| Plan Review Stops For Permit 07070777 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-12-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-10 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-10 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2007-12-10 13:37:07 | PROVISOR: FBC:1210.2 ALL WALLS WITHIN 2 FEET OF URINALS | | | AND WATER CLOSETS SHALL HAVE A SMOOTH "HARD" | | | NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE | | | FLOOR. NOTE: PAINT ON DRYWALL IS NOT CONSIDERED A HARD | | | SURFACE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-14 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-11-14 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-11-14 |
Time |
06:12 |
Sent To |
|
|
| Notes |
| 2007-11-14 07:56:48 | BUILDING PLAN REVIEW | | | PERMIT: O7070777 | | | ADD: 795 BELVEDERE RD | | | CONT:RICHARD LAWRLE INC | | | TEL: (561)656-1128 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND | | | ACTION: DENIED | | | | | | 1)OK | | | | | | 2) 2004 FBC EXISTING | | | 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | **THIS INFORMATION SHALL BE SHOWN ON THE DRAWINGS.** | | | | | | 3)OK | | | | | | 4)OK | | | | | | 5)OK | | | | | | 6)OK | | | | | | 7)DELETED | | | | | | 8)THE TABLES IN THE DINING AREA AND AT THE COUNTER | | | SHALL MEET ALL REQUIREMENTS OF FBC. SEC. 11-5. **FBC | | | 11.4.32.2 SHOW THE CLEAR FLOOR SPACE AT THE ACCESSIBLE | | | COUNTER AS REQUIRED ISN SECTION 11.4.2.4. THE CLEAR | | | FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE THAN19 | | | INCHES. (SEE FIG 45). KNEE CLEARANCE SHALL MEET THE | | | REQUIREMENTS OF 11-4.32.3. TABLES AND COUNTERS SEE | | | 11-4.32.4.** | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-13 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-13 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2007-08-13 12:10:03 | BUILDING PLAN REVIEW | | | PERMIT: O7070777 | | | ADD: 795 BELVEDERE RD | | | CONT:RICHARD LAWRLE INC | | | TEL: (561)656-1128 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2) 2004 FBC EXISTING | | | 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | | | 3)SUBMIT AN EXISTING FLOOR PLAN OF THE EXISTING | | | STRUCTURE AND INDICATE THE WALLS WHICH SHALL BE | | | ALTERED. THEN, THE PROPOSED DRAWINGS SHALL INDICATE THE | | | NEW WALL ON THE THE FLOOR PLAN. CONSTRUCTION DOCUMENTS | | | SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED. FBC | | | 106.1.1 | | | | | | 4)110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR | | | RECORD KEEPING. | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PROJECT IS DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED | | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT | | | . ------------------------------------- | | | ) NUMBER OF ROOMS | | | ) SQ. FT. FOOTPRINT | | | | | | 5)SUBMIT A FINISH SCHEDULE INDICATINGTHE FLAME | | | SPREAD/SMOKE DEVELOPMENT OF EACH ROOM IN ACCORDANCE | | | WITH FBC SEC. 803/ 804 AND 805. | | | | | | 6)NOTE:ANY STRUCTURAL ALTERATION SHALL COMPLY WITH | | | FLORIDA EXISTING BUILDING CODE SECTION 707 AND CH.8. | | | | | | 7)PROVIDE TWO SETS PRODUCT APPROVALS FOR THE NEW | | | SERVICE WINDOW. FBC. 106.3.3* PRODUCT APPROVALS- 2004 | | | THOSE PRODUCTS THAT ARE RGULATED BY DCA RULE 9B-72 | | | SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | 8)THE TABLES IN THE DINING AREA AND AT THE COUNTER | | | SHALL MEET ALL REQUIREMENTS OF FBC. SEC. 11-5. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-12-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-12-27 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-12-27 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2007-12-27 07:29:22 | | | | | | | THE PLANS THAT WERE REVIIEWED ON 11/13/07 AND FOUND | | | COMPLIANT, HAVE BEEN REINSERTED IN THE SET./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-12-04 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-12-04 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2007-12-04 12:32:44 | | | | APPLICATION # 07070777 | | | ELECTRICAL PLAN REVIEW | | | 795 BELVEDERE ROAD | | | 12/4/07 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE | | | NOTED. | | | | | | THE FOLLOWING COMMENTS ARE REPEAT COMMENTS FROM | | | 8/16/07 REVIEW. | | | | | | 3} 250.24(A)(5) LOAD-SIDE GROUNDING CONNECTIONS A | | | GROUNDING CONNECTION SHALL NOT BE MADE TO ANY GROUNDED | | | CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECTING | | | MEANS EXCEPT AS OTHERWISE PERMITTED IN THIS ARTICLE. | | | THE RISER HAS GROUNDING AT THE PANELS, IN VIOLATION OF | | | THIS ARTICLE AND CREATING PARALLEL GROUNDING PATHS WITH | | | THE NEUTRAL. | | | | | | 11} THERE IS NO FIXTURE SCHEDULE TO CONFIRM LIGHTING | | | DENSITIES PER CHAPTER 13, TABLE 13-415.2.C.1. | | | | | | 12} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR | | | SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE | | | SHOWN ON THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-11-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-11-13 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-11-13 |
Time |
06:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-08-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-08-16 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-08-15 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2007-08-15 17:49:12 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS,2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | THE CODE CYCLES REFERENCED ON SHEET E2 ARE INCORRECT, | | | SEE ABOVE. | | | | | | 1} VERIFY THE SERVICE DISCONNECT RATING ( AMPS, VOLTS | | | AND NUMBER OF PHASES) ON THE RISER DIAGRAM. 215.5 NEC. | | | | | | 2} INDICATE THE CONDUIT AND CONDUCTOR SIZES FOR THE | | | SERVICE, METER, DISCONNECT AND TO THE 400 AMP PANEL. | | | | | | 3} 250.24(A)(5) LOAD-SIDE GROUNDING CONNECTIONS A | | | GROUNDING CONNECTION SHALL NOT BE MADE TO ANY GROUNDED | | | CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECTING | | | MEANS EXCEPT AS OTHERWISE PERMITTED IN THIS ARTICLE. | | | THE RISER HAS GROUNDING AT THE PANELS, IN VIOLATION OF | | | THIS ARTICLE AND CREATING PARRALLEL GROUNDING PATHS | | | WITH THE NUETRAL. | | | | | | 4} PROVIDE A PANEL SCHEDULE FOR EP2. | | | | | | 5} VERIFY THAT CIRCUIT EP-1,22 IS 120 VOLLTS AS LISTED | | | ON THE SCHEDULE (SINGLE POLE BREAKER), 220 VOLTS AS | | | LISTED ON THE RECEPTALE, AND COMPLIES WITH 422.16 FOR | | | USE WITH A CORD. ALSO SEE 422.31(B). | | | | | | 6} SEE 210.8(B)(2) FOR GFCI REQUIREMENTS IN THE | | | KITCHEN, INDICATE SAME ON PLANS. | | | | | | 7} SEE ARTICLE 210.23 FOR CORD AND PLUG CONNECTED | | | EQUIPMENT. | | | | | | 8} THE "EQUIPMENT LIST " ON SHEET A1 DOES NOT LIST THE | | | NAMEPLATE RATINGS OF ALL ELECTRICAL EQUIPMENT TO BE | | | INSTALLED. | | | | | | 9} THE OUTSIDE LIGHTS ARE NOT SHOWN ON SHEET E1. THE | | | NOTE ON SHEET A1 INDICATES A TOTAL OF 4000 WATTS, THE | | | CIRCUIT ON SHEET E1 INDICATES 1800 WATTS, SHEET 5 ON | | | THE ENERGY CALCS SHOWS 1500 WATTS. CORRELATE ALL | | | LIGHTING. | | | | | | 10} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | | 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A) | | | (3). | | | | | | 11} THERE IS NO FIXTURE SCHEDULE TO CONFIRM LIGHTING | | | DENSITIES PER CHAPTER 13, TABLE 13-415.2.C.1. | | | | | | 12} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR | | | SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE | | | SHOWN ON THE PLAN. | | | | | | 13} INDICATE COMPLIANCE WITH 220.43 FOR SHOW WINDOW | | | LIGHTING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-12-12 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-12-12 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-12-12 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2007-12-12 10:26:06 | PLANS WERE APPROVED ON 11/16/07. SHEET A-2 WAS STAMPED, | | | SIGNED AND DATED FOR COMPLIANCE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-11-16 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-11-16 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-11-16 |
Time |
10:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-08-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-20 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-20 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2007-08-20 12:53:03 | *****DENIED***** | | | | | | | | | 01.PLEASE INDICATE THE EXISTING AS WELL AS THE | | | PROJECTED USE AND OCCUPANCY CLASSIFICATION. | | | | | | 02.PROVIDE THE OCCUPANT LOAD AS DETERMINED BASED UPON | | | THE CHARACTERISTICS OF THE OCCUPANCY. | | | | | | 03.NFPA 101-LIFE SAFETY CODE-2003 EDITION,NFPA 70 - | | | 2005 EDITION,NFPA 72 - 2002 EDITION,NFPA 90A - 2002 | | | EDITION SHALL BE REFERENCED.(AMEND SHEET E2) | | | | | | 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 05.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | EMERGENCY ACCESS TO THE SAID PROPERTY OR THE VICINITY | | | THEREOF. | | | | | | 06.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 07.ON THE APPROPIATE EXTERIOR ELEVATION, DISPLAY THE | | | NUMERICAL ADDRESS ON THE BUILDING FRONTING BELVEDERE | | | ROAD.AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL | | | BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN | | | WIDTH. | | | | | | 08.PROVIDE A LIFE SAFETY PLAN WHICH SHOWS TRAVEL | | | DISTANCE TO REACH AN EXIT AND THELOCATION OF FIRE | | | EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE. | | | | | | 09.COOKING EQUIPMENT SHALL BE PROTECTED IN ACCORDANCE | | | WITH NFPA 96 - 2001 EDITION.SEPARATE PLANS AND PERMIT | | | WILL BE REQUIRED FOR THE HOOD INSTALLATION AND THE | | | HOOD'S SUPPRESSION SYSTEM. | | | | | | 10.SPECIFY THE INTERIOR FINISH MATERIAL MATERIALS FOR | | | THE WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR | | | CLASS C. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE IN THE PLANS EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-12-18 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-12-18 |
Time |
08:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2007-11-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-11-26 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-11-26 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2007-11-26 09:10:08 | DENIED; | | | 1.CHANGE 2 # SYSTEM TO .5 # . NO REGULATORS REQUIRED. | | | 2.SHOW SEDIMENT TRAP ON GAS RISER DIAGRAM TO COMPLY | | | WITH FBC FUEL GAS SECTION 408.4. | | | 3. GAS RISER DIAGRAM SHOWFIRE SAFTY VALVE OUT SIDE, | | | DRAWINGS BY FLAMEGUARD FIRE EQUIPMENT SHOWS VALVE TO | | | THE RIGHT OF THE HOOD. IF THE F.S.V. IS TO BE INSTALLED | | | OUTSIDE SUBMIT INSTALLATION INSTRUCTIONS. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-08-13 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-08-13 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2007-08-13 09:37:41 | DENIED; | | | 1. FBC-2004 BUILDING CHAPTER 1 ADMINISTRATION CODE | | | SECTION 106.1.1 CONSTUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED. | | | 2. BTU'S FOR EQUIPMENT DO NOT MATCH EQUIPMENT LIST | | | SHOWN ON PAGE A1 OF ALTERATION PLANS. | | | 3. SHOW A FLAT DRAWING OF GAS PIPING ON PLANS WITH | | | LOCATION OF EMERGENCY AND SHUTOFF VALVES. | | | 4. A UNION IS REQUIRED DOWN STREAM OF THE MANUAL | | | SHUTOFF VALVE SO EMERGENCYSHUTOFF VALVE NEEDS TO BE | | | REPLACED. | | | 5.SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | 6. TYPE OF GAS, (LP OR NATURAL) | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-12-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-14 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-14 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2007-12-17 15:38:17 | TO "BOB"#12 | | 2007-12-14 14:54:56 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-11-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-28 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-28 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2007-12-03 14:20:52 | TO "BOB"#3 | | 2007-11-28 16:03:25 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-11-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-06 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-06 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2007-11-07 11:08:04 | TO "BOB"#16 | | 2007-11-06 16:11:16 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-08-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-20 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-27 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2007-08-07 18:01:35 | SENT TO BOB # 10 AS OF 08/07/2007 MMILLER | | 2007-07-27 10:17:24 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-04 |
Time |
15:51 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-12-04 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2007-12-04 15:52:32 | PASSED REVIEW ON 11-26-07, RESTAMP. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-11-26 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-11-26 |
Time |
14:04 |
Rev Time |
1.00 |
| Received By |
tgordon |
Date |
2007-11-26 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2007-11-26 14:07:52 | ADDITIONAL MECHANICAL PERMITS REQUIRED FOR | | | (A) WALK-IN-COOLER (EXISTING). | | | (B) KITCHEN HOOD (HAVE PLAN W/MASTER). | | | (C) FIRE SUPPRESSION (NEED PLAN). | | | ** SUBMIT PLANS FOR FIRE SUPRESSION WITH PERMIT | | | APPLICATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-08-08 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-08-08 |
Time |
13:32 |
Rev Time |
1.15 |
| Received By |
tgordon |
Date |
2007-08-08 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2007-08-08 15:04:22 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER | | | 1 CITY OF WEST PALM BEACH AMENDMENTS. | | | | | | *** DENIED *** | | | 1) ENERGY CALCULATIONS STATE THE A/C SYSTEM AS DESIGN | | | EFF 13.00, THE MECHANICAL PLANS SHOW AN EXISTING SYSTEM | | | 8.7 SEER. IF THE A/C SYSTEM IS NOT TO BE CHANGED THEN | | | YOU MAY WANT TO USE FORM 400C-04 FOR ENERGY | | | CALCULATIONS LISTING ONLY THE ITEMS BEING INSTALLED, OR | | | YOU MAY USE FORM 400A-04R AND REPLACE THE A/C SYSTEM. | | | SEE 2004 FBC 13-400 ENERGY EFFICIENCY. | | | | | | 2) THE PLAN FOR SHOP DRAWING HOOD "HVAC HOOD 1 OF 1" | | | DOES NOT STATE IF THE HOOD IS U.L LISTED OR WHO THE | | | MANUFACTURER IS. PLEASE PROVIDE THAT INFORMATION OR | | | SHOW ON PLANS THAT THE HOOD COMPLIES WITH 2004 FBC/M | | | SECTION 506 THROUGH 508. | | | | | | 3) PLEASE CORRECT PLAN PAGE MP-1 "HVAC PLAN (EXISTING)" | | | DETAIL TO SHOW ONLY THE EXISTING CONDITIONS WHICH WOULD | | | NOT INCLUDE THE KITCHEN HOOD (ONLY EXISTING | | | CONDITIONS). THEN ADD A DETAIL SHOWING PURPOSED | | | CONDITIONS WITH THE KITCHEN HOOD. | | | | | | 4) IN THE PURPOSED CONDITIONS SHOW THE A/C SUPPLY AIR | | | CFM'S AT ALL SUPPLY AIR GRILLS AND THE BATHROOM EXHAUST | | | CFM'S.. PLEASE BE AWARE WHEW CALCULATING THE AIR | | | BALANCING OF 2004 FBC 13-409.1.ABC.3.6.1 NONRESIDENTIAL | | | KITCHEN SPACES. | | | NONRESIDENTIAL KITCHEN SPACE AND AREAS IN DINING ROOMS | | | OR OPEN MALLS WHERE A KITCHEN EXHAUST HOOD IS REQUIRED | | | BY NFPA 96 SHALL COMPLY WITH THE FOLLOWING | | | REQUIREMENTS: | | | 1.BE DESIGNED WITH AN EXHAUST AIR AND MAKE UP AIR | | | BALANCE SUCH THAT THE SPACE IS NEVER UNDER A POSITIVE | | | PRESSURE, AND NEVER UNDER A NEGATIVE PRESSURE EXCEEDING | | | 0.02 INCH W.G. RELATIVE TO ALL INDOOR SPACES | | | SURROUNDING THE KITCHEN SPACE, DURING ALL COOKING | | | HOURS. | | | | | | 5) PLEASE SHOW ON THE PLAN THE MEANS OF VENTILATION | | | (OUT DOOR AIR). PROVIDE CALCULATION IF NATURAL, SEE | | | 2004 FBC/M 402.2, OR IF MECHANICAL MEAN SEE 403.2.. | | | | | | 6) PLEASE SHOW ON PLANS ALL NEW MECHANICAL WORK TO BE | | | DONE AS NEW AND EXISTING AS EXISTING. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL: [email protected]. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-12-18 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-12-18 |
Time |
08:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-12-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-12-13 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-12-13 |
Time |
08:18 |
Sent To |
|
|
| Notes |
| 2007-12-13 08:23:26 | DENIED; | | | FROM LAST REVIEW, NOTE TWO HAS NOT BEEN ADDRESSED. THE | | | GREASE TRAP MUST BE APPROVED BY THE UTILITIES | | | DEPARTMENT. PLESE CONTACT RODNEY COMPO AT 822-2272. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-11-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-11-26 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-11-26 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2007-11-26 09:48:33 | DENIED; | | | 1. PLANS MUST BE STAMPED BY DBPR DIVISION OF HOTEL AND | | | RESTAURANTS AND REVIEW COMMENTSATTACHED TO THE PLANS | | | BEFORE PLUMBING PLAN REVIEW APPROVAL. | | | 2. THE GREASE TRAP HAS NOT YET BEEN APPROVED BY THE | | | UTILITY DEPARTMENT, CONTACT RODNEY COMPO AT 822-2272. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-08-13 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-08-13 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2007-08-13 09:15:42 | DENIED; | | | 1.PLANS MUST BE REVIEWED BY, DEPARTMENT OF BUSINESS AND | | | PROFESSIONAL REGULATIONS DIVISION OF HOTELS AND | | | RESTAURANTS.PHONE NUMBER IS | | | (850)487-1395. WHEN PLANS ARE APPROVED RESUBMIT STAMPED | | | PLANS WITH COMMENTS. | | | 2. GREASE TRAP MUST BE SIZED BY THE CITY'S UTILITY | | | DEPARTMENT, TRAP MUST COMPLY WITH WASTE ORDINANCE # | | | 3434. CONTACT RODNEY COMPO. | | | PHONE NUMBER IS 822-2272 OR FAX 822-2279. | | | 3. A MOP SINK IS REQUIRED BY FBC-2004 PLUMBING TABLE | | | 403.1, MINIMUM PLUMBING FIXTURES. | | | 4.THE 3 COMPARTMENT SINK MUST BE INDIRECT, SEE SECTION | | | 802.1, TO A FLOOR SINK. | | | 5. BATHROOMS DO NOT MEET HANDICAP REQUIREMENTS. SEE | | | FBC-2004 EXISTING BUILDING SECTION 806. MINIMUM WITH OF | | | BATHROOMS WOULD BE 62", SEE PLUMBING CODESECTION | | | 405.3.1. ALSO SHOW TURNING RADIUS IN BATHROOMS. | | | 6. EQUIPMENT LIST, PAGE A1 SHOWS 10843 BTU'S TO THE | | | SOFT DRINK-ICEMAKER. PLEASE CHANGE OR SUBMIT | | | MANUFACTURE'S SPECIFICATIONS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-08-14 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-08-14 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-08-14 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2007-08-14 10:41:50 | *VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | | IMPROVEMENT VALUE. |
|
|