Plan Review Details - Permit 07071039
Plan Review Stops For Permit 07071039
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-05-27 Cont ID  
Sent By mjacobs Date 2008-05-27 Time 12:13 Rev Time 0.00
Received By mjacobs Date 2008-05-27 Time 10:51 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-31 Cont ID  
Sent By jwitmer Date 2008-01-31 Time 11:23 Rev Time 2.22
Received By jwitmer Date 2008-01-31 Time 11:23 Sent To PC
Notes
2008-01-31 11:24:32PERMIT: 07071039
 ADD: 234 SOUTHERN BLVD
 CONT: LEONARD ALBANESE & SONS BUILDERS, INC
 TEL: (561)239-2034
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW/ JAN. 31/08
 ACTION: REVIEWED
  
  
 BUILDING PROVISOS:
  
 BUIULDING PROVISO: LIGHT POLES,TO BE SUBMITTED AS
 SHOP DRAWINGS.
  
 BUILDING PROVISO:109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCEL SHALL AS A PERMIT CONDITION, PROVIDE
 A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATION FROM A LICENSED ENGINEER
 SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECODS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-01-24 Cont ID  
Sent By jwitmer Date 2008-01-24 Time 11:50 Rev Time 2.22
Received By jwitmer Date 2008-01-24 Time 11:50 Sent To  
Notes
2008-01-31 08:43:28PERMIT: 07071039
 ADD: 234 SOUTHERN BLVD
 CONT: LEONARD ALBANESE & SONS BUILDERS, INC
 TEL: (561)239-2034
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW/ JAN. 31/08
 ACTION: REVIEWED
  
  
 BUILDING PROVISOS:
  
 BUIULDING PROVISO: LIGHT POLES,TO BE SUBMITTED AS
 SHOP DRAWINGS.
  
 BUILDING PROVISO:109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCEL SHALL AS A PERMIT CONDITION, PROVIDE
 A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATION FROM A LICENSED ENGINEER
 SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECODS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
2008-01-24 11:55:28PERMIT: 07071039
 ADD: 234 SOUTHERN BLVD
 CONT: LEONARD ALBANESE & SONS BUILDERS, INC
 TEL: (561)239-2034
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW/ JAN. 24/08
 ACTION: DENIED
  
 PLANS APPEAR TO BE CODE COMPLIANT, STILL NEED TO PAY
 IMPACT FEES.
  
 BUILDING PROVISOS:
  
 BUIULDING PROVISO: LIGHT POLES,TO BE SUBMITTED AS
 SHOP DRAWINGS.
  
  
 BUILDING PROVISO:109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCEL SHALL AS A PERMIT CONDITION, PROVIDE
 A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATION FROM A LICENSED ENGINEER
 SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECODS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-02 Cont ID  
Sent By jwitmer Date 2007-11-02 Time 13:53 Rev Time 4.33
Received By jwitmer Date 2007-11-02 Time 13:53 Sent To  
Notes
2007-11-02 13:55:45PERMIT: 07071039
 ADD: 234 SOUTHERN BLVD
 CONT: LEONARD ALBANESE & SONS BUILDERS, INC
 TEL: (561)239-2034
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW/ NOV. 02-07
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT
 ---
 PLEASE DO NOT
 IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3-7) COMPLIED.
  
 8) 2ND REQUEST,A SINGLE SIGNED AND SEALEDGFA
 INTERNATIONAL GEOTECHNICALREPORT WAS SUBMITTED, TWO
 ORIGINAL SIGNED AND SEALED REPORTS ARE REQUIRED. NOTE
 NOT THE SUMMARY OF DRAINAGE CALCULATIONS FROM NUTTING
 ENGINEERING.
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 9)2ND REQUEST,THERE SEEMS TO BE A DISCREPANCY
 BETWEEN THE PERMIT APPLICATION WORK TO BE COMPLETED
 UNDER THIS BUILDING AND THE ENERGY EFFICIENCY CODE
 ENERGY CALCS.
 THE ENERGY CALCULATIONS ARE STATING THAT THEY ARE FOR A
 SHELL BUILDING , THE DESIGNER OF RECORD IN THE LAST
 RESPONCE INDICATED THIS TO BE A "COMPLETE BUILDOUT".
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 10-14) COMPLIED.
  
 15) 2ND REQUEST, DEALS WITH NON-ABSORBENT SURFACES
 AROUND FIXTURES. THE EPOXY PAINT ON DRYWALL HAS NOT
 BEEN ESTABLISHED AS A NON-ABSOBENT MATERIAL SINCE IT
 CAN GET NICKS IN THE SURFACE THROUGH OUT THE LIFE TIME
 OF THE INSTALATION.
 PLEASE COMPLY WITH 1210.2 FOR WALLS , WITH SMOOTH, HARD
 NONABSORBENT SURFACES TO A HEIGHT OF 4'-0" FOR FIXTURES
 THATTHE WALLS CAN BE ADVERSELY AFFECTED BY MOISTURE.
  
 16)-17) COMPLIED.
  
 18) 2ND REQUEST, SHEET S-01& S-06 NOTES NUMBER THREE
 REINFORCING STEEL. VERTICAL WALL REINFORCINGS-01
 INDICATES VERTICAL REINFORCEMENT @ NEXT TO ALL
 OPENINGS, AND CORNERS, BUT IN A STRAIGHT WALL THERE IS
 NO CENTER TO CENTER SPACING PROVIDED ON
 SHEET S-01 OR IN THE NOTES ON S-06. RECITING THE CODE
 OR A REFERENCE STANDARD DOES NOT PROVIDE THE
 INFORMATION NEEDED FOR THE INDIVIDUAL WHO IS IN THE
 FIELD.106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. ACI 530- 8.1.2
 DETAILS OF REINFORCEMENTSHALL BE SHOWN ON PLANS OR
 COVERED BY NOTES ON THE PROJECT DRAWINGS.
  
 19-22) COMPLIED.
  
 23) BUIULDING PROVISO: LIGHT POLES,TO BE SUBMITTED AS
 SHOP DRAWINGS
  
 24)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PLEASE PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS:
  
 24 E) TRUSS ANCHORS- NO REPORT SUBMITTED
  
 25-27) COMPLIED.
 28)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 29) BUILDING PROVISO:109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCEL SHALL AS A PERMIT CONDITION, PROVIDE
 A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATION FROM A LICENSED ENGINEER
 SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 30) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECODS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-08 Cont ID  
Sent By jwitmer Date 2007-09-08 Time 10:39 Rev Time 5.66
Received By jwitmer Date 2007-09-07 Time 15:03 Sent To  
Notes
2007-09-08 10:41:15BUILDING PLAN REVIEW
 PERMIT: 07071039
 ADD: 234 SOUTHERN BLVD
 CONT: LEONARD ALBANESE & SONS BUILDERS, INC
 TEL: (561)239-2034
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1SRREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT
 ---
 PLEASE DO NOT
 IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SLATTERY & ASSOCIATES ARCHITECTSPLANNERS,
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION -
 STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL
 XX- INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING
 THE PLANS, NOTE THE
 FLORIDA REGISTRATION NUMBER BY THE RAISED
 SEAL IS THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
  
 4) STRUCTURAL PLANS, THE ENGINEERING FORM SA-TECH
 ENGINEERING, INC. HASN?T INCLUDED THEIR CERTIFICATE OF
 AUTHORIZATION.471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER.
  
