| 2007-10-05 09:30:41 | RESIDENTIAL SCREEN ENCLOSURE BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | REVIEW DONE UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- IF USING THE AAF GUIDE TO ALUMINUM CONSTRUCTION IN |
| | HIGH WIND AREAS, THEN CORRECT DESIGN |
| | PROCEDURE/CHECKLIST SHALL BE USED.FORM SUBMITTED IS |
| | FOR CHAPTER 5/ATTACHED COVER. CORRECT FORM TO BE USED |
| | IS FOR CHAPTER 2/ SCREEN ROOMS (WITH SOLID ROOF).ALL |
| | DETAILS AND TABLES SUBMITTED ARE FROM CHAPTER 2, WHILE |
| | DESIGN FORM SUBMITTED IS FOR CHAPTER 5.MISMATCHING |
| | INFORMATION IS NOT ALLOWED. |
| | |
| | 2- DESIGN PROCEDURE/ CHECKLIST FORM MUST BE COMPLETE IN |
| | ITS ENTIRETY.FORM SUBMITTED IS MISSING A LOT OF |
| | INFORMATION. PROVIDE CORRECT FORM WITH ALL BLANKS |
| | FILLED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 3- DESIGN PROCEDURE/CHECKLIST SUBMITTED STATES THAT THE |
| | DESIGNER IS "AAF". THIS IS INCORRECT. NEED TO WRITE |
| | NAME OF THE ACTUAL DESIGNER WHO IS USING THIS MANUAL. |
| | |
| | 4- SPECIFY ROOF PITCH. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | 5- PRODUCT APPROVAL SUBMITTED IS FOR 4" OR 6" ROOF |
| | PANELS.DESIGN PROCEDURE/CHECKLIST SUBMITTED STATES 3" |
| | PANELS. MAKE SURE INFORMATION ON THE DESIGN |
| | PROCEDURE/CHECKLIST FORMIS COORDINATED WITH THIS |
| | PRODUCT APPROVAL AND RESPECTIVE TABLES IN CHAPTER 2 OF |
| | THE DESIGN MANUAL. |
| | |
| | 6- DRAWINGS TO CLEARLY INDICATE SCREEN ROOM DIMENSIONS |
| | AND ROOF OVERHANG DIMENSIONS TO VERIFY COMPLIANCE WITH |
| | PRODUCT APPROVAL AND CHAPTER 2 OF THE ALUMINUM DESIGN |
| | MANUAL. DRAWINGS SUBMITTED ARE MISSING THESE |
| | DIMENSIONS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 7- CLEARLY IDENTIFY ROOM TYPE (I OR II) TO MAKE SURE |
| | CORRECT TABLES ARE USED.SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 8- SPECIFY COLUMN SPACING ON SIDE WALLS OF SCREEN |
| | ENCLOSURE. DIMENSIONS NO GIVEN IN THE SUBMITTED |
| | DRAWINGS. |
| | |
| | 9- SPECIFY SIZE OF DOORS. INFORMATION NO GIVEN IN |
| | SUBMITTED DRAWINGS. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 10 SPECIFY THE DESIGN WIND PRESSURES FOR ALUMINUM |
| | SCREEN ENCLOSURES AS REQUIRED BY TABLE 2002.4 OF FBC |
| | 2004. |
| | |
| | 11- MAKE SURE CORRECT FOOTING SIZE IS USED. DESIGN |
| | PROCEDURE/CHECKLIST SUBMITTED STATES 8"X8" FOOTING, |
| | WHILECOPY OF PAGE 2-7 SUBMITTED SHOWS 8"X12" FOOTING |
| | HIGHLIGHTED. COORDINATE ALL INFORMATION AS REQUIRED TO |
| | AVOID CONFLICTS. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 12- VALUE DECLARED IN THE PERMIT APPLICATION ($8950.00) |
| | IS TOO LOW. UPDATE AS REQUIRED BY SEC. 108.3 CITY |
| | AMENDMENTS TO FBC 2004(REPEAT COMMENT). ADDITIONAL |
| | FEES WILL BE ACCESSED ACCORDINGLY. |
| | NOTE: CLARIFY IF DOING COMPLETE CONCRETE SLAB WITH |
| | CONCRETE EDGE FOOTING FOR SCREEN WALL OR JUST THE |
| | PERIMETER FOOTING.CONTRACT COPY CALLS FOR 12"X12" |
| | FOOTER, WHILE ALUMINUM MANUAL PAGE 2-7 SUBMITTED CALLS |
| | FOR CONCRETE SLAB FOUNDATION & MONOLITHIC FOOTING. ALL |
| | THIS INFORMATION MUST BE COORDINATED TO AVOID |
| | CONFLICTS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |