Plan Review Details - Permit 07070800
Plan Review Stops For Permit 07070800
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-25 Cont ID  
Sent By mjacobs Date 2007-10-25 Time 08:59 Rev Time 0.00
Received By jleech Date 2007-10-25 Time 06:09 Sent To  
Notes
2007-10-27 10:19:46REVIEW DONE BY M JOCOBS J LEECH ENTERED ON ERROR
2007-10-25 08:58:44BUILDING PLAN REVIEW
 PERMIT: 07070800
 ADD: 1700 PBL BLVD #130
 CONT: HOLT LEE CONST. INC.
 TEL: (954)725-4881
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD
 ACTION: DENIED
  
 1)OK
 2)OK
 3)OK
 4)OK
 5)OK
 6)OK
 7)OK
 8)OK
 9)OK
 10)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-04 Cont ID  
Sent By mjacobs Date 2007-10-04 Time 15:06 Rev Time 0.00
Received By mjacobs Date 2007-10-04 Time 06:09 Sent To  
Notes
2007-10-04 15:06:55BUILDING PLAN REVIEW
 PERMIT: 07070800
 ADD: 1700 PBL BLVD #130
 CONT: HOLT LEE CONST. INC.
 TEL: (954)725-4881
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) OK
  
 3) OK
  
 4)SHEETS D1 AND D2 IS MISSING THE PRINTED NAME AND
 NUMBER OF THE PERSON SEALING THE PLANS.
 FAC. 61G1-16.004
  
 5)OK
  
 6)OK
  
 7)OK
  
 8)OK
  
 9)OK
  
 10)IF THERE IS A RECEPTIONIST COUNTER, IT SHALL MEET
 THE REQUIREMENTS OF FBC. 11-7 WHEREA PORTION OF THE
 MAIN COUNTER IS A MINIMUM OF 36 INCHES IN LENGTH AND A
 MAXIMUM HEIGHT OF 36 INCHES.
 **NOTED**
 IF THERE IS A WINDOW NEXT TO THE WAITING ROOM WHERE
 CUSTOMERS HAVE TO USE, IT SHALL MEET THE REQUIREMENTS
 OF SECTION 11-7. WALL TYPE ?C? ON SHEET D1 SHALL BE A
 MAXIMUM HEIGHT OF 36 INCHES. THE DESIGN OF ALL AREAS
 USED FOR BUSINESS TRANSACTIONS WITH THE PUBLIC SHALL
 COMPLY WITH SECTION 11-7. PROVIDE AN ELEVATION DETAIL
 DRAWING OF THE AREA WHERE THE WINDOW OR OPENING WILL BE
 INSTALLED. ANY GLASS USED IN THIS AREA SHALL BE
 SAFETY/TEMPERED GLASS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-11 Cont ID  
Sent By mjacobs Date 2007-08-11 Time 16:43 Rev Time 0.00
Received By mjacobs Date 2007-08-11 Time 12:44 Sent To  
Notes
2007-08-11 16:43:00BUILDING PLAN REVIEW
 PERMIT: 07070800
 ADD: 1700 PBL BLVD
 CONT: HOLT LEE CONST. INC.
 TEL: (954)725-4881
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) 2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE/WITH THE 2006 REVISIONS.
  
 4)SHEETS D1 AND D2 IS MISSING THE PRINTED NAME AND
 NUMBER OF THE PERSON SEALING THE PLANS.
 FAC. 61G1-16.004
  
 5)THE DBPR WEB-SITESHOWS MPA DESIGN INC INTERIOR
 DESIGN BUSINESS HAS A "DELIQUENT" STATUS. EITHER REMOVE
 THIS INFORMATION FROM THE DRAWINGS OR THE STATUS SHALL
 BE BROUGHT UP TO DATE WITH AN ACTIVE STATUS. SEE
 INFORMATION SHEET FROM DBPR IN PACKAGE.
  
 6)PROVIDE AN INTERIOR FINISH SCHEDULE FOR EACH ROOM
 INDICATING THE FLAME/SMOKE DEVELOPEMENT COMPLYING WITH
 FBC. 803 / 804 AND 805.
  
 7)ON SHEET A1 SHOW A CROSS CUT SECTION OF THE NEW
 SLAB IN RELATION TO THE DOOR THRESHOLD. FBC 11-4.13.8.
 ALSO SEE 11-4.5.2. INDICATE THE SLOPE.
  
 8)PROVIDE PRODUCT APPROVAL FOR THE NEW DOOR F-3.
 FBC.106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9)FBC. 11-4.24. THE SINK IN THE CONFERENCE ROOM SHALL
 A CLEAR FLOOR SPACE OF AT LEAST 30 INCHES BY 48 INCHES
 IN FRONT OF IT TO ALLOW FORWARD APPROACH. THE SPACE
 SHALL EXTEND A MAXIMUM OF 19 INCHES. UNDERNEATH THE
 SINK. NOTHING SHALL BLOCK THE FORWARD APPROACH.
  
 10)IF THERE IS A RECEPTIONIST COUNTER, IT SHALL MEET
 THE REQUIREMENTS OF FBC. 11-7WHEREA PORTION OF THE
 MAIN COUNTER IS A MINIMUM OF 36 INCHES IN LENGTH AND A
 MAXIMUM HEIGHT OF 36 INCHES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-03 Cont ID  
Sent By btrobaug Date 2007-10-03 Time 11:53 Rev Time 0.00
Received By btrobaug Date 2007-10-03 Time 08:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-17 Cont ID  
Sent By btrobaug Date 2007-08-17 Time 13:25 Rev Time 0.00
Received By btrobaug Date 2007-08-17 Time 12:47 Sent To  
Notes
2007-08-17 13:25:45 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONE COMPLIANT WITH THE FOLLOWING:
  
 1} PAGE #2 OF THE THE INPUT DATA REPORT INDICATES 1
 LUMINAIRE @ 3800 WATTS. PLEASE INDICATE COMPLIANCE WITH
 ALL FIXTURES TO BE USED. ALSO SUBMIT A LEGEND OF
 FIXTURE TYPES AND WATTAGES ON THE PLAN TO CORRELATE
 WITH THE ONES IN THE CALCULATIONS.
  
 2} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.SHEET #2 OF THE ENERGY GAUGE ONLY
 LISTS 1 FLUORESCENT, AND NOTE THAT ALTHOUGH A MANUAL
 CONTROL IS LISTED, IT MUST AUTOMATICALLY TURN LIGHTS
 OFF WITHIN 30 MINUTES OF ALL OCCUPANTS LEAVING THE
 SPACE PER 13-415.1ABC.1.2(A). DESIGNATE WHICH
 MANUFACTURER AND MODELS ARE BEING SPECIFIED FOR THIS
 PROJECT BY THE ENGINEER.
  
 3}PROVIDE EMERGENCY ILLUMINATION PER
 NFPA-101 7.8 (2003), AND CIRCUITED PER
 700.12 NEC. INDICATE SAME ON PLANS. THE BATTERY PACKS
 ARE NOT CIRCUITED WITH THE LOCAL, OR ANY,CIRCUIT.
  
 FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE
 FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE INDICATE
 THE CODE CYCLES UNDER WHICH THIS PLAN WAS DESIGNED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONE COMPLIANT WITH THE FOLLOWING:
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-10-10 Cont ID  
Sent By mawillia Date 2007-10-10 Time 16:22 Rev Time 0.00
Received By mawillia Date 2007-10-10 Time 15:47 Sent To  
Notes
2007-10-10 16:15:52*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS A1, E-1, E-2, AND FP-1
 WERE STAMPED, INITIALED, AND DATED.
  
