Plan Review Details - Permit 07071001
Plan Review Stops For Permit 07071001
Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2008-11-18 Cont ID  
Sent By shill Date 2008-11-18 Time 10:05 Rev Time 0.00
Received By shill Date 2008-11-18 Time 10:05 Sent To  
Notes
2008-11-18 10:06:15REVISION
  
 KNEE WALL AND SOFFIT DETAIL
 LIGHT POLE BASE DETAIL; **PROVISO** SUBMIT SHOP
 DRAWINGS PRIOR TO INSTALLATION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2008-11-18 Cont ID  
Sent By shill Date 2008-11-18 Time 09:39 Rev Time 0.00
Received By shill Date 2008-11-18 Time 09:39 Sent To  
Notes
2008-11-18 09:59:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. ADDITIONAL FEES DUE; 7 SHEETS SUBMITTED FOR THIS
 REVISION.
  
 2. THE ACCESSIBLE PARKING SPACE IS TO BE LOCATED ON THE
 SHORTEST SAFELY ACCESSIBLE ROUTE OF TRAVEL. THE PARKING
 SPACE SELECTED IS NOT THE SHORTEST ROUTE. PLEASE
 EXPLAIN RATIONALE FOR THIS LOCATION. FBC11-4.6.2.
  
 3. THE NEW ACCESSIBLE PARKING SPACE IS LOCATED ON A
 ROUTE WHICH HAS A PORTION WHICH IS 36" WIDE. SEE
 FBC11-4.6.2(1), ACCESSIBLE PARKING SPACES ARE TO BE ON
 AN ACCESSIBLE ROUTE WHICH IS TO BE NO LESS THAN 44
 INCHES.
  
 4. THE TWO WINDOWS ON THE 2ND FLOOR HAVE BEEN REPLACED
 BY A SKYLIGHT. ENERGY CALCS ARE TO BE REVISED.
  
 5. PROVIDE THE VALUE FOR THE ADDITIONAL WORK (5 LIGHT
 POLES AND BASES, SOFFIT, KNE WALLS, ETC.).
  
 6. PRODUCT APPROVALS REQUIRED FOR THE SKYLIGHT,
 FAC9B72. PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER
 OF RECORD PRIOR TO SUBMITTAL. FBC*106.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2008-11-07 Cont ID  
Sent By shill Date 2008-11-07 Time 15:16 Rev Time 0.00
Received By shill Date 2008-11-07 Time 15:16 Sent To  
Notes
2008-11-07 15:18:13REVISION, SHEETS S1, S2, S3, S4; LETTERS RE ACCESSIBLE
 PARKING (RESOLVED IN FIELD) AND UNITY EQUATION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-09-09 Cont ID  
Sent By shill Date 2008-09-09 Time 09:03 Rev Time 0.00
Received By shill Date 2008-09-09 Time 09:03 Sent To  
Notes
2008-09-09 09:04:15BUILDING REVISION PASSED W/PROVISO; ENGINEER TO ADDRESS
 COMMENTS FROM BUILDING REVIEW #8
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-09-09 Cont ID  
Sent By shill Date 2008-09-09 Time 08:57 Rev Time 0.00
Received By shill Date 2008-08-29 Time 07:43 Sent To  
Notes
2008-09-09 09:03:29****CORRECTIONS****
 BUILDING REVISION
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE INCORPORATE ALL CHANGES INTO THE PLAN. FOR
 INSTANCE, SHEET 1 OF 3 CHANGES SHOULD BE INCORPORATED
 INTO THE LOWER ROOF FRAMING DETAIL, S1.
  
 2. THERE APPEAR TO BE SHEETS MISSING FROM THE REVISION.
 IT INCLUDES 1, 2, AND 3 OF 3, AND 1 OF 4. WHERE ARE 2
 THROUGH 4 OF 4?
  
 3. SEE SHEET S2 AND THE SIMPSON 2008 GENERAL CATALOG,
 PAGE 14, ITEM E. THE LINK IS INCLUDED BELOW AND IS
 PRINTED AND ATTACHED FOR YOUR CONVENIENCE. PLEASE
 CLARIFY THE COMBINED STRESS INDEX OF 92% STATED ON THE
 PLAN. IF ALL THREE LOADS ARE TAKEN INTO ACCOUNT AS PER
 THE CATALOG (AND THE CATALOG IN EFFECT AT TIME OF
 DESIGN), THE FORMULA EXCEEDS 1; IT RESULTS IN 1.53. IF
 UPLIFT AND PARALLEL AND UPLIFT AND PERPENDICULAR ARE
 TAKEN INTO ACCOUNT SEPARATELY, IT RESULTS IN 1.22 AND
 .97 RESPECTIVELY. IT IS NOT CLEAR HOW THE ENGINEER HAS
 ARRIVED AT A COMBINED STRESS INDEX OF 92%. PLEASE
 CLARIFY OR REVISE AS NECESSARY.
  
 HTTP://WWW.STRONGTIE.COM/FTP/CATALOGS/C-2008/C-2008-P01
 4.PDF
  
 4. SEE S2, PARALLEL TO TRUSS (F1) AND PERPENDICULAR TO
 TRUSS (F2), PLEASE NOTE THAT F1 IN THE SIMPSON CATALOG
 REFERS TO FORCES PARALLEL TO THE WALL, NOT PARALLEL TO
 TRUSS. F2 REFERS TO FORCES PERPENDICULAR TO THE WALL.
 PLEASE CLARIFY AND REVISE IF NECESSARY.
  
 5. PLEASE PROVIDE A VALUE FOR THE NEW WORK (FRAMING FOR
 SKYLIGHT, SKYLIGHT).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-08-21 Cont ID  
Sent By shill Date 2008-08-21 Time 10:31 Rev Time 0.00
Received By shill Date 2008-08-21 Time 10:31 Sent To  
Notes
2008-08-21 10:31:41REVISION, ROOFING NOAS

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-08-11 Cont ID  
Sent By shill Date 2008-08-11 Time 15:25 Rev Time 0.00
Received By shill Date 2008-08-11 Time 15:25 Sent To  
Notes
2008-08-11 15:26:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC*106.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-06-20 Cont ID  
Sent By shill Date 2008-06-20 Time 09:05 Rev Time 0.00
Received By shill Date 2008-06-20 Time 09:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-05-19 Cont ID  
Sent By shill Date 2008-05-19 Time 13:03 Rev Time 0.00
Received By shill Date 2008-05-08 Time 17:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-02-14 Cont ID  
Sent By shill Date 2008-02-14 Time 10:54 Rev Time 0.00
Received By shill Date 2008-02-14 Time 10:54 Sent To  
Notes
2008-02-14 12:27:26****CORRECTIONS****
  
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST
  
 1.INDICATE LEVEL OF ALTERATION, FBC EB301.5.
  
 LEVEL 2 DECLARED.PLEASE CLARIFY; WORK AREA IS OVER
 50% OF THE BUILDING, THEREFORE APPEARS TO BE A LEVEL 3.
 SEE FBC EB CHAPTER 3.
  
 2-6.)ADDRESSED.
  
 7.I WAS UNABLE TO LOCATE THE SPIRAL STAIR SHOPS.
 PLEASE HAVE THE ARCHITECT INCORPORATE DESIGN INTO THE
 PLAN, FBC1009.9.
  
 3RD REVIEW; SHOPS DO NOT SHOW CODE COMPLIANCE WITH ALL
 REQUIREMENTS OF FBC1009.9.PLEASE INCORPORATE ALL
 REQUIRED DESIGN CRITERIA INTO THE PLAN.
  
 NOTE THE FOLLOWING:
  
 A.FBC1009.9.1, RISER HEIGHT IS NOT TO EXCEED 7".
 FBC1009.9.2 DOES NOT APPLY BECAUSE THIS IS NOT A
 MEZZANINE, FLOOR AREA EXCEEDS 250', AND OCCUPANT LOAD
 SHOULD BE 4.9 1/2" RISER HEIGHT HAS BEEN SPECIFIED,
 PLEASE REVISE.
  
 B.SHOW COMPLIANCE WITH FBC1009.9.1 (2) AND (3)
 REGARDING TREAD DEPTH.A 12" DIMENSION WAS SHOWN BUT
 PURPOSE OF THIS DIMENSION IS NOT CLEAR.
  
 C.FBC1009.9.1 (4), INSIDE HANDRAIL NOT SHOWN. PROVIDE
 A HANDRAIL DETAIL IN COMPLIANCE WITH FBC1009.1(4) AND
 (5).NO HANDRAIL EXTENSIONS ARE SHOWN.
  
 D.A LINE WHICH APPEARS TO GRAPHICALLY SHOW THE
 HANDRAIL TO THE OUTSIDE OF THE STAIR GOES ACROSS THE
 STAIR TREAD.WHAT IS THIS?
  
 E.VERTICAL ACCESSIBILITY CAN BE EXEMPTED
 FBC11-4.1.6(1)(K)(III), A SPACE NOT OPEN TO THE PUBLIC
 AND AN OCCUPANT LOAD OF LESS THAN 5.PLEASE MAKE NOTE
 ON THE PLAN THAT THIS AREA IS NOT OPEN TO THE PUBLIC.
 HOWEVER, EXEMPTION FROM VERTICAL ACCESSIBILITY
 REQUIREMENTS DOES NOT WAIVE OTHER REQUIREMENTS FOR
 ACCESSIBILITY.SEE FBC11-4.1.6(1)(A) AND (B).SEE
 HANDRAIL HEIGHT AND EXTENSION REQUIREMENTS OF
 FBC1009.11, FBC11-4.8.5.PROVIDE GUADRAIL AND HANDRAIL
 DETAILS.
  
 8.ROOF FRAMING ENGINEERING WAS SUBMITTED.THE
 STRUCTURAL ENGINEER HAS SPECIFIED DESIGN CRITERIA OF
 EXPOSURE C (S2) AND A BCLL OF 10PSF (SEE WOOD TRUSS
 NOTES).THE TRUSS ENGINEER HAS STATED THAT A
 NONCURRENT LIVE LOAD OF 10PSF HAS BEEN CHECKED, BUT THE
 ENGINEERING IS FOR 0 BCLL.PLEASE CORRELATE STRUCTURAL
 DESIGN WITH THE TRUSS ENGINEERING, REVISE AS NECESSARY,
 AND HAVE THE TRUSS ENGINEERING REVIEWED BY DESIGNER OF
 RECORD.
  
 9-13. ADDRESSED.
  
 14.ARCHITECT STATES IN HIS RESPONSE LETTER (AND ON
 A1) THAT OCCUPANT LOAD IS LESS THAN 3 FOR THE SECOND
 FLOOR.SEE FBC1004.1, OCCUPANT LOAD CANNOT BE LESS
 THAN FBC TABLE 1004.SEE OTHER COMMENTS REGARDING
 OCCUPANT LOAD.
  
 3RD REVIEW, SEE 2ND FLOOR.WHEN SCALED, THE INTERIOR
 DIMENSIONS ARE 23' (24'6"-16") BY 14.33'(15'8"-16");
 332 SF, OCCUPANT LOAD OF 4.ALL NUMBERS SHOULD BE
 ROUNDED UP TO THE NEAREST WHOLE NUMBER AS THE OCCUPANT
 LOAD CANNOT BE LESS THAN TABLE 1004 AND YOU CANNOT HAVE
 A PORTION OF A PERSON.REVISE OCCUPANT LOAD
 ACCORDINGLY.
  
 15-22. ADDRESSED.
  
 23.PLEASE REVISE OCCUPANCY AND OCCUPANT LOAD FOR
 SECOND FLOOR AS DISCUSSED WITH ARCHITECT.
  
 3RD REVIEW, SEE ITEM 14.
  
 24-25.)ADDRESSED.
  
 26.A1, OCCUPANT LOAD CANNOT BE LESS THAN FBC TABLE
 1004 AS PER FBC1004.1.THE TOTAL SQUARE FOOT AREA USED
 TO CALCULATE OCCUPANT LOAD IS NOT CONSISTENT WITH THE
 SQUARE FOOT AREA OF THE SPACE.PLEASE REVISE.
  
 SEE OTHER COMMENTS REGARDING OCCUPANT LOAD.
  
 27.ADDRESSED.
  
 28.INCLUDE 2007 AMENDMENTS IN GOVERNING CODE
 EFFECTIVE JULY 1, 2007.
  
 PLEASE REVISE STRUCTURAL SHEETS.THIS PROJECT IS
 AFFECTED BY 2007 REVISIONS.
  
 29.ADDRESSED.
  
 NEW COMMENTS:
  
 30.PLEASE PROVIDE FLORIDA STATE PRODUCT APPROVAL FOR
 ALL PRODUCTS, IF AVAILABLE.WWW.FLORIDABUILDING.ORG.
 THIS IS REQUIRED IN ADDITION TO THE MIAMIDADE NOAS
 PROVIDED, FAC9B72.
  
 31.THE SMITH MOUNTAIN WINDOW IS SMALL MISSILE IMPACT
 RATED; LARGE MISSILE REQUIRED, FBC1609.1.4.
  
 32.WHERE WILL THE WOOD INFILL FRAMING DETAIL BE
 INSTALLED, S3?

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-04 Cont ID  
Sent By shill Date 2007-12-04 Time 15:28 Rev Time 0.00
Received By shill Date 2007-12-03 Time 16:53 Sent To  
Notes
2007-12-04 15:31:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST
  
 1.INDICATE LEVEL OF ALTERATION, FBC EB301.5.
  
 PLEASE SEE FBC CHAPTER 3.THE ARCHITECT HAS DECLARED
 LEVEL 2 AND HAS PROVIDED INFORMATION REGARDING
 VALUATION.SEE FBC EB 202, DEFINITIONS, REPAIR.THIS
 IS NOT A REPAIR FOR BUILDING CODE PURPOSES.SEE FBC EB
 305, WORK AREA APPEARS TO BE OVER 50% OF THE BUILDING.
 THE INFORMATION PROVIDED REGARDING VALUATION DOES NOT
 AFFECT THE LEVEL OF ALTERATION DETERMINATION.PLEASE
 CLARIFY CORRECT LEVEL OF ALTERATION AS CODE COMPLIANCE
 AND REQUIREMENTS CANNOT BE DETERMINED BASED ON THE
 INFORMATION PROVIDED.
  
 2.ADDRESSED.
  
 3.THE ARCHITECT STATES THAT THIS IS MERCANTILE CLASS
 B IN HIS LETTER AND AT TOP LEFT OF SHEET A1, AND
 DECLARES THIS AS MERCANTILE GROUP M ON A1, BUILDING
 DATA.PLEASE SEE FBC302.1, PORTIONS OF BUILDINGS TO BE
 CLASSIFIED ACCORDING TO FBC 302.3.IT APPEARS THAT
 THIS SPACE IS MIXED USE AS THE OFFICE AREA DOES NOT
 COMPLY WITH THE DEFINITION OF ACCESSORY USE, FBC302.2.
  
 ARCHITECT IS DECLARING THIS AS MERCANTILE B, BUT B IS
 BUSINESS, MERCANTILE IS M.PLEASE CLASSIFY EACH
 PORTION OF THE BUILDING.WHAT WAS THE PREVIOUS
 OCCUPANCY OF THIS SPACE?
  
 CONTRACTOR HAS INDICATED THAT THIS IS A CHANGE OF
 OCCUPANCY.IF THIS IS NOT THE CASE, REVISE THE
 APPLICATION.IF THIS IS A CHANGE OF OCCUPANCY, INCLUDE
 IN THE BUILDING DATA INFORMATION ON A1.
  
 4-6. ADDRESSED.
  
 7.I WAS UNABLE TO LOCATE THE SPIRAL STAIR SHOPS.
 PLEASE HAVE THE ARCHITECT INCORPORATE DESIGN INTO THE
 PLAN, FBC1009.9.
  
 8.SHOPS FOR ROOF FRAMING WERE NOT SUBMITTED AS
 STATED.THIS CAN BE REVIEWED PRIOR TO INSTALLATION.
  
 9-13. ADDRESSED.
  
 14.ARCHITECT STATES IN HIS RESPONSE LETTER (AND ON
 A1) THAT OCCUPANT LOAD IS LESS THAN 3 FOR THE SECOND
 FLOOR.SEE FBC1004.1, OCCUPANT LOAD CANNOT BE LESS
 THAN FBC TABLE 1004.SEE OTHER COMMENTS REGARDING
 OCCUPANT LOAD.
  
 15-22. ADDRESSED.
  
 NEW COMMENTS:
  
 23.PLEASE REVISE OCCUPANCY AND OCCUPANT LOAD FOR
 SECOND FLOOR AS DISCUSSED WITH ARCHITECT.
  
 24.PLAN A1 SHOWS A SITE WALL TO BE DEMOLISHED, BUT IT
 APPEARS THAT THE STAIR RAIL IS ON THIS WALL.FBC EB
 501.2.
  
 25.2MP1, CONCRETE PADS ARE SHOWN ON THE ROOF.THIS
 CONFLICTS WITH THE DETAIL ON S3.PLEASE CORRELATE AND,
 IF USING CONCRETE PADS, STRUCTURAL ENGINEER IS TO
 ADDRESS THE ADDITIONAL DEAD LOAD ON THE ROOF.
  
 26.A1, OCCUPANT LOAD CANNOT BE LESS THAN FBC TABLE
 1004 AS PER FBC1004.1.THE TOTAL SQUARE FOOT AREA USED
 TO CALCULATE OCCUPANT LOAD IS NOT CONSISTENT WITH THE
 SQUARE FOOT AREA OF THE SPACE.PLEASE REVISE.
  
 27.PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 28.INCLUDE 2007 AMENDMENTS IN GOVERNING CODE
 EFFECTIVE JULY 1, 2007.
  
 29.SHOW ACCESSIBLE ROUTE AND ACCESSIBLE PARKING,
 FBC1104.1.2, 11-4.1.2(1).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-06 Cont ID  
Sent By kconrad Date 2007-09-06 Time 20:54 Rev Time 0.00
Received By kconrad Date 2007-08-28 Time 17:00 Sent To I
Notes
2007-08-28 18:01:51PROJECT: 740 BELVEDERE ROAD/STAR BAKERY CAFE
  
 PROJECT DETAIL: INTERIOR / EXTERIOR ALTERATION &NEW
 COVERED ENTRY
  
 PLAN REVIEW:
  
 2004 FLORIDA EXISTING BUILDING CODE/ 2006 REVS.2004
 FLORIDA BUILDING CODE W/2006 REVS.
 CITY OF WPB ADMINISTRATIVE AMENDMENTS/2004
  
 COMMENTS:
  
 1) PLEASE INDICATE THE LEVEL OF ALTERATION OR
 COMBINATIONS IF APPLICABLE:
  
 301.5 . A DESIGN PROFESSIONAL OR AN OWNER MUST
 ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION 303,304 &
 305 OF THIS CODE.
  
 2) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE
 FOLLOWING:
  
 FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) THE PERMIT APPLICATION REFLECTS A CHANGE OF
 OCCUPANCY. PLEASE INDICATE THE EXISTING OCCUPANCY AS
 PER THE FOLLOWING:
  
 812.1.2CHANGE OF OCCUPANCY GROUP WITH SEPARATION. A
 PORTION OF AN EXISTING BUILDING THAT IS CHANGED TO A
 NEW OCCUPANCY GROUP AND THAT IS SEPARATED FROM THE
 REMAINDER OF THE BUILDING WITH A FIRE RATED
 WALL/CEILING HAVING A FIRE-RESISTANCE RATING AS
 REQUIRED IN THE FLORIDA BUILDING CODE, BUILDING FOR THE
 SEPARATE OCCUPANCY SHALL COMPLY WITH ALL THE
 REQUIREMENTS OF CHAPTER 7 FOR THE NEW OCCUPANCY GROUP
 AND WITH THE REQUIREMENTS OF THIS CHAPTER. EXCEPTION:
 COMPLIANCE WITH ALL OF THE PROVISIONS OF CHAPTER 7 IS
 NOT REQUIRED WHEN THE CHANGE OF USE COMPLIES WITH THE
 REQUIREMENTS OF SECTION 812.3.
  
 4) PROVIDE AN ASBESTOS SURVEY IF APPLICABLE AS PER THE
 FOLLOWING:
  
 105.9 ASBESTOS.
 THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT
 FOR THE DEMOLITION OR RENOVATION OF AN EXISTING
 STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT
 WHICH INDICATES THE OWNER?S OR OPERATOR?S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW.
  
 5) PLEASE INDICATE THE FIRE- RATING OF THE EXISTING
 OCCUPANCY WALL SEPARATION.
  
 6)SHEET A-1 REFLECTS THAT THE EXISTING 2ND FLOOR WILL
 BE USED FOR STORAGE WHICH IS INCIDENTAL TO THE
 MERCHANTILE OCCUPANCY AREA. PLEASE INDICATE THE TYPES
 OF MATERIALS TO BE STORED ON THE 2ND FLOOR. THE FORMER
 SHALL COMPLY WITH THE FOLLOWING:
  
 302.1.1 INCIDENTAL USE AREAS.
 SPACES WHICH ARE INCIDENTAL TO THE MAIN OCCUPANCY SHALL
 BE SEPARATED OR PROTECTED, OR BOTH, IN ACCORDANCE WITH
 TABLE 302.1.1 OR THE BUILDING SHALL BE CLASSIFIED AS A
 MIXED OCCUPANCY AND COMPLY WITH SECTION 302.3. AREAS
 THAT ARE INCIDENTAL TO THE MAIN OCCUPANCY SHALL BE
 CLASSIFIED IN ACCORDANCE WITH THE MAIN OCCUPANCY OF THE
 PORTION OF THE BUILDING IN WHICH THE INCIDENTAL USE
 AREA IS LOCATED.
  
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS/SHOP DRAWINGS
 FOR THE NEW METAL SPIRAL STAIRS AS SHOWN ON SHEET A-2.
 STAIRS MUST COMPLY WITH FBC 1009.9.
  
 8) THE INDICATED SERVICE COUNTER-TOPS SHALL MEET THE
 REQUIREMENTS OF THE ACCESSIBILITY CODE:
  
 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34
 INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION
 OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN
 LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH
 SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT
 ACCESSIBLE TABLES WITHIN THE SAME AREA.
  
 9) PLEASE SUBMIT TOWER ROOF FRAMING LAYOUT AND TRUSS
 ENGINEERING FOR REVIEW.
  
 10) SUBMIT THE STOREFRONT WINDOW FRAMING
 ENGINEERING/PRODUCT APPROVALS
  
 11) SUBMIT PRODUCT APPROVALS FOR WOOD MEMBER
 ANCHORS/HANGERS/STRAPS.
  
 12) PLEASE PROVIDE A DETAIL FOR THE MECHANICAL
 CONNECTION OF THE 2X WOOD LEDGER. SEE SHEET S-1.
  
 13) PLEASE PROVIDE EPOXY SPECIFICATIONS FOR REINFORCING
 STEEL EMBEDMENT AS SHOWN ON SHEET S-1, NOTE 1.
  
 14) PLEASE INDICATE THE MEANS OF EGRESS ILLUMINATION AT
 THE OFFICE/STORAGE EXTERIOR STAIRS. THE SAME SHALL
 COMPLY WITH THE FOLLOWING:
  
 1006.1 MEANS OF EGRESS ILLUMINATION.
  
 1006.1.1
 ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND
 STRUCTURE. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS AND PASSAGEWAYS LEADING TO
 AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 EXCEPTIONS:
 1. WHEN APPROVED BY THE BUILDING OFFICIAL, ILLUMINATION
 OF MEANS OF EGRESS SHALL NOT BE REQUIRED IN INDUSTRIAL
 AND STORAGE OCCUPANCIES THAT ARE OCCUPIED ONLY DURING
 DAYLIGHT HOURS, WITH SKYLIGHTS OR WINDOWS ARRANGED TO
 PROVIDE THE REQUIRED LEVEL OF ILLUMINATION ON ALL
 PORTIONS OF THE MEANS OF EGRESS DURING THESE HOURS.
 2. ASSEMBLY OCCUPANCY PRIVATE PARTY TENTS OF 1,200
 SQUARE FEET (111 M2) OR LESS SHALL NOT BE REQUIRED TO
 PROVIDE ILLUMINATION OF MEANS OF EGRESS.
 3. OPEN STRUCTURES SHALL NOT BE REQUIRED TO PROVIDE
 ILLUMINATION OF MEANS OF EGRESS.
 4. TOWERS OCCUPIED BY NOT MORE THAN THREE PERSONS SHALL
 NOT BE REQUIRED TO PROVIDE ILLUMINATION OF MEANS OF
 EGRESS.
  
 15) PLEASE DIMENSION THE EXISTINGEXTERIOR STAIR WIDTH
 AT THE OFFICE/STORAGE EXIT.
  
 16) PLEASE DIMENSION THE SPANS OF THE 2X12 WOOD
 MEMBERS:
  
 1603.1 GENERAL.
 CONSTRUCTION DOCUMENTS SHALL SHOW THE SIZE, SECTION AND
 RELATIVE LOCATIONS OF STRUCTURAL MEMBERS WITH FLOOR
 LEVELS, COLUMN CENTERS AND OFFSETS FULLY DIMENSIONED.
 THE DESIGN LOADS AND OTHER INFORMATION PERTINENT TO THE
 STRUCTURAL DESIGN REQUIRED BY SECTIONS 1603.1.1 THROUGH
 1603.1.8 SHALL BE CLEARLY INDICATED ON THE CONSTRUCTION
 DOCUMENTS FOR PARTS OF THE BUILDING OR STRUCTURE.
  
 17) PLEASE PROVIDE CLARIFICATION FOR THE FOLLOWING:
  
 A) DETAIL 2-S4 DEPICTS FRAMING ONLY. WHAT IS
 REQUIRED FOR THE WALL SHEATHING AND WALL COVERING? B)
 SHOW ATTACHMENT/FASTENING PATTERN OF THE DESIGN WALL
 SHEATHING.
 C) ON DETAIL 2-S4, THE BOTTOM METAL TRACK IS
 ATTACHED TO THE ROOF JOISTS WITH TEK SCREWS. WHAT IS
 THE MINIMUM EMBEDMENT/LENGTH OF
 SCREW TO BE USED?
  
 18) PROVIDE ROOF FLASHING DETAIL AT TOWER TO LOW ROOF
 TRANSITION.
  
 19) PLEASE REVISE BUCK INSTALLATION CHART TO NOTE THAT
 BUCKS SHALL BE FULL WIDTH OF THE WINDOW/DOOR FRAMES:
  
 1714.5.4.2 MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBSTRATE.
  
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1?
 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S
 PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE
 SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
 WHERE THE WOOD BUCK THICKNESS IS 1? INCHES (38 MM) OR
 GREATER, THE BUCK SHALL BE SECURELY FASTENED TO
 TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBTRATE AND THE BUCK SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME.WINDOW
 AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN
 FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE
 FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE
 MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS.
 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME ASSEMBLY
 TO THE SECURED WOOD BUCK.
  
 20) PLEASE PROVIDE DETAIL FOR IN-FILL FRAMING AT THE
 INDICATED DOOR DELETION. SEE DETAIL 2-A2.
  
 21) REVISE DOOR SCHEDULE: WHERE IS DOOR TYPE 5-11
 LOCATED ON THE PLAN?
  
 22) PRIOR TO RE-SUBMITTING THE REVIEWED PLANS, PLEASE
 MAKE CERTAIN TO REVIEW AND ADDRESS EACH OF THE
 AFOREMENTIONEDCOMMENTS AND MAKE ALL CORRECTIONS WHERE
 APPLICABLE. FAILURE TO DO SOWILL IMPEDE THE
 EXPEDITING OF THE PERMIT ISSUANCE.
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-06-03 Cont ID  
Sent By dpalmer Date 2008-06-03 Time 17:12 Rev Time 0.00
Received By dpalmer Date 2008-06-03 Time 17:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-05-04 Cont ID  
Sent By dpalmer Date 2008-05-04 Time 15:34 Rev Time 0.00
Received By dpalmer Date 2008-05-04 Time 15:34 Sent To  
Notes
2008-05-04 15:34:45** DENIED 4TH REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE:PLEASE SEE THE LIFE SAFETY CODE NFPA-101
 7.8.1.3 AND 7.9.2.
 PLEASE SEE THE PREVIOUS REVIEWS REQUESTED THE LIGHTING
 LEVELS FOR NORMAL AND EMERGENCY LEVELS FOR STAIRS WHICH
 WERE USED FOR REQUIRED EGRESS PATHS. THE LEVELS ARE NOW
 SHOWN FOR THE NEW REVISED INTERIOR EGRESS STAIRS
 HOWEVER THE LIGHTING LEVELS UNDER NORMAL ARE NOT
 SHOWN.
 PLEASE SEE THE EXTERIOR STAIRS ARE NOT SHOWING A
 FIXTURE WHICH IS BATTERY BACK UP. THE PLANS MENTIONS
 THE LIGHTS ARE FLOODS HOWEVER THESE WHICH ARE
 IDENTIFIED AS *ES* FIXTURES ARE NOT ON THE FIXTURE
 LEGEND.
 PLEASE SEE 700.12F FOR REQUIRED BATTERY BACK UP.
 PLEASE SEE THE NEXT COMMENT AS THE LIGHTING CONTROLS ON
 PLANS CLEARLY SHOW A SINGLE POLE SWITCH HOWEVER THE
 PANEL SCHEDULE MENTIONS TO PLACE THESE LIGHTS ON
 PHOTO-SENSOR. HOW IS THIS POSSIBLE WHEN THESE ARE
 BATTERY BACK UP UNLESS THE SPECIFIC FIXTURE IS SHOWN
 WITH THIRD LEG TO *PERMANENT HOT*.
 PARKING LOT LIGHTS,
 LANDSCAPE LIGHTS,
 SCONCE LIGHTS,
 FLOOD LIGHTS, ETC ETC.
  
 2) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1., .1.2 AND
 .1.3.
 HOW CAN THE CALCULATIONS BE VERIFIED FOR COMPLIANCE
 WHEN NOT ALL LIGHT FIXTURES ARE SHOWN ON THE FIXTURES
 LEGEND? THIS IS NOTED ABOVE FOR FLOOD FIXTURES *ES* AND
 FIXTURES NOTED AS *SW*.
 PLEASE COMPLETE LIGHTING PERFORMANCE CALCULATIONS.
  
 *** IMPORTANT, PLEASE BE SURE THE WATTAGE FIGURED INTO
 THE CALCULATIONS IS BASED ON THE MAXIMUM FIXTURE
 WATTAGE, NOT THE WATTAGE OF THE LIGHT BULB. THE CODE
 REQUIRES THE FIXTURE VA RATING.
  
 ** THE ABOVE FIXTURES AS NOTED ARE NOT AN EXHAUSTED
 LIST OF POSSIBLE FIXTURES WHICH ARE NOT INCLUDED IN
 CALCULATIONS PER CODE. THESE ARE NOTED AS A BENEFIT.
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1.4 WHICH REQUIRES TWO
 PERMITTED METHOD OF CONTROLS FOR OUTSIDE LIGHTING
 INCLUDING SIGNS.
 PANEL SCHEDULES MAKE SOME NOTES TO TIME CLOCKS AND
 PHOTO-SENSORS HOWEVER PLANS DO NOT GIVE DETAILS FOR
 CODE COMPLIANCE. PLANS SHOW NO DETAIL FOR TC OR PS.
 PLANS STILL ALSO SHOW STANDARD SINGLE POLE SWITCHES FOR
 MANY OF THE OUTSIDE LIGHTS.
 PLEASE KNOW THE ONLY TIME CLOCK PERMITTED IS AN
 ASTRONOMICAL TIME CLOCK AND REQUIRES A MINIMUM OF 10HRS
 BATTERY BACK UP FOR PROGRAMMING.
 PLEASE SEE ANOTHER EXAMPLE IS REAR DOOR FIXTURE TO
 CIRCUIT *A-36* WHICH CLEARLY DOES NOT EVEN INDICATE ANY
 NOTE FOR OTHER CONTROLS EXCEPT A SINGLE POLE SWITCH.
 PLEASE KNOW THE MINIMUM REQUIRED BY CODE IS THE INTENT
 TO TURN OFF LIGHTING DURING DAYLIGHTS HOURS IN THE EVEN
 OF HUMAN FAILURE TO TURN LIGHTING OFF. THE REASON FOR
 AN ASTRONOMICAL TIME CLOCK IS THAT IT WILL KEEP UP WITH
 DAYLIGHT SAVINGS TIMES AND WILL NOT CONTINUALLY NEED TO
 BE RE-SET ETC. IN THE EVENT OF POWER FAILURE THE
 REQUIRED BACK UP WILL RETAIN PROGRAMMING SO LIGHTS WILL
 NOT COME ON DURING THE DAY. THIS IS THE REASON FOR
 LIGHTING CONTROLS.
 MAY NOT USE A STANDARD SINGLE POLE SWITCH AS THE OVER
 RIDE WITHOUT HAVING AUTOMATED SHUT OFF AT DAYLIGHT.
  
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-02-01 Cont ID  
Sent By dpalmer Date 2008-02-01 Time 14:41 Rev Time 0.00
Received By dpalmer Date 2008-02-01 Time 14:41 Sent To  
Notes
2008-02-01 14:42:01** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF CORRECTIONS. PLEASE ALSO SEE THERE ARE
 NEW COMMENT(S) BASED ON INFORMATION NOW PLACED ON PLANS
 WHICH WAS NOT SHOWN PREVIOUSLY.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #1 WHICH SPECIFICALLY
 REQUESTED THE FOLLOWING CODES TO BE PLACED ON
 ELECTRICAL PLANS>
 THIS IS REQUIRED.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 ** MAY NOT QUOTE *LATEST EDITION*
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEWS WHICH REQUESTED
 NORMAL AND EMERGENCY PHOTO-METRIC LEVELS FOR STAIRS.
 THE LEVELS SUBMITTED AND SHOWN ON ARCHITECTURAL PLANS
 DO NOT MEET THE MINIMUM LEVELS AS SET-FORTH IN THE LIFE
 SAFETY CODE. PLEASE ALSO SEE ONLY ONE LEVEL WAS
 SUBMITTED.
 THIS WAS IN BOTH PREVIOUS REVIEWS.
 PLEASE SEE 7.8.1.3, 7.9.2.2
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEWS REQUESTED TO
 COMPLETE WIRING FOR ALL OUTSIDE AND LANDSCAPE LIGHTING.
 NO SITE ELECTRICAL PLANS COULD BE LOCATED.
 PLEASE ALSO SEE SOME OUTSIDE LIGHTING IS NOW SHOWN ON A
 SINGLE POLE LIGHT SWITCH WHICH IS NOT PERMITTED. PLEASE
 SEE FBC CHAPTER 13, 13-415.1.ABC.1.4, 13-415.1.ABC.2
 WHICH SPECIFICALLY REQUIRES AUTOMATED CONTROLS FOR
 OUTSIDE LIGHTING LEVELS.
 FOR EXAMPLE: OUTSIDE LIGHTS MAY NOT BE TURNED ON BE A
 SINGLE POLE SWITCH WHICH WILL LEAVE LIGHTS ON DURING
 DAYLIGHT HOURS AND CONDITIONS. THIS COMMENT IS FOR ALL
 LIGHTS OUTSIDE INCLUSIVE OF LANDSCAPE, PARKING, WALL
 LIGHTS, SIGN ETC.
 ** PLEASE SEE THERE IS STILL NOT ENOUGH
 PLEASE SEE PREVIOUS NOTES WITH RESPECT TO LIGHTING
 PERFORMANCE CALCULATIONS WHICH ARE NOT COMPLETE. THE
 FIRST REVIEW SUBMITTED METHOD *A* WHICH COULD NOT BE
 USED BASED ON THIS WAS NOT NEW CONSTRUCTION AND DID
 MEET THE DEFINITIONS OF RENOVATIONS. WHEN THIS IS THE
 CASE METHOD *B* OR *C* IS REQUIRED. PLEASE SEE THE
 PERMIT APPLICATION PACKAGE OF PLANS AND SUPPORTING
 DOCUMENTS SUBMITTED DID NOT CONTAIN ANY FLA-COM FORMS.
 THE LIGHTING LEVELS SHOWN ON SHEET E-1 DOES NOT CONTAIN
 THE INFORMATION FOR PERFORMANCE LEVELS AS NEEDED AND
 REQUIRED FOR MINIMUM COMPLIANCE WITH FBC 13-415.2,
 13-415.1.B, 13-415.1.C, 13-400.0.C, 13-400.0.B,
 13-400.3.B, 13-400.3.C, ETC
 PLEASE SEE NO EXTERIOR ALLOWANCES WERE SHOWN, PLEASE
 SEE 13-415.2.ABC.1.3
  
 ***ATTENTION, PLEASE SEE FAC 61G15-33.004 WHICH
 REQUIRES THE ENGINEER OF RECORD TO DESIGN MINIMUM
 COMPLIANCE FOR ALL LIGHTING REQUIRED IN THE NEC< LS 101
 AND FBC.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH STATED THAT
 NEW *EQUIPMENT GROUNDING CONDUCTORS* WERE ADDED BEFORE
 THE FIRST MEANS OF DISCONNECT(S) WHICH IS NOT PERMITTED
 BY THE NEC. PLEASE SEE CODE SECTIONS 250.6, 250.24.
 PLEASE KNOW THE *EQUIPMENT GROUNDING CONDUCTORS* ARE
 ONLY INSTALLED *AFTER* THE FIRST MEANS OF DISCONNECT.
 AS SHOWN THIS WOULD CREATE OBJECTIONABLE CURRENTS AND A
 UNSAFE INSTALLATION. PLEASE REMOVE.
  
 5) NOTE: PLEASE SEE THE COMPLETE GROUNDING ELECTRODE
 SYSTEM HAS NOW BEEN MOVED AND IS NOT IN COMPLIANCE WITH
 ANY SECTION OF NEC 250.
 PLEASE MOVE THIS GROUNDING ELECTRODE SYSTEM TO MEET
 NEC.
 PLEASE SEE REDLINED PLANS.THIS GEC AND SYSTEM SHALL
 BEAS FOLLOWS::
 1/0, 250.66,
 2-GROUND RODS, 250.50, 250.56
 COLD WATER PIPE, 250.50
 GAS *** BOND ONLY***, 250.104
 ** BUILDING STRUCTURAL FOOTER STEEL IS ONLY REQUIRED
 WHERE 20FT OR MORE IS AVAILABLE. PLEASE KNOW AS THIS IS
 AN EXISTING BUILDING AND IT DOES NOT APPEAR NEW FOOTERS
 OF 20FT OR MORE ARE NOT BEING INSTALLED, AN ATTACHMENT
 TO THE EXISTING IS NOT REQUIRED PER 250.50. IF THIS IS
 SHOWN ON THE GROUNDING ELECTRODE RISER THEN IT WILL BE
 REQUIRED.
 EXPOSING OLD/EXISTING FOOTER WOULD BE DETRIMENTAL TO
 THE STRUCTURAL INTEGRITY OF THE EXISTING FOOTERS.
  
 ** IMPORTANT** PLEASE CALL TO GO OVER THIS AS THERE IS
 SOME LOSS IN UNDERSTANDING FROM THE COMMENTS TO WHAT IS
 BEING DONE ON PLANS. THIS IS FOR COMMENT #4 AND 5.
  
 6) NOTE: PLEASE SEE A NEW NOTE WAS ADDED TO E-2 HOWEVER
 WAS NOT PER THE PREVIOUS NOTES OF 13-413.1.ABC.2.1 AND
 .2.2.
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE THAT A FEE OF $3, 408 IS DUE BEFORE
 RE-SUBMITTAL OF PLANS. THIS IS NOT ASSESSED TO THE
 CONTRACTOR OR OWNER.
 ONE SET OF PLANS WILL BE RETAINED BY THIS OFFICE.
  
 8) NOTE: PLEASE SEE FS 713.13(2), THE NOTICE OF
 COMMENCEMENT SUBMITTED IS EXPIRED.
 WHEN WORK HAS NOT COMMENCED WITHIN 90DAYS OF RECORDING
 NOC, THE NOC BECOMES VOID AND WILL BE REQUIRED TO BE
 RE-RECORDED.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-26 Cont ID  
Sent By dpalmer Date 2007-11-26 Time 09:33 Rev Time 0.00
Received By dpalmer Date 2007-11-26 Time 08:06 Sent To  
Notes
2007-11-26 09:33:43** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH SOME NEW COMMENTS DUE
 TO CHANGES ON PLANS.
 NOTE FROM PREVIOUS REVIEW MENTIONED THERE MAY BE NEW
 COMMENTS AS THERE WAS INFORMATION NOT SUBMITTED FOR
 REVIEW.
  
 1) NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW WHICH
 REQUESTED THE CODES ON ELECTRICAL PLANS.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** IT WAS NOTED THAT THESE WERE ADDED TO A-1, HOWEVER
 NEEDS TO BE ON ELECTRICAL PLANS ALSO.
  
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE #2 AS THE LIGHTING
 PERFORMANCE CALCULATIONS FOR INTERIOR AND EXTERIOR ARE
 NOT COMPLETE.
 PLEASE SEE NO INFORMATION WAS SHOWN FOR EXTERIOR AND
 THE INFORMATION FOR INTERIOR CAN NOT BE VERIFIED AS THE
 FIXTURE LEGEND IS NOT COMPLETE WITH FIXTURE
 INFORMATION.
 PREVIOUSLY SUBMITTED METHOD *A* AND NOW SUBMITTING
 *C*.
 PLEASE SEE 13-415.1.A, 13-415.2, 13-415.2.ABC.1.2,
 13-415.2.ABC.1.3, 13-415.2.ABC.1.1
  
 3) NOTE: PLEASE PROVIDE NOTES ON PLANS PER
 13-413.1.ABC.2.1, .2.2
  
 4) NOTE: PLEASE SEE THE PLANS STILL SHOW A *J-BOX* FOR
 FUTURE GENERATOR YET NO INFORMATION WAS LOCATED ON
 RISER OR PLANS. HOW WILL TRANSFER TAKE PLACE:? HOW WILL
 THIS CONNECTION BE MADE?
 PLEASE PROVIDE MORE INFORMATION.
 702.6, 110.3, 90.7
 FBC 106.1.2
  
 5) NOTE: PLEASE CLARIFY WHERE AND HOW LOADS WERE
 FIGURED FOR SHOW WINDOWS. PLEASE BE SURE TO ADJUST LOAD
 CALCULATIONS PER 220.43
  
 6) NOTE: PLEASE SEE RISER NOW SHOWS *EQUIPMENT
 GROUNDING CONDUCTORS* FROM METER TO THE FIRST MEANS OF
 DISCONNECT.
 PLEASE SEE 250.6, 250.24 AS THIS IS NOT PERMITTED.
 EQUIPMENT GROUNDING CONDUCTORS ARE ONLY INSTALLED AFTER
 THE FIRST MEANS OF DISCONNECTS.
  
