Plan Review Details - Permit 07070920
Plan Review Stops For Permit 07070920
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-29 Cont ID  
Sent By jgomez Date 2007-11-29 Time 08:08 Rev Time 0.00
Received By jgomez Date 2007-11-28 Time 12:42 Sent To PC
Notes
2007-11-29 09:20:59SECONDBUILDING REVIEW CHECKLIST FOR NEW RESIDENTIAL
 ADDITION.
 REVIEW DONE UNDERFBC 2004 WITH 2007 REVISIONS.
  
 1- SOIL TEST REPORT TO HAVE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY
 FLORIDA ADMINISTRATIVE CODE SEC. 61G15-23.002(2).
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FLAT ROOF ASSEMBLY TO BE USED. SEE ATTACHED COPY
 OF CITY POLICY FOR ROOFING PERMITS AND REQUIRED
 INFORMATION.
 CLEARLYCIRCLE SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED AND SPECIFIC FASTENING OPTION IF MORE THAN
 ONE OPTION IS LISTED.IN ADDITION,IF SELECTED
 ASSEMBLY IS LIMITED BY GENERAL LIMITATION #7, THEN
 PROVIDE THE REQUIRED RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS.THESE
 CALCULATIONS MAY BE REQUIRED TO BE PERFORMED ONLY BY
 ARCHITECT, ENGINEER OR REGISTERED ROOF CONSULTANT. SEE
 LAST PAGE OF PRODUCT APPROVAL TO SEE WHO'S MUST DO THE
 CALCULATIONS.
 ON THE OTHER HAND IF SELECTED ASSEMBLY IS LIMITED BY
 GENERAL LIMITATION #9, THEN, IT CAN'T BE USED IN THIS
 AREA BECAUSE NAIL ENHANCING IT'S NOT ALLOWED TO
 INCREASE THE UPLIFT CAPACITY OF THE ROOF ASSEMBLY. SEE
 GENERAL LIMITATION #9.(REPEAT COMMENT. INFORMATION
 WAS NOT PROVIDED AT ALL).
  
 B) ALL STRUCTURAL SIMPSON CONNECTORS SPECIFIED ON
 PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN ONLY. GO
 TO WWW.FLORIDA BUILDING.ORG TO DOWNLOAD CORRESPONDING
 INFORMATION. (REPEAT COMMENT. INFORMATION WAS NOT
 PROVIDED AT ALL).
  
 C)"INSWING" DOOR EXTERIOR DOOR AS SHOWN ON NEW
 UTILITY FLOOR PLAN . PRODUCT APPROVAL SUBMITTED IS FOR
 AN "OUTSWING" DOOR.
  
 ***NOTE: IF DOOR IS CHANGED FOR AN "OUTSWING" DOOR,
 THEN KEEP IN MIND THAT COMPLIANCE WITH SECTION R311.4.3
 OF 2004 FLORIDA RESIDENTIAL CODE IS REQUIRED.
  
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 (REPEAT COMMENT. NOT ADDRESSED BY THE ENGINEER OF
 RECORD).
  
 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600.1.C.1.
 NOTE: MAKE SURE CORRECT 2006 REVISED FORM IS USED.
 (REPEAT COMMENT.INFORMATION WAS NOT SUBMITTED AT
 ALL).
  
 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE. (REPEAT COMMENT. NOT
 PROVIDED).
  
 6- SPECIFY HOW ROOFCROSS VENTILATION IS ACHIEVED TO
 COMPLY WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 7- IF ENGINEERINGSHEETS ARE REVISED, THEN PLEASE
 REMOVEOLD SHEETSAND INSERT NEW SHEETS.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-08 Cont ID  
Sent By jleech Date 2007-08-06 Time 09:56 Rev Time 0.00
Received By jgomez Date 2007-08-08 Time 17:57 Sent To PC
Notes
2007-08-08 18:17:17FIRST BUILDING REVIEW CHECKLIST FOR NEW RESIDENTIAL
 ADDITION.
 REVIEW DONE UNDER FBC 2004 RESIDENTIAL CODEAND FBC
 2004.
  
 1- PROVIDE SOIL TEST REPORT AS REQUIRED ON ENGINEER
 FOUNDATION NOTE #3 ON SHEET 2 OF 19.
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FLAT ROOF ASSEMBLY TO BE USED. SEE ATTACHED COPY
 OF CITY POLICY FOR ROOFING PERMITS AND REQUIRED
 INFORMATION.
 CLEARLYCIRCLE SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED AND SPECIFIC FASTENING OPTION IF MORE THAN
 ONE OPTION IS LISTED.IN ADDITION,IF SELECTED
 ASSEMBLY IS LIMITED BY GENERAL LIMITATION #7, THEN
 PROVIDE THE REQUIRED INFORMATION. SEE LAST PAGE OF
 PRODUCT APPROVAL TO SEE WHAT'S THE REQUIRED
 INFORMATION.
 ON THE OTHER HAND IF SELECTED ASSEMBLY IS LIMITED BY
 GENERAL LIMITATION #9, THEN, IT CAN'T BE USED IN THIS
 AREA BECAUSE NAIL ENHANCING IT'S NOT ALLOWED TO
 INCREASE THE UPLIFT CAPACITY OF THE ROOF ASSEMBLY.
  
 B) ALL STRUCTURAL SIMPSON CONNECTORS SPECIFIED ON
 PLANS AND DETAILS.
  
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 4- PLANS TO SPECIFY CONSTRUCTIONTYPE AS REQUIRED BY
 SEC. 602.1 FBC 2004.
  
 5- PROVIDE COMPLETE SPECS AND DETAILS FOR HANDRAILS AND
 STEPSTO VERIFY COMPLIANCE WITH SECTION R311.5OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 6- ARCHITECTURAL PLANS AND ENGINEER'S PLANS DON'T
 MATCH.EG:SEE STEPS,FOOTINGS,ETC. REVISE AS
 REQUIRED TO MATCH.
 ALSO, PROVIDE ALL DIMENSIONS.
  
 7- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600.1.C.1.
 NOTE: MAKE SURE CORRECT 2006 REVISED FORM IS USED.
  
 8- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5115)TO VERIFY IF IMPACT FEES ARE DUE OR
 NOT. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF IMPACT FEES ARE DUE.
  
 9- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 10- SPECIFY HOW ROOFCROSS VENTILATION IS ACHIEVED TO
 COMPLY WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 11- ARCHITECTURAL PLANS ARE WRONG. WEST ELEVATIONS IS
 SHOWN AS A PARTIAL BUILDING SECTION, NOT AS AN
 ELEVATION.SAME THING APPLIES TO SOUTH ELEVATION.
 CLARIFY DRAWINGS AS REQUIRED.
  
 12- PROVIDE COMPLETE SPECIFICATIONS FOR ROOF EAVE
 CONSTRUCTION. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 13- SPECIFY ROOF SLOPE AS REQUIRED BY SEC. R905.11.1 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 14- ROOF SHEATHING SIZE SHOWN ON ARCHITECTURAL PLANS
 DON'T MATCH SPECIFICATIONS SHOWN ON ENGINEERING PLANS
 SHEET 14 OF 19. REVISE AS REQUIRED.
  
 15- ARCHITECTURAL PLANS AND NOTES AND ENGINEERING PLANS
 AND NOTES NEED TO BE COORDINATED TO AVOID CONFLICT OR
 CONFUSION. REVISE AS REQUIRED BOTH SETS OF PLANS TO
 MATCH.
  
 16- ARCHITECTURAL PLANS TO HAVE DESIGNER NAME AND
 SIGNATURE AS REQUIRED BY SEC. 106.1.3 CITY AMENDMENTS
 TO FBC 2004.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-21 Cont ID  
Sent By btrobaug Date 2007-11-21 Time 12:41 Rev Time 0.00
Received By btrobaug Date 2007-11-21 Time 11:12 Sent To B
Notes
2007-11-21 12:41:58 
  
 TO JULIO'S DESK./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-01 Cont ID  
Sent By btrobaug Date 2007-08-01 Time 08:32 Rev Time 0.00
Received By btrobaug Date 2007-08-01 Time 07:17 Sent To P
Notes
2007-08-01 08:31:55 
  
 NONCOMPLIANT
  
 MAKE THE FOLLOWING CORRECTIONS FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW.
  
 PER 210.52(A) GENERAL PROVISIONS IN EVERY KITCHEN,
 FAMILY ROOM, DINING ROOM, LIVING ROOM, PARLOR, LIBRARY,
 DEN, SUNROOM, BEDROOM, RECREATION ROOM, OR SIMILAR ROOM
 OR AREA OF DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE GENERAL PROVISIONS
 SPECIFIED IN 210.52(A)(1) THROUGH (A)(3). LOCATE THESE
 REQUIRED RECEPTALES ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 14:02 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 14:02 Sent To Z
Notes
2007-11-15 14:02:53TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-08 Cont ID  
Sent By jgomez Date 2007-08-08 Time 18:52 Rev Time 0.00
Received By jgomez Date 2007-07-30 Time 11:19 Sent To  
Notes
2007-07-30 11:19:20TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-07-31 Cont ID  
Sent By tgordon Date 2007-07-31 Time 14:56 Rev Time 0.20
Received By tgordon Date 2007-07-31 Time 14:56 Sent To E
Notes
2007-07-31 14:57:09NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-08-06 Cont ID  
Sent By jleech Date 2007-08-06 Time 09:55 Rev Time 0.00
Received By jleech Date 2007-08-06 Time 09:55 Sent To B
Notes
2007-08-06 09:56:12NO PLUMBING SHOWN ON DRAWINGS.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-20 Cont ID  
Sent By choops Date 2007-11-20 Time 08:18 Rev Time 0.00
Received By choops Date 2007-11-20 Time 08:18 Sent To E
Notes
2007-11-20 08:19:19***APPROVED - RESUB #1***
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-31 Cont ID  
Sent By choops Date 2007-07-31 Time 08:38 Rev Time 0.00
Received By choops Date 2007-07-31 Time 08:38 Sent To E
Notes
2007-07-31 08:40:36***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED ADDITION
 TO THE PROPERTY LINES.
  
 2)SHOW ANY PROPOSED A/C EQUIPMENT WITH SETBACK
 DIMENSIONS, IF ANY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720