Plan Review Details - Permit 07070741
Plan Review Stops For Permit 07070741
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-08-11 Cont ID  
Sent By jgomez Date 2008-08-11 Time 09:52 Rev Time 0.00
Received By jgomez Date 2008-08-11 Time 09:52 Sent To PC
Notes
2008-08-11 09:53:12ENERGY CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-07-23 Cont ID  
Sent By jgomez Date 2008-07-23 Time 14:48 Rev Time 0.00
Received By jgomez Date 2008-07-23 Time 14:48 Sent To PC
Notes
2008-07-23 14:51:22ENERGY CALCULATIONS BUILDING REVIEW CHECKLIST.
  
 1-ENERGY CALCULATIONS ARE TAKING THE CROSS
 VENTILATION CREDIT.SEE MECHANICAL PLAN REVIEWER
 COMMENTS AND REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-07-03 Cont ID  
Sent By jgomez Date 2008-07-03 Time 16:55 Rev Time 0.00
Received By jgomez Date 2008-07-03 Time 16:55 Sent To PC
Notes
2008-07-03 17:00:36ENERGY CALCULATIONS SUBMITTAL:
 1-ENERGY CALCULATIONS ARE TAKEN THE CREDIT FOR
 "WHITE ROOF".NEED TO PROVIDE COMPLIANCE WITH THE
 WHITE ROOF CREDITREQUIREMENTS OF SEC. 13-607.1.A.5,
 SEC. 13-607.2.A.3.6 AND SEC. 13-608.2.A.3.7OF 2004
 FBC. READ THOSE CODE SECTIONS AND PROVIDE REQUIRED
 INFORMATION
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-06-11 Cont ID  
Sent By jgomez Date 2008-06-11 Time 13:05 Rev Time 0.00
Received By jgomez Date 2008-06-11 Time 10:42 Sent To M
Notes
2008-06-11 13:12:28BUILDING REVISION CHECKLIST:
 1- ENERGY CALCULATIONS WERE REVISED AND NEW FORM WAS
 USED.FORM 600C-04R SUBMITTED IS FORADDITIONS THAT
 ARE 600SF OR LESS.ADDITIONIN THIS HOUSE IS ABOVE
 600SF.NEED TO SUBMIT CORRECT FORM (600A-04R) FOR THE
 PROPOSED ADDITION AND FOR ENTIRE HOUSE.SEC.
 13-101.2.2 FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-02-26 Cont ID  
Sent By jgomez Date 2008-02-26 Time 16:38 Rev Time 0.00
Received By jgomez Date 2008-02-26 Time 16:38 Sent To PC
Notes
2008-02-26 16:59:26BUILDING REVISION SECOND CHECKLIST:
  
 1- SIZE OF ATTIC ACCESS ON BEDROOM #3 WAS CHANGED. NOW,
 NEW SIZE (22X22) SHOWN ON SHEET A3.0DOESN'T COMPLY
 WITH SEC. R807.1 OF 2004 FLORIDA RESIDENTIAL CODE.
 REVISE AS REQUIRED.
  
 2-GARAGE SIDE DOOR PRODUCT APPROVAL NOA 01-1218.05
 SUBMITTED EXPIRED ON AUGUST 15, 2007. NEED TO PROVIDE
 CURRENT PRODUCT APPROVALAS REQUIRED BY DCA RULE
 9B-72.
  
 ***REMAINDER: ARCHITECT TO REVIEW AND APPROVE IN
 WRITING(NOT SIGNING AND SEALING))ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS
 TO FBC 2004. THIS APPLIES TO NEWDOOR PRODUCT APPROVAL
 AND MAKE SURE IT'S NOT EXPIRED TO AVOID UNNECESSARY
 DELAYS.
  
 3-REVISE ENERGY CALCULATIONS:
 A) CEILING INSULATION CAN'T BE 1848 S.F.IF THE
 EXISTING CONDITIONED AREA IS 1905S.F.. SEE
 ARCHITECTURAL PLANS AND REVISE AS REQUIRED.
  
 B) COMPLETE ALL INFORMATION IN THE FORM PROVIDED.
 NEED BUILDER'S NAME, COMPLETE ITEMS 1 THRU 7. AND,
 COMPLETE INFORMATION ON SECOND PAGE.
  
 4- OWES $10.46 FOR RADON FEES.FILE WAS AUDITED AND
 FOUND THAT RADON FEES WERE NOT PAID.
  
 5- NEED TO BRING PLANS TO PALM BEACH COUNTY(2300 N.
 JOG RD)TO UPDATE TOTAL SQUARE FOOTAGE FOR ADDITION.
 IMPACT FEES STAMP STATES 605S.F., WHILE ACTUAL ADDITION
 IS 1045S.F. SEE AREA CALCULATIONS ON SHEET A3.0.
 BRING BACK RE-STAMPED PLANS BY PALM BEACH COUNTY.AND,
 IF FEES ARE DUE, THEN BRING BACK COPY OF PAID RECEIPT.
 SEEATTACHED COPY OF IMPACT FEES STAMP.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-02-06 Cont ID  
Sent By jgomez Date 2008-02-06 Time 10:46 Rev Time 0.00
Received By jgomez Date 2008-02-06 Time 10:46 Sent To PC
Notes
2008-02-06 11:06:45BUILDING REVISION CHECKLIST:
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) GARAGE DOORSIZE AS SHOWN ON REVISEDPLANS.
 NOTE: PLEASE MAKE SURE PRODUCT APPROVALMEETS THE
 DESIGN PRESSURES CALCULATED BY THE ARCHITECT TO AVOID
 CONFLICTS OR DELAYS.
  
 B) GARAGE SIDE DOOR AS SHOWN ON REVISED PLANS.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALSAS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 3-ARCHITECT NEEDS TO DATE DRAWINGS WHEN THEY ARE
 SEALED AS REQUIRED BY SEC. 61G1-16.004OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 OF FLORIDA
 STATUTE.
  
 4- REVISE ENERGY CALCULATIONS TO REFLECT CHANGES MADE
 INCLUDING NEW ROOF OVER ENTIRE HOUSE.
 NOTE: PLEASE KEEP IN CONSIDERATION THE CEILING AREAS
 REQUIRED BY SEC. 13-604.1.A.1 FBC 2004 TO AVOID
 CONFLICTS OR DELAYS. THERE ARE SOME ROOMS WHICH WERE
 REVISED TO HAVE TRAY CEILINGS AND VAULTED CEILINGS.
  
 5- UPDATEPERMIT VALUATION TO INCLUDE THE ROOF
 TRUSSES FOR ENTIRE HOUSE AS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004.PERMIT FEES WILL BE ADJUSTED
 ACCORDINGLY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-20 Cont ID  
Sent By jgomez Date 2007-11-20 Time 15:57 Rev Time 0.00
Received By jgomez Date 2007-11-20 Time 15:47 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-01 Cont ID  
Sent By jgomez Date 2007-11-01 Time 14:38 Rev Time 0.00
Received By jgomez Date 2007-11-01 Time 07:43 Sent To M
Notes
2007-11-01 14:46:17SINGLE FAMILY RESIDENCE ADDITION AND RENOVATION
 BUILDING REVIEW SECOND CHECKLIST.
 REVIEW DONE UNDER EXISTING BUILDING 2004 CODE, FLORIDA
 RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007
 REVISIONS.
  
 1- SHEET A7.0:REVISE TOP CHORD DEAD LOADS. IF
 INSTALLING CONCRETE ROOF TILE , THEN10PSF TOP CHORD
 DEAD LOAD IS INCORRECT.REVISE AS REQUIRED BY SEC.
 R301.4 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 2- PERSON PREPARING ENERGY ENERGY CALCULATIONS NOW
 STATES THAT USING ICYNENE INSULATION.THIS IS NEW
 INFORMATION, THEREFORE, THE FOLLOWING IS REQUIRED:
 A) PROVIDE COMPLETE SPECIFICATIONS FOR ICYNENE
 INSULATION TO VERIFY COMPLIANCE WITH R VALUES STATED IN
 THE ENERGY CALCULATIONS AT CEILINGS AND WALLS
 (SPECIALLY IN CONCRETE BLOCK WALLS), SEC. R314.3 FOR
 BURNING CHARACTERISTICS AND SEC. R314.4 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR THERMAL BARRIER REQUIREMENTS.
  
 B) ALL ARCHITECTURAL DRAWINGS NEED TO BE REVISED TO
 INCORPORATE THE ICYNENE INSULATION AS PART OF THE
 SPECIFICATIONS FOR COMPLIANCE WITH CHAPTER 13 OFF FBC
 2004. ARCHITECT TO REVIEW ALL ICYNENE SPECS AND
 SECTIONSR314.3,SEC. R314.4 OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE ALL WALL SECTIONS AS
 REQUIRED. SEC. 106.1.2 CIT6Y AMENDMENTS TO FBC 2004.
  
 C) ARCHITECT TO PROVIDE SPECIFICATIONS FOR ICYNENE
 INSULATION BETWEEN EXISTING BUILDING AND NEW ADDITION
 TO SHOW HOWTHE BUILDING ENVELOPE WILL BE SEALED TO
 AVOID HAVING ATTICVENTILATION TO VERIFY COMPLIANCE
 WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) R VALUES SHOWN ON ARCHITECTURAL PLANS AND ENERGY
 CALCULATIONS NEED TO MATCH. INCLUDING BUILDING SECTIONS
 SHOWN ON SHEET A5.0.
  
 3-ENERGY CALCULATIONS WERE REVISED TO HAVE NO CEILING
 FAN CREDIT, THEREFORE CEILING FANS ARE NOT REQUIRED.
 BUT, IF CEILING FAN CREDIT IS REINSTATED, THEN
 ARCHITECT TO SEE TABLE 13-607.1.A.1 FBC 2004 FOR
 MINIMUM CEILING FAN SIZE REQUIRED.SIZES SHOWN ON SOME
 ROOMS DON'T COMPLY.
  
 4- ENERGY CALCULATIONS:
 A) MISSING ADJACENT WALL AT GARAGE AREA. PERSON
 PREPARING THE ENERGY CALCULATIONS NEEDS TO REVIEW
 ARCHITECTURAL PLANS TO SEE COMPLETE SCOPE OF WORK.
 PLANS CALL FOR NEW ADDITIONSAND RENOVATIONS TO THE
 EXISTING HOUSE.THERE ARE NEW OPENINGS IN THE EXTERIOR
 WALL AND SOME OPENINGS ARE CLOSED. IN ADDITION THERE IS
 A NEW ADJACENT WALL IN GARAGE AREA.ENERGY
 CALCULATIONS TO COMPLY WITH SEC. 13-600.1.C.1 AND SEC.
 13-600.1.C.2 OF FBC 2004.
  
 B) OWNER/AGENT TO DATE THE ENERGY CALCULATIONS.
 (REPEAT COMMENT. IT WAS SIGNED, BUT NO DATED).
  
 C) R VALUES IN CEILINGS AND WALLS NED TO MATCH
 ARCHITECTURAL PLANS.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) POLYPRO ADHESIVE ROOF TILE AS SPECIFIED ON TILE
 PRODUCT APPROVAL AND ARCHITECTURAL PLANS.
  
 B) ALL SIMPSON ANDUSP STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS. NEED TO PROVIDE THE 2004 CODE
 VERSION. SOME OF THE PRODUCT APPROVALS SUBMITTED ARE
 FOR 2001 CODE VERSION. (SEE FL503 AND FL474 SUBMITTED).
 GO TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD CURRENT
 PRODUCT APPROVALS.
 ALSO,NEED TO PROVIDE PAGE WHERE SPECIFIC CONNECTOR IS
 SHOWN. (REPEAT COMMENT). ONLY THE COVER PAGE WAS
 SUBMITTED. THIS APPLIES TO ALL CONNECTOR SUBMITTED.
  
 C) BAHAMA SHUTTERS. FL8523-R1 SUBMITTEDIS NOT
 APPROVED YET. APPLICATION STATUS SAYS "PENDING FBC
 APPROVAL".NEED ONE WITH APPROVED STATUS.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL REVISED/RE-SUBMITTED PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 7- NOTICE OF COMMENCEMENT WAS RECORDED ON 07/02/2007.
 ACCORDING TO SEC. 713.13 FLORIDA STATUTENOTICE OF
 COMMENCEMENTS ISEXPIRED IF WORK IS NOT STARTED WITHIN
 90 DAYS OF RECORDING IT. NEED RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 8- REVISE/CLARIFYROOF SHEATHING MATERIALS.
 INFORMATION ON TYPICAL WALL SECTION "C"ON SHEET A9.0,
 TYPICALROOF TILE ATTACHMENT DETAIL ON SHEET A8.0 AND
 ROOF SHEATHING & NAILING NOTE ON SHEET A7.0 DON'T
 MATCH. REVISE AS REQUIRED.
  
 9- PROVIDE COPY OF THE PAID RECEIPT OF THE IMPACT FEES.
 NEED COPY TO BE FILED WITH THE CITY FILE.
  
 10- ARCHITECT TODATE DRAWINGS WHEN THE SEAL IS
 IMPRESSED AS REQUIRED BY SEC. 61G1-16.004(5) OF FLORIDA
 ADMINISTRATIVE CODE. (REPEAT COMMENT).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-21 Cont ID  
Sent By jgomez Date 2007-08-21 Time 12:39 Rev Time 0.00
Received By jgomez Date 2007-08-21 Time 12:39 Sent To PC
Notes
2007-08-21 13:16:45SINGLE FAMILY RESIDENCE ADDITIONAND RENOVATION
 BUILDING FIRST REVIEW CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC
 2004 WITH 2006/2007 REVISIONS.
  
 1- DRAWINGS TITLE BLOCK NEEDS THE NAME OF ARCHITECT
 SIGNING AND SEALING THE PLANS AND DATE WHEN PLANS ARE
 SEALED AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 2- SHEET A1.0 SAYS WIND EXPOSURE "C",WHILE SHEET A2.0
 SAYSWIND EXPOSURE "B". REVISE AS REQUIRED TO MATCH.
  
 3- INTERNAL PRESSURE COEFFICIENT SPECIFIED ON SHEET
 A1.0 IS DIFFERENT THAN THAT SHOWN ON SHEET A2.0. REVISE
 AS REQUIRED. IS THIS STRUCTURE DESIGNED AS OPEN OR
 ENCLOSED?.SPECIFY CORRECT INTERNAL PRESSURE
 COEFFICIENT.
  
 4- SITE PLAN ON SHEET A1.0 SHOWSARROWS FOR DRAINAGE
 THAT LEAD TO THE NEIGHBOR'S PROPERTY.WATER NEEDS TO
 BE DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER
 APPROVED POINT OF COLLECTION.OR WATER TO BE RETAINED
 IN THE SAME LOT.SEE SEC. R401.3 OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE SITE PLAN AS REQUIRED.
  
 5- PROVIDE WINDOW CUT SHEETS SHOWING HOW SPECIFIED
 CASEMENT WINDOWS ON BEDROOMS 2 AND 3 COMPLY WITHTHE
 WIDTHEGRESS REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 6- AREA CALCULATIONS ON SHEET A3.0 DON'T ADD UP
 CORRECTLY. REVISE AS REQUIRED.
  
 7- SPECIFY ALL DEAD AND LIVE LOADS ANDINCLUDETHE
 ATTIC LIVE LOADS AS REQUIRED BY TABLE R301.5 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 8- SOIL TEST REPORT:
 A) PROJECT DESCRIPTION IS TO RAZE EXISTING HOUSE TO
 BUILD A NEW ONE.ARCHITECTURAL PLANS CALL FOR NEW
 ADDITIONS TO EXISTING HOUSE. REVISE/CLARIFY AS
 REQUIRED.
  
 B) NEED THE ENGINEERING FIRM CERTIFICATE OF
 AUTHORIZATION NUMBERIN ALL SHEETS AS REQUIRED BY SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 9- ARCHITECT TO REVIEWSOIL TEST REPORT FOR FOOTING
 RECOMMENDATIONS. PROVIDE RESPONSE STATING THAT SOIL
 TEST REPORTAND RECOMMENDATIONS WAS REVIEWED AND
 DESIGN CONFORMS TO PROPOSED RECOMMENDATIONS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 10- ARCHITECT TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004.
 IF USING NAIL OR SCREWS SPECIFY SIZE AND NUMBER. IF
 USING ADHESIVES SPECIFY SPECIFIC TYPE AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9B-72.
  
 11- ENERGY CALCULATIONS:
 A) CLARIFY WHY THERE IS NOT INFORMATION GIVEN FOR
 WATER HEATER IF NEW BATHROOMS ARE ADDED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 B) INSULATION ON WALLS AND CEILING DON'T MATCH
 ARCHITECTURAL PLANS.
  
 C) MISSING ADJACENT WALL AT GARAGE AREA.
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 12- IF ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT, THENNEED TO SPECIFY CEILING FAN SIZE IN FLOOR
 PLANS AS REQUIRED BY TABLE 13-607.1.A.1 FBC 2004.
  
 13- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) ALL STRUCTURAL SIMPSON OR USP CONNECTORS
 SPECIFIED ON PLANS.
 ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND THE SPECIFIC PAGE SHOWING THE CONNECTOR
 TO SAVE PAPER.
  
 B) WINDOW MULLIONS AND CLEARLY IDENTIFY ANCHORING TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES CALCULATED
 BY THE ARCHITECT. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 C) FIXED WINDOWS WITH SIZES AS SHOWN ON PLANS.
  
 D) ENTRY DOOR ASSEMBLY AS SHOWN ON PLANS. SEE SIZE
 ON ARCHITECTURAL PLANS.
  
 E) WOOD LOUVERED DOORS SHOWN ON FRONT ELEVATION.
  
 F) DECORATIVE BAHAMA SHUTTERS AND CLEARLY IDENTIFY
 FASTENING. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 14- SHEET A7.0:
 A) REVISE RAKED BEAM DETAIL.UPDATEALL SEMCO
 CONNECTORS. COMPANY IS OUT OF BUSINESS.
  
 B) SIMPSON ARCHITECTURAL SERIES CONNECTOR CB46PC
 SPECIFIED TO HOLD HEAVY TIMBER TRUSSES AT ENTRANCE IS A
 COLUMN BASE CONNECTOR. REVISE CONNECTOR AS REQUIRED AND
 PROVIDE COMPLETE DETAIL WITH SPECS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 15- SHEET A3.0: REVISE EGRESS NOTE #4 OF FIRE RATING &
 LIFE SAFETY NOTES.WINDOWS MUST MEET MINIMUM WIDTH AND
 HEIGHT DIMENSIONS, NOT WIDTH OR HEIGHT. REVISE AS
 REQUIRED TO COMPLY WITH SEC. R310 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 16- SHEET A5.0: PROVIDE COMPLETE SPECS/DETAILSAND
 LOAD VALUES FOR SIMPSON ARCHITECTURAL SERIES CUSTOM
 GUSSET PLATES. SIMPSON DOESN'T PROVIDE THIS
 INFORMATION. THIS IS THE RESPONSIBILITY OF THE DESIGNER
 OF RECORD.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 17- SHEET A9.0:
 A) UPDATE GENERAL CONSTRUCTION NOTE #11. SEE FBC
 2004 FOR CORRECT CODE SECTION TO BE REFERENCED.
  
 B) REVISE GENERAL CONSTRUCTION NOTE #17.SEE SEC.
 R606.4 OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT
 CONCRETE MASONRYMINIMUM NET AREA COMPRESSIVE
 STRENGTH.
 ALSO, UPDATE REFERENCED STANDARDS AND YEAR. SEE SEC.
 R606AND CHAPTER 43 OF 2004 FLORIDA RESIDENTIAL CODE
 FOR ADOPTED STANDARDS AND YEAR TO BE USED.
  
 C) REVISE GENERAL CONSTRUCTION NOTE #38. SEE ASTM
 C926 AND ASTMC1063 FOR CORRECT FASTENERS AND SPACING TO
 BE USED ACCORDING TO THE SPECIFIC INSTALLATION AND
 MATERIALS TO BE USED.
  
 D) UPDATE ALL GENERAL NOTES. SEE CHAPTER 35 OF FBC
 2004 AND CHAPTER 43 OF 2004 RESIDENTIAL CODE FOR
 CORRECT ADOPTED STANDARDS AND YEAR TO BE USED AND
 REVISE/UPDATE NOTES AS REQUIRED.
  
 E) REVISE/CLARIFYSPECS ON TYPICAL 1-STORYWALL
 SECTION. ROOF SHEATHING NOTE CALLS FOR 19/32" CD GRADE
 WOOD, WHILE TYPICAL FASCIA CONSTRUCTION CALLS FOR 1X6
 T&G SHEATHING.
  
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-06-09 Cont ID  
Sent By btrobaug Date 2008-06-09 Time 15:10 Rev Time 0.00
Received By btrobaug Date 2008-06-09 Time 15:10 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-01-22 Cont ID  
Sent By btrobaug Date 2008-01-22 Time 13:23 Rev Time 0.00
Received By btrobaug Date 2008-01-22 Time 07:24 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-11-16 Cont ID  
Sent By btrobaug Date 2007-11-16 Time 15:06 Rev Time 0.00
Received By btrobaug Date 2007-11-16 Time 14:06 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-13 Cont ID  
Sent By btrobaug Date 2007-10-09 Time 11:28 Rev Time 0.00
Received By btrobaug Date 2007-10-09 Time 06:40 Sent To P
Notes
2007-10-09 11:28:46 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET A6.0,UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW, THE * IS
 FURTHER COMMENTARY IN AN ATTEMT TO CLARIFY THE
 PREVIOUS.
  
 5} PANEL "G" IS NOT SHOWN ON THE RISER DIAGRAM. PROVIDE
 CONDUCTOR AND CONDUIT SIZE AND TYPE.* PANEL "G" IS NOT
 LOCATED ON THE PLAN.
  
 10} CIRCUIT "A 13" APPEARS TO BE IN THE KITCHEN AND
 THEREFORE IS SUBJECT TO ARTICLE 210.52(B)(1) FOR SMALL
 APPLIANCES.* THIS CONDITION STILL EXISTS, WAS NOT
 CORRECTED BY ADDING CIRCUIT #38.
  
 THIS IS A NEW COMMENT FOR THIS REVIEW
  
 1} A RECEPTACLE NEEDS TO BE ADDED TO THE KITCHEN
 COUNTERTOP FOR SPACING REQUIREMENTS OF 210.52(C)(1).
 SEE REVIEWED PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-31 Cont ID  
Sent By btrobaug Date 2007-07-31 Time 15:09 Rev Time 0.00
Received By btrobaug Date 2007-07-31 Time 12:11 Sent To P
Notes
2007-07-31 15:08:59 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THERE IS NO RECORD OF THE GENERATOR AND TRANSFER
 SWITCH, INCLUDED ON THE RISER DIAGRAM, HAVING BEEN
 PERMITTED. IT APPEARS THAT THE PAD ON THE PLAN DOES NOT
 MEET SETBACK REQUIREMENTS, MANUFACTURERS, NEC OR
 MECHANICAL. A SEPARATE PERMIT IS REQUIRED FOR THIS
 EQUIPMENT.
  
 2} INDICATE THE LOCATION OF THE ?RELOCATED? 200 AMP
 MAIN DISCONNECT. THE LOCATION SHOWN ON THE PLAN READS
 "EXISTING". PLEASE CLARIFY.
  
 3} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. THIS IS NECESSARY AS THE EQUIPMENT
 HAS BEEN MOVED AND FPL WIRE SIZE AND DISTANCE FROM THE
 TRANSFORMER CHANGE THE EQUATION.
  
 4} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 5} PANEL "G" IS NOT SHOWN ON THE RISER DIAGRAM. PROVIDE
 CONDUCTOR AND CONDUIT SIZE AND TYPE.
  
 6} THE DISHWASHER RECEPTACLE IS MISMARKED "G 11", THE
 GARAGE DOOR CIRCUIT.
  
 7} CIRCUIT "G 12" IN THE PANTRY IS NOT ON THE PANEL
 SCHEDULE.
  
 8} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. ALSO SEE THE
 DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72,
 CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. SEE 210.12 FOR AFCI
 CIRCUITING.
  
 9} THE DISCONNECT FOR THE ?EXISTING? CONDENSER DOES NOT
 APPEAR TO MEET THE CLEARANCE REQUIREMENTS OF 110.26
 NEC, IF THE GENERATOR PAD GETS LOCATED WHERE SHOWN.
  
 10} CIRCUIT "A 13" APPEARS TO BE IN THE KITCHEN AND
 THEREFORE IS SUBJECT TO ARTICLE 210.52(B)(1) FOR SMALL
 APPLIANCES.
  
 11} THE DISCONNECT CIRCUIT AT THE NEW CONDENSER IS
 MISMARKED ON THE RANGE CIRCUIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-08-20 Cont ID  
Sent By adarroug Date 2008-08-20 Time 16:05 Rev Time 0.00
Received By adarroug Date 2008-08-20 Time 16:04 Sent To Z
Notes
2008-08-20 16:05:15TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-08-06 Cont ID  
Sent By adarroug Date 2008-08-06 Time 16:56 Rev Time 0.00
Received By adarroug Date 2008-08-06 Time 16:56 Sent To M
Notes
2008-08-06 16:57:13TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-07-21 Cont ID  
Sent By adarroug Date 2008-07-21 Time 11:29 Rev Time 0.00
Received By adarroug Date 2008-07-21 Time 11:29 Sent To M
Notes
2008-07-21 11:29:51TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 11:21 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 11:21 Sent To Z
Notes
2008-07-11 11:22:27TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-07-01 Cont ID  
Sent By adarroug Date 2008-07-01 Time 15:47 Rev Time 0.00
Received By adarroug Date 2008-07-01 Time 15:47 Sent To M
Notes
2008-07-01 15:47:50TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-06-02 Cont ID  
Sent By adarroug Date 2008-06-02 Time 11:53 Rev Time 0.00
Received By adarroug Date 2008-06-02 Time 11:53 Sent To M
Notes
2008-06-02 11:53:56TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 16:36 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 16:36 Sent To Z
Notes
2008-05-30 16:36:17TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-03-05 Cont ID  
Sent By adarroug Date 2008-03-05 Time 13:54 Rev Time 0.00
Received By adarroug Date 2008-03-05 Time 13:53 Sent To M
Notes
2008-03-05 13:54:16TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 12:59 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 12:59 Sent To B
Notes
2008-02-19 12:59:55TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-11 Cont ID  
Sent By spalmer Date 2008-01-11 Time 17:18 Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 17:18 Sent To Z
Notes
2008-01-11 17:18:54TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-09 Cont ID  
Sent By adarroug Date 2007-11-09 Time 12:10 Rev Time 0.00
Received By adarroug Date 2007-11-09 Time 12:10 Sent To  
Notes
2007-11-09 12:10:53TO "BTROBAUG" DESK/RESUB--NEW SHEETS FOR "ELECT."

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-01 Cont ID  
Sent By adarroug Date 2007-10-01 Time 12:45 Rev Time 0.00
Received By adarroug Date 2007-10-01 Time 12:45 Sent To Z
Notes
2007-10-01 12:45:42TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-21 Cont ID  
Sent By jgomez Date 2007-08-21 Time 13:16 Rev Time 0.00
Received By jgomez Date 2007-07-26 Time 13:38 Sent To  
Notes
2007-07-26 13:38:36TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2008-08-26 Cont ID  
Sent By rkussner Date 2008-08-26 Time 08:35 Rev Time 0.00
Received By rkussner Date 2008-08-26 Time 08:35 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-07-15 Cont ID  
Sent By rkussner Date 2008-07-15 Time 16:42 Rev Time 0.00
Received By mcruz Date 2008-07-15 Time 15:34 Sent To  
Notes
2008-07-15 15:36:58MUST PROVIDE LANDSCAPE CALCULATIONS (REQUIRED AND
 PROVIDED).
  
 MUST PROVIDE PLANT SIZE AND SPACING.
  
 BOTH OF THE ABOVE ITEMS CAN BE ON A SEPARATE SHEET AND
 AFFIXED TO THE LANDSCAPE PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2008-08-07 Cont ID  
Sent By tgordon Date 2008-08-07 Time 09:13 Rev Time 0.30
Received By tgordon Date 2008-08-07 Time 09:13 Sent To B
Notes
2008-08-07 09:14:04REVISION TO ENERGY CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status F Date 2008-07-21 Cont ID  
Sent By tgordon Date 2008-07-21 Time 13:49 Rev Time 0.45
Received By tgordon Date 2008-07-21 Time 13:49 Sent To B
Notes
2008-07-21 14:06:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO ENERGY CALCULATIONS.
 *** DENIED ***
  
 1) ENERGY CAL'S. LINE 15 IS TAKING THE CROSS
 VENTILATION CREDIT. PLEASE PROVIDE THE CALCULATIONS
 SHOWING THE WINDOW AND DOOR OPENINGS ARE 12% OF THE
 FLOOR AREA, ADD TO BUILDING PLANSSCREENED DOORS TO
 ALL OUTSIDE DOORS BEING INCLUDED IN THE CALCULATIONS.
 SEE 2004 FBC 13-607.1.A.3.1.
  
 2) AS THE CROSS VENTILATION CREDIT IS MOSTLY FOR
 NORTHERN FLORIDA, PLEASE SUBMIT A METEOROLOGICAL REPORT
 SHOWING THAT WEST PALM BEACH HAS SIGNIFICANT AND
 CONTINUOUS WINDS DURING THE COOLING MONTHS, PER 2004
 FBC 13-607.1.A.3.1.
  
 2004 FBC 13-607.1.A.3.1 CROSS VENTILATION CREDIT.
 HOUSES FOR WHICH CREDIT IS CLAIMED FOR CROSS
 VENTILATION IN ACCORDANCE WITH THE CRITERIA IN SECTION
 13-607.2.A.3.3 SHALL HAVE PROVIDED OPERABLE APERTURE
 AREAS TOTALING A MINIMUM OF 12 PERCENT OF THE FLOOR
 AREA OF THE ROOM FOR ALL PRIMARY LIVING AREAS AND MAIN
 BEDROOMS.
 INSECT SCREENS SHALL BE PROVIDED FOR ALL WINDOWS AND
 DOORS TO BE CONSIDERED OPERABLE APERTURE AREA. ALL
 SCREENED ENTRY DOORS AND INTERIOR DOORS IN THE
 VENTILATED AREAS SHALL BE PROVIDED WITH EITHER (1)
 MECHANICALLY ATTACHED DOOR STOPS (OR SIMILAR DEVICES)
 TO HOLD THE DOOR IN AN OPEN POSITION OR (2) OPERABLE
 LOUVERS.
 THE TOTAL APERTURE AREA SHALL BE PROVIDED BY A MINIMUM
 OF TWO DISTINCT WINDOWS. EACH WINDOW SHALL PROVIDE NOT
 MORE THAN 70 PERCENT OF THE TOTAL APERTURE AREA. THE
 WINDOWS (OR SLIDING GLASS DOORS) SHALL BE PLACED IN
 ADJACENT OR OPPOSITE WALLS. THE WINDOWS MAY BE PLACED
 ON A SINGLE OUTSIDE WALL IF WING WALLS ARE USED.
 WHERE WING WALLS ARE INCLUDED IN THE BUILDING DESIGN
 FOR VENTILATION PURPOSES, THEY SHALL BE PLACED BETWEEN
 WINDOWS TO CREATE A HIGH-PRESSURE AND A LOW-PRESSURE
 ZONE ON EACH WINDOW. WING WALLS SHALL EXTEND FROM THE
 GROUND TO EVE HEIGHT, BE LOCATED ON THE WINDWARD SIDE
 OF THE BUILDING, AND EXTEND OUTWARD FROM THE BUILDING A
 DISTANCE AT LEAST EQUAL TO ONE-HALF THE WIDTH OF THE
 WINDOW.
  
 NOTE: THIS TECHNIQUE IS EFFECTIVE ONLY FOR AREAS WHICH
 EXPERIENCE SIGNIFICANT AND CONTINUOUS WINDS DURING THE
 COOLING MONTHS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2008-07-02 Cont ID  
Sent By tgordon Date 2008-07-02 Time 10:53 Rev Time 0.45
Received By tgordon Date 2008-07-02 Time 10:53 Sent To B
Notes
2008-07-02 11:50:27PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO ENERGY CALCULATIONS
 *** DENIED ***
  
 1) REVISED ENERGY CALCULATIONS LINE 12 SHOWS ONLY ONE
 A/C SYSTEM, ASTHE ENERGY CAL'S. ARE FOR THE WHOLE
 HOUSE BOTH A/C SYSTEMS NEED TO BE SHOWN, AND BOTH
 HEATERS, PER 2004 FBC/ 13-103.3.
  
 2) E-CAL'S LINE 10 IS TAKING THE WHITE ROOF CREDIT. PER
 2004 FBC 13-607.1.A.5 WHITE ROOF CREDIT.
 HOUSES FOR WHICH A WHITE ROOF CREDIT IS CLAIMED IN
 ACCORDANCE WITH SECTION 13-607.2.A.3.6 SHALL HAVE AN
 INSTALLED ROOF THAT MEETS THE FOLLOWING CRITERIA:
  
 1. ROOF TYPE MAY ONLY BE METAL, CONCRETE, TILE OR
 SINGLE-PLY MEMBRANE FOR RESIDENTIAL CONSTRUCTION.
  
 2. ROOF MUST BE WHITE WITH A TESTED TOTAL SOLAR
 REFLECTANCE OF 65 PERCENT OR GREATER WHEN EVALUATED IN
 ACCORDANCE WITH ASTM E 903. ROOF SHALL HAVE A SURFACE
 EMISSIVITY OF 80 PERCENT OR GREATER. TESTING OF A
 QUALIFYING SAMPLE OF THE ROOFING MATERIAL SHALL BE
 PERFORMED BY AN APPROVED INDEPENDENT LABORATORY AND
 PRODUCT LABELING COMMENSURATE WITH THESE RESULTS SHALL
 BE PROVIDED BY THE MANUFACTURER. PLEASE SUBMIT REQUIRED
 TEST REPORTS.
  
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2008-06-11 Cont ID  
Sent By tgordon Date 2008-06-11 Time 13:45 Rev Time 0.30
Received By tgordon Date 2008-06-11 Time 13:45 Sent To  
Notes
2008-06-11 13:46:46PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO ENERGY CALCULATIONS
 *** DENIED ***
  
 1) ENERGY CALCULATIONS YOUR ADDITION CAN NOT USE FORM
 'C' (600C-04R) AS THE ADDITION IS OVER 600 SQUARE FEET,
 PER 2004 FBC 13-600.3.C.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-06-02 Cont ID  
Sent By tgordon Date 2008-06-02 Time 16:19 Rev Time 0.30
Received By tgordon Date 2008-06-02 Time 16:19 Sent To  
Notes
2008-06-02 16:20:26REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-03-06 Cont ID  
Sent By tgordon Date 2008-03-06 Time 08:50 Rev Time 0.35
Received By tgordon Date 2008-03-06 Time 08:50 Sent To  
Notes
2008-03-06 08:50:39REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2008-01-17 Cont ID  
Sent By tgordon Date 2008-01-17 Time 15:49 Rev Time 0.20
Received By tgordon Date 2008-01-17 Time 15:49 Sent To E
Notes
2008-01-17 15:50:57REVISED BUILDING PLANS. NO REVISION TO MECHANICAL PLAN
 SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-16 Cont ID  
Sent By tgordon Date 2007-11-16 Time 15:36 Rev Time 0.35
Received By tgordon Date 2007-11-16 Time 15:35 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-02 Cont ID  
Sent By tgordon Date 2007-11-02 Time 12:00 Rev Time 0.45
Received By tgordon Date 2007-11-02 Time 12:00 Sent To  
Notes
2007-11-02 12:13:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) A NOTE WAS SENT BACK WITH THE PLANS STATING ICYNENE
 IS TO BE INSTALLED, PLEASE SEE BUILDING REVIEW NOTES
 REGARDING ICYNENE AND COMPLY.
  
 2) ENERGY CALCULATIONS LINE 15 IS TAKING THE CROSS
 VENTILATION CREDIT, PLEASE SEE 2004 FBC 13-607.1.A.3
 AND SHOW HOW THIS ADDITION COMPLIES WITH ALL AND HOW
 SOUTH FLORIDA COMPLIES WITH THE LAST NOTE.
  
 2004 FBC 13-607.1.A.3.1 CROSS VENTILATION CREDIT.
 HOUSES FOR WHICH CREDIT IS CLAIMED FOR CROSS
 VENTILATION IN ACCORDANCE WITH THE CRITERIA IN SECTION
 13-607.2.A.3.3 SHALL HAVE PROVIDED OPERABLE APERTURE
 AREAS TOTALING A MINIMUM OF 12 PERCENT OF THE FLOOR
 AREA OF THE ROOM FOR ALL PRIMARY LIVING AREAS AND MAIN
 BEDROOMS.
 INSECT SCREENS SHALL BE PROVIDED FOR ALL WINDOWS AND
 DOORS TO BE CONSIDERED OPERABLE APERTURE AREA. ALL
 SCREENED ENTRY DOORS AND INTERIOR DOORS IN THE
 VENTILATED AREAS SHALL BE PROVIDED WITH EITHER (1)
 MECHANICALLY ATTACHED DOOR STOPS (OR SIMILAR DEVICES)
 TO HOLD THE DOOR IN AN OPEN POSITION OR (2) OPERABLE
 LOUVERS.
 THE TOTAL APERTURE AREA SHALL BE PROVIDED BY A MINIMUM
 OF TWO DISTINCT WINDOWS. EACH WINDOW SHALL PROVIDE NOT
 MORE THAN 70 PERCENT OF THE TOTAL APERTURE AREA. THE
 WINDOWS (OR SLIDING GLASS DOORS) SHALL BE PLACED IN
 ADJACENT OR OPPOSITE WALLS. THE WINDOWS MAY BE PLACED
 ON A SINGLE OUTSIDE WALL IF WING WALLS ARE USED. WHERE
 WING WALLS ARE INCLUDED IN THE BUILDING DESIGN FOR
 VENTILATION PURPOSES, THEY SHALL BE PLACED BETWEEN
 WINDOWS TO CREATE A HIGH-PRESSURE AND A LOW-PRESSURE
 ZONE ON EACH WINDOW. WING WALLS SHALL EXTEND FROM THE
 GROUND TO EVE HEIGHT, BE LOCATED ON THE WINDWARD SIDE
 OF THE BUILDING, AND EXTEND OUTWARD FROM THE BUILDING A
 DISTANCE AT LEAST EQUAL TO ONE-HALF THE WIDTH OF THE
 WINDOW.
 NOTE: THIS TECHNIQUE IS EFFECTIVE ONLY FOR AREAS WHICH
 EXPERIENCE SIGNIFICANT AND CONTINUOUS WINDS DURING THE
 COOLING MONTHS.
  
 3) AS NOTED IN LAST REVIEW 7-27-07 NOTE #5. THE ENERGY
 CALCULATIONS LINE 15 IS TAKING MULTIZONE HEATING
 CREDIT, AS THE CALCULATIONS ARE FOR THE ADDITION ONLY
 AND ONLY ONE SYSTEM IS SERVING THAT AREA THEN IT CAN
 NOT BE MULTIZONE, CORRECT ENERGY CAL'S. SEE 2004 FBC
 13-2 DEFINITIONS.
  
 1 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-27 Cont ID  
Sent By tgordon Date 2007-07-27 Time 09:20 Rev Time 1.00
Received By tgordon Date 2007-07-27 Time 09:20 Sent To E
Notes
2007-07-27 09:42:02*** DENIED ***
 1) BUILDING PLANS, THE TITLE BLOCK IS MISSING THE
 ARCHITECT'S PRINTED NAME AND THE DATE IS MISSING AT THE
 SEAL, SEE FAC 61G1-16.003 AND 61G1-16.004.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) ENERGY CALCULATIONS LINE 11A STATES THE SUPPLY AND
 RETURN AIR DUCTS IN A CONDITIONED SPACE, MECHANICAL
 PLANS SHOW THE DUCTS IN THE ATTIC, PLEASE CORRECT THE
 ENERGY CAL'S.
  
 4) ENERGY CAL'S. STATE THE AIR HANDLER IS IN THE
 INTERIOR, THE MECHANICAL PLANS SHOW THE AIR HANDLER IS
 IN THE ATTIC, PLEASE CORRECT ENERGY CAL'S.
  
 5) ENERGY CAL'S. LINE 15 IS TAKING CREDITS FOR
 MULTIZONE COOLING AND HEATING, AS THE CALCULATIONS ARE
 FOR THE ADDITION ONLY AND ONLY ONE SYSTEM IS SERVING
 THAT AREA THEN IT CAN NOT BE MULTIZONE, CORRECT ENERGY
 CAL'S.
  
 6) COMMENT FOR THE MECHANICAL PLANS, ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. PER FBC 104.2.1.
  
 7) MECHANICAL PLANS NEED TO SHOW THE SIZE OF THE RETURN
 AIR DUCT (FLEX) TO THE MASTER BEDROOM.
  
 8) MECHANICAL PLANS NEED TO SHOW THE EXHAUST FANS IN
 ALL THE BATHROOMS, SEE ELECTRICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-02-05 Cont ID  
Sent By jleech Date 2008-02-05 Time 07:43 Rev Time 0.00
Received By jleech Date 2008-02-05 Time 07:43 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-30 Cont ID  
Sent By btrobaug Date 2007-11-13 Time 08:32 Rev Time 0.00
Received By jleech Date 2007-10-30 Time 07:50 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-08-13 Cont ID  
Sent By jleech Date 2007-08-13 Time 15:17 Rev Time 0.00
Received By rkussner Date 2008-07-15 Time 15:33 Sent To B
Notes
2007-08-13 15:25:35DENIED;
 1. ADD NOTE TO DEMO PAGE. " NO DEAD ENDS PERMITED IN
 THE DRAINAGE SYSTEM, INSPECTION REQUIRED". SEE FBC-2004
 SECTION 704.5
 2. SANITARY RISER DIAGRAM, BATHROOM 2 AND 3 , SHOWER IN
 2 IS NOT VENTED AND TUB IN BATHROOM 3 IS NOT VENTED.
 3. W/M STACK IS TO FAR AWAY FROM KIT. SINK TO RUN A
 WASTE ARM STUB UP UNDER SINK WITH A MECHANICAL VENT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2008-06-02 Cont ID  
Sent By choops Date 2008-06-02 Time 09:38 Rev Time 0.00
Received By choops Date 2008-06-02 Time 09:38 Sent To E
Notes
2008-06-02 09:43:34***APPROVED - REVISION - AS-BUILT CHANGES (GENERATOR
 LOCATION)***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 3 Status P Date 2008-06-02 Cont ID  
Sent By choops Date 2008-02-05 Time 09:28 Rev Time 0.00
Received By choops Date 2008-02-05 Time 09:28 Sent To E
Notes
2008-01-15 13:05:14***APPROVED - REVISION - INTERIOR CHANGES ONLY***
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-05 Cont ID  
Sent By choops Date 2007-10-05 Time 08:37 Rev Time 0.00
Received By choops Date 2007-10-05 Time 08:37 Sent To E
Notes
2007-10-05 08:42:35***APPROVED - RESUB #1***PROVISO: DRIVEWAY TO BE OF A
 SMOOTH, NON-DUSTING SURFACE.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By choops Date 2007-07-26 Time 15:29 Rev Time 0.00
Received By choops Date 2007-07-26 Time 15:29 Sent To I
Notes
2007-07-26 15:37:22***FAILED***
  
  
 1)AS THE VALUE OF PROPOSED WORK EXCEEDS 50% OF THE
 VALUE OF THE HOUSE, A LANDSCAPE PLAN SHALL BE SUBMITTED
 SHOWING COMPLIANCE WITH THE ZONING AND LAND DEVELOPMENT
 REGULATIONS, SECTION 94-442
  
 2)CLARIFY IF DRIVEWAY IS INCLUDED IN SCOPE OF WORK
 FOR THIS PERMIT.IF SO, INCLUDE SQUARE FOOTAGE OF
 PROPOSED DRIVEWAY.
  
 3)PROVIDE NEW MECHANICAL EQUIPMENT SETBACKS TO THE
 PROPERTY LINES.INCLUDE SETBACK DIMENSIONS FROM THE
 OUTDOOR SHOWER TO THE PROPERTY LINES.
  
 4)PROVIDE AN EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (1ST
 FLOOR, CITY HALL)
  
 5)ELEVATION DIMENSIONS SHALL BE SHOWN FROM GRADE TO
 THE MIDPOINT OF THE ROOF'S SLOPE.
  
 6)ALL OVERHANG DIMENSIONS SHALL BE PROVIDED FROM THE
 WALL THE OUTERMOST POINT OF THE ROOF.
  
 7)PROVIDE ELEVATION OF PROPOSED FRONT SITEWALL.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720