 5) STRUCTURAL SHEETS ARE MISSING INFORMATION IN THE
 TITLE BLOCK:
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 6) A WARRANTY DEED WAS SUBMITTED AS PROOF OF OWNERSHIP,
 IN THIS DOCUMENT IT INDICATES (2) PARCELS PARCEL A &
 PARCEL B. THE PERMIT APPLICATION INDICATES THIS
 BUILDING IS BEING BUILT ON LOT 285 BUT IN LOOKING AT
 THE PROPERTY TAX MAPS IT APPEARS THAT THE STRUCTURE
 TRANSGRESSES THE PROPERTY LINE ON TO LOT 291 ALSO, A
 UNITY OF TITLE WILL BE REQUIRED. THE PROPOSED BUILDING
 STRUCTURE TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE
 LOTS WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF
 TITLE' SHALL BE RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT
 SO THAT FBC TABLE 600 BOUNDARY LINE REQUIREMENTS MAY BE
 DEEMED NOT APPLICABLE.
  
 7) 106.1.2* ADDITIONAL INFORMATION IS REQUIRED. THE
 COVER SHEET INDICATES THE OWNERS TO BE LOCKS OF LOVE,
 INC.THE PLANS INDICATE THIS TO BE A BUSINESS
 OCCUPANCY AND THE PLANS ONLY INDICATE THE USE OF THE
 ROOMS AS OFFICES. PLEASE IDENTIFY THE ROOMS WHICH WILL
 BE USING X-RAY EQUIPMENT THIS ASSUMPTION IS MADE
 BECAUSE OF THE CODE CRITERIA FOUND ON A-001 REPORT# 34
 MEDICAL X-RAY AND GAMMA RAY. PLEASE PROVIDE ADDITIONAL
 INFORMATION. MORE COMMENTS MAY APPEAR ON THE NEXT
 REVIEW DEALING WITH THIS ISSUE.
  
 8) A SINGLE SIGNED AND SEALEDGFA INTERNATIONAL
 GEOTECHNICALREPORT WAS SUBMITTED, TWO ORIGINAL SIGNED
 AND SEALED REPORTS ARE REQUIRED.
  
 9)THERE SEEMS TO BE A DISCREPANCY BETWEEN THE PERMIT
 APPLICATION WORK TO BE COMPLETED UNDER THIS BUILDING
 AND THE ENERGY EFFICIENCY CODE ENERGY CALCS.
 THE ENERGY CALCULATIONS ARE STATING THAT THEY ARE FOR A
 SHELL BUILDING ONLY, IS THIS
 THE SCOPE OF WORK FOR THE BUILDING.IS THE PERMIT
 APPLICATION WRONG IN SCOPE OF WORK OR THE ENERGY
 CALCULATIONS?
 10) THE ENERGY CALCULATIONS INDICATE THIS IS TO BE A
 METAL ROOF WHERE AS THE PLANS CALL FOR A SPANISH **S**
 CONCRETE TILE ROOF PLEASE CORRECT.
  
 11) THE ENERGY CALCULATIONS SHOULD ALSO CORRECT THE
 WINDOW SECTION OF HE CALCS, THE PLANS ELEVATIONS ARE
 LABELED BACKWARDSNORTH IS SOUTH AND EAST IS WEST,
 PLEASE CORRECT BOTH THE PLANS AND ENERGY CALCULATIONS.
 DISCREPANCIES.
  
 12) PLEASE ALSO CORRECT THE ENERGY CALCULATIONS AS TO
 TYPE OF INSULATION ENERGY CALCULATIONS INDICATE THE USE
 OF R-19 INSULATION- BATT WHERE AS THE PLAN INDICATES
 THE USE OF ICYNENE BUT NO R FACTOR OR DEPTH IS
 PROVIDED, PLEASE CORRECT BOTH ISSUES. DISCREPANCIES.
  
  
 13) SHEET A-601 WINDOW BUCKS ARE INDICATED AS TAPERED
 BUCKS NOT HAVING SUPPORT BY BOTH FACES OF THE WINDOW
 FRAME.1714.5.4.2 MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBSTRATE.UNLESS OTHERWISE TESTED, BUCKS
 SHALL EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR
 DOOR FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS
 PROVIDED. SHIMS SHALL BE MADE FROM MATERIALS CAPABLE OF
 SUSTAINING APPLICABLE LOADS, LOCATED AND APPLIED IN A
 THICKNESS CAPABLE OF SUSTAINING APPLICABLE LOADS.
 ANCHORS SHALL BE PROVIDED TO TRANSFER LOAD FROM THE
 WINDOW OR DOOR FRAME TO THE ROUGH OPENING SUBSTRATE.
  
 14) SHEET A-901 DOOR SCHEDULE THIS IS PROBABLY A TYPE-0
 SEE DOOR HEIGHT OF DOOR # 113, 5?-6?.
  
 15) SHEET A-901 ROOM SCHEDULE WALL AROUND THE WATER
 CLOSETS INDICATES THE USE OF GYPSUM WALL BOARD, PLEASE
 SEE: 1210.2 WALLS. SMOOTH, HARD, NONABSORBENT SURFACE,
 TO A HEIGHT OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE.
  
 16) SHEET A-201 ROOM 113 INDICATES A BREAK ROOM WITH
 SINK, THE PLANS DO NOT HAVE ANY ELEVATIONS OF THE
 CABINETRY PLEASE PROVIDE ELEVATIONS COMPLYING WITH:
 SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED
 WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH
 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH
 SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 17) SHEET A-201 IS MISSING ATTIC ACCESS:1209.2 ATTIC
 SPACES.
 AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM
 BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A
 CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762
 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT OR ABOVE THE ACCESS OPENING.
  
 18) SHEET A-01 VERTICAL WALL REINFORCING NOTE # 5
 INDICATES ADDITIONAL # 5?S AS VERTICAL REINFORCING,
 WHERE IS NOTE FOR THE CENTER TO CENTER VERTICAL
 REINFORCING. ACI 530.
  
 19) SHEET S-06 NOTE# 5 MASONRYSUB-NOTE JSECTION
 2122.4THIS IS HIGH VELOCITY HURRICANE, ZONE BROWARD
 AND DADE COUNTIES PLEASE CORRECT.
  
 20) SHEET S-06 STRUCTURAL NOTES 6-E INDICATE ROOF
 SHEATHING TO COMPLY WITH 2322.2 THIS IS HIGH VELOCITY
 HURRICANE, ZONE BROWARD AND DADE COUNTIES PLEASE
 CORRECT.
  
 21) SHEET S-06 NOTE # 9 DELEGATED ENGINEERING
 RESPONSIBILITIES
 NOTE # 9, 2319.17.2.1. AGAIN HIGH WIND HURRICANE ZONE,
 BROWARD AND
 DADE COUNTIES, PLEASE CORRECT.
  
 22) SHEET S-06 NOTE# 12 CONDUITS AND PIPES EMBEDDED IN
 CONCRETE
 NOTE# 5 1925.3,2 THIS IS HIGH VELOCITY HURRICANE,
 ZONE BROWARD AND DADE COUNTIES PLEASE CORRECT.
  
