Plan Review Details - Permit 07070780
Plan Review Stops For Permit 07070780
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-24 Cont ID  
Sent By jgomez Date 2007-10-24 Time 10:10 Rev Time 0.00
Received By jgomez Date 2007-10-24 Time 07:38 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-23 Cont ID  
Sent By jgomez Date 2007-10-23 Time 12:47 Rev Time 0.00
Received By jgomez Date 2007-10-23 Time 12:47 Sent To PC
Notes
2007-10-23 13:07:10RESIDENTIAL SCREEN ENCLOSURE BUILDING REVIEW THIRD
 CHECKLIST.
 REVIEW DONE UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- DESIGN PROCEDURE/CHECKLIST SUBMITTED STATES THAT THE
 DESIGNER IS ROBERT S. MONSOUR, P.E. ALLDOCUMENTS
 THAT ARE PREPARED BY AN ENGINEER MUST HAVE THE
 ENGINEER'S SEAL AND ORIGINAL SIGNATURE. IN ADDITION
 COMPLETE ENGINEER'SINFORMATION NEEDS TO BE PROVIDED
 AS REQUIRED BY SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE.
  
 2- DESIGN PACKAGE IS MISSING THE LOCATION OF BRACING (3
 PAIRS AS SPECIFIEDON DESIGN PROCEDURE/CHECKLIST
 SUBMITTED). PROVIDESKETCH SHOWING LOCATION OF THE
 TREE BRACING PAIRS. ALSO, PROVIDE DETAILS FOR ROOF
 PANEL ATTACHMENTS ,ATTACHMENT OF SCREEN ENCLOSURE TO
 EXISTING WALL,AND ALL MISCELLANEOUS DETAILS THAT
 APPLY TO THE INSTALLATION OF THIS SCREEN ENCLOSURE.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 ANDSEC. 1609
 FBC 2004 REGARDING WIND LOADS.
  
 JULIOGOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-05 Cont ID  
Sent By jgomez Date 2007-10-05 Time 07:54 Rev Time 0.00
Received By jgomez Date 2007-10-04 Time 18:34 Sent To PC
Notes
2007-10-05 09:30:41RESIDENTIAL SCREEN ENCLOSURE BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW DONE UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- IF USING THE AAF GUIDE TO ALUMINUM CONSTRUCTION IN
 HIGH WIND AREAS, THEN CORRECT DESIGN
 PROCEDURE/CHECKLIST SHALL BE USED.FORM SUBMITTED IS
 FOR CHAPTER 5/ATTACHED COVER. CORRECT FORM TO BE USED
 IS FOR CHAPTER 2/ SCREEN ROOMS (WITH SOLID ROOF).ALL
 DETAILS AND TABLES SUBMITTED ARE FROM CHAPTER 2, WHILE
 DESIGN FORM SUBMITTED IS FOR CHAPTER 5.MISMATCHING
 INFORMATION IS NOT ALLOWED.
  
 2- DESIGN PROCEDURE/ CHECKLIST FORM MUST BE COMPLETE IN
 ITS ENTIRETY.FORM SUBMITTED IS MISSING A LOT OF
 INFORMATION. PROVIDE CORRECT FORM WITH ALL BLANKS
 FILLED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 3- DESIGN PROCEDURE/CHECKLIST SUBMITTED STATES THAT THE
 DESIGNER IS "AAF". THIS IS INCORRECT. NEED TO WRITE
 NAME OF THE ACTUAL DESIGNER WHO IS USING THIS MANUAL.
  
 4- SPECIFY ROOF PITCH. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 5- PRODUCT APPROVAL SUBMITTED IS FOR 4" OR 6" ROOF
 PANELS.DESIGN PROCEDURE/CHECKLIST SUBMITTED STATES 3"
 PANELS. MAKE SURE INFORMATION ON THE DESIGN
 PROCEDURE/CHECKLIST FORMIS COORDINATED WITH THIS
 PRODUCT APPROVAL AND RESPECTIVE TABLES IN CHAPTER 2 OF
 THE DESIGN MANUAL.
  
 6- DRAWINGS TO CLEARLY INDICATE SCREEN ROOM DIMENSIONS
 AND ROOF OVERHANG DIMENSIONS TO VERIFY COMPLIANCE WITH
 PRODUCT APPROVAL AND CHAPTER 2 OF THE ALUMINUM DESIGN
 MANUAL. DRAWINGS SUBMITTED ARE MISSING THESE
 DIMENSIONS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 7- CLEARLY IDENTIFY ROOM TYPE (I OR II) TO MAKE SURE
 CORRECT TABLES ARE USED.SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 8- SPECIFY COLUMN SPACING ON SIDE WALLS OF SCREEN
 ENCLOSURE. DIMENSIONS NO GIVEN IN THE SUBMITTED
 DRAWINGS.
  
