| 2007-07-31 11:32:29 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING ADDITIONS TO THE PLANS FOR | | | CODE COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | | | 2} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-31 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-07-31 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-07-31 |
Time |
11:19 |
Sent To |
PC |
|
| Notes |
|
|
|