Plan Review Details - Permit 07070921
Plan Review Stops For Permit 07070921
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-28 Cont ID  
Sent By kconrad Date 2007-12-28 Time 19:19 Rev Time 0.00
Received By kconrad Date 2007-12-28 Time 15:45 Sent To I
Notes
2007-12-28 18:37:03PROJECT: 1100 NORTH OLIVE AVENUE
  
 PROJECT DETAIL: CHANGE OF OCCUPANCY/GROUP R-3 TO GROUP
 B CLASSIFICATION
  
 CODE REVIEW:
  
 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH/ FLORIDA BUILDING CODE
 ADMINISTRATION AMENDMENTS, CHAPTER 1, 2004 EDITION
  
 STATUS: FAILED
  
 COMMENTS:
  
 1) 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
  
  
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
 SPECIFIC AUTHORITY 481.2055 FS. LAW IMPLEMENTED
 481.203(6), 481.203(8), 481.2131(1),
 481.219(3),(4),(5), 481.221,
 481.225(1)(E),(G), 481.2251(1)(H) FS. HISTORY?
 NEW 9-7-00.
  
 2) PLEASE INDICATE THE PROPOSED OCCUPANCY LOAD OF THE
 GROUP B CLASSIFICATION.
  
 3) PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING TRAVEL
 DISTANCES/COMMON PATH OF TRAVEL/EXIT SIGNS ETC:
  
 FEBC 705.3EXIT SIGNS.
 MEANS OF EGRESS FROM THE HIGHEST WORK AREA FLOOR TO THE
 FLOOR OF EXIT DISCHARGE SHALL BE PROVIDED WITH EXIT
 SIGNS IN ACCORDANCE WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4) PLEASE SHOW THE ACCESSIBLE ROUTE/ACCESSIBLE MEANS OF
 EGRESS. PLEASE INCLUDE THE ACCESSIBLE PARKING SPACES
 DEPICTING DIMENSIONS. THE ACCESSIBLE ROUTE SHALL COMPLY
 WITH SECTION 11-4.1 OF THE FLORIDA BUILDING CODE.
  
 5) THE TOP LANDINGS AT THE ACCESSIBLE RAMPSHOWN ON
 SHEET A-1 DO NOT MEET THE MINIMUM REQUIREMENTSOF
 SECTION 11-4.8.4:
  
 11-4.8.4 LANDINGS.
  
 RAMPS SHALL HAVE LEVEL LANDINGS AT BOTTOM AND TOP OF
 EACH RAMP AND EACH RAMP RUN. LANDINGS SHALL HAVE THE
 FOLLOWING FEATURES:
 (1) THE LANDING SHALL BE AT LEAST AS WIDE AS THE RAMP
 RUN LEADING TO IT.
 (2) ALL LANDINGS ON RAMPS SHALL BE NOT LESS THAN 60
 INCHES (1524 MM) CLEAR, AND THE BOTTOM OF EACH RAMP
 SHALL HAVE NOT LESS THAN 72 INCHES (1829 MM) OF
 STRAIGHT AND LEVEL CLEARANCE.
 (3) IF RAMPS CHANGE DIRECTION AT LANDINGS, THE MINIMUM
 LANDING SIZE SHALL BE 60 INCHES BY 60 INCHES (1525 MM
 BY 1525 MM).
 (4) IF A DOORWAY IS LOCATED AT A LANDING, THEN THE AREA
 IN FRONT OF THE DOORWAY SHALL COMPLY WITH SECTION
 11-4.13.6.
  
 6) PLEASE SHOW THAT THE RAMP HANDRAILS COMPLY WITH
 SECTION 11-4.8.5:
  
 11-4.8.5 HANDRAILS.
  
 IF A RAMP RUN HAS A RISE GREATER THAN 6 INCHES (150 MM)
 OR A HORIZONTAL PROJECTION GREATER THAN 72 INCHES (1830
 MM), THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES.
 HANDRAILS ARE NOT REQUIRED ON CURB RAMPS OR ADJACENT TO
 SEATING IN ASSEMBLY AREAS. HANDRAILS SHALL COMPLY WITH
 SECTION 11-4.26 AND SHALL HAVE THE FOLLOWING FEATURES:
 (1) HANDRAILS SHALL BE PROVIDED ALONG BOTH SIDES OF
 RAMP SEGMENTS. THE INSIDE HANDRAIL ON SWITCHBACK OR
 DOGLEG RAMPS SHALL ALWAYS BE CONTINUOUS. (2) HANDRAILS
 ON RAMPS WHICH ARE NOT CONTINUOUS SHALL EXTEND NOT LESS
 THAN 18 INCHES (457 MM) BEYOND THE SLOPED SEGMENT AT
 BOTH THE TOP AND BOTTOM, AND SHALL BE PARALLEL TO THE
 FLOOR OR GROUND SURFACE.
 (3) THE CLEAR SPACE BETWEEN THE HANDRAIL AND THE WALL
 SHALL BE 1? INCHES (38 MM).
 (4) GRIPPING SURFACES SHALL BE CONTINUOUS.
 (5) TOP OF HANDRAIL GRIPPING SURFACES SHALL BE MOUNTED
 BETWEEN 34 INCHES AND 38 INCHES (865 MM AND 965 MM)
 ABOVE RAMP SURFACES.
 (6) ENDS OF HANDRAILS SHALL BE EITHER ROUNDED OR
 RETURNED SMOOTHLY TO FLOOR, WALL, OR POST.
 (7) HANDRAILS SHALL NOT ROTATE WITHIN THEIR FITTINGS.
  