 7) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIR AREAS
 UNDER NORMAL AND UNDER EMERGENCY. RESPONSE FROM
 ARCHITECT MENTIONS TO SEE FBC 1006.1.1 EXCEPT #4,
 HOWEVER PLEASE SEE THE LATEST CODE AS THIS SECTION
 COULD NOT BE FOUND. PLEASE KNOW IN EITHER CASE AS THE
 LIFE SAFETY CODE AND FLORIDA ADMINISTRATIVE CODE IS
 MORE RESTRICTIVE, PLEASE SUBMIT AS PREVIOUSLY
 REQUESTED. THESE ARE REQUIRED. FAC 61G15-33.004
 PLEASE SEE THAT THIS NEEDS TO INCLUDE THE EXTERIOR
 STAIR TO THE PUBLIC RIGHT OF WAY. PLEASE PROVIDE
 LIGHTING FIXTURES AND ALSO BATTERY BACK UP AS REQUIRED
 UNDER THE MINIMUM REQUIREMENTS OF THE LIFE SAFETY
 CODE.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2
  
 8) NOTE: PLEASE SEE AS ELECTRICAL FOR SECOND FLOOR IS
 NOW BEING SUBMITTED AND SHOWN, PLEASE CLARIFY WHAT IS
 NEW AND WHAT IS EXISTS? PLANS CONTAIN A NOTE WHICH
 MENTIONS *ALL* IS EXISTING, YET THIS IS NOT POSSIBLE
 WHEN THERE ARE NEW STAIRS AND NEW RECEPTACLES BEING
 INSTALLED.THE ORIGINAL STAIR LOCATION IS NOT THE SAME
 AND THE FLOOR LOCATION IS BEING CLOSED. PLEASE INDICATE
 NEW AND EXISTING.
 10) NOTE: PLEASE SEE HAND DRAWN CHANGES ON PLANS ARE
 NOT PERMITTED. PLEASE BE SURE TO MAKE CHANGES ON
 REVISED PLANS.
 FBC 106.3.
  
 11) NOTE: PLEASE SUBMIT ELECTRICAL FOR SITE
 LIGHTING/LANDSCAPE AS PREVIOUSLY NOTED. RESPONSE
 MENTIONS CIRCUIT PROVIDE, HOWEVER AS NOTED ABOVE FOR
 FBC CHAPTER 13 AND ELECTRICAL FOR FIXTURES, OVER
 CURRENT PROTECTION ETC, NOT ENOUGH INFORMATION IS
 SHOWN.
 FIXTURE LOCATIONS ETC.
 FBC 106.1.2, 106.3.5.1.2
 NEC240.4, 310.16,
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-25 Cont ID  
Sent By dpalmer Date 2007-08-25 Time 18:12 Rev Time 0.00
Received By dpalmer Date 2007-08-25 Time 17:11 Sent To  
Notes
2007-08-25 18:12:452007-08-25 18:12:45
  
 *** DENIED ***
  
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET
 SUBMITTED FOR REVIEW THERE MAY VERY WELL BE NEW
 COMMENTS ONCE SUBMITTED.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE FBC EXISTING BUILDING CODE FOR
 ELECTRICAL WHICH REFERENCES CHAPTER 27 OF THE FBC.
 PLEASE SEE THE SCOPE OF WORK WELL EXCEEDS THE VALUE OF
 THE 30% AS DEFINED FOR RENOVATIONS.
 PLEASE SUBMIT THE COMPLETED ENERGY CALCULATIONS. PLEASE
 SEE THE CERTIFICATION SHEET EVENS STATES NOT VALID WITH
 OUT THE INPUT DATA REPORT.
 PLEASE KNOW AT THIS TIME NOT REVIEW FOR LIGHTING
 COMPLIANCE CAN BE DONE FOR INTERIOR AND EXTERIOR
 LIGHTING POWER ALLOWANCES. PLEASE SEE 13-415.1.A,
 13-415.2, 13-415.2.ABC.1.2, 13-415.2.ABC.1.3,
 13-415.2.ABC.1.1
  
 3) NOTE: PLEASE SEE THE PLANS AND RISER ARE SHOWING A
 NEW SERVICE FOR THIS PORTION OF THE BUILDING HOWEVER
 THE AS THE PLANS INDICATE THIS A ONE BUILDING ALONG
 WITH THE ADJACENT STRUCTURE ONE PROPERTY THE NEW
 SERVICE AS SHOWN IS NOT GRANTED.
 PLEASE PROVIDE STRUCTURAL INFORMATION FOR THE CONNECTED
 TENANTS.
 PLEASE SEE THIS WOULD REQUIRE A *FIRE WALL* AS DEFINED
 IN THE BUILDING CODE WHICH NOT ONLY CONTAINS A FIRE
 RATING BUT ALLOWS STRUCTURAL COLLAPSE ON ONE SIDE OR
 THE OTHER WITHOUT AFFECT THE STRUCTURAL INTEGRITY OF
 THE OTHER STRUCTURE. AS NO INFORMATION ON THE BUILDING
 AND ADJACENT TENANT IS PROVIDED, UNABLE TO MAKE THE
 DETERMINATION IF MEETING 230.2.
 PLEASE SEE THE PLANS ALSO INDICATE ITEMS LOCATED ON THE
 ADJACENT TENANT ROOF WHICH IS ACTUALLY FOR THIS
 BUILDING??
 PLEASE KNOW THAT IF THIS IS CONSIDERED ONE BUILDING AND
 IS ONLY FED FROM SERVICE THEN THIS IS OK, HOWEVER BASED
 ON PLANS REQUESTED A SEPARATE SERVICE ALL ELECTRICAL
 WHICH IS LOCATED ON THE ADJACENT STRUCTURE WOULD NOT BE
 PERMITTED.
 PLEASE ALSO SEE ONE OF THE COMMENTS BELOW WITH RESPECT
 TO THE EGRESS STAIRS.
  
 4) NOTE: PLEASE SEE NO DISCONNECT FOR MINI-SPLIT CU
 SHOWN ON ROOF IS INDICATED ON PLANS.
 PLEASE SHOW 440.1.
  
 5) NOTE: PLEASE SEE MISSING ROOF TOP GFI AS REQUIRED
 PER 210.63, 210.8B3
  
 6) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES FOR
 WINDOWS AT THE FRONT OF THE STORE.
 210.62
 PLEASE BE SURE TO ADJUST LOAD CALCULATIONS PER 220.43
  
 7) NOTE: PLEASE SEE 600.5 AS THE MINIMUM VA FOR THE
 SIGN CIRCUIT IS REQUIRED TO BE 1200 VA. BASED ON THE
 AMPERAGE SHOWN ON PANEL SCHEDULE AT 120V THIS DOES NOT
 SHOW THE MINIMUM LOAD AS NEEDED.
  
 8) NOTE: PLEASE CLARIFY THE PANELS. THESE ARE SHOWN AS
 200MLO, YET THESE ARE SHOWN AS 42SPACES.
 PLEASE VERIFY THE AVAILABILITY OF THESE TYPES OF
 PANELS. THIS IS OK, HOWEVER IF THESE PANELS SHOWN AT 42
 SPACES ARE INDEED 225AMP RATED, THAN PLEASE REVISE
 PLANS TO SHOW THIS.
 ** THIS WOULD ALLEVIATE AND REVISIONS NEEDED AT A LATER
 DATE.
  
 9) NOTE: PLEASE CLARIFY THE COOLER AS THERE IS NO
 LIGHTING PROVIDED ON PLANS.,
 FBC 106.1.2 (ADDITIONAL INFORMATION).
  
 10) NOTE: PLEASE SEE MISSING INFORMATION ON THE TITLE
 BLOCKS FOR THE ARCHITECT AS REQUIRED PER FAC
 61G1-16.004.
  
 11) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIR AREAS
 UNDER NORMAL AND UNDER EMERGENCY.
 PLEASE SEE THAT THIS NEEDS TO INCLUDE THE EXTERIOR
 STAIR TO THE PUBLIC RIGHT OF WAY. PLEASE PROVIDE
 LIGHTING FIXTURES AND ALSO BATTERY BACK UP AS REQUIRED
 UNDER THE MINIMUM REQUIREMENTS OF THE LIFE SAFETY
 CODE.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2
  
 12) NOTE: PLEASE SEE 210.8B2 AS ALL 15 AND 20 AMP 120
 RECEPTACLES IN KITCHEN AND FOOD PREP AREAS ARE REQUIRED
 TO BE GFI OR GFI PROTECTED. THIS DOES NOT MATTER IF
 THESE FEED COUNTER SPACES OR NOT.
  
 13) NOTE: PLEASE SUBMIT ELECTRICAL FOR THE 2ND FLOOR.
 DUE TO THE SCOPE OF WORK, THIS AREA WOULD BE REQUIRED
 TO MEET CODE.
 PLEASE SEE ANY POSSIBLE COMMENTS FROM THE FIRE MARSHAL
 AND BUILDING REVIEWER FOR REQUIRED SMOKE ALARMS OR
 SMOKE DETECTORS.
 AS SHOWN ON PLANS, THIS AREA IS NOT PERMITTED TO BE
 USED FOR SLEEPING/APARTMENT/RESIDENCE. IF SO, THEN
 MINIMUM REQUIRED CIRCUITS AND ARC FAULT PROTECTION
 WOULD BE REQUIRED.
 FBC 106.1.2, 106.3.5.1.2
 NEC 2005.
  
 14) NOTE: PLEASE INDICATE THE SIZE OF THE METER CAN.
 FBC 106.1.2.
  
 15) NOTE: PLANS INDICATE THERE IS GOING TO BE LANDSCAPE
 LIGHTING HOWEVER NO ELECTRICAL SITE PLANS ARE SUBMITTED
 SHOWING THE CIRCUITS, LIGHTING LOCATIONS ETC. PLEASE
 COMPLETE.
 FBC 106.1.2, 106.3.5.1.2
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2008-05-15 Cont ID  
Sent By rchokshi Date 2008-05-15 Time 11:22 Rev Time 0.00
Received By rchokshi Date 2008-05-15 Time 11:22 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2008-02-21 Cont ID  
Sent By rchokshi Date 2008-02-21 Time 13:59 Rev Time 0.00
Received By rchokshi Date 2008-02-21 Time 13:50 Sent To  
Notes
2008-02-21 13:59:37***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1.POLLUTION PREVENTION PLAN:SILT FENCE AROUND YOUR
 SITE SHOULDBE SHOWN ON THE DRAWING, BEFORE YOU START
 CONSTRUCTION.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-11-27 Cont ID  
Sent By rchokshi Date 2007-11-27 Time 13:17 Rev Time 0.00
Received By rchokshi Date 2007-11-27 Time 13:07 Sent To  
Notes
2007-11-27 13:17:07***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1 YOUR DUMPSTER DIMENSIONS ARE LESS THAN CITY
 STANDARDS. SO, YOU NEED AN APPROVAL FROM SANITATION
 DEPT.,NOTFROM ENGINEERING SERVICES DEPT.
 2. PLEASE SHOW TOTAL PERVIOUS,& IMPERVIOUS AREA FOR
 THIS PROJECT,OR SEPARATELAKE,SIDEWALK,
 PARKING,BUILDING AREA ETC.
 3. POLLUTION PREVENTION PLAN:SILT FENCE AROUND YOUR
 SITE SHOULDBE SHOWN ON THE DRAWING IF YOU ARE
 REPAIRING PARKING LOT AND OUTSIDE OF THE BUILDING.
 PLEASE SHOW SILT FENCE DETAILS. HEIGHT OF THE SILT
 FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 4. FOR YOUR INFO: IF YOU ARE REPAIRING ORPUTTING ANY
 NEWCURB, SIDEWALK, ENTRANCE APPROACHES OUTSIDE OF
 YOUR PROPERTY, YOU MUST NEED A CITY'S RIGHT OF WAY
 APPROVAL FROM WINDEL PALMER 494-1040, 45TH STREET
 ENGINEERING
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By rchokshi Date 2007-09-11 Time 15:44 Rev Time 0.00
Received By rchokshi Date 2007-09-11 Time 15:33 Sent To  
Notes
2007-09-11 15:44:30***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1.PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, SIDEWALK SLOPE,DRIVEWAY, APPROACH,
 PARKINGS, HANDICAP PARKINGS, DUMPSTER ENCLOSURE, YOU
 CAN GET A C D FROM 1000, 45 STREET FOR ALL THESE CITY
 STANDARDS NOTES. PHONE# 494-1040
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB,LOCATION MUST BE ACCESSIBLE
 FOR CITY PICKUP TRUCK.
 3. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT,
 LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE
 THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED
 IN STORM WATER QUALITY CALCULATIONS.
 4.PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES.PLEASE SHOW CALCULATION
 FOR EXFILTRATION TRENCHES IN WATER QUALITY CALS.
 PLEASE SHOW DRY DETENTION/WET DETENTION AREAS IN STORM
 WATER CALS.WHERE STORM WATER GOES??
 5. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 6.PLEASE PROVIDE A COPY OF STORM WATER QUALITY
 CALCULATIONS.STORM WATER CALS MUST BE APPROVED FROM
 100045TH STREET ENGINEERING SERVICES.
 7. POLLUTION PREVENTION PLAN: SILT FENCE AROUND YOUR
 SITE MUST BE SHOWN ON THE DRAWING. PLEASE SHOW SILT
 FENCE DETAILS. HEIGHT OF THE SILTFENCE SHOULD BE HIGH
 ENOUGH PER FDEP TO STOP DUST & PARTICLES.
 8. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-11-17 Cont ID  
Sent By mawillia Date 2008-11-17 Time 15:19 Rev Time 0.00
Received By mawillia Date 2008-11-17 Time 15:00 Sent To  
Notes
2008-11-17 15:18:49***** REVISION #4, DATED 10/08/08, APPROVED*****
  
 REVISED PLAN SHEET A-2 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-06-13 Cont ID  
Sent By mawillia Date 2008-06-13 Time 12:06 Rev Time 0.00
Received By mawillia Date 2008-06-13 Time 11:57 Sent To  
Notes
2008-06-13 12:06:27*****APPROVED*****
  
 PLAN SHEETS A-2, A-3, AND A-4 WERE PREVIOUSLY
 FIRE-STAMPED; SHEET E-1 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2008-05-19 Cont ID  
Sent By mawillia Date 2008-05-19 Time 12:02 Rev Time 0.00
Received By mawillia Date 2008-05-19 Time 11:45 Sent To  
Notes
2008-05-19 12:00:10*****PROVISO*****
  
 PLAN SHEETS A-2, A-3, AND A-4 WERE STAMPED, INITIALED,
 AND DATED; HOWEVER, SHEET E-1 TO BE FIRE-STAMPED WHEN
 THE ELECTRICAL REVIEW HAS BEEN SATISFIED,
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-02-27 Cont ID  
Sent By mawillia Date 2008-02-27 Time 15:32 Rev Time 0.00
Received By mawillia Date 2008-02-27 Time 15:14 Sent To  
Notes
2008-02-27 15:24:46*****PROVISO*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 ALL THE OTHER REVIEWERS HAVE BEEN SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-26 Cont ID  
Sent By mawillia Date 2007-11-26 Time 12:17 Rev Time 0.00
Received By mawillia Date 2007-11-26 Time 11:43 Sent To  
Notes
2007-11-26 12:16:10*****PROVISO*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 ALL THE OTHER REVIEWERS HAVE BEEN SATISFIED AND THE
 FOLLOWING COMMENT FROM THE PREVIOUS FIRE PLAN REVIEW
 HAVE BEEN ADDRESSED:
  
 08.THE EXISTING/REMAINING EXIT STAIR INSTALLATION AND
 DISCHARGE OCCURS ON WHICH LEGAL PROPERTY 740 BELVEDERE
 OR 736 BELVEDERE (ADULT ENTERTAINMENT CLUB).PLEASE
 PROVIDE A LEGAL SURVEY. THIS MAY BE ACCOMPLISHED BY
 ADDRESSINGZONING COMMENT# 5
  
  
  
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-18 Cont ID  
Sent By mawillia Date 2007-09-18 Time 18:34 Rev Time 0.00
Received By mawillia Date 2007-09-18 Time 17:06 Sent To  
Notes
2007-09-18 18:34:05*****DENIED*****
  
  
 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL CDOMPLY WITH NFPA 241.
  
