| 2007-08-08 14:05:03 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE CORRESPONDING LENGTHS NEED TO BE INDICATED |
| | FOR THE CUT LENGTHS OF PIPE ON THE ISOMETRIC TO VERIFY |
| | THE INDICATED LONGEST LENGTH OF EIGHTY FEET (80') ON |
| | THE RESUBMITTAL. |
| | |
| | 2. PLEASE NOTE THE RED LINE CORRECTIONS TO THE CSST |
| | PER TABLE 402.4(14) AND THE GALV. DROP TO THE STOVE PER |
| | TABLE 402.4(2) AND CORRECT THESE ERRORS ON THE |
| | RESUBMITTAL. PLEASE REFERENCE THE ATTACHED TABLES TO |
| | THE DENIED GAS COMMENTS INDICATING THESE CORRECTIONS. |
| | |
| | 3. PLEASE NOTE THAT THERE ARE TWO POEPLE TAKING |
| | RESPONSIBILITY FOR THE DESIGN OF THE DRAWING BY |
| | PRINTING, SIGNING AND DATING THE DRAWING. PER FBC-2004 |
| | CHAPTER 1, SECTION 106.3.4.3 ONLY ONE PERSON NEEDS TO |
| | BE RESONSIBLE FOR THE DESIGN OF THE DRAWING. PLEASE |
| | DELETE ONE OF THE SIGNATURES ON THE RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS WHICH HAVE CHANGED AND |
| | PROVIDE ONE COPY OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL= [email protected] |
| | |
| | |