 23) SHEET E1.1 ELECTRIC LIGHT POLE DETAIL PLEASE
 REMEMBER THAT WHEN THE POLE SUPPLIER IS PROVIDING THE
 LIGHT POLETHE DESIGN IS 140 MPH WITH A
 EXPOSURE **C** CATEGORY.
  
 24)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PLEASE PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, (3)
 IF PROJECT REQUIRES A THRESHOLD OR SPECIAL INSPECTOR ,
 MISSING REPORTS ARE AS FOLLOWS:
 A) PICTURE WINDOW- REQUIRES FLORIDA COVER SHEET,
 UPDATE TO CURRENT NOA OR
 DIVIDE THE PRESSURES BY 1.33 OLDER NOA BEFORE
 2004 TOOK 1.33 STEEL
 INCREASES IN FASTENERSOR HAVE ENGINEER CERTIFY
 FASTENERS.
 B) STORE FRONT-- REQUIRES FLORIDA COVER SHEET,C)
 GLAZED EXTERIOR DOORS- REQUIRES FLORIDA COVER SHEET,
 UPDATE TO CURRENT NOA OR DIVIDE THE PRESSURES BY 1.33
 OLDER NOA BEFORE 2004 TOOK 1.33
 STEEL INCREASES IN FASTENERSOR HAVE ENGINEER
 CERTIFY FASTENERS
 D) EXTERIOR METAL DOORS- NO REPORT SUBMITTED
 E) TRUSS ANCHORS- NO REPORT SUBMITTED
 F) ROOF ASSEMBLIES:
 TILE : REQUIRES REPORT HIGHLIGHT TYPE OF ATTACHMENT
 TO ROOF
 UNDERLAYMENTS- REQUIRES BACKUP REPORT
  
 25) THIS SUBMITTAL DOESN'T INCORPORATE ANY ROOFING
 PRODUCT APPROVALS, HERE IS A LIST OF COMMON ISSUES THAT
 WILL FAIL A ROOFING REPORT SUBMITTAL:THIS ROOF IS
 MISSING OR NOT INCOMPLIANCE WITH THE FOLLOW
 ITEMS:
 _XX__ CONTRACTOR FAILED TO PROVIDE BACK UP ROOFING
 REPORT DOCUMENTATION
 ___ CONTRACTOR DID NOT PROVIDE THE MEANROOF HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _XX__
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM OR SUBSYSTEM
 WILL BE USED.
 _XX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2__ .
 _XX__ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THATREQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPAREDSIGNEDAND SEALED BY A FLORIDA
 REGISTEREDPROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 ___THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 26) PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER
 RULE 9B-72.
  
 27) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 28)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 29) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE FLOWS
 SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE SPECIAL DRAINAGE
 DESIGN COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE
 THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCEL SHALL AS A PERMIT CONDITION, PROVIDE
 A
 PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATION FROM A LICENSED ENGINEER
 SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 30) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-05-04 Cont ID  
Sent By dpalmer Date 2008-05-04 Time 11:48 Rev Time 0.00
Received By dpalmer Date 2008-05-04 Time 11:48 Sent To  
Notes
2008-05-04 11:49:24** PROVISO**
  
 1) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1,
 .1.2, .1.3 AS ALL REVISED LIGHTING ON ANY PROJECT SHALL
 HAVE REVISED ENERGY CALCULATIONS. PLEASE SUBMIT REVISED
 ENERGY CALCULATIONS WITH ANY CHANGES FOR REVIEW BEFORE
 FINAL ELECTRICAL INSPECTIONS. THESE MAY ALSO BE
 SUBMITTED AT ANY TIME AS TO MAKE SURE THESE ARE ON FILE
 AND ON JOBSITE FOR INSPECTION.
 13-400.3.A
  
  
 ** ELECTRICAL SHEETS STILL NEED FIRE REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-01-30 Cont ID  
Sent By dpalmer Date 2008-01-30 Time 19:49 Rev Time 0.00
Received By dpalmer Date 2008-01-30 Time 19:49 Sent To  
Notes
2008-01-30 19:51:51** REDLINED SHEET E2.1 WHICH INDICATES TABLE *C*.
 METHID *A* IS ATTACHED PER 13-415.1.A,13-101.1.2.
 NO CORRECTIONS ARE NEEDED. ELECTRICAL PLANS STAMPED.
 STILL NEEDS FIRE REVIEW TO STAMP FA SHEETS,

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-01-03 Cont ID  
Sent By dpalmer Date 2008-01-03 Time 13:52 Rev Time 0.00
Received By dpalmer Date 2008-01-01 Time 16:45 Sent To  
Notes
2008-01-03 13:54:452008-01-03
  
 ** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW WITH
 RESPECT TO THE SUBMITTED ENERGY CALCULATIONS AND
 COORDINATION WITH PLANS.
 PLEASE BE SURE THE FIXTURE LEGEND IS COMPLETE WITH THE
 EXTERIOR FIXTURES SUCH AS SITE/PARKING FIXTURES. (THIS
 WATTAGE WAS SHOWN ON SITE PLAN.)
 PLEASE BE SURE ALL FIXTURE WATTAGES AND NUMBER OF
 FIXTURES MATCH.
 PLEASE SEE FOR EXAMPLE: PLANS INDICATE A TOTAL OF
 73-64W FIXTURES, YET ONLY 58 -64 W FIXTURES ARE SHOWN
 ON THE INPUT DATA REPORT.
 PLEASE SEE THE 34 WATT FIXTURES ON THE INPUT DATA
 REPORT ARE NOT LOCATED ON PLANS OR FIXTURE LEGEND. (ARE
 THESE NOT 64W FIXTURES?)
 PLEASE SEE FOR EXAMPLE: THE TOTAL NUMBER OF 32W
 RECESSED LIGHTS ON PLANS IS AT 11 AND IDR SHOWS 9.
 PLEASE SEE THE LIGHTING TOTAL SHOWN ON E2.1 IS HIGHER
 THAN THE TOTAL ON THE IDR. EXAMPLE: PLANS 5408, IDR-
 4510. BOTH ARE LOW.
 13-415.1.A, 13-415.2, 13-415.2.ABC.1.1. .1.2.
  
 2) NOTE: PLEASE SEE THE LIGHTING CONTROLS ARE STILL IN
 QUESTION AS SHOWN. PLEASE SEE THE LIGHTING PLANS FOR
 EXAMPLE SHOWS CORRIDOR LA-16 WHICH SHOWS A NOTE #2
 WHICH MENTIONS TO GO THROUGH LIGHTING CONTACTOR, YET
 THE LIGHTING CONTACTOR DOES NOT SHOW LA-16
 PLEASE CLARIFY THE USE OF MANY OF THE LIGHTING CIRCUITS
 IN SEPARATE SPACES WHICH GOES THROUGH THE LIGHTING
 CONTACTOR SUCH LA-8, LA-36. HOW ARE THESE CONTROLLED BY
 THE LIGHTING CONTACTOR YET THE DEVICES IN THE SPACE
 DOES NOT SEEM TO BE OVER RIDE(S). PLEASE SEE
 13-415.1.ABC.1.2 WHICH REQUIRES SEPARATE SPACES TO
 CONTAIN OVER RIDES. THE SO DEVICES IN OTHER LOCATIONS
 ARE SHOWN AS OVER RIDES, HOWEVER THE SWS DOES NOT SEEM
 TO SHOW THIS AS A OVER RIDE.
 PLEASE CLARIFY.
 13-415.1.ABC.1.1 AND .1.2.
 PLEASE SEE THE OWNER AGENT STILL NEEDS TO SIGN NEW
 CALCULATIONS ONCE RESUBMITTED.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH
 RESPECT TO FS 553.80(2)(B) AND REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 PLEASE SEE THE SAME CODE SECTIONS ABOVE FOR CHAPTER 13
 APPLY FOR THE THIRD TIME.
 PLEASE BE SURE TO GO OVER PLANS AND COORDINATE ALL.
 PLEASE SEE THE FEE AS REQUIRED UNDER THE FLORIDA
 STATUTES WAS ASSESSED AND IS DUE BEFORE PLANS MAY BE
 RE-SUBMITTED. PLEASE KNOW THAT THE RE-SUB WILL NOT BE
 DUE WHEN RE-SUBMITTING.
 SHEETS E0.1, 2.1 AND 5.1 HAVE BEEN RETAINED ALONG WITH
 ONE COPY OF THE ENERGY CALCULATIONS SUBMITTED.
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2008-01-03 13:53:182008-01-02
  
 NEW ELECTRICAL AND LANDSCAPE SHEETS SUBMITTED.
2008-01-01 16:50:442008-01-01 16:50:44
  
 PLANS IN ELECTRICAL FOR REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-30 Cont ID  
Sent By dpalmer Date 2007-10-30 Time 09:55 Rev Time 0.00
Received By dpalmer Date 2007-10-29 Time 16:31 Sent To  
Notes
2007-10-30 09:55:49 
 ** DENIED 2ND REVIEW **
  
 *** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
 PLEASE SEE THAT SOME OF THE EXACT SAME COMMENTS FROM
 PREVIOUS REVIEW ARE BELOW.
 PLEASE SEE NEW COMMENT BELOW.
  
  
 1) NOTE: PLEASE SEE LANDSCAPE PLANS AND FS 481.319 FOR
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 ** THIS IS BEING NOTED **
  
  
 2) NOTE: PLEASE SEE COMMENT NUMBER 6 FROM PREVIOUS
 REVIEW WHICH IS BEING ATTACHED BELOW AND LABELED AS
 **PREVIOUS REVIEW NOTE **.
 MANY OF THE SAME ITEMS FROM PREVIOUS REVIEW ARE THE
 SAME.
 PLEASE SEE THE LIGHTING CONTROLS ARE NOT COMPLETE AND
 IN FACT THERE ARE SEVERAL LOCATIONS WHICH STILL
 INDICATE A STANDARD SWITCH FOR CONTROL.
 PLEASE SEE THE LIGHTING BEING CONTROLLED MUST BE SEEN
 BY THE OCCUPANT WHICH IS CONTROLLING THE LIGHTING.
 PLEASE SEE SHEET E2.1 WHICH CONTAINS A KEY NOTE #2
 WHICH MENTIONS TO SEE E0.1 FOR DETAIL, YET E0.1 DOES
 NOT CONTAIN ANY DETAIL FOR ANY LIGHTING CONTROLS.
 PLEASE SEE THE LIGHTING ON PLANS DOES NOT CORRELATE
 WITH THE FIXTURE LEGEND FOR ALL FIXTURES AND DOES NOT
 CORRELATE WITH THE INPUT DATA REPORT ON THE SUBMITTED
 ENERGY CALCULATIONS. FOR EXAMPLE: SEE EXTERIOR LIGHTING
 AS NONE ARE SHOWN ON FIXTURE LEGEND. FOR EXAMPLE: SEE
 INTERIOR LIGHTING AS THE WATTAGES IS NOT THE SAME. FOR
 EXAMPLE: COVER SHEET ON ENERGY CALCULATIONS STILL CALL
 FOR THIS AS A *SHELL BUILDING*. HOW IS THIS POSSIBLE
 WHEN PLANS DO NOT INDICATE A SHELL BUILDING???
 PLEASE BE SURE THE OWNER AGENT IS SIGNED ON
 CERTIFICATION SHEETS.
 PLEASE SEE THERE ARE SEVERAL ITEMS AS NOTED ABOVE FOR
 EXAMPLE ALONG WITH MOST OF THE SAME COMMENTS BELOW FROM
 PREVIOUS REVIEW WHICH NEED TO BE ADDRESSED.
  
 ** PREVIOUS REVIEW NOTE #6 ***
 PLEASE SEE THE FOLLOWING NOTES FOR FBC CHAPTER 13.
 PLEASE INDICATE LIGHTING CONTROLS PER
 13-415.1.ABC.1.1, .1.2.
 PLANS INDICATE A TIME CLOCK HOWEVER LOCATIONS FOR ALL
 OVER RIDES AS REQUIRED COULD NOT BE FOUND ON PLANS.
 PLEASE SEE THERE IS SEPARATE SPACE CONTROL MISSING FOR
 MANY AREAS.
 PLEASE SEE NO TIME SCHEDULING WAS SUBMITTED. PLEASE SEE
 NO MAXIMUM OVER RIDE TIMES WERE INDICATED (DEVICES NOT
 SHOWN)
 PLEASE BE SURE ALL DEVICES WHICH WILL BE IN DESIGN AND
 ON PLANS ARE STATED ON LEGEND FOR DEVICES.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH THE PLANS AND DESIGN. THESE INDICATE
 BUILDING BEING A *SHELL* WHEN IN FACT THE BUILDING IS
 BEING BUILT OUT AT THIS TIME. PLEASE ALSO SEE THE INPUT
 DATA REPORT DOES NOT CORRELATE WITH PLANS.
 PLEASE SEE THE TYPE OF FIXTURES.
 PLEASE SEE THE NUMBER OF FIXTURES
 PLEASE SEE THE WATTAGE OF FIXTURES.
 PLEASE SEE NO EXTERIOR LIGHTING WAS INPUTTED IN THE IDR
 WHEN THE PLANS CONTAIN EXTERIOR LIGHTS.
 PLEASE BE SURE THE METHOD OF CONTROLS IS COORDINATED
 WITH PLANS AND DESIGN FOR THE METHOD OF CONTROL. SHOWN
 AS *MANUAL ON/OFF* WHICH IS NOT POSSIBLE AS THE PLANS
 ARE REQUIRED AND CONTAIN AUTOMATED CONTROLS.
 THERE ARE SEVERAL ITEMS ON THE CALCULATIONS WHICH NEED
 TO BE ADDRESSED.
  
 PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO
 ENERGY CALCULATIONS. PLEASE BE SURE THE INPUT DATA
 COORDINATES WITH THE PLANS.
 PLEASE PROVIDE LIGHTING POWER PERFORMANCE CALCULATIONS
 PER 13-415.2.
 PLEASE KNOW AT THIS TIME NO REVIEW FOR LIGHTING
 COMPLIANCE CAN BE DONE FOR INTERIOR AND EXTERIOR
 LIGHTING POWER ALLOWANCES. PLEASE SEE 13-415.2,
 13-415.2.ABC.1.2, 13-415.2.ABC.1.3, 13-415.2.ABC.1.1
  
 3) NOTE: PLEASE SEE THIS COMMENT FROM PREVIOUS REVIEW
 WILL REMAIN AS NOT ALL FIXTURES ON CALCULATIONS,
 FIXTURE LEGEND AND PLANS ARE THE SAME.
 FBC 106.1.2 FOR COORDINATION/ADDITIONAL INFORMATION.
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE ALL FIXTURE DESIGNATIONS ON PLANS AND
 CORRELATE WITH THE LEGEND.
 PLEASE SEE SOME FIXTURES COULD NOT BE IDENTIFIED FOR
 EMERGENCY USE ALTHOUGH THIS IS ONLY ASSUMED AT THIS
 TIME DUE TO THE SHADING ON PLANS.
  
 4) NOTE: PLEASE SEE DISCONNECTS LOCATED OUTSIDE FOR THE
 CONDENSING UNITS DO NOT MEET 110.26 FOR MINIMUM WIDTHS
 OR DEPTHS. THIS IS THE SAME COMMENT. BASED ON THE PLANS
 AND SCALE ON SHEETS, THESE DO NOT MEET THE MINIMUM
 30X36 INCHES REQUIRED.
 PLEASE ADJUST AND PLEASE BE SURE TO ADJUST OTHER SHEETS
 FOR RELEVANT SET-BACKS AND DIMENSIONS.
  
 5) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOE CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
 ONE COPY OF ELECTRICAL PLANS AND ENERGY CALCULATIONS
 HAVE BEEN RETAINED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-29 16:38:33 
  
 IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-25 Cont ID  
Sent By dpalmer Date 2007-08-25 Time 19:53 Rev Time 0.00
Received By dpalmer Date 2007-08-25 Time 19:01 Sent To  
Notes
2007-08-25 19:54:092007-08-25 19:54:09
  
 *** DENIED ***
  
 ** PLEASE KNOW AS SOME INFORMATION WAS NOT YET
 SUBMITTED A COMPLETE AND FULL REVIEW FOR SOME ITEMS
 COULD NOT BE DONE.
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS BELOW (2,3,4
 AND 5) WHICH DO NOT PERTAIN TO KAMM CONSULTING
 ENGINEERING.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON THE TITLE
 BLOCKS FOR THE LANDSCAPE PLANS.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER
 AND INFORMATION AS REQUIRED PER 61G1-16.004. PLEASE SEE
 FS 481.219 FOR REQUIRED MISSING CA #.
  
 3) NOTE: PLEASE SEE ALL SHEETS OF THE SUBMITTED
 LANDSCAPE PLANS ARE IN FACT *PHOTO-COPIES* OF SIGNED
 AND SEALED PLANS.
 PLEASE BE SURE TO SIGN, DATED AND SEALED PLANS WITH THE
 REQUIRED RAISED SEAL AND ORIGINAL SIGNATURE. PLEASE SEE
 FS 481.221, AND PLEASE SEE FAC 61G1-16.002 FOR CORRECT
 SEAL AS REQUIRED.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE(S).
  
 4) NOTE: PLEASE SEE THE CIVIL PLANS SUBMITTED ARE NOT
 SIGNED, DATED AND SEALED AS REQUIRED PER FAC
 61G15-23.002, FS 471.025
 PLEASE ALSO SEE MISSING INFORMATION AS REQUIRED ON
 TITLE BLOCKS ARE REQUIRED PER FAC 61G15-23.002.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE(S).
  
 5) NOTE: PLEASE SEE MISSING INFORMATION ON THE TITLE
 BLOCKS ON THE *S* SHEETS.
 PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER
 AND MISSING CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED PER FAC 61G15-23.002, FS 471.023
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 6) NOTE: PLEASE SEE THE FOLLOWING NOTES FOR FBC CHAPTER
 13.
 PLEASE INDICATE LIGHTING CONTROLS PER
 13-415.1.ABC.1.1, .1.2.
 PLANS INDICATE A TIME CLOCK HOWEVER LOCATIONS FOR ALL
 OVER RIDES AS REQUIRED COULD NOT BE FOUND ON PLANS.
 PLEASE SEE THERE IS SEPARATE SPACE CONTROL MISSING FOR
 MANY AREAS.
 PLEASE SEE NO TIME SCHEDULING WAS SUBMITTED. PLEASE SEE
 NO MAXIMUM OVER RIDE TIMES WERE INDICATED (DEVICES NOT
 SHOWN)
 PLEASE BE SURE ALL DEVICES WHICH WILL BE IN DESIGN AND
 ON PLANS ARE STATED ON LEGEND FOR DEVICES.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH THE PLANS AND DESIGN. THESE INDICATE
 BUILDING BEING A *SHELL* WHEN IN FACT THE BUILDING IS
 BEING BUILT OUT AT THIS TIME. PLEASE ALSO SEE THE INPUT
 DATA REPORT DOES NOT CORRELATE WITH PLANS.
 PLEASE SEE THE TYPE OF FIXTURES.
 PLEASE SEE THE NUMBER OF FIXTURES
 PLEASE SEE THE WATTAGE OF FIXTURES.
 PLEASE SEE NO EXTERIOR LIGHTING WAS INPUTTED IN THE IDR
 WHEN THE PLANS CONTAIN EXTERIOR LIGHTS.
 PLEASE BE SURE THE METHOD OF CONTROLS IS COORDINATED
 WITH PLANS AND DESIGN FOR THE METHOD OF CONTROL. SHOWN
 AS *MANUAL ON/OFF* WHICH IS NOT POSSIBLE AS THE PLANS
 ARE REQUIRED AND CONTAIN AUTOMATED CONTROLS.
 THERE ARE SEVERAL ITEMS ON THE CALCULATIONS WHICH NEED
 TO BE ADDRESSED.
  
 PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO
 ENERGY CALCULATIONS. PLEASE BE SURE THE INPUT DATA
 COORDINATES WITH THE PLANS.
 PLEASE PROVIDE LIGHTING POWER PERFORMANCE CALCULATIONS
 PER 13-415.2.
 PLEASE KNOW AT THIS TIME NO REVIEW FOR LIGHTING
 COMPLIANCE CAN BE DONE FOR INTERIOR AND EXTERIOR
 LIGHTING POWER ALLOWANCES. PLEASE SEE 13-415.2,
 13-415.2.ABC.1.2, 13-415.2.ABC.1.3, 13-415.2.ABC.1.1
  
 7) NOTE: PLEASE COMPLETE ALL FIXTURE DESIGNATIONS ON
 PLANS AND CORRELATE WITH THE LEGEND.
 PLEASE SEE SOME FIXTURES COULD NOT BE IDENTIFIED FOR
 EMERGENCY USE ALTHOUGH THIS IS ONLY ASSUMED AT THIS
 TIME DUE TO THE SHADING ON PLANS.
  
 8) NOTE: PLEASE KNOW THAT THE PLANS NEED TO LABEL AND
 PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS
 AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR
 EACH PANEL. PLEASE SEE THE USE OF *RECEPTACLES AND
 LIGHTING * ON PANEL SCHEDULE DOES NOT PROVIDE THE
 DETAILED INFORMATION NEEDED.
 PLEASE KNOW THESE CAN BE ALPHA OR NUMERIC DESIGNATIONS
 IF THIS HELPS TO ALLEVIATE CONGESTION ON PLANS.PLEASE
 SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE CODE
 WHICH STATES THE USE OF *GEN LT* ETC IS NOT
 ACCEPTABLE.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 9) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS INDICATES
 THE FPL TRANSFORMER IN ONE LOCATION AT THE REAR OF THE
 PROPERTY AND THE ELECTRICAL PLANS INDICATES THIS SAME
 TRANSFORMER AT THE FRONT ENTRANCE.
 THIS LOCATION CONTAINS THE FPL POLES AT THE REAR OF
 PROPERTY. PLEASE COORDINATE AND ADJUST PLANS.
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE MISSING SIGN CIRCUIT REQUIRED AT
 THE FRONT ENTRANCE PER 600.5.
 PLEASE BE SURE TO ADJUST THE CALCULATIONS TO THE
 MINIMUM LOAD OF 1200 VA.
  
 11) NOTE: PLEASE CLARIFY THE REQUIRED DISCONNECTING
 MEANS FOR AIR HANDLER UNITS INSIDE BUILDING PER
 440.11.
  
 12) NOTE: PLEASE SEE DISCONNECTS LOCATED OUTSIDE FOR
 THE CONDENSING UNITS DO NOT MEET 110.26 FOR MINIMUM
 WIDTHS OR DEPTHS.
 PLEASE ADJUST.
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2007-11-15 Cont ID  
Sent By rchokshi Date 2007-11-15 Time 11:26 Rev Time 0.00
Received By rchokshi Date 2007-11-15 Time 11:26 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-08-30 Cont ID  
Sent By rchokshi Date 2007-08-30 Time 14:34 Rev Time 0.00
Received By rchokshi Date 2007-08-30 Time 14:22 Sent To  
Notes
2007-08-30 14:34:31***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. FLOOR ELEVATION, CENTER LINE OF ROAD , SIDEWALK
 ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10, 25, 100
 YEAR FLOOD CRITERIATO DETERMINE THE FLOOR ELEVATION,
 PLEASE SHOW IN YOUR STORM WATER CALS.
 5. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT,
 LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE
 THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED
 IN PRE & POST STORM WATER QUALITY CALCULATIONS.
 6. HOW DO YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR
 SITE SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES
 FROM ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF
 THE CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES,
 BLEEDING ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS.
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS,
 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-05-20 Cont ID  
Sent By mawillia Date 2008-05-20 Time 14:19 Rev Time 0.00
Received By mawillia Date 2008-05-20 Time 13:14 Sent To  
Notes
2008-05-20 13:45:17*****REVISION , DATED 4/18,22/08, APPROVED******
  
  
 REVISED PLAN SHEETS A201, A-350, E2.1, AND FA2.1 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-11-14 Cont ID  
Sent By mcarsill Date 2007-11-14 Time 16:35 Rev Time 0.00
Received By mcarsill Date 2007-11-14 Time 16:08 Sent To  
Notes
2007-11-14 16:35:211. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM DISPLAYED ON THE
 PLANS.
  
 2. A MANUAL PULL STATION APPEARS TO BE NEEDED ON THE
 REAR EXIT DOOR LOCATED IN THE WORK AREA 120 AS THERE
 APPEARS TO BE ONLY ONE INITIATING APPLIANCE TO ACTIVATE
 THE SYSTEM, MANUAL PULL STATION LOCATED IN THE LOBBY.
 ANOTHER PULL STATION WAS OBSERVED ON PAGE FA2.1. PLEASE
 CORRECT DRAWINGS SO THEY MATCH. LS PLAN AND FA2.1.
  
 3. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND
 CEILINGS IN THE MEANS OF EGRESS SHALL BE CLASS A SINCE
 THE BUILDING IS NOT FIRE SPRINKLER PROTECTED.
  
 4. ALL WORK SUBJECT TO FIELD INSPECTION AND APPROVAL BY
 CITY INSPECTORS.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-25 Cont ID  
Sent By mawillia Date 2007-09-25 Time 15:43 Rev Time 0.00
Received By mawillia Date 2007-09-25 Time 14:12 Sent To  
Notes
2007-09-25 15:41:58*****DENIED*****
  
  
 01.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.THE SCOPE OF WORK SHALL IN NO WAY INTERFERE OR
 HINDER EMERGENCY ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES).
  
 04.PLEASE INCLUDE EXIT LIGHTS AND FIRE EXTINGUISHERS
 ON THE FLOOR PLAN (A-201).
  
 05.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM.
  
 06.IT IS INDICATED THAT THE BUILDING WILL BE EQUIPPED
 WITH A KNOX BOX;FOR APPLICATIONS CONTACT WEST PALM
 BEACH FIRE PREVENTION BUREAU AT 561-804-4724.
  
 07.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 SOUTHERN BOULEVARD, SHOW THE ADDRESS NUMBERS ON THE
 BUILDING.AS PER WEST PALM BEACH CODE, THE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.
  
 08.ON SHEET FA0.1 AMEND FIRE ALARM NOTE #17 AS SUCH:
 DELETE "SUPERVISORY SIGNAL ONLY"-INSERT "GENERAL
 FIRE ALARM".AS PER LOCAL REQUIREMENTS, DUCT SMOKE
 DETECTORS SHALL INITIATE A GENARAL FIRE ALARM.
  
 09.ON SHEET A-901, ADD TO DOOR REMARKS AS NOTE 6:A
 DOOR NORMALLY REQUIRED TO BE KEPT CLOSED SHALL NOT BE
 SECURED IN THE OPEN POSITION AT ANY TIME AND SHALL BE
 SELF CLOSING OR AUTOMATIC CLOSING IN ACCORDANCE WITH
 7.2.1.8.2 OF NFPA 101 - 2003 EDITION.
  
 10. ON SHEET A-901,PLEASE EXPLAIN DOOR REMARK #2 IN
 REFERENCE TO DOORS 124 AND 125 AS LOCATED ON A-201.
 WILL A PERSON OR PERSONS BE ABLE TO EGRESS FROM THESE
 AREA ONCE INSIDE WITHOUT A KEY, A TOOL, OR SPECIAL
 KNOWLEDGE?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-07-15 Cont ID  
Sent By adarroug Date 2008-07-15 Time 09:31 Rev Time 0.00
Received By adarroug Date 2008-07-15 Time 09:31 Sent To M
Notes
2008-07-15 09:31:59TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-01 Cont ID  
Sent By adarroug Date 2008-05-01 Time 10:40 Rev Time 0.00
Received By adarroug Date 2008-05-01 Time 10:40 Sent To  
Notes
2008-05-01 10:43:23TO "COMM" BD#24

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-30 Cont ID  
Sent By adarroug Date 2008-01-30 Time 10:08 Rev Time 0.00
Received By adarroug Date 2008-01-30 Time 10:06 Sent To  
Notes
2008-01-30 10:12:14TO "COMM" BD#1/PLANS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-27 Cont ID  
Sent By spalmer Date 2007-12-27 Time 10:24 Rev Time 0.00
Received By spalmer Date 2007-12-27 Time 10:24 Sent To  
Notes
2007-12-27 10:24:56TO COMM BOARD # 48

