Plan Review Details - Permit 07070560
Plan Review Stops For Permit 07070560
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-23 Cont ID  
Sent By rmcdouga Date 2007-10-23 Time 17:46 Rev Time 0.00
Received By rmcdouga Date 2007-10-23 Time 17:41 Sent To  
Notes
2007-10-23 17:46:09DENIED BY BUILDING
 SAME COMMENTS AS THE LAST REVIEW.
  
 1) THE SOIL ANCHOR PLAN HAS AN ENGINEER'S TITLE BLOCK
 AND COPIED SIGNATURE. THE FLORIDA STATUTES FS 471 AND
 FAC 61G15-23.002 REQUIRES ALL PLANS OR OTHER DOCUMENTS
 FROM AN ENGINEER SUBMITTED FOR PUBLIC RECORD TO HAVE
 THE ENGINEER'S ORIGINAL SIGNATURE AND EMBOSSED SEAL ON
 THEM. THE MODULAR BUILDING PLANS WITH THE STATE STAMPS
 ARE EXEMPT FROM THIS REQUIREMENT, BUT THE ANCHORING
 PLANS ARE NOT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-04 Cont ID  
Sent By rmcdouga Date 2007-10-04 Time 08:36 Rev Time 0.00
Received By rmcdouga Date 2007-10-04 Time 08:36 Sent To  
Notes
2007-10-04 08:49:36DENIED BY BUILDING
  
 1) THE SOIL ANCHOR SCHEDULE HAS AN ENGINEER'S TITLE
 BLOCK AND COPIED SIGNATURE. THE FLORIDA STATUTES FS 471
 AND FAC 61G15-23.002 REQUIRES ALL PLANS OR OTHER
 DOCUMENTS FROM AN ENGINEER SUBMITTED FOR PUBLIC RECORD
 TO HAVE THE ENGINEER'S ORIGINAL SIGNATURE AND EMBOSSED
 SEAL ON THEM. THE MODULAR BUILDING PLANS WITH THE STATE
 STAMPS ARE EXEMPT FROM THIS REQUIREMENT, BUT THE
 ANCHORING PLANS ARE NOT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-10 Cont ID  
Sent By rmcdouga Date 2007-08-10 Time 15:13 Rev Time 0.00
Received By rmcdouga Date 2007-08-10 Time 15:13 Sent To  
Notes
2007-08-10 15:12:432004 FBC W/2007 REVISIONS
 BUILD A 120 SQFT STORAGE SHED
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO SETS OF DRAFTSMAN QUALITY PLANS DRAWN TO
 A MINIMUM 1/8TH INCH SCALE FOR THE SHED. THE PLANS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE PROPOSED WORK AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF 2004 FBC AND RELEVANT LAWS, ORDANCES, RULES AND
 REGULATIONS AS DETERMINED BY THE BUILDING OFFICIAL. SEE
 2004 FBC * CITY AMENDMENT 106.1.1 AND 106.1.3. PROVIDE
 FOUNDATION PLAN, WALL SECTIONS, ELEVATIONS, ETC.
 SPECIFY ALL STRAPS, ANCHORS, TRUSS CONNETORS, ETC.
  
  
 2) 2004 FBC* CITY AMENDMENT 106.1.3 THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN
 IS REQUIRED TO BE ON ALL DRAWINGS.
  
 3) SPECIFY THE BASIC WIND SPEED ON THE PLANS. THE BASIC
 WINDSPEED FOR THE CITY OF WPB IS 140 MPH, 3-SECOND
 GUST. R301.2.1.5
  
 4) R301.1 DESIGN.
 BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, SHALL
 BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING
 DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS AND
 WIND LOADS AS PRESCRIBED BY THIS CODE. THE CONSTRUCTION
 OF BUILDINGS AND STRUCTURES SHALL RESULT IN A SYSTEM
 THAT PROVIDES A COMPLETE LOAD PATH CAPABLE OF
 TRANSFERRING ALL LOADS FROM THEIR POINT OF ORIGIN
 THROUGH THE LOAD-RESISTING ELEMENTS TO THE FOUNDATION.
  
  
 5) FBCR401.2 REQUIREMENTS.
 FOUNDATIONS SHALL BE CAPABLE OF RESISTING ALL LOADS
 FROM ROOF UPLIFT AND BUILDING OVERTURN. FOUNDATION
 CONSTRUCTION SHALL ALSO BE CAPABLE OF ACCOMMODATING ALL
 GRAVITY LOADS ACCORDING TO SECTION R301 AND OF
 TRANSMITTING THE RESULTING LOADS TO THE SUPPORTING
 SOIL.
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF STATE OF FLORIDA OR MIAMI-DADE PRODUCT
 APPROVALS AS REQUIRED BY RULE 9B-72 FOR: EXTERIOR
 WINDOWS AND DOORS, ROOFING MATERIAL, ETC.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 7)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-19 Cont ID  
Sent By adarroug Date 2007-10-19 Time 08:11 Rev Time 0.00
Received By adarroug Date 2007-10-19 Time 08:11 Sent To Z
Notes
2007-10-19 08:12:04TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 09:24 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 09:24 Sent To Z
Notes
2007-09-28 09:25:22TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-10 Cont ID  
Sent By rmcdouga Date 2007-08-10 Time 15:13 Rev Time 0.00
Received By rmcdouga Date 2007-07-19 Time 16:07 Sent To  
Notes
2007-07-19 16:07:15TO "Z" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-23 Cont ID  
Sent By choops Date 2007-10-23 Time 16:46 Rev Time 0.00
Received By choops Date 2007-10-23 Time 16:46 Sent To B
Notes
2007-10-23 16:46:34***APPROVED - RESUB #2*** PROVISO:MUST MAINTAIN 6'
 MIN. SEPARATION DISTANCE FROM SHED TO PRINCIPAL
 STRUCTURE.
  
 SENT TO "B" = RMC

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-02 Cont ID  
Sent By choops Date 2007-10-02 Time 10:25 Rev Time 0.00
Received By choops Date 2007-10-02 Time 10:25 Sent To B
Notes
2007-10-02 10:26:30***APPROVED - RESUB #1*** PROVISO:MUST MAINTAIN 6'
 MIN. SEPARATION DISTANCE FROM SHED TO PRINCIPAL
 STRUCTURE.
  
 SENT TO "B" = RMC

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-23 Cont ID  
Sent By choops Date 2007-07-23 Time 11:32 Rev Time 0.00
Received By choops Date 2007-07-23 Time 11:32 Sent To B
Notes
2007-07-23 11:35:00***FAILED***
  
  
 1)INDICATE HEIGHT OF PROPOSED SHED.
  
 2)PROVIDE SETBACK DIMENSIONS FROM SHED TO PROPERTY
 LINES.NOTE: MUST BE A MINIMUM OF 5' TO REAR AND SIDE
 PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720