| 2007-08-26 14:59:57 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)PROVIDE A CODE SUMMARY; BUILDING TYPE FBC6, |
| | BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, |
| | OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY. |
| | |
| | |
| | 2.)PROVIDE INFORMATION IN REGARDS TO THE EXISTING |
| | BUILDING CONSTRUCTION; SPECIFICALLY REGARDING THE |
| | TECTUM DECK.IT IS MY UNDERSTANDING THAT TECTUM HAS A |
| | CLASS A INTERIOR FINISH CLASSIFICATION AND IS |
| | CONSIDERED A NONCOMBUSTIBLE; YOU ARE REPLACING NON |
| | COMBUSTIBLE STRUCTURAL ELEMENTS (PERLINS AND ROOF |
| | SHEATHING) WITH COMBUSTIBLE.REQUIREMENTS ARE NOT |
| | READILY APPARENT AS YOU HAVE NOT PROVIDED ALMOST NO |
| | INFORMATION IN REGARDS TO THE EXISTING BUILDING; SEE |
| | OTHER COMMENTS. |
| | |
| | 3.)PROVIDE A SITE PLAN SHOWING BUILDING LOCATION ON |
| | THE LOT AND LOCATION OF WORK PROPOSED.INCLUDE |
| | APPROXIMATE SQUARE FOOT AREA.FROM THE PLAN, IT |
| | APPEARS AS THOUGH THE ENTIRE ROOF DECK IS TO BE |
| | REPLACED; IS THIS CORRECT? |
| | |
| | 4.)DECLARE EITHER LEVEL OF ALTERATION OR DECLARE THIS |
| | A "REPAIR" ON THE PLAN, FBC EB CHAPTER 3. |
| | |
| | 5.)PROVIDE PRODUCT APPROVALS FOR THE ROOF.THE |
| | ENGINEERING LETTER FOR ENHANCED FASTENING REFERS TO AN |
| | NOA BUT THE EVALUATION REPORT WAS NOT PROVIDED. |
| | |
| | 6.)PROVIDE CALCULATIONS FOR THE ROOF PRESSURES. |
| | |
| | 7.)A ROOF PERMIT IS REQUIRED. SUBMIT AN APPLICATION. |
| | |
| | |