORING INFORMATION TO COMPLY WITH
 FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS,
 AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS
 FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF
 THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD
 LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE USED.
  
 2.)THE SLAB/ANCHORING DETAIL WAS SUBMITTED PREVIOUSLY
 BUT WAS A PHOTOCOPY AND PREPARED BY A DESIGN
 PROFESSIONAL (REQUIRED TO BE A SIGNED, SEALED, DATED
 ORIGINAL).THIS PERMIT IS TO SHOW CODE COMPLIANCE.IT
 APPEARS THAT THE SLAB IS EXISTING, PERMITTED UNDER
 ANOTHER PERMIT.YOU MAY SHOW "EXISTING SLAB" ON YOUR
 SITE PLAN WITH THE PERMIT NUMBER, THEREFORE A SLAB
 DETAIL WILL NOT BE REQUIRED.THAT PERMIT DID NOT
 INCLUDE THE GENERATOR ANCHORING.THIS INFORMATION MUST
 BE INCLUDED IN THIS PERMIT; PLEASE PROVIDE THE REQUIRED
 INFORMATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By shill Date 2007-09-11 Time 09:20 Rev Time 0.00
Received By shill Date 2007-09-11 Time 09:20 Sent To  
Notes
2007-09-11 09:21:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FS471.025 (SLAB AND ANCHORING DETAIL).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-29 Cont ID  
Sent By btrobaug Date 2007-11-29 Time 14:56 Rev Time 0.00
Received By btrobaug Date 2007-11-29 Time 14:31 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-08 Cont ID  
Sent By btrobaug Date 2007-08-08 Time 13:14 Rev Time 0.00
Received By btrobaug Date 2007-08-08 Time 12:58 Sent To M
Notes
2007-08-08 13:14:22 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR
 INDICATING RECOMMENDED SETBACKS FROM STRUCTURES.
  
 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE
 PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE
 SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO
 RESUBMITTING.106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-12-07 Cont ID  
Sent By mperson Date 2007-12-07 Time 09:13 Rev Time 0.00
Received By mperson Date 2007-12-07 Time 09:13 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-08-13 Cont ID  
Sent By mperson Date 2007-08-13 Time 14:42 Rev Time 0.33
Received By mperson Date 2007-08-13 Time 14:42 Sent To B
Notes
2007-08-13 14:52:14DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. SEE ZONING AND ELECTRICAL REVIEW NOTE #1 IN
 REFERENCE TO THE PROPOSED GENERATOR LOCATION ON SURVEY
 AND CORRELATE GAS ISOMETRIC IF NEEDED.
  
 2. PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS
 THAT CLEARLY INDICATE THE MODEL NUMBER BEING USED AND
 THE BTU LOAD OF THE PROPOSED GENERTOR TO VERIFY GAS
 ISOMETRIC.
  
 3. PLEASE SUBMIT MANUFACTURER SPECIFICATIONS OF THE MP
 REGULATORS WITH THE FOLLOWING INFORMATION.
 A} MAKE.
 B} MODE NUMBER.
 C} LOAD CAPACITY.
 D} LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY (NRTL).
  
 4. THE MAXIMUM DELIVERY PRESSURE OF NAT/GAS SYSTEMS TO
 RESIDENCES BY FLORIDA PUBLIC UTILITIES IS 2.0 PSI.
 PLEASE CORRECT THE DELIVERY PRESSURE ON THE GAS
 ISOMETRIC TO REFLECT THIS ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-11 Cont ID  
Sent By spalmer Date 2008-01-11 Time 17:09 Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 17:09 Sent To  
Notes
2008-01-11 17:09:35TO SAMANTHA HILLS DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-18 Cont ID  
Sent By adarroug Date 2007-12-18 Time 11:17 Rev Time 0.00
Received By adarroug Date 2007-12-18 Time 11:17 Sent To B
Notes
2007-12-18 11:17:49TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-26 Cont ID  
Sent By adarroug Date 2007-11-26 Time 13:48 Rev Time 0.00
Received By adarroug Date 2007-11-26 Time 13:48 Sent To Z
Notes
2007-11-26 13:49:16TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-11 Cont ID  
Sent By shill Date 2007-09-11 Time 09:21 Rev Time 0.00
Received By shill Date 2007-08-03 Time 08:55 Sent To  
Notes
2007-08-03 08:56:14TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-07 Cont ID  
Sent By tgordon Date 2007-12-07 Time 10:41 Rev Time 0.20
Received By tgordon Date 2007-12-07 Time 10:41 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-09 Cont ID  
Sent By tgordon Date 2007-08-09 Time 11:10 Rev Time 0.30
Received By tgordon Date 2007-08-09 Time 11:09 Sent To G
Notes
2007-08-09 11:16:41*** DENIED ***
 1) WHEN SHOWING THE LOCATION OF THE GENERATOR PLEASE
 STATE THE DISTANCES TO THE BUILDING, LOT LINE, WINDOWS,
 DOORS, AND OTHER BUILDING OPENINGS.
 ** PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT
 PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL
 COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA
 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES
 (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT
 FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES
 HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT
 REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].
  

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-28 Cont ID  
Sent By choops Date 2007-11-28 Time 13:23 Rev Time 0.00
Received By choops Date 2007-11-28 Time 13:23 Sent To E
Notes
2007-11-28 13:23:52***APPROVED - RESUB #1***
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-06 Cont ID  
Sent By choops Date 2007-08-06 Time 14:29 Rev Time 0.00
Received By choops Date 2007-08-06 Time 14:29 Sent To E
Notes
2007-08-06 14:31:21***FAILED***
  
  
 1)PLEASE INDICATE THE SETBACK DIMENSIONS FROM
 GENERATOR TO THE PROPERTY LINES ON BOTH COPIES OF THE
 SURVEY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved