| Plan Review Stops For Permit 07070741 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-08-11 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-08-11 |
Time |
09:52 |
Sent To |
PC |
|
| Notes |
| 2008-08-11 09:53:12 | ENERGY CALCULATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2008-07-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-07-23 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-07-23 |
Time |
14:48 |
Sent To |
PC |
|
| Notes |
| 2008-07-23 14:51:22 | ENERGY CALCULATIONS BUILDING REVIEW CHECKLIST. | | | | | | 1-ENERGY CALCULATIONS ARE TAKING THE CROSS | | | VENTILATION CREDIT.SEE MECHANICAL PLAN REVIEWER | | | COMMENTS AND REVISE AS REQUIRED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2008-07-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-07-03 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-07-03 |
Time |
16:55 |
Sent To |
PC |
|
| Notes |
| 2008-07-03 17:00:36 | ENERGY CALCULATIONS SUBMITTAL: | | | 1-ENERGY CALCULATIONS ARE TAKEN THE CREDIT FOR | | | "WHITE ROOF".NEED TO PROVIDE COMPLIANCE WITH THE | | | WHITE ROOF CREDITREQUIREMENTS OF SEC. 13-607.1.A.5, | | | SEC. 13-607.2.A.3.6 AND SEC. 13-608.2.A.3.7OF 2004 | | | FBC. READ THOSE CODE SECTIONS AND PROVIDE REQUIRED | | | INFORMATION | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2008-06-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-06-11 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-06-11 |
Time |
10:42 |
Sent To |
M |
|
| Notes |
| 2008-06-11 13:12:28 | BUILDING REVISION CHECKLIST: | | | 1- ENERGY CALCULATIONS WERE REVISED AND NEW FORM WAS | | | USED.FORM 600C-04R SUBMITTED IS FORADDITIONS THAT | | | ARE 600SF OR LESS.ADDITIONIN THIS HOUSE IS ABOVE | | | 600SF.NEED TO SUBMIT CORRECT FORM (600A-04R) FOR THE | | | PROPOSED ADDITION AND FOR ENTIRE HOUSE.SEC. | | | 13-101.2.2 FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2008-02-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-02-26 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-02-26 |
Time |
16:38 |
Sent To |
PC |
|
| Notes |
| 2008-02-26 16:59:26 | BUILDING REVISION SECOND CHECKLIST: | | | | | | 1- SIZE OF ATTIC ACCESS ON BEDROOM #3 WAS CHANGED. NOW, | | | NEW SIZE (22X22) SHOWN ON SHEET A3.0DOESN'T COMPLY | | | WITH SEC. R807.1 OF 2004 FLORIDA RESIDENTIAL CODE. | | | REVISE AS REQUIRED. | | | | | | 2-GARAGE SIDE DOOR PRODUCT APPROVAL NOA 01-1218.05 | | | SUBMITTED EXPIRED ON AUGUST 15, 2007. NEED TO PROVIDE | | | CURRENT PRODUCT APPROVALAS REQUIRED BY DCA RULE | | | 9B-72. | | | | | | ***REMAINDER: ARCHITECT TO REVIEW AND APPROVE IN | | | WRITING(NOT SIGNING AND SEALING))ALL PRODUCT | | | APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS | | | TO FBC 2004. THIS APPLIES TO NEWDOOR PRODUCT APPROVAL | | | AND MAKE SURE IT'S NOT EXPIRED TO AVOID UNNECESSARY | | | DELAYS. | | | | | | 3-REVISE ENERGY CALCULATIONS: | | | A) CEILING INSULATION CAN'T BE 1848 S.F.IF THE | | | EXISTING CONDITIONED AREA IS 1905S.F.. SEE | | | ARCHITECTURAL PLANS AND REVISE AS REQUIRED. | | | | | | B) COMPLETE ALL INFORMATION IN THE FORM PROVIDED. | | | NEED BUILDER'S NAME, COMPLETE ITEMS 1 THRU 7. AND, | | | COMPLETE INFORMATION ON SECOND PAGE. | | | | | | 4- OWES $10.46 FOR RADON FEES.FILE WAS AUDITED AND | | | FOUND THAT RADON FEES WERE NOT PAID. | | | | | | 5- NEED TO BRING PLANS TO PALM BEACH COUNTY(2300 N. | | | JOG RD)TO UPDATE TOTAL SQUARE FOOTAGE FOR ADDITION. | | | IMPACT FEES STAMP STATES 605S.F., WHILE ACTUAL ADDITION | | | IS 1045S.F. SEE AREA CALCULATIONS ON SHEET A3.0. | | | BRING BACK RE-STAMPED PLANS BY PALM BEACH COUNTY.AND, | | | IF FEES ARE DUE, THEN BRING BACK COPY OF PAID RECEIPT. | | | SEEATTACHED COPY OF IMPACT FEES STAMP. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2008-02-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-02-06 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-02-06 |
Time |
10:46 |
Sent To |
PC |
|
| Notes |
| 2008-02-06 11:06:45 | BUILDING REVISION CHECKLIST: | | | | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72 FOR: | | | A) GARAGE DOORSIZE AS SHOWN ON REVISEDPLANS. | | | NOTE: PLEASE MAKE SURE PRODUCT APPROVALMEETS THE | | | DESIGN PRESSURES CALCULATED BY THE ARCHITECT TO AVOID | | | CONFLICTS OR DELAYS. | | | | | | B) GARAGE SIDE DOOR AS SHOWN ON REVISED PLANS. | | | | | | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALSAS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 3-ARCHITECT NEEDS TO DATE DRAWINGS WHEN THEY ARE | | | SEALED AS REQUIRED BY SEC. 61G1-16.004OF FLORIDA | | | ADMINISTRATIVE CODE AND CHAPTER 481 OF FLORIDA | | | STATUTE. | | | | | | 4- REVISE ENERGY CALCULATIONS TO REFLECT CHANGES MADE | | | INCLUDING NEW ROOF OVER ENTIRE HOUSE. | | | NOTE: PLEASE KEEP IN CONSIDERATION THE CEILING AREAS | | | REQUIRED BY SEC. 13-604.1.A.1 FBC 2004 TO AVOID | | | CONFLICTS OR DELAYS. THERE ARE SOME ROOMS WHICH WERE | | | REVISED TO HAVE TRAY CEILINGS AND VAULTED CEILINGS. | | | | | | 5- UPDATEPERMIT VALUATION TO INCLUDE THE ROOF | | | TRUSSES FOR ENTIRE HOUSE AS REQUIRED BY SEC. 108.3 CITY | | | AMENDMENTS TO FBC 2004.PERMIT FEES WILL BE ADJUSTED | | | ACCORDINGLY. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-11-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-11-20 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-11-20 |
Time |
15:47 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-01 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-11-01 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-11-01 |
Time |
07:43 |
Sent To |
M |
|
| Notes |
| 2007-11-01 14:46:17 | SINGLE FAMILY RESIDENCE ADDITION AND RENOVATION | | | BUILDING REVIEW SECOND CHECKLIST. | | | REVIEW DONE UNDER EXISTING BUILDING 2004 CODE, FLORIDA | | | RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007 | | | REVISIONS. | | | | | | 1- SHEET A7.0:REVISE TOP CHORD DEAD LOADS. IF | | | INSTALLING CONCRETE ROOF TILE , THEN10PSF TOP CHORD | | | DEAD LOAD IS INCORRECT.REVISE AS REQUIRED BY SEC. | | | R301.4 OF 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 2- PERSON PREPARING ENERGY ENERGY CALCULATIONS NOW | | | STATES THAT USING ICYNENE INSULATION.THIS IS NEW | | | INFORMATION, THEREFORE, THE FOLLOWING IS REQUIRED: | | | A) PROVIDE COMPLETE SPECIFICATIONS FOR ICYNENE | | | INSULATION TO VERIFY COMPLIANCE WITH R VALUES STATED IN | | | THE ENERGY CALCULATIONS AT CEILINGS AND WALLS | | | (SPECIALLY IN CONCRETE BLOCK WALLS), SEC. R314.3 FOR | | | BURNING CHARACTERISTICS AND SEC. R314.4 OF 2004 FLORIDA | | | RESIDENTIAL CODE FOR THERMAL BARRIER REQUIREMENTS. | | | | | | B) ALL ARCHITECTURAL DRAWINGS NEED TO BE REVISED TO | | | INCORPORATE THE ICYNENE INSULATION AS PART OF THE | | | SPECIFICATIONS FOR COMPLIANCE WITH CHAPTER 13 OFF FBC | | | 2004. ARCHITECT TO REVIEW ALL ICYNENE SPECS AND | | | SECTIONSR314.3,SEC. R314.4 OF 2004 FLORIDA | | | RESIDENTIAL CODE AND REVISE ALL WALL SECTIONS AS | | | REQUIRED. SEC. 106.1.2 CIT6Y AMENDMENTS TO FBC 2004. | | | | | | C) ARCHITECT TO PROVIDE SPECIFICATIONS FOR ICYNENE | | | INSULATION BETWEEN EXISTING BUILDING AND NEW ADDITION | | | TO SHOW HOWTHE BUILDING ENVELOPE WILL BE SEALED TO | | | AVOID HAVING ATTICVENTILATION TO VERIFY COMPLIANCE | | | WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. | | | | | | C) R VALUES SHOWN ON ARCHITECTURAL PLANS AND ENERGY | | | CALCULATIONS NEED TO MATCH. INCLUDING BUILDING SECTIONS | | | SHOWN ON SHEET A5.0. | | | | | | 3-ENERGY CALCULATIONS WERE REVISED TO HAVE NO CEILING | | | FAN CREDIT, THEREFORE CEILING FANS ARE NOT REQUIRED. | | | BUT, IF CEILING FAN CREDIT IS REINSTATED, THEN | | | ARCHITECT TO SEE TABLE 13-607.1.A.1 FBC 2004 FOR | | | MINIMUM CEILING FAN SIZE REQUIRED.SIZES SHOWN ON SOME | | | ROOMS DON'T COMPLY. | | | | | | 4- ENERGY CALCULATIONS: | | | A) MISSING ADJACENT WALL AT GARAGE AREA. PERSON | | | PREPARING THE ENERGY CALCULATIONS NEEDS TO REVIEW | | | ARCHITECTURAL PLANS TO SEE COMPLETE SCOPE OF WORK. | | | PLANS CALL FOR NEW ADDITIONSAND RENOVATIONS TO THE | | | EXISTING HOUSE.THERE ARE NEW OPENINGS IN THE EXTERIOR | | | WALL AND SOME OPENINGS ARE CLOSED. IN ADDITION THERE IS | | | A NEW ADJACENT WALL IN GARAGE AREA.ENERGY | | | CALCULATIONS TO COMPLY WITH SEC. 13-600.1.C.1 AND SEC. | | | 13-600.1.C.2 OF FBC 2004. | | | | | | B) OWNER/AGENT TO DATE THE ENERGY CALCULATIONS. | | | (REPEAT COMMENT. IT WAS SIGNED, BUT NO DATED). | | | | | | C) R VALUES IN CEILINGS AND WALLS NED TO MATCH | | | ARCHITECTURAL PLANS. | | | | | | 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72 FOR: | | | A) POLYPRO ADHESIVE ROOF TILE AS SPECIFIED ON TILE | | | PRODUCT APPROVAL AND ARCHITECTURAL PLANS. | | | | | | B) ALL SIMPSON ANDUSP STRUCTURAL CONNECTORS | | | SPECIFIED ON PLANS. NEED TO PROVIDE THE 2004 CODE | | | VERSION. SOME OF THE PRODUCT APPROVALS SUBMITTED ARE | | | FOR 2001 CODE VERSION. (SEE FL503 AND FL474 SUBMITTED). | | | GO TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD CURRENT | | | PRODUCT APPROVALS. | | | ALSO,NEED TO PROVIDE PAGE WHERE SPECIFIC CONNECTOR IS | | | SHOWN. (REPEAT COMMENT). ONLY THE COVER PAGE WAS | | | SUBMITTED. THIS APPLIES TO ALL CONNECTOR SUBMITTED. | | | | | | C) BAHAMA SHUTTERS. FL8523-R1 SUBMITTEDIS NOT | | | APPROVED YET. APPLICATION STATUS SAYS "PENDING FBC | | | APPROVAL".NEED ONE WITH APPROVED STATUS. | | | | | | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | ALL REVISED/RE-SUBMITTED PRODUCT APPROVALS AS REQUIRED | | | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 7- NOTICE OF COMMENCEMENT WAS RECORDED ON 