Plan Review Details - Permit 07070776
Plan Review Stops For Permit 07070776
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-15 Cont ID  
Sent By shill Date 2007-09-15 Time 10:28 Rev Time 0.00
Received By shill Date 2007-09-15 Time 10:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-02 Cont ID  
Sent By shill Date 2007-09-02 Time 14:33 Rev Time 0.00
Received By shill Date 2007-09-02 Time 14:33 Sent To  
Notes
2007-09-02 14:35:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.)SEE PREVIOUS LIST IN REGARDS TO IMPACT PROTECTION
 REQUIREMENTS.CONTRACTOR RESPONDED BY SUBMITTING THE
 SAME PAPERWORK WITH A NOTE "THESE WINDOWS ARE IMPACT".
 SEE SHEET 1 OF 4 OF THE PRODUCT APPROVAL, GENERAL NOTE
 7, "THESE WINDOW SYSTEMS ARE NON-IMPACT RATED & MUST BE
 SHUTTERED WHERE REQUIRED BY CODE." I HAVE
 HIGHLIGHTED THIS FOR YOU; SEE ATTACHED.PLEASE
 ADDRESS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-21 Cont ID  
Sent By shill Date 2007-08-21 Time 09:25 Rev Time 0.00
Received By shill Date 2007-08-21 Time 09:25 Sent To  
Notes
2007-08-21 09:27:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 ***WINDOW OR DOOR PERMIT APPLICATION, ONLY CHECKED
 ITEMS APPLY***
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 ____2.PROVIDE BUILDING HEIGHT.DESIGN PRESSURES
 FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2.PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE.
 IF FBC COMPLIANT IMPACT PROTECTION WAS ALREADY
 INSTALLED ON THIS BUILDING, PROVIDE A PERMIT NUMBER FOR
 THE SHUTTERS.
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____6.PROVIDE A FLOOR PLAN SHOWING: WINDOW
 LOCATIONS, SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE
 EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE
 FOR BEDROOMS, FBC R310, FBC EB 505.1.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-11 Time 16:37 Rev Time 0.00
Received By adarroug Date 2007-09-11 Time 16:37 Sent To B
Notes
2007-09-11 16:37:52TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 12:19 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 12:19 Sent To B
Notes
2007-08-30 12:19:31TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-21 Cont ID  
Sent By shill Date 2007-08-21 Time 09:27 Rev Time 0.00
Received By shill Date 2007-07-27 Time 10:40 Sent To  
Notes
2007-07-27 10:41:04TO "MISC" BOX#1