Plan Review Details - Permit 07070777
Plan Review Stops For Permit 07070777
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-10 Cont ID  
Sent By mjacobs Date 2007-12-10 Time 13:44 Rev Time 0.00
Received By mjacobs Date 2007-12-10 Time 12:52 Sent To  
Notes
2007-12-10 13:37:07PROVISOR: FBC:1210.2 ALL WALLS WITHIN 2 FEET OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH "HARD"
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE
 FLOOR. NOTE: PAINT ON DRYWALL IS NOT CONSIDERED A HARD
 SURFACE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-14 Cont ID  
Sent By mjacobs Date 2007-11-14 Time 07:56 Rev Time 0.00
Received By mjacobs Date 2007-11-14 Time 06:12 Sent To  
Notes
2007-11-14 07:56:48BUILDING PLAN REVIEW
 PERMIT: O7070777
 ADD: 795 BELVEDERE RD
 CONT:RICHARD LAWRLE INC
 TEL: (561)656-1128
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 1)OK
  
 2) 2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 **THIS INFORMATION SHALL BE SHOWN ON THE DRAWINGS.**
  
 3)OK
  
 4)OK
  
 5)OK
  
 6)OK
  
 7)DELETED
  
 8)THE TABLES IN THE DINING AREA AND AT THE COUNTER
 SHALL MEET ALL REQUIREMENTS OF FBC. SEC. 11-5. **FBC
 11.4.32.2 SHOW THE CLEAR FLOOR SPACE AT THE ACCESSIBLE
 COUNTER AS REQUIRED ISN SECTION 11.4.2.4. THE CLEAR
 FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE THAN19
 INCHES. (SEE FIG 45). KNEE CLEARANCE SHALL MEET THE
 REQUIREMENTS OF 11-4.32.3. TABLES AND COUNTERS SEE
 11-4.32.4.**
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-13 Cont ID  
Sent By mjacobs Date 2007-08-13 Time 16:29 Rev Time 0.00
Received By mjacobs Date 2007-08-13 Time 10:51 Sent To  
Notes
2007-08-13 12:10:03BUILDING PLAN REVIEW
 PERMIT: O7070777
 ADD: 795 BELVEDERE RD
 CONT:RICHARD LAWRLE INC
 TEL: (561)656-1128
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) 2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)SUBMIT AN EXISTING FLOOR PLAN OF THE EXISTING
 STRUCTURE AND INDICATE THE WALLS WHICH SHALL BE
 ALTERED. THEN, THE PROPOSED DRAWINGS SHALL INDICATE THE
 NEW WALL ON THE THE FLOOR PLAN. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED. FBC
 106.1.1
  
 4)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING.
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT
 . -------------------------------------
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
  
 5)SUBMIT A FINISH SCHEDULE INDICATINGTHE FLAME
 SPREAD/SMOKE DEVELOPMENT OF EACH ROOM IN ACCORDANCE
 WITH FBC SEC. 803/ 804 AND 805.
  
 6)NOTE:ANY STRUCTURAL ALTERATION SHALL COMPLY WITH
 FLORIDA EXISTING BUILDING CODE SECTION 707 AND CH.8.
  
 7)PROVIDE TWO SETS PRODUCT APPROVALS FOR THE NEW
 SERVICE WINDOW. FBC. 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 8)THE TABLES IN THE DINING AREA AND AT THE COUNTER
 SHALL MEET ALL REQUIREMENTS OF FBC. SEC. 11-5.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-12-27 Cont ID  
Sent By btrobaug Date 2007-12-27 Time 07:29 Rev Time 0.00
Received By btrobaug Date 2007-12-27 Time 07:21 Sent To  
Notes
2007-12-27 07:29:22 
  
 THE PLANS THAT WERE REVIIEWED ON 11/13/07 AND FOUND
 COMPLIANT, HAVE BEEN REINSERTED IN THE SET./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-12-04 Cont ID  
Sent By btrobaug Date 2007-12-04 Time 12:55 Rev Time 0.00
Received By btrobaug Date 2007-12-04 Time 12:10 Sent To  
Notes
2007-12-04 12:32:44 
 APPLICATION # 07070777
 ELECTRICAL PLAN REVIEW
 795 BELVEDERE ROAD
 12/4/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 THE FOLLOWING COMMENTS ARE REPEAT COMMENTS FROM
 8/16/07 REVIEW.
  
 3} 250.24(A)(5) LOAD-SIDE GROUNDING CONNECTIONS A
 GROUNDING CONNECTION SHALL NOT BE MADE TO ANY GROUNDED
 CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECTING
 MEANS EXCEPT AS OTHERWISE PERMITTED IN THIS ARTICLE.
 THE RISER HAS GROUNDING AT THE PANELS, IN VIOLATION OF
 THIS ARTICLE AND CREATING PARALLEL GROUNDING PATHS WITH
 THE NEUTRAL.
  
 11} THERE IS NO FIXTURE SCHEDULE TO CONFIRM LIGHTING
 DENSITIES PER CHAPTER 13, TABLE 13-415.2.C.1.
  
 12} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-13 Cont ID  
Sent By btrobaug Date 2007-11-13 Time 07:45 Rev Time 0.00
Received By btrobaug Date 2007-11-13 Time 06:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-16 Cont ID  
Sent By btrobaug Date 2007-08-16 Time 15:36 Rev Time 0.00
Received By btrobaug Date 2007-08-15 Time 17:25 Sent To  
Notes
2007-08-15 17:49:12 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS,2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 THE CODE CYCLES REFERENCED ON SHEET E2 ARE INCORRECT,
 SEE ABOVE.
  
 1} VERIFY THE SERVICE DISCONNECT RATING ( AMPS, VOLTS
 AND NUMBER OF PHASES) ON THE RISER DIAGRAM. 215.5 NEC.
  
 2} INDICATE THE CONDUIT AND CONDUCTOR SIZES FOR THE
 SERVICE, METER, DISCONNECT AND TO THE 400 AMP PANEL.
  
 3} 250.24(A)(5) LOAD-SIDE GROUNDING CONNECTIONS A
 GROUNDING CONNECTION SHALL NOT BE MADE TO ANY GROUNDED
 CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECTING
 MEANS EXCEPT AS OTHERWISE PERMITTED IN THIS ARTICLE.
 THE RISER HAS GROUNDING AT THE PANELS, IN VIOLATION OF
 THIS ARTICLE AND CREATING PARRALLEL GROUNDING PATHS
 WITH THE NUETRAL.
  
 4} PROVIDE A PANEL SCHEDULE FOR EP2.
  
 5} VERIFY THAT CIRCUIT EP-1,22 IS 120 VOLLTS AS LISTED
 ON THE SCHEDULE (SINGLE POLE BREAKER), 220 VOLTS AS
 LISTED ON THE RECEPTALE, AND COMPLIES WITH 422.16 FOR
 USE WITH A CORD. ALSO SEE 422.31(B).
  
 6} SEE 210.8(B)(2) FOR GFCI REQUIREMENTS IN THE
 KITCHEN, INDICATE SAME ON PLANS.
  
 7} SEE ARTICLE 210.23 FOR CORD AND PLUG CONNECTED
 EQUIPMENT.
  
 8} THE "EQUIPMENT LIST " ON SHEET A1 DOES NOT LIST THE
 NAMEPLATE RATINGS OF ALL ELECTRICAL EQUIPMENT TO BE
 INSTALLED.
  
 9} THE OUTSIDE LIGHTS ARE NOT SHOWN ON SHEET E1. THE
 NOTE ON SHEET A1 INDICATES A TOTAL OF 4000 WATTS, THE
 CIRCUIT ON SHEET E1 INDICATES 1800 WATTS, SHEET 5 ON
 THE ENERGY CALCS SHOWS 1500 WATTS. CORRELATE ALL
 LIGHTING.
  
 10} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A)
 (3).
  
 11} THERE IS NO FIXTURE SCHEDULE TO CONFIRM LIGHTING
 DENSITIES PER CHAPTER 13, TABLE 13-415.2.C.1.
  
 12} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.
  
