| Plan Review Stops For Permit 07070989 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-08-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-08-02 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-08-02 |
Time |
06:59 |
Sent To |
I |
|
| Notes |
| 2007-08-02 07:47:40 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1} PROVIDE A RISER DIAGRAM FOR THE SERVICE THATS IN THE | | | DESCRIPTION ON THE APPLICATION. | | | | | | 2}PROVIDE A SITE PLAN INDICATING THE LOCATION OF THE | | | SERVICE. | | | | | | THE PLANS FOR THE TRAILERS DO NOT NEED TO BE SUBMITTED, | | | UNLESS THEY ARE BEING INTERNALLY WIRED UNDER THIS | | | APPLICATION, IF SO ADJUST THE VALUE TO REFLECT SAME. | | | | | | THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 | | | FS, RESPECTIVELY. | | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES | | | APPLY. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-08-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-08-02 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-08-01 |
Time |
08:54 |
Sent To |
PC |
|
| Notes |
| 2007-08-01 08:55:07 | TO "E" BOX |
|
|
|