Plan Review Details - Permit 07070893
Plan Review Stops For Permit 07070893
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-07 Cont ID  
Sent By jjohnsto Date 2007-11-07 Time 16:02 Rev Time 1.00
Received By jjohnsto Date 2007-11-07 Time 16:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-01 Cont ID  
Sent By jwitmer Date 2007-09-01 Time 14:02 Rev Time 0.77
Received By jwitmer Date 2007-09-01 Time 14:02 Sent To  
Notes
2007-09-01 14:13:02BUILDING PLAN REVIEW
 PERMIT: 07070893
 ADD: 4295 45TH ST 1ST FL
 CONT: PLAN REVIEW
 TEL: (772)214-4246
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) PLEASE SEE L1& L2 PLANS IT APPEARS THAT THE
 LANDSCAPE ARCHITECT HAS SIGNED AND SEALED THE PLANS BUT
 THE WORD DOCUMENT INDICATES THIS TO BE A DESIGN
 ENGINEER. PLEASE CORRECT
 TITLE BLOCK.
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2007-10-25 Cont ID  
Sent By dpalmer Date 2007-10-25 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2007-10-25 Time 12:59 Sent To  
Notes
2007-10-25 16:43:08THIS PERMIT APPLICATION AND PLANS IS NOT FOR ANY SITE
 ELECTRICAL WORK, OR RE-LOCATING OFLIGHTING POLES
 ETC.
 SEPARATE PERMITS, PLANS AND FEES WILL BE REQUIRED FOR
 ANY OTHER WORK AS MENTIONED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-23 Cont ID  
Sent By dpalmer Date 2007-08-23 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2007-08-23 Time 20:06 Sent To  
Notes
2007-08-23 20:06:422007-08-23 20:06:42
  
 *** DENIED***
  
 ** PLAN REVIEW FOR SAMS/WAL-MART SITE WORK.
  
 1) NOTE: PLEASE SEE THIS HAS ONLY BEEN SUBMITTED FOR
 *PLAN REVIEW* AND HAS NOT BEEN SUBMITTED FOR PERMIT.
 PLEASE KNOW THAT EVEN WHEN PLANS ARE COMPLETELY CODE
 COMPLIANT AND PERMIT HAS NOT BEEN APPLIED FOR THE
 STATUS WILL STILL REMAIN FAILED.
  
 2) NOTE: PLEASE SEE THE SHEET C-1 IS A IN FACT A
 *PHOTO-COPY* OF SIGNED AND SEALED PLANS WHICH IS NOT
 PERMITTED. ALL PLANS SHALL CONTAIN AN ORIGINAL
 SIGNATURE, DATE AND SIGNATURE AS REQUIRED UNDER THE
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002, AND FLORIDA
 STATUTES 471.023 (ENGINEERS).
 FLORIDA STATUTES 481.221 FOR ARCHITECTS.
 PLEASE SEE THE TITLE BLOCKS FOR THESE SAME SHEET C-1
 ARE MISSING THE REQUIRED LICENSE INFORMATION AS
 REQUIRED PER FAC 61G1-16.004
 ** THESE ARE REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 3) NOTE: PLEASE CLARIFY SCOPE OF WORK FOR ELECTRICAL.
 PLEASE SEE THAT NO INFORMATION WAS SUBMITTED FOR ANY
 REVISED SITE LIGHTING OR LANDSCAPE LIGHTING. PLEASE
 INDICATE REVISED LOCATIONS OF POLES ETC PLEASE BE SURE
 TO SUBMIT MINIMUM WIND LOADS FOR RE-LOCATED OR NEW
 POLES BEING INSTALLED. (MUST MEET FBC 2004 140MPH
 3SECOND GUST WITH RELATIVE SUSTAINED LEVEL OF 120MPH.
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE THE SEAL ON THE LANDSCAPE PLANS IS
 NO LONGER VALID IN THE STATE OF FLORIDA. PLEASE SEE
 RULING IN THE FLORIDA ADMINISTRATIVE CODE 61G1-16.002
 WHICH REQUIRES A NEW SEAL.
 (IF AN ENGINEER, PLEASE SEE FAC 61G15-23.001
 THIS RULING WAS CHANGED YEARS AGO AND NEW SEAL NEEDS TO
 BE OBTAINED.
 ** PLEASE KNOW THIS COMMENT APPLIES EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE SEE THE SEAL BEING USED ON THE
 LANDSCAPE PLANS ARE FOR THAT OF A LANDSCAPE ARCHITECT
 HOWEVER THE PRINTED NAME AND LICENSE INFORMATION ON THE
 TITLE BLOCKS STATES AN ENGINEER. THE PRINTED LICENSE
 NUMBER, PRINTED NAME AND INFORMATION DO NOT CORRELATE
 WITH SEAL ON PLANS.
 PLEASE SEE FAC 61G15-23.002/61G1-16.004
 FS 481/471
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2007-10-31 Cont ID  
Sent By rchokshi Date 2007-10-31 Time 14:45 Rev Time 0.00
Received By rchokshi Date 2007-10-31 Time 14:29 Sent To  
Notes
2007-10-31 14:45:24TO DAY, 10/31/07, MR. GREGORY WILFONG OF KIMLEY HORN
 SAID ON TELEPHONE THATCONNECTING TWO DRIVEWAYS
 BETWEEN TWO PARKING LOTS OF SAM'S & WALMART WILL BE
 BUILT DURING THE CONSTRUCTION OF WALMART'S PARKING LOT.
 THEY WILL USE ONE BIG SILT FENCE AS A POLLUTION
 PREVENTION MEASURE FOR WALMART PARKING LOT CONSTRUCTION
 AND DURING THE TWO DRIVE WAYS CONSTRUCTION. THEREFORE,
 THEY ARE NOT PUTTING SEPARATE POLLUTION PREVENTION SILT
 FENCES FOR TWO DRIVEWAYS CONSTRUCTION.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-08-30 Cont ID  
Sent By rchokshi Date 2007-08-30 Time 13:26 Rev Time 0.00
Received By rchokshi Date 2007-08-30 Time 13:19 Sent To  
Notes
2007-08-30 13:25:56***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. FLOOR ELEVATION, CENTER LINE OF ROAD , SIDEWALK
 ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10, 25, 100
 YEAR FLOOD CRITERIATO DETERMINE THE FLOOR ELEVATION,
 PLEASE SHOW IN YOUR STORM WATER CALS.
 5. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT,
 LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE
 THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED
 IN PRE & POST STORM WATER QUALITY CALCULATIONS.
 6. HOW DO YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR
 SITE SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES
 FROM ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF
 THE CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES,
 BLEEDING ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS.
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS,
 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-11-02 Cont ID  
Sent By mwennerg Date 2007-11-02 Time 13:45 Rev Time 0.00
Received By mwennerg Date 2007-11-02 Time 13:45 Sent To  
Notes
2007-11-02 13:47:59COMMENTS FROM FIRST FIRE PLAN REVIEW ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-18 Cont ID  
Sent By mawillia Date 2007-09-18 Time 12:26 Rev Time 0.00
Received By mawillia Date 2007-09-18 Time 11:44 Sent To  
Notes
2007-09-18 12:24:50*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS OF THE PROJECT SITE SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.SEE
 SHEET C-1,L-1 AND L-2.
  
 2.PLAN SHEETS L-1 AND L-2 REFER TO WAL-MART INSTEAD
 OF SAM'S CLUB.
  
 2.NO LEGEND TO CLEARLY IDENTIFY FIRE HYDRANTS.SHOW
 THE LOCATION OF THE FIRE HYDRANTS.
  
 3.PLEASE INDICATE IF THE SCOPE OF WORK WILL CAUSE
 FIRE HYDRANT(S) TO BE RE-LOCATED.
  
 4. THE EXISTING FUELING STATION ANDMCDONALD'S ARE
 SHOWN ON SHEET C-1, BUT ARE NOT LOCATED ON SHEET C-2.
 WILL OR HAVE THESE STRUCTURES BEEN REMOVED?DOES THE
 PROPOSED RETENTION PONDOF 0.98 ACRES BE IN THE PLACE
 WHERE MCDONALD'S IS/WAS?
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 08:46 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 08:46 Sent To  
Notes
2007-10-23 09:39:34TO "COMM" BD#21
2007-10-03 08:47:07WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-18 Cont ID  
Sent By mawillia Date 2007-09-18 Time 12:24 Rev Time 0.00
Received By mawillia Date 2007-07-28 Time 14:29 Sent To  
Notes
2007-08-10 10:49:19TO COMM BOARD #47
2007-07-28 14:30:02WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-09-10 Cont ID  
Sent By kstevens Date 2007-09-10 Time 07:08 Rev Time 0.00
Received By kstevens Date 2007-09-10 Time 07:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-29 Cont ID  
Sent By lfranco Date 2007-10-29 Time 17:23 Rev Time 0.00
Received By lfranco Date 2007-10-29 Time 17:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-08-22 Cont ID  
Sent By lfranco Date 2007-08-22 Time 16:33 Rev Time 0.00
Received By lfranco Date 2007-08-22 Time 16:33 Sent To  
Notes
2007-08-22 16:46:06PLANNING AND ZONING:**** PASSED ****
  
 1.THE PROJECT IS PART OF THE NORTH TRAIL PLAZA CPD,
 IT HAS BEEN APPROVED VIA A MINOR AMENDMENT, WHICH MEETS
 THE ZLDR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 CITY OF WEST PALM BEACH
 TEL: (561) 822-1443
  
  