Plan Review Details - Permit 07070699
Plan Review Stops For Permit 07070699
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-17 Cont ID  
Sent By jgomez Date 2007-10-17 Time 12:39 Rev Time 0.00
Received By jgomez Date 2007-10-17 Time 12:32 Sent To PC
Notes
2007-10-17 13:27:07RESIDENTIAL REROOF BUILDING REVIEW SECOND CHECKLIST.
 REVIEW DONE UNDER EXISTING BUILDING CODE 2004,FLORIDA
 RESIDENTIAL BUILDING CODE 2004 AND FBC 2004.
  
  
 1- NEED TO SPECIFY WHICH APPROVED FLAT ROOF ASSEMBLY IS
 GOING TO BE INSTALLED AS REQUIRED FOR CITY POLICY FOR
 RE-ROOFING PERMITS. SEE ATTACHED COPY (REPEAT
 COMMENT).
  
 2- SPECIFYBASE SHEET SPECIFIC FASTENING OPTION TO BE
 USED ON SELECTED FLAT ROOF ASSEMBLY (REPEAT COMMENT).
  
 3- IF SELECTED ASSEMBLYIS LIMITED BY GENERAL
 LIMITATION #7, THEN PROVIDE RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 03-0501.02 SUBMITTEDAND TABLE 1609.6.2.1(2) OF FBC
 2004.
 ***NOTE: IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN IT CAN'T BE USED IN THIS AREA
 BECAUSE GENERAL LIMITATION #9 ON LAST PAGE OF NOA
 SUBMITTED DOESN'T ALLOW NAIL ENHANCING (REPEAT
 COMMENT).
  
 4- PROVIDE 2 COPIES OF ROOFING PRODUCT APPROVAL. ONLY
 ONE COPY WAS SUBMITTED THIS TIME.
  
 5- RE-SUBMITTAL FEES ARE DUE EACH TIME AFTER THE FIRST
 RESUBMITTAL.SEE FEES ON TOP OF SUBMITTAL FORM.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-23 Cont ID  
Sent By jgomez Date 2007-07-23 Time 16:34 Rev Time 0.00
Received By jgomez Date 2007-07-23 Time 16:34 Sent To PC
Notes
2007-07-23 16:41:21BUILDING REVIEW CHECKLIST:
 1- NEED TO SPECIFY WHICH APPROVED FLAT ROOF ASSEMBLY IS
 GOING TO BE INSTALLED AS REQUIRED FOR CITY POLICY FOR
 RE-ROOFING PERMITS. SEE ATTACHED COPY.
  
 2- SPECIFYBASE SHEET SPECIFIC FASTENING OPTION TO BE
 USED ON SELECTED FLAT ROOF ASSEMBLY.
  
 3- IF SELECTED ASSEMBLYIS LIMITED BY GENERAL
 LIMITATION #7, THEN PROVIDE RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 03-0501.02 SUBMITTEDAND TABLE 1609.6.2.1(2) OF FBC
 2004.
 ***NOTE: IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN IT CAN'T BE USED IN THIS AREA
 BECAUSE GENERAL LIMITATION #9 ON LAST PAGE OF NOA
 SUBMITTED DOESN'T ALLOW NAIL ENHANCING.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-07-20 Cont ID  
Sent By ssherman Date 2007-07-20 Time 12:24 Rev Time 0.00
Received By ssherman Date 2007-07-20 Time 12:24 Sent To  
Notes
2007-07-20 12:24:27HISTORICAL APPROVAL PER JILLIAN PAPA