Plan Review Details - Permit 07070482
Plan Review Stops For Permit 07070482
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-02-04 Cont ID  
Sent By lursu Date 2008-02-04 Time 14:56 Rev Time 0.00
Received By lursu Date 2008-02-04 Time 14:56 Sent To  
Notes
2008-02-04 14:57:12PERMIT ASSIGNED TO SUITE 201.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-08-15 Cont ID  
Sent By lursu Date 2007-08-15 Time 10:22 Rev Time 0.00
Received By lursu Date 2007-08-15 Time 10:22 Sent To  
Notes
2007-08-15 10:29:45THE PERMIT APPLICATION DOES NOT HAVE ANY INDICATIONS OF
 THE SUITE( UNIT) NUMBER IN WHICH THE IMPROVEMENT WORK
 IS TO BE PERFORMED.IT IS THE OWNER RESPONSIBILITY TO
 ASSIGN UNIT NUMBERS ( USED AS SITE ADDRESSES ) TO ALL
 UNITS INSIDE THE BUILDING.
  
 GUIDELINE IN ASSIGNING THESE NUMBERS :
  
 GROUND/FIRST FLOOR: FROM 100 TO 199 AS : 100 MAIN ST. #
 101, INDICATES THE UNIT ON THE FIRST FLOOR
 SECOND FLOOR: FROM 200 TO 299 AS 100 MAIN ST. # 201,
 INDICATES THE FIRST UNIT ON THE SECOND FLOOR
  
 PLEASE INDICATE THE CORRECT UNIT NUMBER ON THE PERMIT
 APPLICATION AND SITE PLANS .
 IF YOU HAVE ANY QUESTIONS PLEASE CALL .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-03-22 Cont ID  
Sent By mawillia Date 2008-04-10 Time 17:12 Rev Time 0.00
Received By mjacobs Date 2008-03-22 Time 12:58 Sent To  
Notes
2008-03-22 15:28:29PROVISO:
 DOORS #12 AND #14 SHALL AUTOMATICALLY OPEN AND
 ACCESSIBLE DURING ANY EMERGENCY SITUATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-02-27 Cont ID  
Sent By mjacobs Date 2008-02-27 Time 09:58 Rev Time 0.00
Received By mjacobs Date 2008-02-26 Time 12:13 Sent To  
Notes
2008-02-27 09:56:48BUILDING PLAN REVIEW
 PERMIT: 07070482
 ADD: 1920 WEKIVA WAY
 CONT: PHOENIX REALTY HOMES
 TEL: (561)799-5900
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD 2-27-08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)FBC 1013.2. AN EXIT ACCESS SHALL NOT PASS THROUGH A
 ROOM THAT CAN BE LOCKED TO PREVENT EGRESS. DOORS 12 AND
 14 ARE LOOKED DOORS THAT LEAD TO THE EXIT STAIRS. DOORS
 LEADING TO THE EGRESS SHALL BE READILY OPERABLE IN THE
 DIRECTION OF EGRESS TRAVEL WITHOUT THE USE OF KEYS,
 SPECIAL KNOWLEDGE OR EFFORT.
  
 3)1008.1.3.2 POWER-OPERATED DOORS.
 WHERE MEANS OF EGRESS DOORS ARE OPERATED BY POWER, SUCH
 AS DOORS WITH A PHOTOELECTRIC-ACTUATED MECHANISM TO
 OPEN THE DOOR UPON THE APPROACH OF A PERSON, OR DOORS
 WITH POWER-ASSISTED MANUAL OPERATION, THE DESIGN SHALL
 BE SUCH THAT IN THE EVENT OF POWER FAILURE, THE DOOR IS
 CAPABLE OF BEING OPENED MANUALLY TO PERMIT MEANS OF
 EGRESS TRAVEL OR CLOSED WHERE NECESSARY TO SAFEGUARD
 MEANS OF EGRESS.
  