 03.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 BELVEDERE ROAD, DISPLAY THE NUMERICAL ADDRESS ON THE
 BUILDING.AS PER WEST PALM BEACH CODE, THE ADDRESS
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.
  
 04.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
 SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF CLASS I
 OR CLASS II.
  
 05.PROVIDE A LIFE SAFETY PLAN SHOWING THE TRAVEL
 DISTANCE TO THE EXITS.THE LOCATION OF THE 2A:10BC
 FIRE EXTINGUISHER(S) WHICH SATIFIES THE 75' TRAVEL
 DISTANCE CAN ALSO BE INCLUDED.
  
 06.ALL FIRE RATED DOORS AND FIRE RATED WINDOWS SHALL
 COMPLY WITH NFPA 80.
  
 07.VERIFY/SUBMIT THE PRESCRIPTIVE STRENGHT FOR THE
 HANDRAIL/GUARDRAIL FOR THE EXISTING/REMAINING EXIT
 STAIR AS CODE COMPLIANT.
  
 08.THE EXISTING/REMAINING EXIT STAIR INSTALLATION AND
 DISCHARGE OCCURS ON WHICH LEGAL PROPERTY 740 BELVEDERE
 OR 736 BELVEDERE (ADULT ENTERTAINMENT CLUB).PLEASE
 PROVIDE A LEGAL SURVEY.
  
 09.SPECIFY THE HAZARD OF THE CONTENTS OF THE STORAGE
 ROOM IN TERMS OF LOW, ORDINARY, OR HIGH.
  
 10.PLEASE PROVIDE THE CRITERIA/SPECIFICATIONS FOR THE
 PROPOSED SPIRAL STAIRS COMPLYING WITH 7.2.2.2.3 OF THE
 LIFE SAFETY CODE -NFPA 101.
  
 11.COMMERCIAL COOKING EQUIPMENT SHALL BE IN
 ACCORDANCE WITH NFPA 96 - 2001 EDITION.SEPARATE PLANS
 AND PERMIT WILL BE REQUIRED FOR THE BOTH THE
 INSTALLATION OF THE COOKING HOOD AND THE COOKING HOOD'S
 SUPPRESSION SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 7 Status P Date 2008-11-24 Cont ID  
Sent By kstevens Date 2008-11-24 Time 15:02 Rev Time 0.00
Received By kstevens Date 2008-11-24 Time 15:02 Sent To M
Notes
2008-11-24 15:03:16GAS REVISIONS OK -- SHTS MP-1 & MP-2

Review Stop G GAS REVIEW
Rev No 6 Status F Date 2008-11-24 Cont ID  
Sent By kstevens Date 2008-11-24 Time 14:59 Rev Time 0.00
Received By kstevens Date 2008-11-19 Time 16:57 Sent To  
Notes
2008-11-24 15:02:36REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. -- REVISED RISER DIAGARM DOES NOT
 REFLECT THE FLOOR PLAN. FLOOR PLAN
 SHOWS THE GAS LINE INTO THE BUILDING AND AT THE FIRST
 RISER SHOWS NO PIPING TO THE RANGE, FRYERS ETC., BUT
 THE RISER DIAGRAM SHOWS A LINE BACK TO THE RANGE,
 FRYERS ETC. PLEASE CORRELATE.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- NEW RISER ADDITION
 SHOWS THE MOST REMOTE OUTLET AT 65 FEET. PLEASE CHANGE
 INFORMATION.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -- THE PIPE SIZES
 ARE NOT CORRECT. 2" PIPE IS REQUIRED UP TO THE TEE PAST
 THE SHUT OFF VALVE AND THE EMERGENCY SHUT OFF VALVE.
 MINIMUM 1-1/4" IS REQUIRED UP TO THE DEEP FRYER. 1" IS
 REQUIRED UP TO THE SIMMERING COOKER. 1-1/4" IS REQUIRED
 TO THE WATER HEATER. 1" IS REQUIRED TO THE SINGLE RACK
 OVEN AND THE MINI RACK OVENS. PLEASE SHOW ALL CORRECT
 PIPE SIZES. TABLE 402.4(2).
  
 4. GAS PIPING SHALL BE SLEEVED AS IT ENTERS THE
 BUILDING. SECTION 404.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2008-11-04 Cont ID  
Sent By kstevens Date 2008-11-04 Time 11:49 Rev Time 0.00
Received By kstevens Date 2008-11-04 Time 11:49 Sent To  
Notes
2008-11-04 12:05:49REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. -- REVISED RISER DIAGARM DOES NOT
 REFLECT THE FLOOR PLAN. FLOOR PLAN
 SHOWS THE GAS LINE INTO THE BUILDING AND AT THE FIRST
 RISER SHOWS NO PIPING TO THE RANGE, FRYERS ETC., BUT
 THE RISER DIAGRAM SHOWS A LINE BACK TO THE RANGE,
 FRYERS ETC. PLEASE CORRELATE.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- NEW RISER ADDITION
 SHOWS THE MOST REMOTE OUTLET AT 65 FEET. PLEASE CHANGE
 INFORMATION.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -- THE PIPE SIZES
 ARE NOT CORRECT. 2" PIPE IS REQUIRED UP TO THE TEE PAST
 THE SHUT OFF VALVE AND THE EMERGENCY SHUT OFF VALVE.
 MINIMUM 1-1/4" IS REQUIRED UP TO THE DEEP FRYER. 1" IS
 REQUIRED UP TO THE SIMMERING COOKER. 1-1/4" IS REQUIRED
 TO THE WATER HEATER. 1" IS REQUIRED TO THE SINGLE RACK
 OVEN AND THE MINI RACK OVENS. PLEASE SHOW ALL CORRECT
 PIPE SIZES. TABLE 402.4(2).
  
 4. GAS PIPING SHALL BE SLEEVED AS IT ENTERS THE
 BUILDING. SECTION 404.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2008-06-24 Cont ID  
Sent By mperson Date 2008-06-24 Time 14:51 Rev Time 0.00
Received By mperson Date 2008-06-24 Time 14:51 Sent To  
Notes
2008-06-24 14:55:01****************PROVISO****************
 PER FBC-2004 FUEL GAS TABLE 402.4(2) THE GAS PIPE FOR
 THE 250,000 BTU WATER HEATER SHALL BE 1".
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-05-16 Cont ID  
Sent By kstevens Date 2008-05-16 Time 11:21 Rev Time 0.00
Received By kstevens Date 2008-05-15 Time 15:50 Sent To  
Notes
2008-05-16 11:22:57PASSED/PROVISO
  
 1" PIPE REQUIRED FOR THE MINI RACK OVEN AND 1" REQUIRED
 FOR THE SINGLE RACK OVEN.--REVISIONS REQUIRED.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-02-25 Cont ID  
Sent By kstevens Date 2008-02-25 Time 14:09 Rev Time 0.00
Received By kstevens Date 2008-02-25 Time 14:08 Sent To  
Notes
2008-02-25 14:10:54DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ******FROM PREVIOUS REVIEW:
  
 ********NEW COMMENTS**********
 (MISSED THE GAS REVIEW THE FIRST TIME THROUGH)
  
 1B. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. RISER DOES NOT SHOW THE CUT LENGTH
 SECTIONS, NOR DOES IT REFLECT THE FLOOR PLAN.
 ******RESPONSE NOTED, BUT THE RISER STILL DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES THE RISER SHOW ALL THE
 CUT LENGTH SECTIONS. SEE THE SECTIONS THAT COME OFF THE
 METER VERTICALLY, TURN HORIZONTAL, DROP DOWN
 UNDERGROUND THEN TURN HORIZONTAL. ALSO THE SECTIONS OF
 PIPE THAT TURNS TOWARD THE BUILDING, UP PAST THE SHUT
 OFF VALVE, HORIZONTALL, THEN DROPS DOWN TO 4 FEET ABOVE
 THE FLOOR FOR THE KITCHEN APPLIANCES. ALSO SEE THE CUT
 SECTIONS OFF THE MAIN TO THE DOUBLE RACH OVEN AND THE
 CUT SECTIONS TO THE WATER HEATER.
  
 B. OK
 C. OK
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN
 COMMENT A IS SUBMITTED).
 ******RESPONSE NOTED, BUT AS INDICATED IN THE LAST
 REVIEW, THIS WILL BE VERIFIED WHEN ALL CUT SECTIONS ARE
 GIVEN FOR COMMENT "A".
  
 F. OK
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ******RESPONSE NOTED, BUT NO MANUFACTURE SHEETS WERE
 SUBMITTED FOR THE STEAMER OR THE WATER HEATER.
  
 H. N/A
 I. N/A
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ******RESPONSE NOTED, BUT AN EMERGENCY HOOD SHUT DOWN
 SHUT OFF VALVE IS REQUIRED AS WELL AS A UNION EITHER
 BETEWEEN THE SHUT OFF VALVE AND THE EMERGNECY HOOD SHUT
 OFF VALVE OR DOWN STREAM OF THE EMERGENCY SHUT OFF
 VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-12-05 Cont ID  
Sent By kstevens Date 2007-12-05 Time 15:43 Rev Time 0.00
Received By kstevens Date 2007-12-05 Time 15:43 Sent To  
Notes
2007-12-05 15:46:28DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. RISER DOES NOT SHOW THE CUT LENGTH
 SECTIONS, NOR DOES IT REFLECT THE FLOOR PLAN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN
 COMMENT A IS SUBMITTED).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE,IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-01-20 Cont ID  
Sent By adarroug Date 2009-01-20 Time 13:44 Rev Time 0.00
Received By adarroug Date 2009-01-20 Time 13:44 Sent To M
Notes
2009-01-20 13:44:53TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-12-17 Cont ID  
Sent By adarroug Date 2008-12-17 Time 11:05 Rev Time 0.00
Received By adarroug Date 2008-12-17 Time 11:05 Sent To Z
Notes
2008-12-17 11:06:03TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-11-24 Cont ID  
Sent By adarroug Date 2008-11-24 Time 10:51 Rev Time 0.00
Received By adarroug Date 2008-11-24 Time 10:51 Sent To  
Notes
2008-11-24 10:54:54TO "COMM" BD#13

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-11-04 Cont ID  
Sent By adarroug Date 2008-11-04 Time 16:03 Rev Time 0.00
Received By adarroug Date 2008-11-04 Time 16:03 Sent To  
Notes
2008-11-04 16:09:56TO "COMM" BD#21

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-10-22 Cont ID  
Sent By adarroug Date 2008-10-22 Time 08:53 Rev Time 0.00
Received By adarroug Date 2008-10-22 Time 08:53 Sent To B
Notes
2008-10-22 08:54:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-10-20 Cont ID  
Sent By adarroug Date 2008-10-20 Time 11:05 Rev Time 0.00
Received By adarroug Date 2008-10-20 Time 11:05 Sent To  
Notes
2008-10-21 13:43:43TO "COMM" BD#42
2008-10-20 11:05:31WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-08-25 Cont ID  
Sent By tgordon Date 2008-08-25 Time 11:39 Rev Time 0.00
Received By tgordon Date 2008-08-25 Time 11:39 Sent To B
Notes
2008-08-25 11:40:33TO BUILD. SAMANTHA H.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-08-20 Cont ID  
Sent By adarroug Date 2008-08-20 Time 16:16 Rev Time 0.00
Received By adarroug Date 2008-08-20 Time 16:16 Sent To B
Notes
2008-08-20 16:17:13TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 08:33 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 08:33 Sent To P
Notes
2008-07-11 08:33:44TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 12:23 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 12:23 Sent To  
Notes
2008-05-30 12:26:23TO "COMM" BD#59

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-01 Cont ID  
Sent By adarroug Date 2008-05-01 Time 16:09 Rev Time 0.00
Received By adarroug Date 2008-05-01 Time 16:09 Sent To  
Notes
2008-05-01 16:13:21TO "COMM" BD#37

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 14:55 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 14:55 Sent To  
Notes
2008-01-29 14:55:56TO "COMM" BD#54

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-22 Cont ID  
Sent By adarroug Date 2007-10-22 Time 10:39 Rev Time 0.00
Received By adarroug Date 2007-10-22 Time 10:39 Sent To  
Notes
2007-11-07 13:07:33TO "COMM" BD#60
2007-10-22 10:39:15WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-18 Cont ID  
Sent By mawillia Date 2007-09-18 Time 17:06 Rev Time 0.00
Received By mawillia Date 2007-07-31 Time 15:25 Sent To  
Notes
2007-08-14 14:45:59TO "COMM" BD#52
2007-07-31 15:27:08WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-12-18 Cont ID  
Sent By rkussner Date 2008-12-18 Time 13:30 Rev Time 0.00
Received By rkussner Date 2008-12-18 Time 13:30 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2009-02-03 Cont ID  
Sent By hmoser Date 2009-02-03 Time 10:20 Rev Time 0.00
Received By hmoser Date 2009-02-03 Time 10:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-11-24 Cont ID  
Sent By rregueir Date 2008-11-24 Time 19:45 Rev Time 0.00
Received By rregueir Date 2008-11-24 Time 19:45 Sent To PC
Notes
2008-11-24 19:45:21REV MP-1 AND MP-2

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-11-15 Cont ID  
Sent By rregueir Date 2008-11-15 Time 13:28 Rev Time 0.00
Received By rregueir Date 2008-11-15 Time 13:23 Sent To  
Notes
2008-11-15 13:24:11MECH REVISION #6 OK. PLANS CANNOT BE STAMPED UNTIL
 PLUMBING REVIEW HAS PASSED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-19 Cont ID  
Sent By rregueir Date 2008-05-19 Time 09:48 Rev Time 0.00
Received By rregueir Date 2008-05-19 Time 09:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-16 Cont ID  
Sent By rregueir Date 2008-02-16 Time 12:56 Rev Time 0.00
Received By rregueir Date 2008-02-16 Time 11:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By rregueir Date 2007-12-03 Time 10:49 Rev Time 0.00
Received By rregueir Date 2007-12-01 Time 15:51 Sent To  
Notes
2007-12-03 10:49:46REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. PREVIOUS COMMENT REQUESTED OUTSIDE AIR CALCULATIONS
 FOR ALL AREAS, NOT JUST CUSTOMER AREA. KITCHEN AREA AND
 2ND FLOOR AREA CALCULATIONS ARE ALSO REQUIRED.
 NOTE: 2ND FLOOR AREA IS PART OF LEVEL 2 ALTERATION AS
 THERE ARE WINDOW OPENINGS BEING CLOSED. LEVEL 2
 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE
 ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW PER FBC,
 EB 304.1. SHOW HOW OUTSIDE AIR REQUIREMENTS FOR THESE
 AREAS ARE TO BE MET IN ACCORDANCE WITH FBC, M 403.3.
  
 4. OK. VENTING INSTALLATION INSTRUCTIONS REQUIRED ON
 SITE FOR INSPECTION.
  
 5. RUSKIN SUBMITTAL FOUND IN PACKAGE. PRODUCT APPROVAL
 OR NOA WAS NOT PROVIDED IN PACKAGE. THE NOA FOR THIS
 LOUVER WAS PRINTED BY THIS OFFICE AND ADDED TO THE
 PACKAGE. THIS WILL NOT BE DONE IN THE FUTURE. THIS
 INFORMATION SHALL BE PROVIDED BY THE DESIGNER OR
 CONTRACTOR.
  
 6. OK
  
 7. OK
  
 8. OK. SEE COMMENT 3 ABOVE REGARDING 2ND FLOOR.
  
 NEW COMMENTS:
 THE FOLLOWING COMMENTS HAVE BEEN GENERATED AS A RESULT
 OF CHANGES TO THE PLANS AND/OR NEW INFORMATION WHICH
 WAS NOT PART OF PREVIOUS SUBMITTAL.
  
 A. DETAIL #2 ON MP-1 SHOWS TWO ROOF CONDENSERS SITTING
 ON CONCRETE PADS. HAS THERE BEEN AN ENGINEERING
 ANALYSIS OF THE ROOF FRAMING TO VERIFY THAT IT IS
 SUITABLE FOR THE ADDITIONAL DEAD LOADS OF THE EQUIPMENT
 AND SIZEABLE 4 INCH THICK CONCRETE PADS?
  
 B. THERE IS NO DETAIL FOR HOW THE CONDENSING UNITS ARE
 TO BE FASTENED TO THE CONCRETE PADS TO MEET 140 MPH
 WIND LOADS IN ACCORDANCE WITH FBC, M 301.13 AND FBC
 1609. PLEASE NOTE THAT THE PRESCRIPTIVE METHOD SHOWN IN
 FBC, M 301.13.1 IS FOR R-3 OCCUPANCY ONLY. ENGINEERING
 IS REQUIRED.
  
 C. PG S-3 SHOWS A CONNECTION DETAIL FOR ROOFTOP
 CONDENSERS WHICH IS IN CONFLICT WITH DETAIL #2 ON MP-1.
 WHICH METHOD IS TO BE USED? ALSO, DETAIL ON S-3 REFERS
 TO A PRODUCT APPROVAL FOR AN A/C STAND. NO SUCH PRODUCT
 APPROVAL WAS FOUND IN THE SUBMITTAL PACKAGE FOR THIS
 PERMIT. DETERMINE WHICH METHOD IS TO BE USED AND
 PROVIDE ALL REQUIRED DOCUMENTATION TO SHOW COMPLIANCE
 WITH THESE SECTIONS.
  
 NOTE: DOCUMENTATION FOR TYPE I KITCHEN HOOD AND DUCT
 SYSTEM HAVE NOT BEEN PROVIDED. FULL DOCUMENTATION FOR
 HOOD PERMIT WILL BE REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-21 Cont ID  
Sent By rregueir Date 2007-08-21 Time 16:38 Rev Time 0.00
Received By rregueir Date 2007-08-21 Time 13:16 Sent To  
Notes
2007-08-21 16:37:55REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. A LEVEL OF ALTERATION IS TO BE DECLARED IN
 ACCORDANCE WITH FBC,EB 301.5. INCLUDE THIS INFORMATION
 IN THE BUILDING DATA ON A-1. THIS APPEARS TO BE A LEVEL
 3 ALTERATION.
  
 2. THIS BUILDING IS CONSIDERED A RENOVATION UNDER THE
 DEFINITION OF A RENOVATION IN FBC 13-202 AS THE VALUE
 OF THE PROPOSED IMPROVEMENT IS ABOVE THE THRESHOLD OF
 30% OF THE STRUCTURES VALUE OF $220,746. SEE PROPERTY
 APPRAISER DATA (ATTACHED). RENOVATED BUILDINGS SHALL
 COMPLY WITH THE PRESCRIPTIVE REQUIREMENTS CONTAINED IN
 FORM 400C OR WITH METHOD B OF SUBCHAPTER 13-4 FOR
 INSULATION, HVAC SYSTEMS, LIGHTING, WATER HEATING
 SYSTEMS AND EXTERIOR ENVELOPE COMPONENTS BEING
 RETROFITTED OR REPLACED. FBC 13-101.1.3. PROVIDE FORM
 400C OR 400B TO SHOW COMPLIANCE. FORM 400A IS NOT AN
 OPTION FOR THIS TYPE OF PROJECT.
  
 3. ALL VENTILATION REQUIREMENTS OF FBC,M CHAPTER 4 AND
 THE EXHAUST REQUIREMENTS OF FBC,M CHAPTER 5 SHALL BE
 MET PER FBC, EB 609.1. PROVIDE OUTDOOR AIR CALCULATIONS
 SHOWING OCCUPANCY CLASSIFICATION, OCCUPANT LOAD AND CFM
 OF OUTDOOR AIR REQUIRED/PROVIDED FOR ALL AREAS PER
 FBC,M TABLE 403.3.
  
 4. PROVIDE A TYPE II COMMERCIAL KITCHEN EXHAUST HOOD
 OVER THE OVENS PER FBC,M 507.2.
  
 5. OUTDOOR WALL LOUVERS ARE SUBJECT TO FAC RULE 9B-72
 AND AS SUCH. PRODUCT APPROVAL IS REQUIRED. PROVIDE
 SPECIFIC PRODUCT APPROVAL FOR THE MANUFACTURER AND
 MODEL OF LOUVERS TO BE USED. FOR MORE INFORMATION ON
 THE FLORIDA PRODUCT APPROVAL SYSTEM PLEASE VISIT:
 WWW.FLORIDABUILDING.ORG
  
 6. SHOW ON PLANS THE MEANS AND LOCATION OF CONDENSATE
 DISPOSAL. THE LOCATION SHALL COMPLY WITH FBC,M 307.2.1
 AND FBC 1503.6. IT SHALL NOT DISCHARGE ONTO ASPHALT AS
 DESCRIBED IN PLUMBING GENERAL NOTE #18.
  
 7. SHOW MEANS OF AUXILIARY OR SECONDARY DRAIN
 PROTECTION IN ACCORDANCE WITH FBC,M 307.2.3. A WATER
 LEVEL DETECTION DEVICE I(FLOAT SWITCH) N THE SECONDARY
 DRAIN PAN WILL MET THIS REQUIREMENT.
  
 8. SECOND FLOOR HVAC PLAN STATES "SEE NOTE #1" BUT NO
 NOTE COULD BE FOUND RELATED TO THIS AREA. PLEASE
 CLARIFY.
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE HOODS, HOOD
 SUPPRESSION SYSTEM(S) AND THE WALK-IN COOLERS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 9 Status P Date 2008-11-24 Cont ID  
Sent By kstevens Date 2008-11-24 Time 15:03 Rev Time 0.00
Received By kstevens Date 2008-11-24 Time 15:03 Sent To M
Notes
2008-11-24 15:04:21PLUMBING REVISIONS OK -- SHTS MP-1 & MP-2.

Review Stop P PLUMBING
Rev No 8 Status F Date 2008-11-24 Cont ID  
Sent By kstevens Date 2008-11-24 Time 14:57 Rev Time 0.00
Received By kstevens Date 2008-11-19 Time 16:57 Sent To  
Notes
2008-11-24 14:57:55REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. SHT MP-1 REVISION #5 INDICATED IN THE REVISION INDEX
 HAS NOT BEEN FOUND ON THE FLOOR PLAN. (THIS WAS A
 COMMENT FROM THE PREVIOUS REVISION SUBMITTED). SECTION
 106.1.3. PLEASE INDICATE WHERE REVISION #5 IS ON THE
 FLOOR PLAN. SHOW WITH A CLOUD AND NUMBERED TRIANGLE.
  
 2. SHT MP-1 MANY CHANGES DETECTED ON THE SHEET WITH NO
 CLOUDS OR NUMBERED TRIANGLES. ALL REVISIONS SHALL BE
 INDICATED WITH CLOUDS AND NUMBERED TRIANGLES. IF THERE
 ARE MANY REVISIONS THEN CLOUD THE COMPLETE FLOOR PLAN,
 BUT PLEASE INDICATE ALL REVISIONS. SECTION 106.1.3.
  
 3. SHT MP-1 INDICATE IF THE 3 COMPARTMENT OR THE 2
 COMPARTMENT SINKS ARE UTILIZIED FOR STORAGE,
 PREPARATION OR HANDLING OF FOOD. IF SO THE SINK/SINKS
 SHALL DISCHARGE THROUGH AN INDIRECT WASTE PIPE BY MEANS
 OF AN AIR GAP. SECTION 802.1.1. SECTION 106.1.2.
  
 4. SHT MP-2 MANY REVISIONS/CHANGES SHOWN ON THE RISER
 DIAGRAMS ARE NOT CLOUDED OR NUMBERED. ALL REVISIONS
 SHALL BE INDICATED WITH CLOUDS AND NUMBERED TRIANGLES.
 SECTION 106.1.3.
  
 5. SHT MP-2 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN FOR THE SUPPLY PIPING TO THE DRINKING
 FOUNTAIN. THE FLOOR PLAN SHOWS THE WATER SUPPLY LOCATED
 THRU THE CABINETS, BUT THE RISER DIAGRAM SHOWS A DROP
 FROM THE CEILING ON THE RISER AT THE DRINKING FOUNTAIN.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1.
  
 6. SHT MP-2 WATER RISER DIAGRAM. ALL HOSE BIBBS SHALL
 HAVE A SHUT OFF VALVE ON THE SUPPLY LINE TO THE HOSE
 BIBBS. SECTION 606.2(2).
  
 7. SHT MP-2 SANITARY/GREASE RISER DIAGRAM. THE BYPASS
 LINE AT THE GREASE INTERCEPTOR IS NOT APPROVED AND DOES
 NOT REFLECT THE FLOOR PLAN. ARTICLE III SECTION
 90-124(7) & SECTION 106.1.1.
  
 8. SHT MP-2 SANITARY/GREASE RISER DIAGRAM. THE 2
 COMPARTMENT SINK DRAIN LINE THAT USED TO CONNECT TO THE
 3 COMPARTMENT SINK IS NOW A DEAD END. DEAD ENDS ARE NOT
 APPROVED. PLEASE DELETE OR USE FOR ONE SIDE OF THE 2
 COMPARTMENT SINK SO IT CAN DRAIN INTO THE DRAIN LINE
 AND THE AAV REINSTALLED AT THE TOP OF THE LINE. SECTION
 704.5.
  
 9. SHT MP-2 SANITARY/GREASE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AT THE 2 COMPARTMENT SINK. THE
 FLOOR PLAN DOES NOT SHOW THE WASTE ARMS TO THE SINK
 TRAPS.
  
 (SEE COMMENTS FOR GAS REVIEW IN GAS STOP).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 7 Status F Date 2008-11-04 Cont ID  
Sent By kstevens Date 2008-11-04 Time 10:58 Rev Time 0.00
Received By kstevens Date 2008-11-03 Time 16:57 Sent To  
Notes
2008-11-04 11:48:57REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. SHT MP-1 REVISION #5 INDICATED IN THE REVISION INDEX
 HAS NOT BEEN FOUND ON THE FLOOR PLAN. (THIS WAS A
 COMMENT FROM THE PREVIOUS REVISION SUBMITTED). SECTION
 106.1.3. PLEASE INDICATE WHERE REVISION #5 IS ON THE
 FLOOR PLAN. SHOW WITH A CLOUD AND NUMBERED TRIANGLE.
  
 2. SHT MP-1 MANY CHANGES DETECTED ON THE SHEET WITH NO
 CLOUDS OR NUMBERED TRIANGLES. ALL REVISIONS SHALL BE
 INDICATED WITH CLOUDS AND NUMBERED TRIANGLES. IF THERE
 ARE MANY REVISIONS THEN CLOUD THE COMPLETE FLOOR PLAN,
 BUT PLEASE INDICATE ALL REVISIONS. SECTION 106.1.3.
  
 3. SHT MP-1 INDICATE IF THE 3 COMPARTMENT OR THE 2
 COMPARTMENT SINKS ARE UTILIZIED FOR STORAGE,
 PREPARATION OR HANDLING OF FOOD. IF SO THE SINK/SINKS
 SHALL DISCHARGE THROUGH AN INDIRECT WASTE PIPE BY MEANS
 OF AN AIR GAP. SECTION 802.1.1. SECTION 106.1.2.
  
 4. SHT MP-2 MANY REVISIONS/CHANGES SHOWN ON THE RISER
 DIAGRAMS ARE NOT CLOUDED OR NUMBERED. ALL REVISIONS
 SHALL BE INDICATED WITH CLOUDS AND NUMBERED TRIANGLES.
 SECTION 106.1.3.
  
 5. SHT MP-2 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN FOR THE SUPPLY PIPING TO THE DRINKING
 FOUNTAIN. THE FLOOR PLAN SHOWS THE WATER SUPPLY LOCATED
 THRU THE CABINETS, BUT THE RISER DIAGRAM SHOWS A DROP
 FROM THE CEILING ON THE RISER AT THE DRINKING FOUNTAIN.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1.
  
 6. SHT MP-2 WATER RISER DIAGRAM. ALL HOSE BIBBS SHALL
 HAVE A SHUT OFF VALVE ON THE SUPPLY LINE TO THE HOSE
 BIBBS. SECTION 606.2(2).
  
 7. SHT MP-2 SANITARY/GREASE RISER DIAGRAM. THE BYPASS
 LINE AT THE GREASE INTERCEPTOR IS NOT APPROVED AND DOES
 NOT REFLECT THE FLOOR PLAN. ARTICLE III SECTION
 90-124(7) & SECTION 106.1.1.
  
 8. SHT MP-2 SANITARY/GREASE RISER DIAGRAM. THE 2
 COMPARTMENT SINK DRAIN LINE THAT USED TO CONNECT TO THE
 3 COMPARTMENT SINK IS NOW A DEAD END. DEAD ENDS ARE NOT
 APPROVED. PLEASE DELETE OR USE FOR ONE SIDE OF THE 2
 COMPARTMENT SINK SO IT CAN DRAIN INTO THE DRAIN LINE
 AND THE AAV REINSTALLED AT THE TOP OF THE LINE. SECTION
 704.5.
  
 9. SHT MP-2 SANITARY/GREASE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AT THE 2 COMPARTMENT SINK. THE
 FLOOR PLAN DOES NOT SHOW THE WASTE ARMS TO THE SINK
 TRAPS.
  
 (SEE COMMENTS FOR GAS REVIEW IN GAS STOP).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-07-23 Cont ID  
Sent By kstevens Date 2008-07-23 Time 14:59 Rev Time 0.00
Received By kstevens Date 2008-07-23 Time 14:59 Sent To  
Notes
2008-07-23 15:03:28REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FLORIDA STATUTES
 FBC-2004 CHAPTER 1
  
 1. SHT MP-1 REVISIONS TO A PLAN SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER SHALL BE SIGNED AND SEALED BY THE
 ENGINEER OF RECORD. FS 471.--REVISION #5 IS NOT
 CLOUDED NOR INDICATED WITH A REVISION NUMBER.--ANY
 CHANGE TO A SANITARY SYSTEM INDICATED ON THE FLOOR PLAN
 SHALL BE REFLECTED WITH A REVISION TO THE SANITARY
 RISER DIAGRAM AS WELL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-06-24 Cont ID  
Sent By mperson Date 2008-06-24 Time 14:50 Rev Time 0.00
Received By mperson Date 2008-06-24 Time 14:50 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-05-16 Cont ID  
Sent By kstevens Date 2008-05-16 Time 11:21 Rev Time 0.00
Received By kstevens Date 2008-05-15 Time 15:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-02-25 Cont ID  
Sent By kstevens Date 2008-02-25 Time 13:51 Rev Time 0.00
Received By kstevens Date 2008-02-25 Time 13:51 Sent To  
Notes
2008-02-25 14:08:38DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT SHALL BE INDICATED IN THE TITLE
 BLOCK PER FAC 61G1-16.004(6) & FS 481.2055.
 ****RESPONSE NOTED, BUT DOES NOT ADDRESS THE COMMENT
 FOR THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT
 ON THE ARCHITECTURAL SHEETS.
 ******NO RESPONSE NOTED, BUT THE PRINTED NAME IS NOT
 SHOWN ON SHT A-4.
  
 2. OK
 3. OK
 4. OK
  
 5. SHT A-2DETAIL 1/A-2, THE TOILET ROOM SHALL BE
 ACCESSIBLE PER SECTION 806.1 OF THE EXISTING BUILDING
 CODE. SUBMIT DETAILS/ELEVATIONS SHOWING COMPLIANCE WITH
 SECTION 11-4.22 & ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT THE FOLLOWING HAS NOT BEEN
 ADDRESSED:
 ___FOR THE W/C:
 A. OK
 B. 11-4.16.5 FLUSH CONTROLS
 ******NO RESPONSE NOTED, NOT ADDRESSED.
 ___FOR THE URINAL:
 A. OK
 B. 11-4.18.4 FLUSH CONTROLS
 ******NO RESPONSE NOTED, NOT ADDRESSED.
 ___FOR THE LAV:
 A. OK
 B. OK
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
  
 ********NEW COMMENTS**********
 (MISSED THE GAS REVIEW THE FIRST TIME THROUGH)
  
 1B. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. RISER DOES NOT SHOW THE CUT LENGTH
 SECTIONS, NOR DOES IT REFLECT THE FLOOR PLAN.
 ******RESPONSE NOTED, BUT THE RISER STILL DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES THE RISER SHOW ALL THE
 CUT LENGTH SECTIONS. SEE THE SECTIONS THAT COME OFF THE
 METER VERTICALLY, TURN HORIZONTAL, DROP DOWN
 UNDERGROUND THEN TURN HORIZONTAL. ALSO THE SECTIONS OF
 PIPE THAT TURNS TOWARD THE BUILDING, UP PAST THE SHUT
 OFF VALVE, HORIZONTALL, THEN DROPS DOWN TO 4 FEET ABOVE
 THE FLOOR FOR THE KITCHEN APPLIANCES. ALSO SEE THE CUT
 SECTIONS OFF THE MAIN TO THE DOUBLE RACK OVEN AND THE
 CUT SECTIONS TO THE WATER HEATER.
  
 B. OK
 C. OK
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN
 COMMENT A IS SUBMITTED).
 ******RESPONSE NOTED, BUT AS INDICATED IN THE LAST
 REVIEW, THIS WILL BE VERIFIED WHEN ALL CUT SECTIONS ARE
 GIVEN FOR COMMENT "A".
  
 F. OK
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ******RESPONSE NOTED, BUT NO MANUFACTURE SHEETS WERE
 SUBMITTED FOR THE STEAMER OR THE WATER HEATER.
  
 H. N/A
 I. N/A
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ******RESPONSE NOTED, BUT AN EMERGENCY HOOD SHUT DOWN
 SHUT OFF VALVE IS REQUIRED AS WELL AS A UNION EITHER
 BETEWEEN THE SHUT OFF VALVE AND THE EMERGNECY HOOD SHUT
 OFF VALVE OR DOWN STREAM OF THE EMERGENCY SHUT OFF
 VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-05 Cont ID  
Sent By kstevens Date 2007-12-05 Time 15:12 Rev Time 0.00
Received By kstevens Date 2007-12-05 Time 15:12 Sent To  
Notes
2007-12-05 15:43:27DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT SHALL BE INDICATED IN THE TITLE
 BLOCK PER FAC 61G1-16.004(6) & FS 481.2055.
 ****RESPONSE NOTED, BUT DOES NOT ADDRESS THE COMMENT
 FOR THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT
 ON THE ARCHITECTURAL SHEETS.
  
 2. OK
  
 3. TABLE 403.1 REQUIRES A DRINKING FOUNTAIN. PLEASE
 INDICATE THE LOCATION OF THE DRINKING FOUNTAIN AND
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15
 AND ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ****RESPONSE NOTED, BUT SECTION 11-4.1.3(10)(A) HAS NOT
 BEEN ADDRESSED.
  
 4. OK
  
 5. SHT A-2DETAIL 1/A-2, THE TOILET ROOM SHALL BE
 ACCESSIBLE PER SECTION 806.1 OF THE EXISTING BUILDING
 CODE. SUBMIT DETAILS/ELEVATIONS SHOWING COMPLIANCE WITH
 SECTION 11-4.22 & ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT THE FOLLOWING HAS NOT BEEN
 ADDRESSED:
 ___FOR THE W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 ___FOR THE URINAL:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
 ___FOR THE LAV:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
 (NOTE: THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE).
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
  
 11. SHT MP-1 NOTES FOR GREASE INTERCEPTOR: NOTE 6.
 GREASE INTERCEPTORS ARE TO BE SIZED BY ENVIRONMENTAL
 COMPLIANCE SECTION OF THE UTILITY DEPT. PLEASE CONTACT
 RODNEY COMPO, (561) 822-2272, E-MAIL [email protected], OR
 CALVIN WILLIAMS, (561) 822-2284, E-MAIL
 [email protected]. THEIR FAX NUMBER IS (561) 822-2287.
 A WRITTEN VERIFICATION FROM ENVIRONMENTAL COMPLIANCE
 SHALL BE SUBMITTED WITH PLANS FOR GREASE INTERCEPTOR
 APPROVAL.
 ****RESPONSE NOTED, BUT NO WRITTEN DOCUMENTATION
 SUBMITTED.
  
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
  
 ********NEW COMMENTS**********
 (MISSED THE GAS REVIEW THE FIRST TIME THROUGH)
  
 1B. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. RISER DOES NOT SHOW THE CUT LENGTH
 SECTIONS, NOR DOES IT REFLECT THE FLOOR PLAN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN
 COMMENT A IS SUBMITTED).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,IDENTIFYING THE
 SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-07 Cont ID  
Sent By kstevens Date 2007-09-07 Time 14:48 Rev Time 0.00
Received By kstevens Date 2007-09-07 Time 14:48 Sent To  
Notes
2007-09-07 17:07:53DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT SHALL BE INDICATED IN THE TITLE
 BLOCK PER FAC 61G1-16.004(6) & FS 481.2055.
  
 2. SHT A-2 DETAIL 1/A-2 CUSTOMERS, PATRONS & VISITORS
 SHALL BE PROVIDED WITH PUBLIC TOILET FACILITIES IN
 STRUCTURES & TENANT SPACES INTENDED FOR PUBLIC
 UTILIZATION. PLEASE PROVIDE TOILET FACILITIES. SECTION
 403.6.
  
 3. TABLE 403.1 REQUIRES A DRINKING FOUNTAIN. PLEASE
 INDICATE THE LOCATION OF THE DRINKING FOUNTAIN AND
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15
 AND ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 4. INDICATE THE ALTERATION LEVEL PER SECTIONS 303, 304
 OR 305 OF THE EXISTING BUILDING CODE.
  
 5. SHT A-2DETAIL 1/A-2, THE TOILET ROOM SHALL BE
 ACCESSIBLE PER SECTION 806.1 OF THE EXISTING BUILDING
 CODE. SUBMIT DETAILS/ELEVATIONS SHOWING COMPLIANCE WITH
 SECTION 11-4.22 & ALL SUBSECTIONS.
  
 6. SHT A-2DETAIL 2/A-2 THE BATHROOM, (RM 201), SHALL
 BE ACCESSIBLE. PER SECTION 806.1 OF THE EXISTING
 BUILDING CODE. SUBMIT DETAILS/ELEVATIONS SHOWING
 COMPLIANCE WITH SECTION 11-4.23 AND ALL SUBSECTIONS.
  
 7. SUBMIT A ROOF DETAIL. SINCE THERE HAS BEEN ADDED
 VERTICAL WALLS AND ROOF AREA DRAINING ONTO THE ROOF
 FROM ABOVE, THE ROOF DRAINAGE REQUIREMENTS SHALL BE
 REVIEWED. SHOW THE LOCATIONS FOR ALL THE PRIMARY AND
 SECONDARY ROOF DRAINS AND INDICATE THE SIZE OF ALL
 DRAINS. INDICATE THE SLOPE OF THE ROOF TO THE ROOF
 DRAINS. SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE BEING
 DRAINED AT EACH ROOF DRAIN ALONG WITH 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS AS WELL AS ANY ROOF
 AREA THAT DRAINS ONTO THE ROOF FROM ABOVE FOR EACH
 AREA. SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS AND
 TABLES. SECTION 106.1.2.
  
 8. SHT A-4 FINISH SCHEDULE, ROOM 201 SHALL MEET THE
 REQUIREMENTS OF SECTION 1210.1 & 1210.2. PLEASE SHOW ON
 THE FINISH SCHEDULE.
  
 9. SHTS S-1 THRU S-4 THE ENGINEER SHALL LEGIBLY
 INDICATE THEIR ADDRESS AS WELL AS THE ADDRESS OF THE
 ENGINEERING BUSINESS IN THE TITLE BLOCKS. FAC
 61G15-23.002(2) & FS 471.025.
  
 10. SHT MP-1 NOTES FOR GREASE INTERCEPTOR: NOTE 3 PER
 SECTION 90-124(7)(F) GREASE INTERCEPTORS SHALL BE STEEL
 REINFORCED CONCRETE AND FIBERGLASS INTERCEPTORS ARE NOT
 APPROVED. PLEASE INDICATE ON PLANS.
  
 11. SHT MP-1 NOTES FOR GREASE INTERCEPTOR: NOTE 6.
 GREASE INTERCEPTORS ARE TO BE SIZED BY ENVIRONMENTAL
 COMPLIANCE SECTION OF THE UTILITY DEPT. PLEASE CONTACT
 RODNEY COMPO, (561) 822-2272, E-MAIL [email protected], OR
 CALVIN WILLIAMS, (561) 822-2284, E-MAIL
 [email protected]. THEIR FAX NUMBER IS (561) 822-2287.
 A WRITTEN VERIFICATION FROM ENVIRONMENTAL COMPLIANCE
 SHALL BE SUBMITTED WITH PLANS FOR GREASE INTERCEPTOR
 APPROVAL.
  
 12. NOTE: FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE
 INTERCEPTORS. PER SECTIONS 802.3 & 802.3.2.
  
 13. SHT MP-2 SANTITARY/GREASE ISOMETRIC RISER DIAGRAM.
 THE RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN, NOR
 DOES IT MEET CODE REQUIREMENTS.--2-WAY CLEANOUTS
 ARE REQUIRED AT THE INLET AND THE OUTLET OF THE GREASE
 INTERCEPTOR AS WELL AS NEAR THE JUNCTION OF THE
 BUILDING DRAIN & BUILDING SEWER AS THE LINE EXITS THE
 BUILDING.--A VENT IS REQUIRED FOR THE CAN WASH.--
 FLOOR DRAIN NOT APPROVED UNDER THE EXPRESS MACHINE #2,
 FLOOR SINK REQUIRED.--FLOOR SINK REQUIRED FOR THE 3
 COMPARTMENT SINK IN THE FOOD PREP AREA.--2" FLOOR
 DRAIN SHOWN BETWEEN THE EXISTING LAV AND THE 3
 COMPARTMENT SINK IS NOT SHOWN ON THE FLOOR PLAN.--
 FLOOR SINK IS REQUIRED AT THE ICE MAKER.--THE 4"
 FLOOR DRAIN SHOWN BY THE EXISTING W/C IN THE 2ND FLOOR
 BATHROOM DOES NOT CONNECT TOSANITARY PIPING, NOR IS
 IT SHOWN ON THE FLOOR PLAN.--THE PIPING TO THE
 TRENCH DRAIN AND THE DRAIN CONNECTION DO NOT REFLECT
 THE FLOOR PLAN.PLEASE MAKE SURE THE RISER DIAGRAM
 CORRELATES WITH THE FLOOR PLAN AND MEETS CODE
 REQUIREMENTS. SECTIONS 1006.1.1,708.3.5,901.2.1 &
 802.3, & UTILITY DEPT. STANDARDS.
  
 14. SHT MP-2 HOT & COLD RISER DIAGRAMS. HOT WATER &
 BACKFLOW PROTECTION REQUIRED TO SUPPLY THE CAN WASH.
 SECTIONS 414.1, 601.7, 608.13.1 THRU 608.13.6 &
 608.13.8.
  
 15. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION
 607.3.2. INDICATE METHOD ON THE WATER HEATER DETAIL.
  
 16. SHT MP-2 PLUMBING GENERAL NOTE #7, AIR CHAMBERS ARE
 NOT APPROVED. PLEASE DELETE FROM NOTE. SECTION 604.9.
 WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES, IN AN "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 6 Status P Date 2008-10-21 Cont ID  
Sent By adavila Date 2008-10-21 Time 17:40 Rev Time 0.00
Received By adavila Date 2008-10-21 Time 17:40 Sent To  
Notes
2008-10-21 17:42:42PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 PROVISO GROUND COVER TO BE PLANTED UNDER THE STAIRWELL
 SHALL BE FOXTAIL FERN.
  
 PROVISO NEW LANDSCAPE AREAS (REVISION NO. 5) SHALL BE
 PLANTED PER ATTACHED LETTER DATED 10-15-2008. A REVISED
 LANDSCAPE PLAN SHOWING THE APPROVED CHANGES OF THIS
 SITE PLAN SHALL BE SUBMITTED, AND APPROVED BY THE CITY
 PRIOR TO C.O.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
  

Review Stop Z ZONING
Rev No 5 Status P Date 2008-06-04 Cont ID  
Sent By adavila Date 2008-06-04 Time 16:40 Rev Time 0.00
Received By adavila Date 2008-06-04 Time 16:40 Sent To  
Notes
2008-06-04 16:40:19PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
  
 AN IRRIGATION PERMIT SHALL BE OBTAINED PRIOR TO THE
 INSTALLATION OF IRRIGATION AND LANDSCAPING,AS WELL AS
 A RIGHT-OF-WAY PERMIT FOR IRRIGATION ON THE
 RIGHT-OF-WAY.

Review Stop Z ZONING
Rev No 4 Status P Date 2008-05-05 Cont ID  
Sent By adavila Date 2008-05-05 Time 16:10 Rev Time 0.00
Received By adavila Date 2008-05-05 Time 16:10 Sent To  
Notes
2008-05-05 16:17:11PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 PROVISO GLARE SHALL NOT EXCEED 0.5 FOOT CANDLE AT OR
 BEYOND THE CENTERLINE OF THE ALLEY.
  
 PROVISO A COPY OF THE RECORDED ACCESS EASEMENT PRIOR TO
 OBTAINING THE CERTIFICATE OF OCCUPANCY.
  
 AN IRRIGATION PERMIT SHALL BE OBTAINED PRIOR TO THE
 INSTALLATION OF IRRIGATION AND LANDSCAPING,AS WELL AS
 A RIGHT-OF-WAY PERMIT FOR IRRIGATION ON THE
 RIGHT-OF-WAY.
  
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-01-31 Cont ID  
Sent By adavila Date 2008-01-31 Time 15:20 Rev Time 0.00
Received By adavila Date 2008-01-31 Time 09:18 Sent To  
Notes
2008-01-31 15:25:53PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 PROVISO GLARE SHALL NOT EXCEED 0.5 FOOT CANDLE AT OR
 BEYOND THE CENTERLINE OF THE ALLEY.
  
 PROVISO WHEEL STOP SHALL BE 2 FEET FROM THE CURB TO THE
 BACK OF THE WHEEL STOP.
  
 PROVISO A COPY OF THE RECORDED ACCESS EASEMENT PRIOR TO
 OBTAINING THE CERTIFICATE OF OCCUPANCY.
  
 AN IRRIGATION PERMIT SHALL BE OBTAINED PRIOR TO THE
 INSTALLATION OF IRRIGATION AND LANDSCAPING.
  
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
  
  
2008-01-31 09:19:05IN ZONING FOR REVIEW.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-30 Cont ID  
Sent By adavila Date 2007-10-30 Time 11:10 Rev Time 0.00
Received By adavila Date 2007-10-30 Time 09:18 Sent To  
Notes
2007-10-30 11:10:25PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. THE SUBMITTED APPRAISAL OF REAL PROPERTY REPORT,
 DATED SEPTEMBER 29, 2007, STATES THAT THE DEPRECIATED
 REPLACEMENT VALUE FOR THE SUBJECT PROPERTY IS
 $328,600.00.ACCORDING TO THE RESPONSE LETTER DATED
 OCTOBER 16, 2007, THE TOTAL AMOUNT OF CONTRACT IS
 $234,000.00.THIS AMOUNT EXCEEDS 50% OF THE
 IMPROVEMENT VALUE ($164,300).THUS, THE SITE SHALL BE
 BROUGHT INTO COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS.
 A. PER SECTION 94-443(C)(3)(A), TERMINAL LANDSCAPE
 ISLANDS SHALL CONTAIN AT LEAST 1 SHADE OR FLOWERING
 TREE.AT LEAST 1 OF THE PROPOSED CABBAGE PALMS SHALL
 BE REPLACED BY A SHADE OR FLOWERING TREE ON EACH
 TERMINAL LANDSCAPE ISLAND.
 B. LANDSCAPE AREA SHALL BE PROVIDED ALONG THE EAST
 PROPERTY LINE.IT IS STAFF?S RECOMMENDATION THAT THE
 ADDITIONAL CABBAGE PALMS BE RELOCATED ALONG THE EAST
 BUILDING FA?ADE OF THE ADULT ENTERTAINMENT BUILDING
 (AREA WHERE THE EXISTING BILLBOARD STRUCTURE IS
 LOCATED).
 C. PER SECTION 94-444(B), WALLS OF A DUMPSTER ENCLOSURE
 SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT
 TWO-FOOT INTERVALS.SHRUBS AND HEDGES SHALL BE PLANTED
 ALONG THE NORTH WALL OF THE PROPOSED DUMPSTER
 ENCLOSURE.
  
 3. THERE APPEARS TO BE A DISCREPANCY IN THE DUMPSTER
 ENCLOSURE DIMENSIONS SHOWN ON SHEET A-1.1.ACCORDING
 TO THE DUMPSTER ENCLOSURE DETAIL, THE PROPOSED DUMPSTER
 ENCLOSURE WILL BE 8 FEET WIDE.HOWEVER, THE DETAIL
 ALSO SHOWS A 10 FOOT WIDE STOP BAR AND A 12 FEET BY 12
 FEET CONCRETE PAD INSIDE THE DUMPSTER ENCLOSURE.
 PLEASE REVISE.
  
 4. PER SECTION 94-485(P), LOADING SPACE SHALL BE 10
 FEET BY 25 FEET.PLEASE REVISE.PLEASE NOTE THAT THE
 SURVEY AND SITE PLAN SHOW A REAR SETBACK OF 8.9?.
  
 5. AN ACCESS EASEMENT ALONG THE SOUTH PROPERTY LINE
 SHALL BE RECORDED.PLEASE CONTACT MR. VINCE NOEL, CITY
 SURVEYOR, ENGINEERING SERVICES DEPARTMENT, AT (561)
 494-1040 FOR FURTHER INFORMATION.
  
 6. PLEASE VERIFY WITH THE CONSTRUCTION SERVICES
 DEPARTMENT HOW THE ACCESSIBLE ROUTE FROM THE SIDEWALK
 TO THE BUILDING WILL BE PROVIDED.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-13 Cont ID  
Sent By adavila Date 2007-08-13 Time 14:36 Rev Time 0.00
Received By adavila Date 2007-08-09 Time 08:37 Sent To  
Notes
2007-08-13 14:37:37PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PLEASE NOTE THAT 4 FEET OF THE EXISTING ALLEY IS
 UNPAVED.PLACING A LANDSCAPE BUFFER ALONG THE SOUTH
 PROPERTY LINE WILL DECREASE THE WIDTH OF THE ALLEY TO 8
 FEET.PROVIDE APPROVAL, IN WRITING, FROM THE
 ENGINEERING SERVICES DEPARTMENT FOR THE LOCATION OF THE
 LANDSCAPE ISLANDS ALONG THE SOUTH PROPERTY LINE.
  
 3. PER SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), RENOVATIONS, REPAIR,
 ALTERATION OR REDEVELOPMENT WHICH EXCEEDS 50 PERCENT OF
 THE VALUE OF THE STRUCTURE SHALL COMPLY WITH THE
 STANDARDS SET FORTH IN ARTICLE XIV OF THE ZLDRS.AS
 THE PROPOSED RENOVATIONS EXCEED 50 PERCENT OF THE VALUE
 OF THE STRUCTURE, A LANDSCAPE PLAN PREPARED, SIGNED AND
 SEALED BY A REGISTERED LANDSCAPE ARCHITECT, AND MEETING
 THE LANDSCAPE PROVISIONS SET OUT IN ARTICLE XIV OF THE
 ZLDRS, SHALL BE PROVIDED.
 A. PLEASE PROVIDE A DATA TABLE STATING THE REQUIRED AND
 PROVIDED LANDSCAPE, TO INCLUDE THE RATIO OF SHADE TREES
 SUBSTITUTED BY PALM TREES, AS DEFINED IN SECTION
 94-442(B) AND (C) OF THE ZLDRS.
 B. PROVIDE XERISCAPE REQUIREMENT POINTS.
 C. PROVIDE TREE PLANTING PLAN DETAILS MEETING THE
 CITY?S ZLDRS.PLEASE SEE THE ATTACHED DIAGRAM FOR
 REFERENCE.
 D. PLEASE NOTE THAT PER SECTION 94-443(B), THE OWNER OF
 THE PROPERTY SHALL INSTALL AND MAINTAIN A LANDSCAPE
 BUFFER STRIP ALONG THE ENTIRE EDGE OF THE PROPERTY
 ADJACENT TO A PUBLIC THOROUGHFARE AND OTHER
 NONRESIDENTIAL ZONING DISTRICTS. THE BUFFER STRIP SHALL
 BE AT LEAST FIVE (5) FEET WIDE.AT LEAST ONE SHADE OR
 FLOWERING TREE SHALL BE PLANTED FOR EACH 30 LINEAR FEET
 OR PORTION THEREOF.THE BUFFER STRIP MAY NOT BE
 INTERRUPTED BY MORE THAN 25% OF ITS REQUIRED LENGTH TO
 PROVIDE FOR SIGNS OR VEHICULAR INGRESS AND EGRESS.
 E. PLEASE NOTE THAT PER SECTION 94-443(C)(2), VEHICULAR
 USE AREAS SHALL BE SCREENED FROM THOROUGHFARES AND
 RESIDENTIAL USES AND DISTRICTS BY A LANDSCAPE BUFFER OF
 AT LEAST FIVE (5) FEET IN WIDTH.
 F. PURSUANT TO SECTION 94-443(C)(5)(A), LANDSCAPE AREAS
 SHALL BE SEPARATED FROM VEHICULAR USE AREAS BY
 NONMOUNTABLE, CONCRETE CURBING OF THE TYPE CATEGORIZED
 AS ?TYPE D.?LABEL THE TYPE OF CURB WHEREVER
 APPLICABLE.
 G. PLEASE CONTACT THE PLANNER REVIEWER TO DISCUSS
 LANDSCAPE OPTIONS.
  
 4. PURSUANT TO SECTION 94-443(C)(3)(A) OF THE ZLDRS,
 EACH ROW OF PARKING SPACES SHALL BE TERMINATED BY
 LANDSCAPE ISLANDS OF NOT LESS THAN 5 FEET IN WIDTH AND
 NOT LESS THAN THE LENGTH OF THE ADJACENT PARKING STALL.
 THE LANDSCAPE ISLAND SHALL CONTAIN AT LEAST 1 SHADE OR
 FLOWERING TREE.
 A. A TERMINAL ISLAND SHALL BE PROVIDED ADJACENT TO THE
 HANDICAP PARKING SPACE.
 B. A TERMINAL ISLAND SHALL BE PROVIDED AT THE END OF
 EACH PARKING ROW.
 C. THE PARKING SPACE ALONG THE SOUTH PROPERTY LINE OF
 THE PARKING ROW ADJACENT TO THE WEST BUILDING FA?ADE
 SHALL BE REMOVED IN ORDER TO PROVIDE THE REQUIRED 5
 FOOT WIDE TERMINAL ISLAND AT THE END OF THE PARKING ROW
 SUBJECT TO THE APPROVAL OF THE ENGINEERING SERVICES
 DEPARTMENT.
  
 5. PER SECTION 94-305(E) OF THE ZLDRS, AT ANY ROAD
 INTERSECTIONS, VISIBILITY SHALL NOT BE OBSCURED BY THE
 CONSTRUCTION, PLACEMENT, OR MAINTENANCE OF A STRUCTURE
 WALL, SIGN, FENCE, BERM, PLANT MATERIAL, SHRUBS, OR ANY
 SIMILAR ITEM BETWEEN 18 INCHES OR EIGHT FEET IN HEIGHT
 WITHIN THE VISIBILITY TRIANGLE.ALL TREES WITHIN THE
 VISIBILITY TRIANGLE SHALL BE APPROVED, IN WRITING, BY
 THE CITY?S TRAFFIC ENGINEER, ENGINEERING SERVICES
 DEPARTMENT.
  
 6. APPROVAL FROM THE PALM BEACH COUNTY TRAFFIC DIVISION
 SHALL BE PROVIDED FOR THE REMOVAL OF THE EXISTING CURB
 ALONG THE NORTH PROPERTY LINE.
  
 7. PLEASE NOTE THAT WHILE THE EXISTING ADULT
 ENTERTAINMENT BUILDING IS A SEPARATE BUSINESS FROM THE
 PROPOSED BAKERY, IT SHALL ALSO BE INCLUDED IN THE TOTAL
 PARKING COUNT FOR THAT SITE.
  
 8. PROVIDE PLANS STAMPED APPROVED FROM THE ENGINEERING
 SERVICES DEPARTMENT FOR THE SIZE AND LOCATION OF THE
 DUMPSTER ENCLOSURE.
  
 9. PROVIDE WIDTH DIMENSION OF THE INGRESS/EGRESS POINT
 ALONG THE SOUTH PROPERTY LINE.PLEASE NOTE THAT THE
 INGRESS/EGRESS POINT SHALL BE NO LESS THAN 20 FEET
 WIDE.
  
 10. HANDICAP SYMBOL SHALL BE 2 FEET FROM THE OPEN END
 OF THE PARKING SPACE.
  
 11. THERE SHALL BE DOUBLE STRIPING BETWEEN THE HANDICAP
 PARKING SPACE AND THE HANDICAP ACCESS AISLE.PLEASE
 SEE ATTACHED DIAGRAM FOR REFERENCE.
  
 12. PROVIDE EXISTING VS. PROPOSED PERCENTAGE OF
 IMPERVIOUS AND PERVIOUS AREAS.
  
 13. STAIRS ALONG THE WEST BUILDING FA?ADE ARE NOT SHOWN
 ON THE PLANS.PLEASE CLARIFY AND ADDRESS.
  
 14. THERE IS A SMALL RAMP FROM THE PARKING LOT TO A
 DOOR ON WEST BUILDING FA?ADE, SOUTH PROPERTY LINE.THE
 PROPOSED SITE PLAN SHOWS A LANDSCAPE AREA IN FRONT OF
 THE DOOR.PLEASE CLARIFY AND ADDRESS.
  
 15. ALL SIGNS SHALL BE APPROVED UNDER A SEPARATE
 PERMIT.PROVIDE A PERMIT FOR ALL SIGNS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.