| Plan Review Stops For Permit 07080030 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-01-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-14 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-14 |
Time |
08:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-12-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-27 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-27 |
Time |
17:06 |
Sent To |
|
|
| Notes |
| 2007-12-27 17:08:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.FS481, ALL DOCUMENTS PREPARED BY AN ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS.ONE WAS A PHOTOCOPY.PLEASE PROVIDE | | | TWO COLLATED IDENTICAL ORIGINAL SETS OF PERMIT | | | DOCUMENTS. | | | | | | 2.PLEASE PROVIDE TWO COLLATED SETS FOR PERMIT | | | ISSUANCE.YOU MAY REMOVE THE COPY OF THE ISSUED PERMIT | | | WHICH YOU PROVIDED FOR REFERENCE.THE OTHER DOCUMENTS | | | SHOULD BE IN TWO IDENTICAL SETS. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-12-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-11 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-11 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2007-12-11 09:32:29 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)PROVIDE ANCHORING INFORMATION TO COMPLY WITH | | | FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS, | | | AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE | | | SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING, | | | UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS | | | FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF | | | THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD | | | LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | | DURING A DESIGN WIND EVENT SHALL BE USED. | | | | | | 2.)THE SLAB/ANCHORING DETAIL WAS SUBMITTED PREVIOUSLY | | | BUT WAS A PHOTOCOPY AND PREPARED BY A DESIGN | | | PROFESSIONAL (REQUIRED TO BE A SIGNED, SEALED, DATED | | | ORIGINAL).THIS PERMIT IS TO SHOW CODE COMPLIANCE.IT | | | APPEARS THAT THE SLAB IS EXISTING, PERMITTED UNDER | | | ANOTHER PERMIT.YOU MAY SHOW "EXISTING SLAB" ON YOUR | | | SITE PLAN WITH THE PERMIT NUMBER, THEREFORE A SLAB | | | DETAIL WILL NOT BE REQUIRED.THAT PERMIT DID NOT | | | INCLUDE THE GENERATOR ANCHORING.THIS INFORMATION MUST | | | BE INCLUDED IN THIS PERMIT; PLEASE PROVIDE THE REQUIRED | | | INFORMATION. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-11 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-09-11 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2007-09-11 09:21:08 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED | | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS FS471.025 (SLAB AND ANCHORING DETAIL). | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-11-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-11-29 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-11-29 |
Time |
14:31 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-08-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-08-08 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-08-08 |
Time |
12:58 |
Sent To |
M |
|
| Notes |
| 2007-08-08 13:14:22 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE | | | GENERATOR | | | INDICATING RECOMMENDED SETBACKS FROM STRUCTURES. | | | | | | 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON | | | A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE, | | | DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH | | | ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE | | | PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE | | | SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO | | | RESUBMITTING.106.1 FBC AS AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2007-12-07 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-12-07 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-12-07 |
Time |
09:13 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-08-13 |
Time |
14:42 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-08-13 |
Time |
14:42 |
Sent To |
B |
|
| Notes |
| 2007-08-13 14:52:14 | DENIED | | | REFERENCE: | | | ** FBC-2004 FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | 1. SEE ZONING AND ELECTRICAL REVIEW NOTE #1 IN | | | REFERENCE TO THE PROPOSED GENERATOR LOCATION ON SURVEY | | | AND CORRELATE GAS ISOMETRIC IF NEEDED. | | | | | | 2. PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS | | | THAT CLEARLY INDICATE THE MODEL NUMBER BEING USED AND | | | THE BTU LOAD OF THE PROPOSED GENERTOR TO VERIFY GAS | | | ISOMETRIC. | | | | | | 3. PLEASE SUBMIT MANUFACTURER SPECIFICATIONS OF THE MP | | | REGULATORS WITH THE FOLLOWING INFORMATION. | | | A} MAKE. | | | B} MODE NUMBER. | | | C} LOAD CAPACITY. | | | D} LISTING FROM A NATIONALLY RECOGNIZED TESTING | | | LABORATORY (NRTL). | | | | | | 4. THE MAXIMUM DELIVERY PRESSURE OF NAT/GAS SYSTEMS TO | | | RESIDENCES BY FLORIDA PUBLIC UTILITIES IS 2.0 PSI. | | | PLEASE CORRECT THE DELIVERY PRESSURE ON THE GAS | | | ISOMETRIC TO REFLECT THIS ON THE RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2008-01-11 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2008-01-11 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2008-01-11 17:09:35 | TO SAMANTHA HILLS DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-18 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-18 |
Time |
11:17 |
Sent To |
B |
|
| Notes |
| 2007-12-18 11:17:49 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-11-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-26 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-26 |
Time |
13:48 |
Sent To |
Z |
|
| Notes |
| 2007-11-26 13:49:16 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-11 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-08-03 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2007-08-03 08:56:14 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-12-07 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-07 |
Time |
10:41 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-12-07 |
Time |
10:41 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-08-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-08-09 |
Time |
11:10 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-08-09 |
Time |
11:09 |
Sent To |
G |
|
| Notes |
| 2007-08-09 11:16:41 | *** DENIED *** | | | 1) WHEN SHOWING THE LOCATION OF THE GENERATOR PLEASE | | | STATE THE DISTANCES TO THE BUILDING, LOT LINE, WINDOWS, | | | DOORS, AND OTHER BUILDING OPENINGS. | | | ** PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT | | | PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL | | | COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE | | | WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA | | | 37. | | | NFPA 37 INSTALLATION & USE OF STATIONARY | | | COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES | | | (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT | | | FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES | | | HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT | | | REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE | | | RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF | | | ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, | | | AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1 | | | EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES | | | OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION | | | INTAKES. | | | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS | | | LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE | | | TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF | | | STRUCTURE. | | | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL | | | EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, | | | GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED | | | CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E. | | | FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES | | | AROUND EQUIPMENT FOR SERVICING,AND PROVIDE | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE | | | FOR THE FIELD INSPECTOR. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL: [email protected]. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-11-28 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-11-28 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-11-28 |
Time |
13:23 |
Sent To |
E |
|
| Notes |
| 2007-11-28 13:23:52 | ***APPROVED - RESUB #1*** | | | | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-08-06 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-08-06 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-08-06 |
Time |
14:29 |
Sent To |
E |
|
| Notes |
| 2007-08-06 14:31:21 | ***FAILED*** | | | | | | | | | 1)PLEASE INDICATE THE SETBACK DIMENSIONS FROM | | | GENERATOR TO THE PROPERTY LINES ON BOTH COPIES OF THE | | | SURVEY. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|