 7) PLEASE SHOW THAT THE STAIRS AND HANDRAILING MEET THE
 REQUIREMENTS OF SECTION 11-4.9 OF THE FLORIDA
 ACCESSIBILITY CODE. THE EXISTING STAIRS SHALL MEET THE
 MINIMUM REQUIREMENTS OF SECTION
 703.1FEBC:
  
 703.1EXISTING SHAFTS AND VERTICAL OPENINGS. EXISTING
 STAIRWAYS THAT ARE PART OF THE MEANS OF EGRESS SHALL
 COMPLY WITH THE APPROPRIATE SECTIONS OF THE FLORIDA
 FIRE PREVENTION CODE.
  
 8) PLEASE INDICATE THE ACCESSIBLE BATHROOM. SHOW CLEAR
 FLOOR SPACE, HEIGHT AND WALL DIMENSIONS OF LAVATORY AND
 WATER CLOSET. ALSO, INDICATE THE CLEAR OPENING DOOR
 WIDTH. GRAB BARS SHALL BE SHOWN ANDSHALL MEET THE
 MINIMUM REQUIREMENTS OF SECTION 11-4.26.
  
 9) THE MEANS OF EGRESS SHALL MEET THE MINIMUM
 REQUIREMENTS OF SECTION 605, FLORIDA EXISTING BUILDING
 CODE.
  
 10) PLEASE INDICATE THE EXISTING INTERIOR WALL AND
 CEILING FINISHES AS PER THE FOLLOWING:
  
 FEBC 812.3.1MINIMUM REQUIREMENTS.
 REGARDLESS OF T HE OCCUPANCY GROUP INVOLVED, THE
 FOLLOWING REQUIREMENTS SHALL BE MET:
 1. THE CAPACITY OF THE MEANS OF EGRESS SHALL COMPLY
 WITH FLORIDA BUILDING CODE, BUILDING.
 2. THE INTERIOR FINISH OF WALLS AND CEILINGS SHALL
 COMPLY WITH THE REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING FOR THE NEW OCCUPANCY GROUP.
 3. COMPLIANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 END OF REVIEW
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-01 Cont ID  
Sent By kconrad Date 2007-08-01 Time 17:28 Rev Time 0.00
Received By kconrad Date 2007-08-01 Time 17:28 Sent To I
Notes
2007-08-01 17:54:06REQUIRE PLAN SUBMITTALS. ANY CHANGE OF OCCUPANCY GROUP
 SHALL COMPLY WITH THE FOLLOWING OF THE FLORIDA EXISTING
 BUILDING CODE:
  
  
 SECTION 812
  
 CHANGE OF OCCUPANCY CLASSIFICATION
 812.1COMPLIANCE WITH CHAPTER 7.
 THE OCCUPANCY CLASSIFICATION OF AN EXISTING BUILDING
 MAY BE CHANGED, PROVIDED THAT THE BUILDING MEETS ALL OF
 THE REQUIREMENTS OF CHAPTER 7 APPLIED THROUGHOUT THE
 BUILDING FOR THE NEW OCCUPANCY GROUP AND COMPLIES WITH
 THE REQUIREMENTS OF SECTIONS 802 THROUGH 812.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-13 Cont ID  
Sent By btrobaug Date 2007-12-13 Time 16:43 Rev Time 0.00
Received By btrobaug Date 2007-12-13 Time 07:24 Sent To  
Notes
2007-12-13 16:43:11 
  
 APPLICATION #07070921
 ELECTRICAL PLAN REVIEW
 1100 N OLIVE AVE
 12/13/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1}SUBMIT FORMS, SHOW DEVICES REQUIRED, PROVIDE A
 FIXTURE SCHEDULE INDICATING DENSITY COMPLIANCE REQUIRED
 BY FBC 13-101.3 CHANGES OF OCCUPANCY TYPE, AND ALL
 RELATED ARTICLES OF CHAPTER 13.
 13-101.3.1 BUILDINGS HAVING A CHANGE OF OCCUPANCY TYPE
 THAT WERE PERMITTED PRIOR TO MARCH 15, 1979, SHALL MEET
 THE REQUIREMENTS FOR RENOVATIONS IN SECTION 101.1.3 OR
 SECTION 101.2.3, AS APPROPRIATE, FOR THOSE COMPONENTS
 WHICH ARE BEING RETROFITTED OR REPLACED.
  
 2} A TITLE BLOCK FOR THE ENGINEER WITH INFORMATION PER
 61G15-23.002(2) FAC. IS REQUIRED.
  
 3} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8
 (2003), AND CIRCUITED
 PER 700.12 NEC (F)(4). INDICATE SAME ON PLANS.
  
 4} PROVIDE A RISER DIAGRAM AND LOAD CALCULATIONS
 INDICATING COMPLIANCE WITH ARTICLE 220 FOR A COMMERCIAL
 BUILDING.
  
 5} INDICATE THE RATING OF THE EXISTING SERVICE. 215.5
 NEC. SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC.
  
 6} LOCATE ALL SERVICE EQUIPMENT ON THE PLAN. 106.1.3
 FBC AS AMENDED.
  
 7} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES.106.3.5 FBC.
  
 8} NFPA 101-7.8.1.3*
 THE FLOORS AND OTHER WALKING SURFACES WITHIN AN EXIT
 AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND EXIT
 DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE ILLUMINATED TO
 VALUES OF AT LEAST 1 FT-CANDLE (10 LUX) MEASURED AT THE
 FLOOR. INDICATE ON PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-24 Cont ID  
Sent By mwennerg Date 2007-12-24 Time 11:14 Rev Time 0.00
Received By mwennerg Date 2007-12-24 Time 11:14 Sent To  
Notes
2007-12-24 11:20:25***DENIED***
  
 1) ADDRESS NUMBER SHALL COMPLY WITH CITY OF WEST PALM
 BEACH REQUIREMENTS FOR COMMERCIAL BUILDINGS. THE
 CHARACTERS SHALL BE MINIMUM OF 6" IN HEIGHT AND
 CONTRASTING TO BACKGROUND.
  
 2) HANDRAILS REQUIRED ON BOTH SIDES OF STAIRS.
  
 3) ILLUMINATED EXIT SIGNS ARE REQUIRED.
  
 4) BUILDING INFORMATION INDICATES FIRE SPRINKLERS.
 PLEASE ADVISE AND IF APPLICABLE PROVIDE MORE DETAILS.
 IF NOT PART OF THE SCOPE OF THIS WORK, PLEASE REMOVE
 REFERENCE FROM DRAWINGS.
  
 5) ARE STAIRS SHOWN ON LEFT ELEVATION PART OF REQUIRED
 MEANS OF EGRESS?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-28 Time 19:32 Rev Time 0.00
Received By kconrad Date 2007-12-06 Time 16:18 Sent To  
Notes
2007-12-10 16:09:20TO "BOB"#17
2007-12-06 16:18:50WAITING FOR "BOB" PER "RBROWN"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-11 Cont ID  
Sent By tgordon Date 2007-12-11 Time 09:19 Rev Time 0.30
Received By tgordon Date 2007-12-11 Time 09:19 Sent To  
Notes
2007-12-11 09:29:00PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT MECHANICAL PLANS SHOWING EXISTING
 CONDITIONS, SEE 2004 FBC/EXIST. 809.1.
  
 *** 809.1 MECHANICAL REQUIREMENTS.
 WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF
 AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO DIFFERENT KITCHEN EXHAUST
 REQUIREMENTS OR TO INCREASED MECHANICAL VENTILATION
 REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, MECHANICAL , THE INTENT OF THE RESPECTIVE FLORIDA
 BUILDING CODE, MECHANICAL PROVISIONS SHALL BE COMPLIED
 WITH FOR THE NEW OCCUPANCY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-15 Cont ID  
Sent By jleech Date 2007-12-15 Time 08:09 Rev Time 0.00
Received By jleech Date 2007-12-15 Time 07:31 Sent To  
Notes
2007-12-15 08:33:20DENIED;
 1. BATHROOMS ARE REQUIRED TO MEET FBC-BUILDING CHAPTER
 11 HANDICAP REQUIREMENTS. SHOW DETAILS ON DRAWINGS;
 TURNING RADIUS, CLEAR FLOOR SPACE, GRAB BARS AND SHOWER
 ETC.
 2. KITCHEN SINK, BREAK SINK MUST MEET CHAPTER 11
 SECTIONS 11-4.24.1 THRU 11-4.23.7. SHOW DETAILS ON
 DRAWINGS. CLEAR FLOOR SPACE SHALL EXSTEND 19" UNDER THE
 SINK.
 3. MINIMUUM PLUMBING FIXTURES REQUIRED, FBC PLUMBING
 TABLE 403.1 OCCUPENCY "B" A DRINKING FOUNTAIN IS
 REQUIRED. THE DRINKING FOUNTAIN MUST MEET THE HANDICAP
 REQUIREMENTS. SEE SECTIONS 11-4.15.1 THRU 11-4.15.4.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-21 Cont ID  
Sent By astelly Date 2007-12-21 Time 16:37 Rev Time 0.00
Received By astelly Date 2007-12-21 Time 16:36 Sent To  
Notes
2007-12-21 16:38:03AMY STELLY
 URBAN DESIGN
 822-1440
  
 PLEASE SUBMIT A SITE PLAN WHICH SHOWS PARKING.