| Notes |
| 2007-08-13 11:32:44 | ****************PROVISO**************** | | | IF DRYER ROOM IS A CONFINED SPACE, OPENINGS REQUIRED | | | PER SECTION 304.5 OR SECTION 304.6 SHALL BE INSTALLED. | | | MINIMUM 1,000 CUBIC FEET REQUIRED. | | | | | | IF WATER HEATER ROOM IS A CONFINED | | | SPACE, OPENINGS REQUIRED PER SECTION | | | 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. | | | MINIMUM 2,000 CUBIC FEET REQUIRED. | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL= [email protected] |
|
|