Plan Review Details - Permit 07070651
Plan Review Stops For Permit 07070651
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-10 Cont ID  
Sent By rmcdouga Date 2007-09-10 Time 16:09 Rev Time 0.00
Received By rmcdouga Date 2007-09-10 Time 16:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-31 Cont ID  
Sent By rmcdouga Date 2007-08-31 Time 08:39 Rev Time 0.00
Received By rmcdouga Date 2007-08-31 Time 08:11 Sent To  
Notes
2007-08-31 09:52:252004 FBC W/2007 SUPPLEMENTS
 INSTALL HURRICANE IMPACT SCREENS
 2ND REVIEW
  
 DENIED BY BUILDING
  
 1) THE IMPACT SCREEN MULLIONS DO NOT HAVE STATE OR
 MIAMI-DADE PRODUCT APPROVALS AS REQUIRED BY FAC RULE
 9B-72. THE MANUFACTURER IS REQUIRED TO APPLY FOR
 LOCAL/SITE SPECIFICPRODUCT APPROVAL. SEE ATTACHMENT.
 FBC 1609.1.4 REQUIRES IMPACT-RESISTANT PRODUCTS TO BE
 TESTED.
  
 2) THE ENGINEERING SUBMITTED IS NOT ACCEPTABLE. FBC
 1609.1.4 REQUIRES IMPACT RESISTANT COVERINGS TO MEET
 THE REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E
 1996, OR MIAMI-DADE TAS 201, 202, AND 203. OPENINGS
 LOCATED WITHIN 30 FEET OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSLE TEST. SUBMIT LARGE
 MISSILE IMPACT TEST REPORTS SPECIFIED FOR THE
 MULLIONS.
  
 3)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-20 Cont ID  
Sent By rmcdouga Date 2007-08-20 Time 12:18 Rev Time 0.00
Received By rmcdouga Date 2007-08-20 Time 12:18 Sent To  
Notes
2007-08-20 12:19:102004 FBC W/2007 SUPPLEMENTS
 INSTALL HURRICANE IMPACT SCREENS
  
 DENIED BY BUILDING
  
 1) THE IMPACT SCREEN MULLIONS DO NOT HAVE STATE OR
 MIAMI-DADE PRODUCT APPROVALS AS REQUIRED BY FAC RULE
 9B-72. THE MANUFACTURER IS REQUIRED TO APPLY FOR
 LOCAL/SITE SPECIFICPRODUCT APPROVAL. SEE ATTACHMENT.
 FBC 1609.1.4 REQUIRES IMPACT-RESISTANT PRODUCTS TO BE
 TESTED.
  
 2)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-07 Cont ID  
Sent By adarroug Date 2007-09-07 Time 09:45 Rev Time 0.00
Received By adarroug Date 2007-09-07 Time 09:45 Sent To B
Notes
2007-09-07 09:46:08TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 11:29 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 11:29 Sent To B
Notes
2007-08-30 11:30:17TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-20 Cont ID  
Sent By rmcdouga Date 2007-08-20 Time 12:18 Rev Time 0.00
Received By rmcdouga Date 2007-07-23 Time 10:18 Sent To  
Notes
2007-07-23 10:17:32TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-24 Cont ID  
Sent By choops Date 2007-07-24 Time 14:55 Rev Time 0.00
Received By choops Date 2007-07-24 Time 14:55 Sent To B
Notes
***NONE***