| 2007-08-31 15:01:53 | RESIDENTIALCONCRETE BLOCK FENCE BUILDING REVIEW FIRST |
| | CHECKLIST. |
| | REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND |
| | 2004 FBC WITH 2007 REVISIONS: |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13FLORIDA STATUTE. |
| | |
| | 2- PLANS CALL FOR 8'-0" HIGH CONCRETE BLOCK WALL, WHILE |
| | PERMIT APPLICATION CALLS FOR 6'-0" HIGH WALL. REVISE AS |
| | REQUIRED. |
| | ALSO, SEE ZONING COMMENTS REGARDING ALLOWED HEIGHT. |
| | |
| | 3- ACCORDINGTO THE SURVEY, THE FOOTING OF PROPOSED |
| | WALL IS ENCROACHING INTO THE NEIGHBOR'S PROPERTY. |
| | ENCROACHING IN TO NEIGHBOR'S PROPERTY IS NOT ALLOWED. |
| | REVISE FOOTING AS REQUIRED. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 4- PLANS TO HAVE ARCHITECT'S ORIGINAL SEAL, SIGNATURE |
| | AND DATE AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE AND |
| | SEC. 61G1-16.003 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 5- ARCHITECT'S TITLE BLOCK IS MISSING THE FOLLOWING |
| | REQUIRED INFORMATION AS REQUIRED BYCHAPTER 481 AND |
| | SEC. 61G1-16.004 OF FLORIDA ADMINISTRATIVE CODE: |
| | A) NAME OF ARCHITECT SEALING THE PLANS. |
| | B) FIRM LICENSE NUMBER. |
| | C) DATE PREPARED. |
| | |
| | 6- PLANS TO PROVIDECOMPLETE WIND LOAD SPECIFICATIONS |
| | AS REQUIRED BY SEC. 1609.1 FBC 2004. |
| | |
| | 7- REVISE GENERAL STRUCTURAL NOTES ON SHEET A1: |
| | A) NOTE #2NEED TO REFERENCE CITY OF WEST PALM |
| | BEACHAMENDMENTS,NOT PALM BEACH COUNTY AMENDMENTS. |
| | THESEARE TWO DIFFERENT JURISDICTIONS ANDAMENDMENTS |
| | ARE DIFFERENT TOO.REVISE NOTE AS REQUIRED. |
| | |
| | B) NOTE #3: REVISE THE MINIMUM COMPRESSIVE STRENGTH |
| | OF MASONRY UNITS. SEE SEC. R606.4 OF2004 FLORIDA |
| | RESIDENTIAL CODE AND REVISE AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |