| Plan Review Stops For Permit 07070682 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-10-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-10 |
Time |
07:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-10 |
Time |
06:18 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-09-19 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-19 |
Time |
18:13 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-19 |
Time |
18:13 |
Sent To |
|
|
| Notes |
| 2007-09-19 18:15:24 | BUILDING PLAN REVIEW | | | PERMIT: 07070682 | | | ADD: 5707 S.DIXIE HWY. #B | | | CONT: SURGE SOLUTIONS GROUP | | | TEL: (561)333-3600 EX3 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)OK | | | | | | 3)OK | | | | | | 3)FBC 106.1.2 THE PERSON TAKING RESPONSIBILITY FOR | | | THE DRAWINGS SHALL SIGN/SEAL AND DATE THE DRAWINGS. ALL | | | DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATAREQUIRED | | | BY THE BUILDING OFFICIAL TO BE PREPARED BY AN ARCHITECT | | | OR ENGINEER SHALL BE AFFIXED WITH THEIR OFFICIAL SEAL, | | | SIGNATURE AND DATE AS STATE LAW REQUIRES. | | | **NEW** | | | THE INFORMATION ON THE ARCHITECT SEAL SHALL BE CLEAR | | | AND LEGIBLE. FBC 106.1.1* | | | | | | 4)A TITLE BLOCK WITH THE INFORMATION SPECIFIED PER | | | 61G1-16.004 FAC SHALL BE PRESENT ON DRAWINGS ISSUED BY | | | THE RESPONSIBLE ARCHITECT AND MUST, | | | AT A MINIMUM CONTAIN | | | 1) FIRM NAME, ADDRESS, AND TELEPHONE # | | | 2) FIRM LICENCE # | | | 3) NAME OF PROJECT | | | 4) DATE PREPARED | | | 5) A SPACE FOR SIGNATURE & DATED SEAL | | | 6) A SPACE FOR PRINTED NAME OF PERSON SEALING THE | | | DOCUMENT. | | | **NEW** | | | THE SEAL OF THE ARCHITECT IS ILLEGIBLE. FBC 106.1.1* | | | | | | 5) PROVIDE AN EXISTING AND PROPOSED FLOOR PLAN OF THE | | | PROJECT SHOWING ALL EXISTING WALLS AND THE PROPOSED NEW | | | WALLS. THE DRAWINGS SHALL HAVE THE COMPLETE ADDRESS | | | INCLUDING THE SUITE NUMBER ON EACH SHEET. A WALL LEGEND | | | INDICATING THE EXISTING WALLS AND THE NEW WALLS LISTING | | | ALL THE MATERIALS TO BE USED. | | | **NEW** | | | ADDITIONAL INFORMATION IS REQUIRED FOR THE STABILITY OF | | | THE 8 FOOT WALL. SHOW HOW THE WALLS WILL BE BRACED. | | | | | | 6)OK | | | | | | 7)OK | | | | | | 8)OK | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-13 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-11 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2007-08-11 09:51:08 | BUILDING PLAN REVIEW | | | PERMIT: 07070682 | | | ADD: 5707 S.DIXIE HWY. #B | | | CONT: SURGE SOLUTIONS GROUP | | | TEL: (561)333-3600 EX3 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR | | | RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PROJECT IS DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED | | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT | | | . ------------------------------------- | | | ) NUMBER OF UNITS | | | ) NUMBER OF FLOORS | | | ) NUMBER OF ROOMS | | | ) SQ. FT. FOOTPRINT | | | | | | 3)2004 FBC EXISTING | | | 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | | | 3)FBC 106.1.2THE PERSON TAKING RESPONSIBILITY FOR | | | THE DRAWINGS SHALL SIGN/SEAL AND DATE THE DRAWINGS. ALL | | | DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATAREQUIRED | | | BY THE BUILDING OFFICIAL TO BE PREPARED BY AN ARCHITECT | | | OR ENGINEER SHALL BE BE AFFIXED WITH THEIR OFFICIAL | | | SEAL,SIGNATURE AND DATE AS STATE LAW REQUIRES. | | | | | | 4)A TITLE BLOCK WITH THE INFORMATION SPECIFIED PER | | | 61G1-16.004 FAC SHALL BE PRESENT ON DRAWINGS ISSUED BY | | | THE RESPONSIBLE ARCHITECT AND MUST, | | | AT A MINIMUM CONTAIN | | | 1) FIRM NAME,ADDRESS, AND TELEPHONE # | | | 2) FIRM LICENCE # | | | 3) NAME OF PROJECT | | | 4) DATE PREPARED | | | 5) A SPACE FOR SIGNATURE & DATED SEAL | | | 6) A SPACE FOR PRINTED NAME OF PERSON | | | SEALING THE DOCUMENT. | | | | | | 5) PROVIDE AN EXISTING AND PROPOSED FLOOR PLAN OF THE | | | PROJECT SHOWING ALL EXISTING WALLS AND THE PROPOSED NEW | | | WALLS. THE DRAWINGS SHALL HAVE THE COMPLETE ADDRESS | | | INCLUDING THE SUITE NUMBER ON EACH SHEET. A WALL LEGEND | | | INDICATING THE EXISTING WALLS AND THE NEW WALLS LISTING | | | ALL THE MATERIALS TO BE USED. | | | | | | 6)ON A FINISH SCHEDULE PROVIDE THE FLAME SPREAD/SMOKE | | | DEVELOPMENT IN COMPLIANCE WITH FBC. 803 / 804 AND 805. | | | | | | 7)A LIFE SAFETY PLAN SHOWING ALL MEANS OF EGRESS PER | | | FBC CH. 10. | | | | | | 8)106.1.3 THE BUILDING OFFICIAL | | | MAY SET STANDARDS THROUGH DEPARTMENTAL | | | POLICY STANDARDS FOR PLANS AND SPRCIFICA | | | TIONS. "NO WHITE OUT". "NO HANDWRITING" ON THE | | | DRAWINGS. PLANS SHALL BE DRAWI TO A MINIMUM 1/8 INCH | | | SCALE UPON SUBSTANTIAL PAPER. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-09-17 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-09-17 |
Time |
07:47 |
Sent To |
|
|
| Notes |
| 2007-09-18 12:32:47 | | | | | | | ELECTRICAL PLANS SUBMITTED FOR EXISTING ONLY. NO | | | ELECTRICAL CONTRACTOR SIGNED ON./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-08-15 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-08-15 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-08-15 |
Time |
17:04 |
Sent To |
|
|
| Notes |
| 2007-08-15 17:17:29 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS,2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} INDICATE COMPLIANCE WITH NFPA-101, 700.12 NEC,FOR | | | EMERGENCY AND EGRESS LIGHING. | | | | | | 2} INDICATE COMPLIANCE WITH CHAPTER 13 FBC. | | | | | | 3} SHOW RELOCATION AND ADDITIION OF RECEPTACLES, | | | OUTLETS AND VOICE AND DATA DEVICES. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-10-09 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-09 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-09 |
Time |
10:20 |
Sent To |
B1 |
|
| Notes |
| 2007-10-09 10:37:15 | *****APPROVED***** | | | | | | THECOMMENTS FROM THE PREVIOUS REVIEWS HAVE BEEN | | | ADDRESSED;PLAN SHEETS A-2.2 AND E-1.0 WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-09-25 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-09-25 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2007-09-25 11:41:05 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS REVIEW | | | STILL NEED TO BE ADDRESSED: | | | | | | | | | 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED.REFERENCE THE 2003 EDITION, NOT THE 2000 | | | EDITION AS INDICATED ONA-1.2 | | | | | | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | REFERENCE 241, NOT 242 AS INDICATED ON A-1.2 | | | | | | 7.PROVIDE A LIFE SAFETY PLAN WHICH SHOWS TRAVEL | | | DISTANCE TO THE EXIT, LOCATION OF FIRE EXTINGUISHER(S), | | | EXIT AND EMERGENCY LIGHTS.TRAVEL DISTANCE NOT SHOWN; | | | THE TRAVEL DISTANCE TO AN EXIT SHALL BE MEASURED AS PER | | | 7.6.1 OF NFPA 101 | | | | | | 8.SPECIFY THE INTERIOR FINISH MATERIAL MATERIALS FOR | | | THE NEW WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | INDICATE CLASSIFICATIONS FOR EXITS, EXIT AISLE | | | CORRIDORS, AND OTHER SPACES ON A-2.2 | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-08-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-20 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-20 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2007-08-20 11:04:08 | *****DENIED***** | | | | | | | | | 1.THE PROJECT SITE, INCLUDING THE SUITE NUMBER, SHALL | | | BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 2.PLEASE INDICATE THE EXISTING AS WELL AS THE | | | PROJECTED USE AND OCCUPANCY CLASSIFICATION. | | | | | | 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 5.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | EMERGENCY ACCESS TO THE SAID PROPERTY OR THE VICINITY | | | THEREOF. | | | | | | 6.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 7.PROVIDE A LIFE SAFETY PLAN WHICH SHOWS TRAVEL | | | DISTANCE TO THE EXIT, LOCATION OF FIRE EXTINGUISHER(S), | | | EXIT AND EMERGENCY LIGHTS. | | | | | | 8.SPECIFY THE INTERIOR FINISH MATERIAL MATERIALS FOR | | | THE NEW WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS | | | C. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-10-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-02 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-02 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2007-10-05 15:28:00 | TO "BOB"#13 | | 2007-10-02 12:29:19 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-06 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-06 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2007-09-11 14:06:39 | TO "BOB"#10 | | 2007-09-06 11:06:47 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-08-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-20 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-24 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2007-08-01 11:10:09 | TO "BOB"#5 | | 2007-07-24 09:31:09 | WAITING FOR "BOB" |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-08-06 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-08-06 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-08-06 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2007-08-06 16:54:24 | *ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK | | | DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. |
|
|