 4)OK
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-09 Cont ID  
Sent By jjohnsto Date 2007-11-09 Time 14:34 Rev Time 2.00
Received By jjohnsto Date   Time   Sent To  
Notes
2007-11-09 14:30:53CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR,
 WEST PALM BEACH, FLORIDA33401
 TEL:561-805-6713FAX:561-805-6731
  
 JAMES JOHNSTON,
 BUILDING PLAN EXAMINER II
 E-MAIL:JJOHNSTON @WPB.ORG
  
  
 PERMIT NO 07070482
 PROJECT MERCHANT SERVICES
 ADDRESS1920WEKIVA WAY, SUITE 201
 DATE NOVEMBER 9, 2007
  
  
 BUILDINGPLANREVIEW
  
 FLORIDA BUILDING CODES 2004 W REVISIONS
  
 RESULTS OF A PLAN REVIEW BY JIM WHITMER,BUILDING
  
 4)KNEE CLEARANCE BREAK ROOM,CONFERENCE ROOM
  
 COMMENT
 THE CABINETS UNDER THE SINKS ARE IN VIOLATION OF
  
 THEFLORIDA ACCESSIBILITY CODE11-4.24.3
 PLEASE REMOVE THE CABINET AND FURNISH A
 COUNTER FOR KNEE ACCESSIBILITY AT EACH SPACE.
  
 SEE THIS CODE SECTION FOR FURTHER EXPLANATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-17 Cont ID  
Sent By jwitmer Date 2007-08-17 Time 12:51 Rev Time 2.22
Received By jwitmer Date 2007-08-17 Time 12:51 Sent To  
Notes
2007-08-17 14:39:461920 WEKIVA WAY 2ND FLOOR BUILD-OUT
  
  
 PERMIT: 07070482
 ADD: 1920 WEKIVA WAY
 CONT: ANDERSON-MOORE CONSTRUCTION
 ? THE CAPITAL CITY OF THE PALM BEACHES?
 TEL: (561)662-1819
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLEASE PROVIDE THE OCCUPANT LOAD THAT WILL BE GOING
 THROUGH VARIOUS DOORS. IT APPEARS THAT
 SOME OF THE DOORS MAY HAVE AN OCCUPANT LOAD GREATER
 THAN 50 REQUIRINGTHE DOOR TO SWING IN THE DIRECTION
 OF EGRESS TRAVEL SEE 1008.1.2 AND 1002.1 (DEFINITIONS)
 OCCUPANT LOAD.
  
 4) SHEET A2.10.1THE BREAK ROOM SINK AND THE
 CONFERENCE ROOM SINK WILL BOTH REQUIRE THE FOLLOWING:
 SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH
 THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 5) SHEET A125.2 DOOR # 9 IS MISSING THE 18? ON THE
 LATCH SIDE OF THE DOOR. 11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
 6) SHEET A125.3 DOOR# 19 IS ALSO MISSING THE REQUIRED
 18? AT THE LATCH SIDE. 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 7) SHEET A125.4 DOOR # 27 MAY OR MAY NOT MEET THE 18?
 REQUIRED FOR THE LATCH SIDE OF THE DOOR , PLEASE
 PROVIDE MEASUREMENTS. 11-4.13.6 MANEUVERING
 CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT
 ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE FLOOR
 OR GROUND AREA WITH IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 8) MISSING SHEET A150.3 REFLECTED CEILING PLAN
 NORTHEAST QUADRANT, 106.1.2 ADDITIONAL INFORMATION
 REQUIRED. TABLE 1006 . > 2 STORIES OR LED OR > 50
 PEOPLE ABOVE OR BELOW.
  
 9) SHEET A400.2 PROVIDE VARIOUS DETAILS OF SOFFITS, THE
 PLANS LACKATTACHMENT OF TOP TRACK TO DECK ABOVE?
  
 10) PLEASE SEE ELECTRICAL NOTE# 1 THAT MAY CREATE A
 PROBLEM BEFORE THE SHELL BUILDING RECEIVES THEIR
 CERTIFICATE OF COMPLETION.)
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-04-10 Cont ID  
Sent By dpalmer Date 2008-04-10 Time 16:23 Rev Time 0.00
Received By dpalmer Date 2008-04-10 Time 16:23 Sent To FIRE
Notes
2008-04-10 16:25:35ELEC OK, SENT PLANS TO FIRE AS THEY NEED TO STAMPE
 SHEETS.
  
 WILL NEED ALL FINAL STAMPS AND PROCESSING ONCE THAT IS
 DONE. PLANS WILL GO TO LUIS MARTINEZ

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-03-18 Cont ID  
Sent By dpalmer Date 2008-03-18 Time 15:16 Rev Time 0.00
Received By dpalmer Date 2008-03-18 Time 15:16 Sent To  
Notes
2008-03-18 15:16:22** DENIED 4TH REVIEW **
  
 ** PLEASE SEE COMMENT IS THE SAME FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS ON PLANS DO NOT COORDINATE WITH THE
 ELECTRICAL LIGHTING SHOWN.
 PLEASE SEE SOME OF THESE APPEAR TO BE MISPRINTS HOWEVER
 SOME AREAS ARE NOT CLEAR AS THEY DO NOT CONTAIN LABELS,
 OR IDENTIFICATIONS OF ANY KIND AND LIGHTING BEING
 FIGURED INTO SOME OF THESE AREAS ARE ONLY BEING
 "ASSUMED".
 PLEASE SEE SOME OF AREA DESIGNATIONS ARE NOT LISTED ON
 THE CALCULATIONS AND SOME OF THE ITEMS LISTED ON THE
 CALCULATIONS ARE NOT ON PLANS.
 PLEASE SEE FOR EXAMPLE: OFFICE 17 IS SHOWN TWICE ON
 PLANS, OFFICE AREA 18 ON PLANS NOT LISTED ON
 CALCULATIONS, CONFERENCE ROOM #15 ON PLANS, NOT LISTED
 ON CALCULATIONS ETC
 PLEASE SEE FOR EXAMPLE: OFFICE AREA #21, SOME OTHER
 OFFICE AREAS LIKE #24 INCLUDED THE COPY ROOMS EVEN
 THOUGH NONE OF THESE WERE LABELED IN CALCULATIONS THIS
 WAS FIGURED BY THIS OFFICE. HOWEVER PLEASE SEE #21 AS
 THE COPY ROOM IN THIS AREA WAS NOT FIGURED IN THE AREA
 CALCULATIONS.
 PLEASE SEE FOR EXAMPLE: THERE IS A MARKETING CLOSET #32
 SHOWN ON CALCULATIONS HOWEVER WHERE IS THIS ON PLANS?
  
 PLEASE GO OVER ALL LIGHTING, ROOM/AREA DESIGNATIONS
 PLEASE CORRELATE AND COORDINATE ALLOWANCES. 13-415.2,
 13-415.2.ABC.1.1, .1.2, 13-415.2.B
  
 ** PLEASE KNOW ONE COPY OF E-1 WILL BE RETAINED BY THIS
 OFFICE.
  
 2) NOTE: ** ATTENTION CONTRACTOR**/ PHOENIX REALTY.
 WHEN PRINTING ON-LINE FORM, AS INSTRUCTED AT THE TOP OF
 WEB- PAGE; PLEASE CLICK ON THE "SUBMIT" BUTTON IN ORDER
 TO PRINT THE CORRECT RE-SUBMISSION FORM. THE *PRINT
 SCREEN* SHEET USED WHEN RESUBMITTED WAS NOT CORRECT AND
 SHOULD NOT HAVE BEEN USED OR SUBMITTED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-02-01 Cont ID  
Sent By dpalmer Date 2008-02-01 Time 17:49 Rev Time 0.00
Received By dpalmer Date 2008-02-01 Time 17:48 Sent To  
Notes
2008-02-01 17:49:17** DENIED 3RD REVIEW **
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO LIGHTING PERFORMANCE CALCULATIONS.
 RESPONSE LETTERS MENTIONS NO ENERGY CALCULATIONS WERE
 TO BE SUBMITTED. SHELL PERMIT HAD THESE ITEMS AS
 ASSUMPTIONS, SHELL PERMIT IS ALSO NOW HAS A CERTIFICATE
 OF OCCUPANCY SINCE LAST REVIEW.
 PLEASE KNOW THE LIGHTING PERFORMANCE CALCULATIONS AS
 NOTED ON SHEET E-1 ARE NOT ENOUGH FOR REVIEW.
 PLANS MENTIONS METHOD *B* BEING USED, HOWEVER COULD NOT
 LOCATE SPACE BY SPACE CALCULATIONS. THERE ARE ALSO
 OTHER SPACES BESIDE THE ONES LISTED ON PLANS WHICH DO
 FALL UNDER OTHER AREAS IN TABLE 13-415.2.B.
 LEVELS AS SHOWN ON PLANS NEED TO COMPLY WITH TABLE *B*
 AS NOTED. FOR EXAMPLE: PLEASE SEE HALLWAYS WHICH PLANS
 INDICATES 1.0 YET THE FBC TABLE *B* SHOWS .05 (MAX).
 PLEASE SEE AS STATED ON PREVIOUS REVIEW THE LEVELS
 WHICH NEED TO BE SHOWN AND FIGURED FOR TRACK LIGHTING
 PER 13-415.2.ABC.1.2
 PLEASE CALL TO GO OVER HOW COMPLIANCE NEEDS TO BE
 SHOWN.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-04 Cont ID  
Sent By dpalmer Date 2007-11-04 Time 10:09 Rev Time 0.00
Received By dpalmer Date 2007-11-04 Time 09:34 Sent To I
Notes
2007-11-04 10:09:312007-11-04 10:09:31
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS DUE
 TO SOME CHANGES ON PLANS AND/OR DOCUMENTS AS
 SUBMITTED.
 SOME OF THESE COMMENTS COULD NOT HAVE BEEN MADE ON
 PREVIOUS REVIEWS AS THEY WERE NOT SUBMITTED.
  
 1) NOTE: PLEASE SEE FROM PREVIOUS REVIEW STILL NEED TO
 SPECIFY MAXIMUM TIMES ON ALL LIGHTING CONTROL DEVICES.
 13-415.1.ABC.1.1, .1.2.
  
 2) NOTE: PLEASE KNOW IF ANY MODULAR FURNITURE HAS
 PERMANENTLY INSTALLED TASK LIGHTING, CONTROLS ARE
 REQUIRED PER 13-415.1.ABC .1.3.
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED ARE METHOD *A* FOR WHOLE BUILDING. HOW IS
 THIS POSSIBLE WHEN THIS IS NOT A WHOLE BUILDING? PLEASE
 KNOW FOR ELECTRICAL AS THIS BUILDING IS ALREADY AIR
 CONDITIONED AND ASSUMPTIONS WERE DONE UNDER BASE
 BUILDING FOR SHELL, ONLY LIGHTING PERFORMANCE
 CALCULATIONS ARE NEEDED PER 13-415.2.
 PLEASE SEE EVEN AS THE METHOD *A* WAS SUBMITTED THE
 INFORMATION ON THE INPUT DATA REPORTS IS NOT CORRECT
 AND DOES NOT CORRELATE WITH THE AMOUNT OF FIXTURES, THE
 WATTAGE OF FIXTURES ETC AS REQUIRED TO BE ON THE INPUT
 DATA REPORT. FOR EXAMPLE: PLEASE SEE THE IDR, WHICH
 ONLY INDICATES *ONE* LIGHT FIXTURE BEING INSTALLED.
 THIS IS NOT POSSIBLE WHEN THERE ARE OVER A HUNDRED ON
 PLANS.
 ** PLEASE BE SURE TO SEE 13-415.2.ABC .1.2 FOR TRACK
 LIGHTING.
 ** PLEASE KNOW AS THIS IS NOT COMPLETE AT THIS TIME, A
 REVIEW OF THESE CAN NOT BE DONE.
 ** PLEASE BE SURE TO SEE COMMENTS FROM MECHANICAL OR
 OTHER TRADES WHICH WILL AFFECT THIS COMMENT ALSO.
  
 4) NOTE: PLEASE SUBMIT LOAD CALCULATIONS PER NEC 220.
 PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. PLEASE
 SEE TRACK LIGHTING NEEDS TO BE SHOWN PER 220.43.
 220.12, 220.14, 220.42, 220.43, 215.3, 230.42 ETC. FBC
 106.3.5.1.2, 106.1.2
  
 5) NOTE: PLEASE SEEPREVIOUS COMMENT WITH RESPECT TO
 CODES ON PLANS. THIS IS REQUIRED ON ELECTRICAL PLANS AS
 STATED.
 PLEASE SEE THE FOLLOWING IS TO BE ON ELECTRICAL PLANS
 FOR THESE SETS OF RECORD PLANS.
  
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 6) NOTE: PLEASE KNOW THE ADDRESS FOR SUITE/UNIT NUMBER
 IS STILL NEEDED AND INFORMATION WAS FORWARDED TO THE
 ADDRESSING REVIEWER.
 PLEASE KNOW ONCE THE SUITE/UNIT NUMBER IS DETERMINED,
 PLEASE INCLUDE ON TITLE BLOCKS FOR ALL SHEETS.
 FBC 106.5, 106.1.2, FAC 61G15-23.002
  
 7) NOTE: PLEASE DO NOT ATTAH DOCUMENTS SUCH AS ENERGY
 CALCULATIONS, RESPONSES ETC DOWN THE LEFT HAND SIDE OF
 PLANS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-11-04 09:34:512007-11-04 09:34:51
  
 IN ELECTRICAL FOR REVIEW. PLANS REMOVED FROM INCOMING
 AND WILL BE RETURNED TO INCOMING ONCE COMPLETED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-13 Cont ID  
Sent By dpalmer Date 2007-08-13 Time 11:12 Rev Time 0.00
Received By dpalmer Date 2007-08-12 Time 10:16 Sent To  
Notes
2007-08-13 11:12:35** DENIED **
  
  
  
 1) NOTE: PLEASE KNOW THAT AS OF THIS REVIEW AND DATE
 THE CO ON THE BASE SHELL BUILDING AHS NOT BEEN
 ACHIEVED. ANY DESIGN CHANGES FOR KNOWN LOADS ON THE
 SERVICE, KNOWN LOADS ON THE ENERGY CALCULATIONS AND
 CHANGES TO THE BASE BUILDING ELECTRICAL SYSTEM WILL BE
 REQUIRED ON THE BASE BUILDING PLANS BEFORE THE PERMIT
 FOR CONSTRUCTION CAN BE ISSUED.
 PLEASE KNOW THAT IF THE INTENT IS TO PERMIT THIS SCOPE
 OF WORK BEFORE THE CO OF THE SHELL ALL OF THE ABOVE
 ITEMS MUST BE ADDRESSED ON THOSE PLANS AND SUPPORTING
 DOCUMENTS BEFORE THE CO CAN BE ISSUED.
 IF CO IS OBTAINED BEFORE PERMIT ISSUANCE OF BUILD OUT
 THEN THIS WOULD BE OK AS IS.
 PLEASE ALSO KNOW THAT ANY BUILD OUT WORK WHICH IS DONE
 ON THE SHELL BUILDING BEFORE ISSUANCE OF CO IS STILL TO
 BE UNDER THE REVIEW OF THE BASE BUILDING ARCHITECT AND
 ENGINEERING FIRM(S). THIS HAS BEEN CONFIRMED WITH THE
 STATE AND THE BUILDING OFFICIAL AS THE BUILDING IS
 STILL UNDER THE BASE DESIGN TEAMS RESPONSIBILITY.
  
 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 3) NOTE: PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER ON TITLE BLOCKS OF MEP PLANS AS
 REQUIRED PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002
 AND FLORIDA STATUTES 471.023.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 4) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED ARE NOT COMPLETE AT THIS TIME FOR COMPLETE
 REVIEW. PLEASE SEE THE SHEETS ARE MISSING THE INPUT
 DATA REPORTS FOR REVIEW AND COORDINATION WITH PLANS.
 PLEASE SEE SHEET 2 OF THE SUMMARY SHEETS WHICH STATES
 THE INPUT DATA REPORTS MUST ACCOMPANY THE SUMMARY
 SHEETS.
 PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH THE
 CALCULATIONS FOR TYPE OF FIXTURES, WATTAGES, NUMBER OF
 FIXTURES ETC.
 13-415.1.A, 13-415.2, 13-103.1.1.1.
 PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED ON.
  
 5) NOTE: PLEASE SEE THE FLOOR LAYOUT SEEMS TO SHOW WHAT
 APPEARS TO BE COMMON AREA INCLUDING : ELEVATOR LOBBY,
 BATHROOMS, EXIT STAIR ACCESS, ELECTRICAL ROOM ETC YET
 THE PLANS INDICATE CIRCUITING FROM THE TENANT
 ELECTRICAL??
 PLEASE SEE IF THESE ARE COMMONS AREAS, THEY ARE
 REQUIRED TO BE FED FROM HOUSE PANELS.
 PLEASE ALSO SEE NO CIRCUITING IS BEING SHOWN ON
 BATHROOMS WHEN THE PLANS CLEARLY SHOWS THIS AS ALL ONE
 TENANT SPACE ALONG WITH NOTE #9 ON E-1 WHICH MENTIONS
 CONTROLS FOR BATHROOMS.?
 PLEASE CLARIFY THE SERVICE AS SHOWN AS THE PLANS ARE
 FOR ONE TENANT AND RISER SHOWS EACH PANEL ON ITS OWN
 METER. THIS SCENARIO IS NOT PERMITTED AT THIS TIME AS
 THIS IS ONE TENANT AND ONE METER IS PERMITTED.
 PLEASE SEE SHEET E-2 WHICH CLEARLY STATES TO SEE
 EXISTING ELECTRICAL ROOM LAYOUT ON E-5, YET THERE WAS
 NO E-5 SUBMITTED?
 HOUSE AND MAIN POWER MAY NOT BE LOCATED IN THE TENANT
 SPACE.
 THIS INFORMATION WILL ALSO BE FORWARDED TO THE FIRE
 MARSHAL, ZONING AND BUILDING REVIEWS AS THE USE OF
 MULTIPLE METERS FOR ONE TENANT IS NOT PERMITTED.
 REVISING THE RISER WILL BE NEEDED. 215.5, 230.70,
 230.2, 240.24,ETC.
 FBC 106.1.2 AND 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
 THERE ARE TOO MANY UNKNOWNS AT THIS TIME FOR DETAILED
 REVIEW.
  
 6) NOTE: PLEASE SEE MISSING REQUIRED DISCONNECTING
 MEANS FOR ELECTRICAL IN SERVER ROOM. THIS AS SHOWN
 APPEARS TO BE AN IT ROOM AND NEED MORE INFORMATION ON
 EQUIPMENT BEING INSTALLED AND PROPOSED FOR ROOM. UPS,
 EQUIPMENT ETC.
 PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR ANY
 EQUIPMENT BEING INSTALLED. 110.3, 90.7
 PLEASE SEE 645.10,645.11, 645.4
 PLEASE SEE 645.5A FOR BRANCH CIRCUITS.
 PLEASE KNOW AT THIS TIME AS THE ROOM IS SHOWN THIS IS
 BEING CONSIDERED AS AN IT ROOM AND WILL NEED THE 1HR
 RATING OF WALLS AND DISCONNECTING MEANS FOR EQUIPMENT
 INCLUDING THE DEDICATED A/C.
 NFPA-75
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE 605.6, 605.7, 608.8D ETC FOR
 REQUIRED INFORMATION AND BREAKERS FOR MODULAR
 FURNITURE.
  
 8) NOTE: PLEASE KNOW THAT EVEN AS LOW VOLTAGE FOR
 PHONE/DATA IS SHOWN ON PLANS, THESE WILL STILL BE
 REQUIRED TO BE UNDER A SEPARATE PERMIT. THEPLANS MAY
 BE REFERENCED FOR A TURN AROUND PERMIT AS LONG AS THE
 PLANS INDICATE ALL LOW VOLTAGE AS APPLIED.
 PLEASE KNOW FEES WILL BE DUE BASED ON LV SCOPE.
 THIS NOTE IS ONLY FOR INFORMATIONAL PURPOSES ONLY AND
 NO INFORMATION NEEDS TO BE PLACED ON PLANS.
  
 9) NOTE: PLEASE SUPPLY MORE INFORMATION ON CHAPTER 13
 13-415.1.ABC.1.1, AND .1.2.
 PLEASE BE SURE ALL MAXIMUM TIMES ARE STATED FOR EACH
 DEVICE AS CHOSEN.
 PLEASE SEE SOME AREAS WHICH STILL CONTAIN ONLY A
 STANDARD WALL SWITCH AS LISTED ON SYMBOL LEGEND.
 (EXAMPLE SEE SUPPLY CLOSET)
  
  
 10 ) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA
 SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
  
 11) NOTE: PLEASE KNOW THAT THE PLANS NEED TO LABEL AND
 PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS
 AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR
 EACH PANEL.PLEASE KNOW THAT A NUMERICAL DESIGNATION
 MAY BE USED. (EXAMPLE OFFICE 103, OFFICE 105 ETC)
 PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE
 CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT
 ACCEPTABLE.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 12) NOTE: PLEASE OBTAIN INFORMATION FROM THE BASE
 BUILDING PLANS AS THE FEEDERS AS SHOWN THIS RISER AS
 EXISTING IS NOT ACCURATE WITH THE PLANS ON BASE
 BUILDING. THESE WERE REVISED.
 FBC 106.1.2
  
 13) NOTE: PLEASE DO NOT STAPLE AND ATTACH SUPPORTING
 DOCUMENTS DOWN THE SIDE OF PLANS. THE SUPPORTING
 DOCUMENTS SHOULD BE ATTACHED INTO EACH SET OF THEIR OWN
 FOR REVIEW.
 FBC 106.1
  