  
  
  
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-08-20 Cont ID  
Sent By mawillia Date 2007-08-20 Time 12:18 Rev Time 0.00
Received By mawillia Date 2007-08-20 Time 11:11 Sent To  
Notes
2007-08-20 12:16:21*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 ACCESS TO/EGRESS FROM THE OTHER TENANT SPACES ON THE
 FLOOR, THE BUILDING, OR THE VICINITY THEREOF.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6.ON SHEET E-2, AMEND FIRE ALARM SYSTEM NOTE #13 TO
 REFLECT THAT DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM (AS PER LOCAL CODES).
  
 7.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR FIRE
 ALARM AND/OR FIRE SPRINKLER REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 11:57 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 11:57 Sent To  
Notes
2007-10-22 09:45:59TO "BOB"#12
2007-10-15 11:57:46WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 16:02 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 16:02 Sent To  
Notes
2007-09-24 15:49:13TO "BOB"#11
2007-09-17 16:02:49WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-20 Cont ID  
Sent By mawillia Date 2007-08-20 Time 11:12 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 13:59 Sent To  
Notes
2007-08-01 11:09:39TO "BOB"#6
2007-07-26 13:59:36WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-25 Cont ID  
Sent By tgordon Date 2007-10-25 Time 16:00 Rev Time 0.30
Received By tgordon Date 2007-10-25 Time 16:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-28 Cont ID  
Sent By tgordon Date 2007-09-28 Time 11:44 Rev Time 0.30
Received By tgordon Date 2007-09-28 Time 11:44 Sent To  
Notes
2007-09-28 11:51:50PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 8-2-07 NOTE #2. PLEASE
 SUBMIT COOLING LOAD CALCULATIONS, SEE 2004 FBC
 13-407.1.ABC.1. WHAT WAS SUBMITTED WERE ENERGY
 CALCULATIONS NOT COOLING LOAD CALCULATIONS.
  
 2) PAGE AC-2 ON ONE SET OF PLANS WERE NOT SEALED BY THE
 ENGINEER, SEE F.A.C. 61G15-23.002, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-02 Cont ID  
Sent By tgordon Date 2007-08-02 Time 13:30 Rev Time 0.40
Received By tgordon Date 2007-08-02 Time 13:30 Sent To  
Notes
2007-08-02 14:05:26*** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK. (MAG
 ENGINEERING INC. CA# 70615 IS NOT LISTED WITH DBPR,
 PLEASE CORRECT)
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 3) SHOW ON MECHANICAL PLAN HOW RETURN AIR IS GETTING BY
 THE CEILING TO THE OPEN PLENUM ABOVE TO GET BACK TO HP
 UNITS, SEE 2004 FBC/M 601.4.
  
 4) THE EXHAUST DUCTS FOR EF-1 AND 2 CAN NOT BE IN THE
 OPEN PLENUM, PER 2004 FBC/M 601.3 CONTAMINATION
 PREVENTION.
 EXHAUST DUCTS UNDER POSITIVE PRESSURE, CHIMNEYS, AND
 VENTS SHALL NOT EXTEND INTO OR PASS THROUGH DUCTS OR
 PLENUMS. PLEASE CORRECT.
  
 5) PLEASE SHOW ON THE MECHANICAL PLANS IF THE EXISTING
 EXHAUST DUCTS ARE POSITIVE OR NEGATIVE PRESSURE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-27 Cont ID  
Sent By jleech Date 2007-10-27 Time 10:20 Rev Time 0.00
Received By jleech Date 2007-10-27 Time 10:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-09 Cont ID  
Sent By jleech Date 2007-10-09 Time 09:14 Rev Time 0.00
Received By jleech Date 2007-10-09 Time 08:55 Sent To  
Notes
2007-10-09 09:13:44DENIED;
 PAGE D2 NOTE "H", THE DRAINAGE PIPING SHALL COMPLY WITH
 FBC-PLUMBING SECTION 704.5, DEAD ENDS. PLEASE READ
 SECTION AND CHANGE NOTE "H" TO COMPLY.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-06 Cont ID  
Sent By choops Date 2007-08-06 Time 16:56 Rev Time 0.00
Received By choops Date 2007-08-06 Time 16:56 Sent To  
Notes
2007-08-06 16:56:59*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.