Plan Review Details - Permit 07070873
Plan Review Stops For Permit 07070873
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-29 Cont ID  
Sent By shill Date 2007-10-29 Time 17:08 Rev Time 0.00
Received By shill Date 2007-10-29 Time 17:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-05 Cont ID  
Sent By shill Date 2007-10-05 Time 14:53 Rev Time 0.00
Received By shill Date 2007-10-05 Time 14:53 Sent To  
Notes
2007-10-05 14:55:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.)A ROOFING CONTRACTOR IS REQUIRED TO APPLY FOR A
 ROOFING PERMIT.PLEASE PROVIDE WITH THIS APPLICATION.
  
 2.)THE NOA PROVIDED IS INCOMPLETE.PLEASE PROVIDE A
 COMPLETE NOA, TWO SETS.
  
 3.)INFORMATIONAL ONLY - THIS PERMIT HAS BEEN CHANGED
 FROM A ROOFING PERMIT TO A BUILDING PERMIT.WHEN
 APPLYING FOR A ROOFING PERMIT, REFER TO THIS PERMIT AS
 THE MASTER.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-26 Cont ID  
Sent By shill Date 2007-08-26 Time 14:34 Rev Time 0.00
Received By shill Date 2007-08-26 Time 14:34 Sent To  
Notes
2007-08-26 14:59:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE A CODE SUMMARY; BUILDING TYPE FBC6,
 BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION,
 OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY.
  
  
 2.)PROVIDE INFORMATION IN REGARDS TO THE EXISTING
 BUILDING CONSTRUCTION; SPECIFICALLY REGARDING THE
 TECTUM DECK.IT IS MY UNDERSTANDING THAT TECTUM HAS A
 CLASS A INTERIOR FINISH CLASSIFICATION AND IS
 CONSIDERED A NONCOMBUSTIBLE; YOU ARE REPLACING NON
 COMBUSTIBLE STRUCTURAL ELEMENTS (PERLINS AND ROOF
 SHEATHING) WITH COMBUSTIBLE.REQUIREMENTS ARE NOT
 READILY APPARENT AS YOU HAVE NOT PROVIDED ALMOST NO
 INFORMATION IN REGARDS TO THE EXISTING BUILDING; SEE
 OTHER COMMENTS.
  
 3.)PROVIDE A SITE PLAN SHOWING BUILDING LOCATION ON
 THE LOT AND LOCATION OF WORK PROPOSED.INCLUDE
 APPROXIMATE SQUARE FOOT AREA.FROM THE PLAN, IT
 APPEARS AS THOUGH THE ENTIRE ROOF DECK IS TO BE
 REPLACED; IS THIS CORRECT?
  
 4.)DECLARE EITHER LEVEL OF ALTERATION OR DECLARE THIS
 A "REPAIR" ON THE PLAN, FBC EB CHAPTER 3.
  
 5.)PROVIDE PRODUCT APPROVALS FOR THE ROOF.THE
 ENGINEERING LETTER FOR ENHANCED FASTENING REFERS TO AN
 NOA BUT THE EVALUATION REPORT WAS NOT PROVIDED.
  
 6.)PROVIDE CALCULATIONS FOR THE ROOF PRESSURES.
  
 7.)A ROOF PERMIT IS REQUIRED. SUBMIT AN APPLICATION.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 15:38 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 15:38 Sent To B
Notes
2007-10-03 15:38:21TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-26 Cont ID  
Sent By shill Date 2007-08-26 Time 15:00 Rev Time 0.00
Received By shill Date 2007-08-01 Time 08:43 Sent To  
Notes
2007-08-01 14:37:298-1-07--PER "SHILL" PLANS ARE NOT RE-ROOF.TO "MISC"
 BOX#1
2007-08-01 08:43:56TO "SHILL" DESK/PLANS WERE A PRE-INSPECT.REVIEW IS
 REQUIRED.