 13} INDICATE COMPLIANCE WITH 220.43 FOR SHOW WINDOW
 LIGHTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-12-12 Cont ID  
Sent By mwennerg Date 2007-12-12 Time 10:24 Rev Time 0.00
Received By mwennerg Date 2007-12-12 Time 10:24 Sent To  
Notes
2007-12-12 10:26:06PLANS WERE APPROVED ON 11/16/07. SHEET A-2 WAS STAMPED,
 SIGNED AND DATED FOR COMPLIANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-11-16 Cont ID  
Sent By mwennerg Date 2007-11-16 Time 10:13 Rev Time 0.00
Received By mwennerg Date 2007-11-16 Time 10:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-08-20 Cont ID  
Sent By mawillia Date 2007-08-20 Time 13:55 Rev Time 0.00
Received By mawillia Date 2007-08-20 Time 12:29 Sent To  
Notes
2007-08-20 12:53:03*****DENIED*****
  
  
 01.PLEASE INDICATE THE EXISTING AS WELL AS THE
 PROJECTED USE AND OCCUPANCY CLASSIFICATION.
  
 02.PROVIDE THE OCCUPANT LOAD AS DETERMINED BASED UPON
 THE CHARACTERISTICS OF THE OCCUPANCY.
  
 03.NFPA 101-LIFE SAFETY CODE-2003 EDITION,NFPA 70 -
 2005 EDITION,NFPA 72 - 2002 EDITION,NFPA 90A - 2002
 EDITION SHALL BE REFERENCED.(AMEND SHEET E2)
  
 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 05.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS TO THE SAID PROPERTY OR THE VICINITY
 THEREOF.
  
 06.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 07.ON THE APPROPIATE EXTERIOR ELEVATION, DISPLAY THE
 NUMERICAL ADDRESS ON THE BUILDING FRONTING BELVEDERE
 ROAD.AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL
 BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH.
  
 08.PROVIDE A LIFE SAFETY PLAN WHICH SHOWS TRAVEL
 DISTANCE TO REACH AN EXIT AND THELOCATION OF FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 09.COOKING EQUIPMENT SHALL BE PROTECTED IN ACCORDANCE
 WITH NFPA 96 - 2001 EDITION.SEPARATE PLANS AND PERMIT
 WILL BE REQUIRED FOR THE HOOD INSTALLATION AND THE
 HOOD'S SUPPRESSION SYSTEM.
  
 10.SPECIFY THE INTERIOR FINISH MATERIAL MATERIALS FOR
 THE WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLANS EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-12-18 Cont ID  
Sent By jleech Date 2007-12-18 Time 08:26 Rev Time 0.00
Received By jleech Date 2007-12-18 Time 08:26 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-11-26 Cont ID  
Sent By jleech Date 2007-11-26 Time 08:59 Rev Time 0.00
Received By jleech Date 2007-11-26 Time 08:59 Sent To  
Notes
2007-11-26 09:10:08DENIED;
 1.CHANGE 2 # SYSTEM TO .5 # . NO REGULATORS REQUIRED.
 2.SHOW SEDIMENT TRAP ON GAS RISER DIAGRAM TO COMPLY
 WITH FBC FUEL GAS SECTION 408.4.
 3. GAS RISER DIAGRAM SHOWFIRE SAFTY VALVE OUT SIDE,
 DRAWINGS BY FLAMEGUARD FIRE EQUIPMENT SHOWS VALVE TO
 THE RIGHT OF THE HOOD. IF THE F.S.V. IS TO BE INSTALLED
 OUTSIDE SUBMIT INSTALLATION INSTRUCTIONS.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-08-13 Cont ID  
Sent By jleech Date 2007-08-13 Time 09:18 Rev Time 0.00
Received By jleech Date 2007-08-13 Time 09:18 Sent To  
Notes
2007-08-13 09:37:41DENIED;
 1. FBC-2004 BUILDING CHAPTER 1 ADMINISTRATION CODE
 SECTION 106.1.1 CONSTUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
 2. BTU'S FOR EQUIPMENT DO NOT MATCH EQUIPMENT LIST
 SHOWN ON PAGE A1 OF ALTERATION PLANS.
 3. SHOW A FLAT DRAWING OF GAS PIPING ON PLANS WITH
 LOCATION OF EMERGENCY AND SHUTOFF VALVES.
 4. A UNION IS REQUIRED DOWN STREAM OF THE MANUAL
 SHUTOFF VALVE SO EMERGENCYSHUTOFF VALVE NEEDS TO BE
 REPLACED.
 5.SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 6. TYPE OF GAS, (LP OR NATURAL)
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-14 Cont ID  
Sent By adarroug Date 2007-12-14 Time 14:53 Rev Time 0.00
Received By adarroug Date 2007-12-14 Time 14:53 Sent To  
Notes
2007-12-17 15:38:17TO "BOB"#12
2007-12-14 14:54:56WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 16:02 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 16:02 Sent To  
Notes
2007-12-03 14:20:52TO "BOB"#3
2007-11-28 16:03:25WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 16:11 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 16:11 Sent To  
Notes
2007-11-07 11:08:04TO "BOB"#16
2007-11-06 16:11:16WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-20 Cont ID  
Sent By mawillia Date 2007-08-20 Time 12:29 Rev Time 0.00
Received By mawillia Date 2007-07-27 Time 10:14 Sent To  
Notes
2007-08-07 18:01:35SENT TO BOB # 10 AS OF 08/07/2007 MMILLER
2007-07-27 10:17:24WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-04 Cont ID  
Sent By tgordon Date 2007-12-04 Time 15:51 Rev Time 0.25
Received By tgordon Date 2007-12-04 Time 15:51 Sent To  
Notes
2007-12-04 15:52:32PASSED REVIEW ON 11-26-07, RESTAMP.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-26 Cont ID  
Sent By tgordon Date 2007-11-26 Time 14:04 Rev Time 1.00
Received By tgordon Date 2007-11-26 Time 14:04 Sent To  
Notes
2007-11-26 14:07:52ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 (A) WALK-IN-COOLER (EXISTING).
 (B) KITCHEN HOOD (HAVE PLAN W/MASTER).
 (C) FIRE SUPPRESSION (NEED PLAN).
 ** SUBMIT PLANS FOR FIRE SUPRESSION WITH PERMIT
 APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-08 Cont ID  
Sent By tgordon Date 2007-08-08 Time 13:32 Rev Time 1.15
Received By tgordon Date 2007-08-08 Time 13:32 Sent To  
Notes
2007-08-08 15:04:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) ENERGY CALCULATIONS STATE THE A/C SYSTEM AS DESIGN
 EFF 13.00, THE MECHANICAL PLANS SHOW AN EXISTING SYSTEM
 8.7 SEER. IF THE A/C SYSTEM IS NOT TO BE CHANGED THEN
 YOU MAY WANT TO USE FORM 400C-04 FOR ENERGY
 CALCULATIONS LISTING ONLY THE ITEMS BEING INSTALLED, OR
 YOU MAY USE FORM 400A-04R AND REPLACE THE A/C SYSTEM.
 SEE 2004 FBC 13-400 ENERGY EFFICIENCY.
  
 2) THE PLAN FOR SHOP DRAWING HOOD "HVAC HOOD 1 OF 1"
 DOES NOT STATE IF THE HOOD IS U.L LISTED OR WHO THE
 MANUFACTURER IS. PLEASE PROVIDE THAT INFORMATION OR
 SHOW ON PLANS THAT THE HOOD COMPLIES WITH 2004 FBC/M
 SECTION 506 THROUGH 508.
  
 3) PLEASE CORRECT PLAN PAGE MP-1 "HVAC PLAN (EXISTING)"
 DETAIL TO SHOW ONLY THE EXISTING CONDITIONS WHICH WOULD
 NOT INCLUDE THE KITCHEN HOOD (ONLY EXISTING
 CONDITIONS). THEN ADD A DETAIL SHOWING PURPOSED
 CONDITIONS WITH THE KITCHEN HOOD.
  
 4) IN THE PURPOSED CONDITIONS SHOW THE A/C SUPPLY AIR
 CFM'S AT ALL SUPPLY AIR GRILLS AND THE BATHROOM EXHAUST
 CFM'S.. PLEASE BE AWARE WHEW CALCULATING THE AIR
 BALANCING OF 2004 FBC 13-409.1.ABC.3.6.1 NONRESIDENTIAL
 KITCHEN SPACES.
 NONRESIDENTIAL KITCHEN SPACE AND AREAS IN DINING ROOMS
 OR OPEN MALLS WHERE A KITCHEN EXHAUST HOOD IS REQUIRED
 BY NFPA 96 SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 1.BE DESIGNED WITH AN EXHAUST AIR AND MAKE UP AIR
 BALANCE SUCH THAT THE SPACE IS NEVER UNDER A POSITIVE
 PRESSURE, AND NEVER UNDER A NEGATIVE PRESSURE EXCEEDING
 0.02 INCH W.G. RELATIVE TO ALL INDOOR SPACES
 SURROUNDING THE KITCHEN SPACE, DURING ALL COOKING
 HOURS.
  
 5) PLEASE SHOW ON THE PLAN THE MEANS OF VENTILATION
 (OUT DOOR AIR). PROVIDE CALCULATION IF NATURAL, SEE
 2004 FBC/M 402.2, OR IF MECHANICAL MEAN SEE 403.2..
  
 6) PLEASE SHOW ON PLANS ALL NEW MECHANICAL WORK TO BE
 DONE AS NEW AND EXISTING AS EXISTING.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-12-18 Cont ID  
Sent By jleech Date 2007-12-18 Time 08:27 Rev Time 0.00
Received By jleech Date 2007-12-18 Time 08:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-12-13 Cont ID  
Sent By jleech Date 2007-12-13 Time 08:19 Rev Time 0.00
Received By jleech Date 2007-12-13 Time 08:18 Sent To  
Notes
2007-12-13 08:23:26DENIED;
 FROM LAST REVIEW, NOTE TWO HAS NOT BEEN ADDRESSED. THE
 GREASE TRAP MUST BE APPROVED BY THE UTILITIES
 DEPARTMENT. PLESE CONTACT RODNEY COMPO AT 822-2272.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-26 Cont ID  
Sent By jleech Date 2007-11-26 Time 09:37 Rev Time 0.00
Received By jleech Date 2007-11-26 Time 09:37 Sent To  
Notes
2007-11-26 09:48:33DENIED;
 1. PLANS MUST BE STAMPED BY DBPR DIVISION OF HOTEL AND
 RESTAURANTS AND REVIEW COMMENTSATTACHED TO THE PLANS
 BEFORE PLUMBING PLAN REVIEW APPROVAL.
 2. THE GREASE TRAP HAS NOT YET BEEN APPROVED BY THE
 UTILITY DEPARTMENT, CONTACT RODNEY COMPO AT 822-2272.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-08-13 Cont ID  
Sent By jleech Date 2007-08-13 Time 08:35 Rev Time 0.00
Received By jleech Date 2007-08-13 Time 07:43 Sent To  
Notes
2007-08-13 09:15:42DENIED;
 1.PLANS MUST BE REVIEWED BY, DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATIONS DIVISION OF HOTELS AND
 RESTAURANTS.PHONE NUMBER IS
 (850)487-1395. WHEN PLANS ARE APPROVED RESUBMIT STAMPED
 PLANS WITH COMMENTS.
 2. GREASE TRAP MUST BE SIZED BY THE CITY'S UTILITY
 DEPARTMENT, TRAP MUST COMPLY WITH WASTE ORDINANCE #
 3434. CONTACT RODNEY COMPO.
 PHONE NUMBER IS 822-2272 OR FAX 822-2279.
 3. A MOP SINK IS REQUIRED BY FBC-2004 PLUMBING TABLE
 403.1, MINIMUM PLUMBING FIXTURES.
 4.THE 3 COMPARTMENT SINK MUST BE INDIRECT, SEE SECTION
 802.1, TO A FLOOR SINK.
 5. BATHROOMS DO NOT MEET HANDICAP REQUIREMENTS. SEE
 FBC-2004 EXISTING BUILDING SECTION 806. MINIMUM WITH OF
 BATHROOMS WOULD BE 62", SEE PLUMBING CODESECTION
 405.3.1. ALSO SHOW TURNING RADIUS IN BATHROOMS.
 6. EQUIPMENT LIST, PAGE A1 SHOWS 10843 BTU'S TO THE
 SOFT DRINK-ICEMAKER. PLEASE CHANGE OR SUBMIT
 MANUFACTURE'S SPECIFICATIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-14 Cont ID  
Sent By choops Date 2007-08-14 Time 10:41 Rev Time 0.00
Received By choops Date 2007-08-14 Time 10:41 Sent To  
Notes
2007-08-14 10:41:50*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved