| 2007-07-25 17:18:42 | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | TWO SETS OF PRODUCT APPROVAL SHALL BE SUBMITTED. |
| | _OK___1.)A NOTICE OF COMMENCEMENT MUST BE FILED |
| | WITH THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, |
| | FS713.13. |
| | |
| | ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION ON THE APPLICATION, SEE ATTACHED |
| | POLICY:MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / |
| | AREA OF EACH ROOF TYPE |
| | |
| | ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| | |
| | ____4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| | IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. |
| | |
| | ____5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES. |
| | |
| | ____ 6.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| | |
| | |
| | 2) FBC 1609.6.2.2THE SYSTEM SELECTED |
| | FROM THE SUBMITTED FLAT ROOF PRODUCT |
| | SHALL HAVE DESIGN PRESSURE NOT LESS THAN -89 PSF |
| | GENERAL LIMITATION #9PROHIBITS |
| | RATIONAL ANALYSIS OR EXTRAPOLATION TO |
| | ENHANCE THE UPLIFT PRESSURE AT PERIMETER |
| | AND CORNER AREAS BY REDUCING THE |
| | FASTENER SPACING IN THESE AREAS.EITHER |
| | SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT |
| | APPROVAL) THAT DOES NOT CITE GENERAL |
| | LIMITATION #9.ALTERNATIVELY IF THE |
| | SELECTED SYSTEM DOES CITE GENERAL |
| | LIMITATION #9, IT MUST HAVE A MAXIMUM |
| | DESIGN PRESSURE THAT EXCEEDS THE |
| | PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 |
| | PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR |
| | LESS). |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |
| | |
| | |