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 09:03 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 09:03 Sent To  
Notes
2007-10-29 08:23:42TO "COMM" BD#48
2007-10-10 09:03:51WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-25 Cont ID  
Sent By mawillia Date 2007-09-25 Time 15:42 Rev Time 0.00
Received By mawillia Date 2007-08-02 Time 15:25 Sent To  
Notes
2007-08-23 13:06:37TO "COMM" BD#37
2007-08-02 15:25:47WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-09-24 Cont ID  
Sent By rkussner Date 2008-09-24 Time 12:17 Rev Time 0.00
Received By rkussner Date 2008-09-24 Time 12:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-08-04 Cont ID  
Sent By rregueir Date 2008-08-04 Time 16:50 Rev Time 0.00
Received By rregueir Date 2008-08-04 Time 16:33 Sent To PC
Notes
2008-08-04 16:50:29REVISION 7 PAGES M0.1 AND M2.1

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-05-19 Cont ID  
Sent By rregueir Date 2008-05-19 Time 08:43 Rev Time 0.00
Received By rregueir Date 2008-05-16 Time 16:52 Sent To  
Notes
2008-05-19 08:44:00REV.6 PG M2.1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-15 Cont ID  
Sent By rregueir Date 2007-11-15 Time 17:36 Rev Time 0.00
Received By rregueir Date 2007-11-15 Time 15:50 Sent To  
Notes
2007-11-15 17:36:07PASSED PENDING ACCEPTANCE OF ENERGY CALCULATIONS BY
 OTHER INTERESTED TRADES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-24 Cont ID  
Sent By rregueir Date 2007-08-24 Time 17:22 Rev Time 0.00
Received By rregueir Date 2007-08-24 Time 15:17 Sent To  
Notes
2007-08-24 17:22:38REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M0.1 MECH NOTES #12: THERMOSTATIC CONTROLS SHALL
 COMPLY WITH FBC 13-407.1.ABC.2.4.1.
  
 2. M0.1 AIR BALANCE SCHEDULE: AHU #5 IS MISSING FROM
 THE SCHEDULE. PLEASE CORRECT AND RESUBMIT.
  
 3. M0.1 FAN SCHEDULE: CONTROLS INDICATE "LIGHT
 INTERLOCK." PROVISIONS SHALL ALSO BE MADE TO INTERLOCK
 FANS WITH AHU #4 TO ASSURE THAT ALL AIR SUPPLIED TO THE
 TOILET ROOMS IS EXHAUSTED AND NOT RECIRCULATED IN
 ACCORDANCE WITH FBC,M 403.2.1(3).
  
 4. M2.1: AHU #4 ON FLOOR PLAN SHOWS 1330 CFM WHILE AHU
 #5 SHOWS 1050 CFM. EQUIPMENT SCHEDULE CALLS FOR 1200
 CFM EACH. PERHAPS ONE OR MORE DROPS IS ATTACHED TO THE
 WRONG SYSTEM. SHOW AN AIR BALANCE WHICH IS IN
 CONJUNCTION WITH EQUIPMENT SCHEDULE.
  
 5. M5.1: DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE
 BUILDING FIRE ALARM SYSTEM PER FBC,M 606.4.1.
  
 6. M5.1: LOUVER DETAIL INDICATES A MIAMI-DADE NOA WHICH
 HAS EXPIRED. PROVIDE AN UPDATED FLORIDA PRODUCT
 APPROVAL OR NOA SUBMITTAL.
  
 7. M5.1: AHU DETAIL SHOWS LOUVERED DOORS BUT FLOOR PLAN
 SHOWS SOLID DOORS WITH WALL GRILL. PLEASE COORDINATE
 PLANS.
  
 8. ENERGY CALCULATIONS: THIS SPACE IS NOT COOLED BY ONE
 SYSTEM OF 240,000 TO 760,000 BTU/H COOLING CAPACITY.
 ADJUST CALCULATIONS TO ACCURATELY REFLECT THE EQUIPMENT
 BEING USED AND THE MINIMUM EFFICIENCY RATING REQUIRED.
 EXAMPLE: FOR EQUIPMENT <65,000 BTU/H THE EFFICIENCY
 CRITERIA IS 13.00 NOT 9.50 AS STATED ON CALCULATIONS
 SYSTEM REPORT.
  
 9. ROOF TYPE ON INPUT DATA REPORT SHOWS A METAL
 BUILDING ROOF WITH R-19 BATTS. THIS IS NOT A METAL
 BUILDING AND THERE ARE NO BATTS AT THE ROOF. PLEASE
 CORRECT TO ACCURATELY REFLECT THE SYSTEM BEING USED ON
 THIS BUILDING AND RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 4 Status N Date 2008-05-01 Cont ID  
Sent By mperson Date 2008-05-01 Time 16:37 Rev Time 0.00
Received By mperson Date 2008-05-01 Time 16:37 Sent To  
Notes
2008-05-01 16:40:18REVISION SHEETS A-201 & A-350: NO PLUMBING CHANGES.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-01-07 Cont ID  
Sent By mperson Date 2008-01-07 Time 10:09 Rev Time 0.00
Received By mperson Date 2008-01-07 Time 10:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-04 Cont ID  
Sent By mperson Date 2007-12-04 Time 06:29 Rev Time 0.00
Received By mperson Date 2007-12-04 Time 06:29 Sent To PC
Notes
2007-12-04 08:00:34PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE STILL
 REQUIRED FOR PLUMBING PLAN REVIEW TO MEET CODE
 COMPLIANCE ON THE RESUBMITTED PLANS:
  
 1. OK, COMMENT ADDRESSED.
  
 2. OK, COMMENT ADDRESSED.
  
 3. OK, COMMENT ADDRESSED.
  
 4. SHEET A-901 ROOM FINISH SCHEDULE: ROOMS 114, 115 &
 118. THE WALLS WITH IN 2 FEET OF A WATER CLOSET SHALL
 HAVE A SMOOTH, HARD, NONABSORBANT SURFACE UP TO 4 FEET.
 PER SECTION *1210.2.
  
 **NOTE: RESUBMITTED FINISH SCHEDULE ON THIS SHEET ARE
 NOW INDICATING EPOXY PAINT ON DRYWALL. PLEASE REFERENCE
 BUILDING PLAN REVIEWERS COMMENT #15 THAT EPOXY PAINT ON
 DRYWALL HAS NOT BEEN ESTABLISHED AS A NON-ABSORBANT
 MATERIAL SINCE IT CAN GET NICKS IN THE SURFACE THROUGH
 OUT THE LIFE TIME OF THE INSTALLATION AND COMPLY PER
 SECTION *1210.2 WALLS.
  
 5. OK, COMMENT ADDRESSED.
  
 6. SHEETS L1 THRU L4 SHALL BE SIGNED, SEALED WITH AN
 EMBOSSED SEAL AND DATED AS REQUIRED IN SECTION 106.1.
 ALSO THE FIRM LICENSE NUMBER IS REQUIRED IN THE TITLE
 BLOCK. FAC 61G15-23.002(2) & FS 417.025. PLEASE SHOW
 THE THE PRINTED NAME OF THE ENGINEER SEALING THE
 DOCUMENT AS WELL AS THE CA# ON EACH SHEET.
  
 **NOTE: THE RESUBMITTED SHEETS ARE MISSING THE PRINTED
 NAME AND LICENSE NUMBER OF THE PERSON SEALING THE
 SHEETS AS WELL AS THE CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE FIRM.
  
 7. SHEET P0.1 WATER RISER DIAGRAM THE WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS. PLEASE LOCATE
 THE WHA'S AS REQUIRED.
  
 **NOTE: THE RESUBMITTED WATER RISER DIAGRAM IS LOCATING
 THE WATER HAMMER ARRESTOR FOR THE SINK IN BREAK ROOM
 113 WRONG. PLEASE LOCATE THE WATER HAMMER ARRESTORS AS
 REQUIRED.
  
 8. SEPERATE IRRIGATION PLANS & PERMIT REQUIRED PRIOR
 TO C. O. SECTION 106.3.5.1.3(9).
  
 *****THE FOLLOWING ARE NEW COMMENTS*****
  
 9. NOTE, THE ADDED RESTROOM #118 ON SHEET A-201 TO
 MEET THE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES:
 THE REQUIRED PLUMBING FOR THIS REST ROOM NEEDS TO BE
 ADDED TO SHEETS P0.1 DOMESTIC WATER AND SANITARY RISER
 DIAGRAMS AS WELL AS TO SHEET SHEET P2.1 PLUMBING PLANS.
 PLEASE COMPLY ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-15 Cont ID  
Sent By kstevens Date 2007-09-15 Time 17:17 Rev Time 0.00
Received By kstevens Date 2007-09-15 Time 17:17 Sent To  
Notes
2007-09-15 17:44:42DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS CS-1 AND ALL ARCHITECTUAL SHEETS. THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT SHALL BE IN THE
 TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(6) & FS
 481.2055. PLEASE INDICATE THE PRINTED NAME.
  
 2. SHT 1 OF 1, (DCES), SHALL BE SIGNED, SEALED AND
 DATED PER SECTION 106.1.
  
 3. SHT A-201 PER TABLE 403.1 THREE WATER CLOSETS AND
 THREE LAVS ARE REQUIRED FOR THE BUSINESS OCCUPANCY AT
 7260SF. ONLY 2 W/C'S AND 2 LAVS WERE PROVIDED. PLEASE
 SHOW COMPLIANCE WITH TABLE 403.1 REQUIEMENT.
  
 4. SHT A-901 ROOM FINISH SCHEDULE. ROOMS 114 & 115. THE
 WALLS WITH IN 2 FEET OF A WATER CLOSET SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT SURFACE UP TO 4 FEET. THE
 SCHEDULE INDICATES PAINTED GWB. PAINTED SURFACES DOES
 NOT COMPLY WITH THE REQUIREMENT FOR A HARD SURFACE.
 PLEASE SHOW COMPLIANCE WITH SECTION 1210.2.
  
 5. SHTS S-01 THRU S-06. ENGINEER SHALL LEGIBLY INDICATE
 THEIR NAME ON EACH SHEET. ALSO THE CERTIFICATE OF
 AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61G15-23.002(2) & FS 471.025. PLEASE SHOW
 THE PRINTED NAME OF THE ENGINEERING SEALING THE
 DOCUMENT AS WELL AS THE CA# ON EACH SHEET.
  
 6. SHTS L1 THRU L4 SHALL BE SIGNED, SEALED WITH AN
 EMBOSSED SEAL AND DATED AS REQUIRED IN SECTION 106.1.
 ALSO THE FIRM LICENSE NUMBER IS REQUIRED IN THE TITLE
 BLOCK. FAC 61G1-16.004(2)(5) & FS 481.2055. PLEASE
 SIGN, SEAL & DATE EACH SHEET AND INDICATE THE FIRM
 LICENSE NUMBER AS WELL.
  
 7. SHT P0.1 WATER RISER DIAGRAM. THE WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS. PLEASE LOCATE
 THE WHA'S AS REQUIRED.
  
 8. SEPARATE IRRIGATION PLANS & PERMIT REQUIRED PRIOR TO
 C.O. SECTION 106.3.5.1.3(9).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-12-28 Cont ID  
Sent By adavila Date 2007-12-28 Time 11:37 Rev Time 0.00
Received By adavila Date 2007-12-28 Time 11:37 Sent To  
Notes
2007-12-28 11:40:43PLANNING AND ZONING DEPARTMENT
  
 PROVISO WHEEL STOPS SHALL BE 2 FEET FROM THE CURB TO
 THE BACK OF THE WHEEL STOP.HANDICAP SYMBOL SHALL BE 3
 FEET OR 5 FEET HIGH AND WHITE IN COLOR.HANDICAP
 SYMBOL SHALL BE 2 FEET FROM THE OPEN END OF THE PARKING
 SPACE.
  
 PROVISO ALL ELECTRICAL CONDUIT SHALL RUN AROUND AND
 AWAY FROM ANY ROOT BALLS.LIGHT POLES ARE TO BE 2 FEET
 FROM THE TERMINATING POINTS OF THE ISLANDS.
  
 PROVISO LANDSCAPE PLANS SHALL BE SEALED PRIOR TO
 OBTAINING C.O.SIGNED AND SEALED COPIES SHALL BE
 SUBMITTED TO THE CITY.PER ANGELLA VANN, DEPUTY
 PLANNING DIRECTOR.
  
 ALL PROVISOS SHALL BE MET PRIOR TO OBTAINING C.O.
  
 SEE SPECIFIC SHEETS FOR EACH PROVISO.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-22 Cont ID  
Sent By adavila Date 2007-10-22 Time 16:05 Rev Time 0.00
Received By adavila Date 2007-10-22 Time 16:05 Sent To  
Notes
2007-10-22 16:06:01PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PLANS SHALL BE REVISED TO SHOW CONDITIONS PER THE
 SITE PLAN APPROVAL LETTER.
  
 2. PARKING STALL DETAILS IN SHEET C-3 OF 4, ?PAVING,
 GRADING AND DRAINAGE DETAILS,? SHALL MATCH THE PARKING
 STALL DETAILS PER THE APPROVED SITE PLANS.
  
 3. PLEASE NOTE THAT ALL PLANS SHALL SHOW SAME
 CONDITIONS.
  
 4. PLEASE SUBMIT (2) COPIES OF A SIGNED AND SEALED
 SURVEY.
  
 5. AN IRRIGATION PLAN SHALL BE SUBMITTED WITH THE
 IRRIGATION PERMIT.
  
 COMMENT/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-09 Cont ID  
Sent By adavila Date 2007-08-09 Time 09:02 Rev Time 0.00
Received By adavila Date 2007-08-09 Time 08:38 Sent To  
Notes
2007-08-09 09:06:46PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.PLANS REQUIRE SITE PLAN APPROVAL FROM THE PLANNING
 AND ZONING DEPARTMENT PRIOR TO BUILDING PERMIT
 APPROVAL.PLEASE NOTE THAT ALL PPRC COMMENTS SHALL BE
 ADDRESSED PRIOR TO SITE PLAN APPROVAL.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.