Plan Review Details - Permit 07070891
Plan Review Stops For Permit 07070891
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-20 Cont ID  
Sent By mjacobs Date 2007-08-20 Time 08:41 Rev Time 0.00
Received By mjacobs Date 2007-08-20 Time 07:09 Sent To PC
Notes
2007-08-20 08:41:42BUILDING PLAN REVIEW
 PERMIT: 07070891
 ADD: 2025 N.DIXIE HWY
 CONT: GR CONCEPTS INC.
 TEL: (561)743-0066
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THE
 WINDOWS AND DOORS.
 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 3)SUBMIT A WALL DETAIL DRAWING FOR THE NEW CONCRETE
 INFILL AREAS. SHOW THE LAYOUT OF THESTEEL IN THESE
 WALLS, ALONG WITH THE HEADDER DETAIL OF THE NEW DOOR
 AND WINDOW.
  
 4)IF THIS APPLICATION IS FOR THE EXISTING BUILDING,
 THEN, THE ELEVATION DRAWINGS SHALL REFLECT ONLY THAT
 BUILDING.
  
 5)FBC. 106.1TWO SETS OF DRAWINGS SHALL BE SUBMITTED
 TO THE BUILDING DEPARTMENT FOR REVIEW.
  
 6)A WINDOW AND DOOR SCHEDULE IS REQUIRED WITH THE
 SIZE OF EACH OPENING.
  
 7)) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE
 FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF
 THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6) THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-08-24 Cont ID  
Sent By mawillia Date 2007-08-24 Time 12:56 Rev Time 0.00
Received By mawillia Date 2007-08-24 Time 12:27 Sent To  
Notes
2007-08-24 12:55:34******UNSAT*****
  
  
 1.WALL OPENINGS WHICH ARE REQUIRED TO HAVE FIRE
 PROTECTION RATING SHALL BE PROTECTED BY APPROVED,
 LISTED, LABELED FIRE DOOR ASSEMBLIES AND FIRE WINDOW
 ASSEMBLIES AND THEIR ACCOMPANYING HARDWARE IN
 ACCORDANCE WITH NFPA 80.
  
 2.ON THE APPROPIATE EXISTING BUILDING ELEVATION WHICH
 FRONTS NORTH DIXIE HIGHWAY, DISPLAY THE NUMERICAL
 ADDRESS ON THE BUILDING.AS PER WEST PALM BEACH CODE,
 THOSE NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO
 LESS THAN 1" IN WIDTH.ADDRESS TO BE VISIBLE BEFORE,
 DURING, AND AFTER SCOPE OF WORK.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-24 Cont ID  
Sent By mawillia Date 2007-08-24 Time 12:56 Rev Time 0.00
Received By mawillia Date 2007-07-28 Time 15:07 Sent To  
Notes
2007-08-10 11:04:04TO COMM BOARD #12
2007-07-28 15:07:59WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-21 Cont ID  
Sent By bpowell Date 2007-08-21 Time 08:19 Rev Time 0.00
Received By bpowell Date 2007-08-21 Time 08:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-20 Cont ID  
Sent By bpowell Date 2007-08-20 Time 14:44 Rev Time 0.00
Received By bpowell Date 2007-08-20 Time 14:44 Sent To  
Notes
2007-08-20 14:46:381. THE NORTH ARROW ON THE DEMO AND REMODEL PLAN IS
 FACING THE WRONG DIRECTION.
  