07/02/2007. | | | ACCORDING TO SEC. 713.13 FLORIDA STATUTENOTICE OF | | | COMMENCEMENTS ISEXPIRED IF WORK IS NOT STARTED WITHIN | | | 90 DAYS OF RECORDING IT. NEED RE-RECORDED NOTICE OF | | | COMMENCEMENT. | | | | | | 8- REVISE/CLARIFYROOF SHEATHING MATERIALS. | | | INFORMATION ON TYPICAL WALL SECTION "C"ON SHEET A9.0, | | | TYPICALROOF TILE ATTACHMENT DETAIL ON SHEET A8.0 AND | | | ROOF SHEATHING & NAILING NOTE ON SHEET A7.0 DON'T | | | MATCH. REVISE AS REQUIRED. | | | | | | 9- PROVIDE COPY OF THE PAID RECEIPT OF THE IMPACT FEES. | | | NEED COPY TO BE FILED WITH THE CITY FILE. | | | | | | 10- ARCHITECT TODATE DRAWINGS WHEN THE SEAL IS | | | IMPRESSED AS REQUIRED BY SEC. 61G1-16.004(5) OF FLORIDA | | | ADMINISTRATIVE CODE. (REPEAT COMMENT). | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-08-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-08-21 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-08-21 |
Time |
12:39 |
Sent To |
PC |
|
| Notes |
| 2007-08-21 13:16:45 | SINGLE FAMILY RESIDENCE ADDITIONAND RENOVATION | | | BUILDING FIRST REVIEW CHECKLIST. | | | REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC | | | 2004 WITH 2006/2007 REVISIONS. | | | | | | 1- DRAWINGS TITLE BLOCK NEEDS THE NAME OF ARCHITECT | | | SIGNING AND SEALING THE PLANS AND DATE WHEN PLANS ARE | | | SEALED AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA | | | ADMINISTRATIVE CODE. | | | | | | 2- SHEET A1.0 SAYS WIND EXPOSURE "C",WHILE SHEET A2.0 | | | SAYSWIND EXPOSURE "B". REVISE AS REQUIRED TO MATCH. | | | | | | 3- INTERNAL PRESSURE COEFFICIENT SPECIFIED ON SHEET | | | A1.0 IS DIFFERENT THAN THAT SHOWN ON SHEET A2.0. REVISE | | | AS REQUIRED. IS THIS STRUCTURE DESIGNED AS OPEN OR | | | ENCLOSED?.SPECIFY CORRECT INTERNAL PRESSURE | | | COEFFICIENT. | | | | | | 4- SITE PLAN ON SHEET A1.0 SHOWSARROWS FOR DRAINAGE | | | THAT LEAD TO THE NEIGHBOR'S PROPERTY.WATER NEEDS TO | | | BE DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER | | | APPROVED POINT OF COLLECTION.OR WATER TO BE RETAINED | | | IN THE SAME LOT.SEE SEC. R401.3 OF 2004 FLORIDA | | | RESIDENTIAL CODE AND REVISE SITE PLAN AS REQUIRED. | | | | | | 5- PROVIDE WINDOW CUT SHEETS SHOWING HOW SPECIFIED | | | CASEMENT WINDOWS ON BEDROOMS 2 AND 3 COMPLY WITHTHE | | | WIDTHEGRESS REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 6- AREA CALCULATIONS ON SHEET A3.0 DON'T ADD UP | | | CORRECTLY. REVISE AS REQUIRED. | | | | | | 7- SPECIFY ALL DEAD AND LIVE LOADS ANDINCLUDETHE | | | ATTIC LIVE LOADS AS REQUIRED BY TABLE R301.5 OF 2004 | | | FLORIDA RESIDENTIAL CODE. | | | | | | 8- SOIL TEST REPORT: | | | A) PROJECT DESCRIPTION IS TO RAZE EXISTING HOUSE TO | | | BUILD A NEW ONE.ARCHITECTURAL PLANS CALL FOR NEW | | | ADDITIONS TO EXISTING HOUSE. REVISE/CLARIFY AS | | | REQUIRED. | | | | | | B) NEED THE ENGINEERING FIRM CERTIFICATE OF | | | AUTHORIZATION NUMBERIN ALL SHEETS AS REQUIRED BY SEC. | | | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. | | | | | | 9- ARCHITECT TO REVIEWSOIL TEST REPORT FOR FOOTING | | | RECOMMENDATIONS. PROVIDE RESPONSE STATING THAT SOIL | | | TEST REPORTAND RECOMMENDATIONS WAS REVIEWED AND | | | DESIGN CONFORMS TO PROPOSED RECOMMENDATIONS. SEC. | | | 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | 10- ARCHITECT TO SPECIFY ROOF TILE FASTENING AS | | | REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. | | | IF USING NAIL OR SCREWS SPECIFY SIZE AND NUMBER. IF | | | USING ADHESIVES SPECIFY SPECIFIC TYPE AND PROVIDE | | | PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9B-72. | | | | | | 11- ENERGY CALCULATIONS: | | | A) CLARIFY WHY THERE IS NOT INFORMATION GIVEN FOR | | | WATER HEATER IF NEW BATHROOMS ARE ADDED. SEC. 106.1.2 | | | CITY AMENDMENTS TO FBC 2004. | | | | | | B) INSULATION ON WALLS AND CEILING DON'T MATCH | | | ARCHITECTURAL PLANS. | | | | | | C) MISSING ADJACENT WALL AT GARAGE AREA. | | | | | | D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. | | | | | | 12- IF ENERGY CALCULATIONS ARE TAKING THE CEILING FAN | | | CREDIT, THENNEED TO SPECIFY CEILING FAN SIZE IN FLOOR | | | PLANS AS REQUIRED BY TABLE 13-607.1.A.1 FBC 2004. | | | | | | 13- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72 FOR: | | | A) ALL STRUCTURAL SIMPSON OR USP CONNECTORS | | | SPECIFIED ON PLANS. | | | ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL | | | COVER PAGE AND THE SPECIFIC PAGE SHOWING THE CONNECTOR | | | TO SAVE PAPER. | | | | | | B) WINDOW MULLIONS AND CLEARLY IDENTIFY ANCHORING TO | | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES CALCULATED | | | BY THE ARCHITECT. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | | 2004. | | | | | | C) FIXED WINDOWS WITH SIZES AS SHOWN ON PLANS. | | | | | | D) ENTRY DOOR ASSEMBLY AS SHOWN ON PLANS. SEE SIZE | | | ON ARCHITECTURAL PLANS. | | | | | | E) WOOD LOUVERED DOORS SHOWN ON FRONT ELEVATION. | | | | | | F) DECORATIVE BAHAMA SHUTTERS AND CLEARLY IDENTIFY | | | FASTENING. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | 14- SHEET A7.0: | | | A) REVISE RAKED BEAM DETAIL.UPDATEALL SEMCO | | | CONNECTORS. COMPANY IS OUT OF BUSINESS. | | | | | | B) SIMPSON ARCHITECTURAL SERIES CONNECTOR CB46PC | | | SPECIFIED TO HOLD HEAVY TIMBER TRUSSES AT ENTRANCE IS A | | | COLUMN BASE CONNECTOR. REVISE CONNECTOR AS REQUIRED AND | | | PROVIDE COMPLETE DETAIL WITH SPECS. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 15- SHEET A3.0: REVISE EGRESS NOTE #4 OF FIRE RATING & | | | LIFE SAFETY NOTES.WINDOWS MUST MEET MINIMUM WIDTH AND | | | HEIGHT DIMENSIONS, NOT WIDTH OR HEIGHT. REVISE AS | | | REQUIRED TO COMPLY WITH SEC. R310 OF 2004 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 16- SHEET A5.0: PROVIDE COMPLETE SPECS/DETAILSAND | | | LOAD VALUES FOR SIMPSON ARCHITECTURAL SERIES CUSTOM | | | GUSSET PLATES. SIMPSON DOESN'T PROVIDE THIS | | | INFORMATION. THIS IS THE RESPONSIBILITY OF THE DESIGNER | | | OF RECORD.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | 17- SHEET A9.0: | | | A) UPDATE GENERAL CONSTRUCTION NOTE #11. SEE FBC | | | 2004 FOR CORRECT CODE SECTION TO BE REFERENCED. | | | | | | B) REVISE GENERAL CONSTRUCTION NOTE #17.SEE SEC. | | | R606.4 OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT | | | CONCRETE MASONRYMINIMUM NET AREA COMPRESSIVE | | | STRENGTH. | | | ALSO, UPDATE REFERENCED STANDARDS AND YEAR. SEE SEC. | | | R606AND CHAPTER 43 OF 2004 FLORIDA RESIDENTIAL CODE | | | FOR ADOPTED STANDARDS AND YEAR TO BE USED. | | | | | | C) REVISE GENERAL CONSTRUCTION NOTE #38. SEE ASTM | | | C926 AND ASTMC1063 FOR CORRECT FASTENERS AND SPACING TO | | | BE USED ACCORDING TO THE SPECIFIC INSTALLATION AND | | | MATERIALS TO BE USED. | | | | | | D) UPDATE ALL GENERAL NOTES. SEE CHAPTER 35 OF FBC | | | 2004 AND CHAPTER 43 OF 2004 RESIDENTIAL CODE FOR | | | CORRECT ADOPTED STANDARDS AND YEAR TO BE USED AND | | | REVISE/UPDATE NOTES AS REQUIRED. | | | | | | E) REVISE/CLARIFYSPECS ON TYPICAL 1-STORYWALL | | | SECTION. ROOF SHEATHING NOTE CALLS FOR 19/32" CD GRADE | | | WOOD, WHILE TYPICAL FASCIA CONSTRUCTION CALLS FOR 1X6 | | | T&G SHEATHING. | | | | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2008-06-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-09 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-09 |
Time |
15:10 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-01-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-01-22 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-01-22 |
Time |
07:24 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-11-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-11-16 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-11-16 |
Time |
14:06 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-11-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-09 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-09 |
Time |
06:40 |
Sent To |
P |
|
| Notes |
| 2007-10-09 11:28:46 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | ALL COMMENTS RELATE TO SHEET A6.0,UNLESS OTHERWISE | | | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | | OTHERWISE NOTED. | | | | | | THESE COMMENTS ARE FROM THE PREVIOUS REVIEW, THE * IS | | | FURTHER COMMENTARY IN AN ATTEMT TO CLARIFY THE | | | PREVIOUS. | | | | | | 5} PANEL "G" IS NOT SHOWN ON THE RISER DIAGRAM. PROVIDE | | | CONDUCTOR AND CONDUIT SIZE AND TYPE.* PANEL "G" IS NOT | | | LOCATED ON THE PLAN. | | | | | | 10} CIRCUIT "A 13" APPEARS TO BE IN THE KITCHEN AND | | | THEREFORE IS SUBJECT TO ARTICLE 210.52(B)(1) FOR SMALL | | | APPLIANCES.* THIS CONDITION STILL EXISTS, WAS NOT | | | CORRECTED BY ADDING CIRCUIT #38. | | | | | | THIS IS A NEW COMMENT FOR THIS REVIEW | | | | | | 1} A RECEPTACLE NEEDS TO BE ADDED TO THE KITCHEN | | | COUNTERTOP FOR SPACING REQUIREMENTS OF 210.52(C)(1). | | | SEE REVIEWED PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | CONSTRUCTION SERVICES DEPARTMENT | | | 561) 805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-07-31 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-07-31 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-07-31 |
Time |
12:11 |
Sent To |
P |
|
| Notes |
| 2007-07-31 15:08:59 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THERE IS NO RECORD OF THE GENERATOR AND TRANSFER | | | SWITCH, INCLUDED ON THE RISER DIAGRAM, HAVING BEEN | | | PERMITTED. IT APPEARS THAT THE PAD ON THE PLAN DOES NOT | | | MEET SETBACK REQUIREMENTS, MANUFACTURERS, NEC OR | | | MECHANICAL. A SEPARATE PERMIT IS REQUIRED FOR THIS | | | EQUIPMENT. | | | | | | 2} INDICATE THE LOCATION OF THE ?RELOCATED? 200 AMP | | | MAIN DISCONNECT. THE LOCATION SHOWN ON THE PLAN READS | | | "EXISTING". PLEASE CLARIFY. | | | | | | 3} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. THIS IS NECESSARY AS THE EQUIPMENT | | | HAS BEEN MOVED AND FPL WIRE SIZE AND DISTANCE FROM THE | | | TRANSFORMER CHANGE THE EQUATION. | | | | | | 4} THE EQUIPMENT GROUND BETWEEN THE METER AND | | | DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH | | | TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN | | | ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN | | | FROM THE FIRST MEANS OF DISCONNECT. 250.6. | | | | | | 5} PANEL "G" IS NOT SHOWN ON THE RISER DIAGRAM. PROVIDE | | | CONDUCTOR AND CONDUIT SIZE AND TYPE. | | | | | | 6} THE DISHWASHER RECEPTACLE IS MISMARKED "G 11", THE | | | GARAGE DOOR CIRCUIT. | | | | | | 7} CIRCUIT "G 12" IN THE PANTRY IS NOT ON THE PANEL | | | SCHEDULE. | | | | | | 8} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN | | | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS | | | SHALL BE INTERCONNECTED AND HARD WIRED. ALSO SEE THE | | | DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72, | | | CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID | | | CONFUSION IN THE FIELD. SEE 210.12 FOR AFCI | | | CIRCUITING. | | | | | | 9} THE DISCONNECT FOR THE ?EXISTING? CONDENSER DOES NOT | | | APPEAR TO MEET THE CLEARANCE REQUIREMENTS OF 110.26 | | | NEC, IF THE GENERATOR PAD GETS LOCATED WHERE SHOWN. | | | | | | 10} CIRCUIT "A 13" APPEARS TO BE IN THE KITCHEN AND | | | THEREFORE IS SUBJECT TO ARTICLE 210.52(B)(1) FOR SMALL | | | APPLIANCES. | | | | | | 11} THE DISCONNECT CIRCUIT AT THE NEW CONDENSER IS | | | MISMARKED ON THE RANGE CIRCUIT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | CONSTRUCTION SERVICES DEPARTMENT | | | 561) 805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2008-08-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-20 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-20 |
Time |
16:04 |
Sent To |
Z |
|
| Notes |
| 2008-08-20 16:05:15 | TO "Z" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2008-08-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-06 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-06 |
Time |
16:56 |
Sent To |
M |
|
| Notes |
| 2008-08-06 16:57:13 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2008-07-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-21 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-21 |
Time |
11:29 |
Sent To |
M |
|
| Notes |
| 2008-07-21 11:29:51 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2008-07-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-11 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-11 |
Time |
11:21 |
Sent To |
Z |
|
| Notes |
| 2008-07-11 11:22:27 | TO "Z" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2008-07-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-01 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-01 |
Time |
15:47 |
Sent To |
M |
|
| Notes |
| 2008-07-01 15:47:50 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2008-06-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-02 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-02 |
Time |
11:53 |
Sent To |
M |
|
| Notes |
| 2008-06-02 11:53:56 | TO "M" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-05-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-30 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-30 |
Time |
16:36 |
Sent To |
Z |
|
| Notes |
| 2008-05-30 16:36:17 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-03-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-05 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-05 |
Time |
13:53 |
Sent To |
M |
|
| Notes |
| 2008-03-05 13:54:16 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-19 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-19 |
Time |
12:59 |
Sent To |
B |
|
| Notes |
| 2008-02-19 12:59:55 | TO "JGOMEZ" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2008-01-11 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2008-01-11 |
Time |
17:18 |
Sent To |
Z |
|
| Notes |
| 2008-01-11 17:18:54 | TO ZONING BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-09 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-09 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2007-11-09 12:10:53 | TO "BTROBAUG" DESK/RESUB--NEW SHEETS FOR "ELECT." |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-10-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-01 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-01 |
Time |
12:45 |
Sent To |
Z |
|
| Notes |
| 2007-10-01 12:45:42 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-08-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-08-21 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-07-26 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2007-07-26 13:38:36 | TO "SFR" "Z" |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
2008-08-26 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2008-08-26 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2008-08-26 |
Time |
08:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2008-07-15 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2008-07-15 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-07-15 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2008-07-15 15:36:58 | MUST PROVIDE LANDSCAPE CALCULATIONS (REQUIRED AND | | | PROVIDED). | | | | | | MUST PROVIDE PLANT SIZE AND SPACING. | | | | | | BOTH OF THE ABOVE ITEMS CAN BE ON A SEPARATE SHEET AND | | | AFFIXED TO THE LANDSCAPE PLAN. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
10 |
Status |
P |
Date |
2008-08-07 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-07 |
Time |
09:13 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-08-07 |
Time |
09:13 |
Sent To |
B |
|
| Notes |
| 2008-08-07 09:14:04 | REVISION TO ENERGY CAL'S. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
9 |
Status |
F |
Date |
2008-07-21 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-07-21 |
Time |
13:49 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2008-07-21 |
Time |
13:49 |
Sent To |
B |
|
| Notes |
| 2008-07-21 14:06:47 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | REVISION TO ENERGY CALCULATIONS. | | | *** DENIED *** | | | | | | 1) ENERGY CAL'S. LINE 15 IS TAKING THE CROSS | | | VENTILATION CREDIT. PLEASE PROVIDE THE CALCULATIONS | | | SHOWING THE WINDOW AND DOOR OPENINGS ARE 12% OF THE | | | FLOOR AREA, ADD TO BUILDING PLANSSCREENED DOORS TO | | | ALL OUTSIDE DOORS BEING INCLUDED IN THE CALCULATIONS. | | | SEE 2004 FBC 13-607.1.A.3.1. | | | | | | 2) AS THE CROSS VENTILATION CREDIT IS MOSTLY FOR | | | NORTHERN FLORIDA, PLEASE SUBMIT A METEOROLOGICAL REPORT | | | SHOWING THAT WEST PALM BEACH HAS SIGNIFICANT AND | | | CONTINUOUS WINDS DURING THE COOLING MONTHS, PER 2004 | | | FBC 13-607.1.A.3.1. | | | | | | 2004 FBC 13-607.1.A.3.1 CROSS VENTILATION CREDIT. | | | HOUSES FOR WHICH CREDIT IS CLAIMED FOR CROSS | | | VENTILATION IN ACCORDANCE WITH THE CRITERIA IN SECTION | | | 13-607.2.A.3.3 SHALL HAVE PROVIDED OPERABLE APERTURE | | | AREAS TOTALING A MINIMUM OF 12 PERCENT OF THE FLOOR | | | AREA OF THE ROOM FOR ALL PRIMARY LIVING AREAS AND MAIN | | | BEDROOMS. | | | INSECT SCREENS SHALL BE PROVIDED FOR ALL WINDOWS AND | | | DOORS TO BE CONSIDERED OPERABLE APERTURE AREA. ALL | | | SCREENED ENTRY DOORS AND INTERIOR DOORS IN THE | | | VENTILATED AREAS SHALL BE PROVIDED WITH EITHER (1) | | | MECHANICALLY ATTACHED DOOR STOPS (OR SIMILAR DEVICES) | | | TO HOLD THE DOOR IN AN OPEN POSITION OR (2) OPERABLE | | | LOUVERS. | | | THE TOTAL APERTURE AREA SHALL BE PROVIDED BY A MINIMUM | | | OF TWO DISTINCT WINDOWS. EACH WINDOW SHALL PROVIDE NOT | | | MORE THAN 70 PERCENT OF THE TOTAL APERTURE AREA. THE | | | WINDOWS (OR SLIDING GLASS DOORS) SHALL BE PLACED IN | | | ADJACENT OR OPPOSITE WALLS. THE WINDOWS MAY BE PLACED | | | ON A SINGLE OUTSIDE WALL IF WING WALLS ARE USED. | | | WHERE WING WALLS ARE INCLUDED IN THE BUILDING DESIGN | | | FOR VENTILATION PURPOSES, THEY SHALL BE PLACED BETWEEN | | | WINDOWS TO CREATE A HIGH-PRESSURE AND A LOW-PRESSURE | | | ZONE ON EACH WINDOW. WING WALLS SHALL EXTEND FROM THE | | | GROUND TO EVE HEIGHT, BE LOCATED ON THE WINDWARD SIDE | | | OF THE BUILDING, AND EXTEND OUTWARD FROM THE BUILDING A | | | DISTANCE AT LEAST EQUAL TO ONE-HALF THE WIDTH OF THE | | | WINDOW. | | | | | | NOTE: THIS TECHNIQUE IS EFFECTIVE ONLY FOR AREAS WHICH | | | EXPERIENCE SIGNIFICANT AND CONTINUOUS WINDS DURING THE | | | COOLING MONTHS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
F |
Date |
2008-07-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-07-02 |
Time |
10:53 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2008-07-02 |
Time |
10:53 |
Sent To |
B |
|
| Notes |
| 2008-07-02 11:50:27 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | REVISION TO ENERGY CALCULATIONS | | | *** DENIED *** | | | | | | 1) REVISED ENERGY CALCULATIONS LINE 12 SHOWS ONLY ONE | | | A/C SYSTEM, ASTHE ENERGY CAL'S. ARE FOR THE WHOLE | | | HOUSE BOTH A/C SYSTEMS NEED TO BE SHOWN, AND BOTH | | | HEATERS, PER 2004 FBC/ 13-103.3. | | | | | | 2) E-CAL'S LINE 10 IS TAKING THE WHITE ROOF CREDIT. PER | | | 2004 FBC 13-607.1.A.5 WHITE ROOF CREDIT. | | | HOUSES FOR WHICH A WHITE ROOF CREDIT IS CLAIMED IN | | | ACCORDANCE WITH SECTION 13-607.2.A.3.6 SHALL HAVE AN | | | INSTALLED ROOF THAT MEETS THE FOLLOWING CRITERIA: | | | | | | 1. ROOF TYPE MAY ONLY BE METAL, CONCRETE, TILE OR | | | SINGLE-PLY MEMBRANE FOR RESIDENTIAL CONSTRUCTION. | | | | | | 2. ROOF MUST BE WHITE WITH A TESTED TOTAL SOLAR | | | REFLECTANCE OF 65 PERCENT OR GREATER WHEN EVALUATED IN | | | ACCORDANCE WITH ASTM E 903. ROOF SHALL HAVE A SURFACE | | | EMISSIVITY OF 80 PERCENT OR GREATER. TESTING OF A | | | QUALIFYING SAMPLE OF THE ROOFING MATERIAL SHALL BE | | | PERFORMED BY AN APPROVED INDEPENDENT LABORATORY AND | | | PRODUCT LABELING COMMENSURATE WITH THESE RESULTS SHALL | | | BE PROVIDED BY THE MANUFACTURER. PLEASE SUBMIT REQUIRED | | | TEST REPORTS. | | | | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
F |
Date |
2008-06-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-06-11 |
Time |
13:45 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-06-11 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2008-06-11 13:46:46 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | REVISION TO ENERGY CALCULATIONS | | | *** DENIED *** | | | | | | 1) ENERGY CALCULATIONS YOUR ADDITION CAN NOT USE FORM | | | 'C' (600C-04R) AS THE ADDITION IS OVER 600 SQUARE FEET, | | | PER 2004 FBC 13-600.3.C. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2008-06-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-06-02 |
Time |
16:19 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-06-02 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2008-06-02 16:20:26 | REVISION TO MECH. PLAN. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2008-03-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-03-06 |
Time |
08:50 |
Rev Time |
0.35 |
| Received By |
tgordon |
Date |
2008-03-06 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2008-03-06 08:50:39 | REVISION TO MECH. PLAN. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
N |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-01-17 |
Time |
15:49 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2008-01-17 |
Time |
15:49 |
Sent To |
E |
|
| Notes |
| 2008-01-17 15:50:57 | REVISED BUILDING PLANS. NO REVISION TO MECHANICAL PLAN | | | SUBMITTED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-11-16 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-11-16 |
Time |
15:36 |
Rev Time |
0.35 |
| Received By |
tgordon |
Date |
2007-11-16 |
Time |
15:35 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-11-02 |
Time |
12:00 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2007-11-02 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2007-11-02 12:13:06 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) A NOTE WAS SENT BACK WITH THE PLANS STATING ICYNENE | | | IS TO BE INSTALLED, PLEASE SEE BUILDING REVIEW NOTES | | | REGARDING ICYNENE AND COMPLY. | | | | | | 2) ENERGY CALCULATIONS LINE 15 IS TAKING THE CROSS | | | VENTILATION CREDIT, PLEASE SEE 2004 FBC 13-607.1.A.3 | | | AND SHOW HOW THIS ADDITION COMPLIES WITH ALL AND HOW | | | SOUTH FLORIDA COMPLIES WITH THE LAST NOTE. | | | | | | 2004 FBC 13-607.1.A.3.1 CROSS VENTILATION CREDIT. | | | HOUSES FOR WHICH CREDIT IS CLAIMED FOR CROSS | | | VENTILATION IN ACCORDANCE WITH THE CRITERIA IN SECTION | | | 13-607.2.A.3.3 SHALL HAVE PROVIDED OPERABLE APERTURE | | | AREAS TOTALING A MINIMUM OF 12 PERCENT OF THE FLOOR | | | AREA OF THE ROOM FOR ALL PRIMARY LIVING AREAS AND MAIN | | | BEDROOMS. | | | INSECT SCREENS SHALL BE PROVIDED FOR ALL WINDOWS AND | | | DOORS TO BE CONSIDERED OPERABLE APERTURE AREA. ALL | | | SCREENED ENTRY DOORS AND INTERIOR DOORS IN THE | | | VENTILATED AREAS SHALL BE PROVIDED WITH EITHER (1) | | | MECHANICALLY ATTACHED DOOR STOPS (OR SIMILAR DEVICES) | | | TO HOLD THE DOOR IN AN OPEN POSITION OR (2) OPERABLE | | | LOUVERS. | | | THE TOTAL APERTURE AREA SHALL BE PROVIDED BY A MINIMUM | | | OF TWO DISTINCT WINDOWS. EACH WINDOW SHALL PROVIDE NOT | | | MORE THAN 70 PERCENT OF THE TOTAL APERTURE AREA. THE | | | WINDOWS (OR SLIDING GLASS DOORS) SHALL BE PLACED IN | | | ADJACENT OR OPPOSITE WALLS. THE WINDOWS MAY BE PLACED | | | ON A SINGLE OUTSIDE WALL IF WING WALLS ARE USED. WHERE | | | WING WALLS ARE INCLUDED IN THE BUILDING DESIGN FOR | | | VENTILATION PURPOSES, THEY SHALL BE PLACED BETWEEN | | | WINDOWS TO CREATE A HIGH-PRESSURE AND A LOW-PRESSURE | | | ZONE ON EACH WINDOW. WING WALLS SHALL EXTEND FROM THE | | | GROUND TO EVE HEIGHT, BE LOCATED ON THE WINDWARD SIDE | | | OF THE BUILDING, AND EXTEND OUTWARD FROM THE BUILDING A | | | DISTANCE AT LEAST EQUAL TO ONE-HALF THE WIDTH OF THE | | | WINDOW. | | | NOTE: THIS TECHNIQUE IS EFFECTIVE ONLY FOR AREAS WHICH | | | EXPERIENCE SIGNIFICANT AND CONTINUOUS WINDS DURING THE | | | COOLING MONTHS. | | | | | | 3) AS NOTED IN LAST REVIEW 7-27-07 NOTE #5. THE ENERGY | | | CALCULATIONS LINE 15 IS TAKING MULTIZONE HEATING | | | CREDIT, AS THE CALCULATIONS ARE FOR THE ADDITION ONLY | | | AND ONLY ONE SYSTEM IS SERVING THAT AREA THEN IT CAN | | | NOT BE MULTIZONE, CORRECT ENERGY CAL'S. SEE 2004 FBC | | | 13-2 DEFINITIONS. | | | | | | 1 MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-27 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-07-27 |
Time |
09:20 |
Rev Time |
1.00 |
| Received By |
tgordon |
Date |
2007-07-27 |
Time |
09:20 |
Sent To |
E |
|
| Notes |
| 2007-07-27 09:42:02 | *** DENIED *** | | | 1) BUILDING PLANS, THE TITLE BLOCK IS MISSING THE | | | ARCHITECT'S PRINTED NAME AND THE DATE IS MISSING AT THE | | | SEAL, SEE FAC 61G1-16.003 AND 61G1-16.004. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 3) ENERGY CALCULATIONS LINE 11A STATES THE SUPPLY AND | | | RETURN AIR DUCTS IN A CONDITIONED SPACE, MECHANICAL | | | PLANS SHOW THE DUCTS IN THE ATTIC, PLEASE CORRECT THE | | | ENERGY CAL'S. | | | | | | 4) ENERGY CAL'S. STATE THE AIR HANDLER IS IN THE | | | INTERIOR, THE MECHANICAL PLANS SHOW THE AIR HANDLER IS | | | IN THE ATTIC, PLEASE CORRECT ENERGY CAL'S. | | | | | | 5) ENERGY CAL'S. LINE 15 IS TAKING CREDITS FOR | | | MULTIZONE COOLING AND HEATING, AS THE CALCULATIONS ARE | | | FOR THE ADDITION ONLY AND ONLY ONE SYSTEM IS SERVING | | | THAT AREA THEN IT CAN NOT BE MULTIZONE, CORRECT ENERGY | | | CAL'S. | | | | | | 6) COMMENT FOR THE MECHANICAL PLANS, ALL INFORMATION, | | | DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL | | | BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. PER FBC 104.2.1. | | | | | | 7) MECHANICAL PLANS NEED TO SHOW THE SIZE OF THE RETURN | | | AIR DUCT (FLEX) TO THE MASTER BEDROOM. | | | | | | 8) MECHANICAL PLANS NEED TO SHOW THE EXHAUST FANS IN | | | ALL THE BATHROOMS, SEE ELECTRICAL PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2008-02-05 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2008-02-05 |
Time |
07:43 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-11-13 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-10-30 |
Time |
07:50 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-08-13 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2008-07-15 |
Time |
15:33 |
Sent To |
B |
|
| Notes |
| 2007-08-13 15:25:35 | DENIED; | | | 1. ADD NOTE TO DEMO PAGE. " NO DEAD ENDS PERMITED IN | | | THE DRAINAGE SYSTEM, INSPECTION REQUIRED". SEE FBC-2004 | | | SECTION 704.5 | | | 2. SANITARY RISER DIAGRAM, BATHROOM 2 AND 3 , SHOWER IN | | | 2 IS NOT VENTED AND TUB IN BATHROOM 3 IS NOT VENTED. | | | 3. W/M STACK IS TO FAR AWAY FROM KIT. SINK TO RUN A | | | WASTE ARM STUB UP UNDER SINK WITH A MECHANICAL VENT. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2008-06-02 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-06-02 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-06-02 |
Time |
09:38 |
Sent To |
E |
|
| Notes |
| 2008-06-02 09:43:34 | ***APPROVED - REVISION - AS-BUILT CHANGES (GENERATOR | | | LOCATION)*** | | | | | | | | | | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-06-02 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-02-05 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-02-05 |
Time |
09:28 |
Sent To |
E |
|
| Notes |
| 2008-01-15 13:05:14 | ***APPROVED - REVISION - INTERIOR CHANGES ONLY*** | | | | | | | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-10-05 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-10-05 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-10-05 |
Time |
08:37 |
Sent To |
E |
|
| Notes |
| 2007-10-05 08:42:35 | ***APPROVED - RESUB #1***PROVISO: DRIVEWAY TO BE OF A | | | SMOOTH, NON-DUSTING SURFACE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-07-26 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-07-26 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-07-26 |
Time |
15:29 |
Sent To |
I |
|
| Notes |
| 2007-07-26 15:37:22 | ***FAILED*** | | | | | | | | | 1)AS THE VALUE OF PROPOSED WORK EXCEEDS 50% OF THE | | | VALUE OF THE HOUSE, A LANDSCAPE PLAN SHALL BE SUBMITTED | | | SHOWING COMPLIANCE WITH THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS, SECTION 94-442 | | | | | | 2)CLARIFY IF DRIVEWAY IS INCLUDED IN SCOPE OF WORK | | | FOR THIS PERMIT.IF SO, INCLUDE SQUARE FOOTAGE OF | | | PROPOSED DRIVEWAY. | | | | | | 3)PROVIDE NEW MECHANICAL EQUIPMENT SETBACKS TO THE | | | PROPERTY LINES.INCLUDE SETBACK DIMENSIONS FROM THE | | | OUTDOOR SHOWER TO THE PROPERTY LINES. | | | | | | 4)PROVIDE AN EASEMENT CONSENT FORM FROM THE CITY OF | | | WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (1ST | | | FLOOR, CITY HALL) | | | | | | 5)ELEVATION DIMENSIONS SHALL BE SHOWN FROM GRADE TO | | | THE MIDPOINT OF THE ROOF'S SLOPE. | | | | | | 6)ALL OVERHANG DIMENSIONS SHALL BE PROVIDED FROM THE | | | WALL THE OUTERMOST POINT OF THE ROOF. | | | | | | 7)PROVIDE ELEVATION OF PROPOSED FRONT SITEWALL. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|