Plan Review Details - Permit 07070511
Plan Review Stops For Permit 07070511
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-04 Cont ID  
Sent By rmcdouga Date 2007-10-04 Time 14:05 Rev Time 0.00
Received By rmcdouga Date 2007-10-04 Time 10:27 Sent To FIRE
Notes
2007-10-04 14:05:48BUILDING PROVISO
  
 THE GATES SHALL COMPLY WITH THE EGRESS REQUIREMENTS OF
 FBC 1008. GATES SHALL SWING IN THE DIRECTION OF TRAVEL
 AND SHALL BE READILY OPENABLE FROM THE EGRESS SIDE
 WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE OR
 EFFORT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-13 Cont ID  
Sent By rmcdouga Date 2007-08-13 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2007-08-13 Time 07:14 Sent To  
Notes
2007-08-13 11:47:042004 FBC W/ 2007 REVISIONS
 INSTALL ALUMINUM GATES AND FENCE
  
 DENIED BY BUILDING
  
 1) THE SITE PLAN SPECIFIES 9 FT. FENCE HEIGHT AND THE
 ENGINEERING IS FOR A MAXIMUM HEIGHT OF 6 FT. ( 72") .
 PLEASE CORRECT.
  
 2) THE LOCATION OF THE WORK IS REQUIRED TO BE
 IDENTIFIED IN THE TITLE BLOCK OF THE ENGINEERED
 DRAWINGS. FBC 106.1.3* AMENDED BY THE CITY OF WPB.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-10-04 Cont ID  
Sent By mwennerg Date 2007-10-04 Time 15:12 Rev Time 0.00
Received By mwennerg Date 2007-10-04 Time 15:12 Sent To  
Notes
2007-10-04 15:18:26***PROVISO***
  
 SIDE-HINGED OR PIVOTED-SWINGING TYPE DOORS THAT ARE
 PART OF A REQUIRED MEANS OF EGRESS SHALL SWING IN THE
 DIRECTION OF TRAVEL WHERE SERVING ROOMS OR AN AREA WITH
 AN OCCUPANT LOAD OF 50 OR GREATER IN ACCORDANCE WITH
 NFPA 101, SEC. 7.2.1.4.2. LOCKS SHALL NOT REQUIRE THE
 USE OF A KEY, TOOL OR SPECIAL KNOWLEDGE TO OPERATE FROM
 EGRESS SIDE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 09:32 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 09:32 Sent To Z
Notes
2007-10-11 09:33:04TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 16:21 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 16:21 Sent To Z
Notes
2007-09-28 16:21:17TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-13 Cont ID  
Sent By rmcdouga Date 2007-08-13 Time 16:42 Rev Time 0.00
Received By rmcdouga Date 2007-07-19 Time 09:04 Sent To  
Notes
2007-07-19 09:04:21TO "Z" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-15 Cont ID  
Sent By choops Date 2007-10-15 Time 13:31 Rev Time 0.00
Received By choops Date 2007-10-15 Time 13:30 Sent To PC
Notes
2007-10-15 13:31:51***APPROVED - RESUB #2***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-04 Cont ID  
Sent By choops Date 2007-10-04 Time 09:18 Rev Time 0.00
Received By choops Date 2007-10-04 Time 09:18 Sent To B
Notes
2007-10-04 09:19:19***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)PLEASE PROVIDE AN EASEMENT CONSENT FORM FROM THE
 CITY OF WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES
 (1ST FLOOR, CITY HALL)
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-23 Cont ID  
Sent By choops Date 2007-07-23 Time 11:01 Rev Time 0.00
Received By choops Date 2007-07-23 Time 11:01 Sent To B
Notes
2007-07-23 11:07:01***FAILED***
  
  
 1)PLEASE PROVIDE AN EASEMENT CONSENT FORM FROM THE
 CITY OF WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES
 (1ST FLOOR, CITY HALL)
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720