 9- SPECIFY SIZE OF DOORS. INFORMATION NO GIVEN IN
 SUBMITTED DRAWINGS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 10 SPECIFY THE DESIGN WIND PRESSURES FOR ALUMINUM
 SCREEN ENCLOSURES AS REQUIRED BY TABLE 2002.4 OF FBC
 2004.
  
 11- MAKE SURE CORRECT FOOTING SIZE IS USED. DESIGN
 PROCEDURE/CHECKLIST SUBMITTED STATES 8"X8" FOOTING,
 WHILECOPY OF PAGE 2-7 SUBMITTED SHOWS 8"X12" FOOTING
 HIGHLIGHTED. COORDINATE ALL INFORMATION AS REQUIRED TO
 AVOID CONFLICTS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 12- VALUE DECLARED IN THE PERMIT APPLICATION ($8950.00)
 IS TOO LOW. UPDATE AS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004(REPEAT COMMENT). ADDITIONAL
 FEES WILL BE ACCESSED ACCORDINGLY.
 NOTE: CLARIFY IF DOING COMPLETE CONCRETE SLAB WITH
 CONCRETE EDGE FOOTING FOR SCREEN WALL OR JUST THE
 PERIMETER FOOTING.CONTRACT COPY CALLS FOR 12"X12"
 FOOTER, WHILE ALUMINUM MANUAL PAGE 2-7 SUBMITTED CALLS
 FOR CONCRETE SLAB FOUNDATION & MONOLITHIC FOOTING. ALL
 THIS INFORMATION MUST BE COORDINATED TO AVOID
 CONFLICTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-30 Cont ID  
Sent By jgomez Date 2007-08-30 Time 15:08 Rev Time 0.00
Received By jgomez Date 2007-08-30 Time 15:08 Sent To PC
Notes
2007-08-30 15:11:28RESIDENTIAL SCREEN ENCLOSURE BUILDING REVIEW FIRST
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- ENGINEER NEEDS TO SIGN AND SEAL SITE SPECIFIC
 DRAWINGS AS WELL.MASTER DRAWINGS FOR ALUMINUM
 STRUCTURESARE NOT ALLOWED.SEC. 106.1 CITY
 AMENDMENTS TO FBC 2004.
  
 3- CLEARLY IDENTIFY EACH DETAIL THAT APPLIES TO THIS
 JOB, INCLUDING FOOTING DETAILS AND SIZING, CONNECTIONS
 TO EXISTING STRUCTURE, ETC. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 4- VALUE DECLARED IN THE APPLICATIONIS TOO LOW.
 UPDATE VALUE AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS
 TO FBC 2004.INCLUDE COMPLETE SCOPE OF WORK TO BE
 PERFORMED INCLUDING CONCRETE SLAB FOOTING AND
 PROFESSIONAL DESIGNER FEES. OTHERWISE,FEES WILL BE
 ESTIMATED USING THE REFERENCES LISTED IN THE ABOVE
 MENTIONED SECTION.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR ROOF PANELS SPECIFIED ON PLANS.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS (NOT SIGNING AND SEALING), AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 7- RADON FEES OF $3.84 WILL BE ASSESED FOR NEW
 ADDITION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-09 Cont ID  
Sent By adarroug Date 2007-10-09 Time 15:46 Rev Time 0.00
Received By adarroug Date 2007-10-09 Time 15:46 Sent To B
Notes
2007-10-09 15:46:40TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 14:53 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 14:53 Sent To Z
Notes
2007-09-24 14:53:25TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-30 Cont ID  
Sent By jgomez Date 2007-08-30 Time 15:11 Rev Time 0.00
Received By jgomez Date 2007-07-27 Time 10:32 Sent To  
Notes
2007-07-27 10:32:31TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-28 Cont ID  
Sent By choops Date 2007-09-28 Time 13:13 Rev Time 0.00
Received By choops Date 2007-09-28 Time 13:13 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-30 Cont ID  
Sent By choops Date 2007-07-30 Time 08:27 Rev Time 0.00
Received By choops Date 2007-07-30 Time 08:27 Sent To B
Notes
2007-07-30 08:30:36***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT LEGIBLE
 SURVEY SHOWING THE SCOPE OF WORK (INDICATED WITH A
 PERMANENT UTENSIL, IN PLACE OF OR IN ADDITION TO,
 HIGHLIGHTER) WITH CLEAR SETBACK DIMENSIONS FROM
 PROPOSED PATIO TO ALL PROPERTY LINES.
  
 2)NEEDS NOTICE OF COMMENCEMENT.
  
 3)PROVIDE OVERHANG DIMENSIONS, IF ANY.
  
 4)PROVIDE AN HOA APPROVAL LETTER.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720