 14) NOTE: PLANS WILL BE ROUTED TO ADDRESSING AS A
 SUITE/UNIT NUMBER WILL NEED TO BE DETERMINED.
 ONCE THIS HAS BEEN DETERMINED PLEASE BE SURE TO PLANS
 ON TITLE BLOCK OF PLANS.
 AT THIS TIME NONE HAS BEEN ASSIGNED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-04-10 Cont ID  
Sent By mawillia Date 2008-04-10 Time 17:12 Rev Time 0.00
Received By mawillia Date 2008-04-10 Time 16:46 Sent To B
Notes
2008-04-10 16:54:25*****APPROVED*****
  
 PLAN SHEETS A120.1, A130.1, AND A150.1 THRU A150.5 WERE
 PREVIOUSLY FIRE-STAMPED ON 04/07/08;PLAN SHEETS E1AND
 FP-1 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-04-07 Cont ID  
Sent By mawillia Date 2008-04-07 Time 12:15 Rev Time 0.00
Received By mawillia Date 2008-04-07 Time 10:40 Sent To  
Notes
2008-04-07 11:48:00*****PROVISO*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED.PLAN SHEETS A120.1, A130.1, AND A150.1
 THRU A150.5 WERE STAMPED, INTIALED, AND DATED; HOWEVER,
 PLAN SHEET E1 TO BE FIRE-STAMPED WHEN THE ELECTRICAL
 REVIEW COMMENT HAS BEEN SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-02-27 Cont ID  
Sent By mwennerg Date 2008-02-27 Time 13:39 Rev Time 0.00
Received By mwennerg Date 2008-02-27 Time 13:39 Sent To  
Notes
2008-02-27 14:06:49***DENIED***
  
 PLEASE NOTE THAT MOST OF THE COMMENTS HAVE BEEN
 ADDRESSED ON THE PLANS. THE FOLLOWING COMMENTS TAKEN
 FROM THE LAST REVIEW REQUIRE A WRITTEN RESPONSE. A
 RESPONSE LETTER ADDRESSING THESE COMMENTS WOULD HELP
 EXPEDITE THIS PLAN REVIEW PROCESS:
  
 06. IN THE EVENT OF A FIRE, STAIRWELLS INSTEAD OF THE
 ELEVATORS WILL BE USED. PLEASE EXPLAIN RATIONALE FOR
 GOING THROUGH THE CONFERENCE ROOM OR GOING THROUGH THE
 BREAK ROOM TO ACCESS THOSE FIRE-RATED STAIRWELLS.
 PROVIDE DATA/CRITERIA AS PER NFPA 101, CHAPTER-7 THAT
 ALLOWS THIS ARRANGEMENT.
  
 10. HOW DOES A PERSON(S) GET IN OR OUT OF THE MODULAR
 OFFICES? PLEASE ACKNOWLEDGE
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-12-11 Cont ID  
Sent By mawillia Date 2007-12-11 Time 15:44 Rev Time 0.00
Received By mawillia Date 2007-12-11 Time 13:02 Sent To  
Notes
2007-12-11 15:44:08*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 01.THE LOCATION OF THE PROJECT AS INDICATED ON THE
 LOCATION MAP (COVER SHEET) IS INACCURATE.PLEASE BE
 ADVISED THAT THE PROJECT SITE LOCATION IS MUCH FARTHER
 WEST OF WHAT IS SHOWN
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 COMMENT TOA 110.1
  
 04.IT APPEARS THAT THIS BUILDOUT WILL COMPRISE OF THE
 ENTIRE SECOND FLOOR.IF A SUITE NUMBER IS ASSIGNED TO
 THIS SITE,THE SUITE NEMBER SHALL BE INCLUDED IN THE
 ADDRESS LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.NO SUITE NUMBER SHOWN ONA110.1, A125.1,
 A150.1, A150.2, A150.4, A210.1, A400.2, A500.1, M1 THRU
 M7, E1 THRU E4, AND P1 THRU P3.
  
 05.COULD NOT LOCATE SHEET A135.1 AS INDICATED IN THE
 SHEET INDEX OF THE COVER SHEET.PLAN SHEET NOT
 INCLUDED
  
 06.IN THE EVENT OF A FIRE, STAIRWELLS INSTEAD OF THE
 ELEVATORS WILL BE USED.PLEASE EXPLAIN RATIONALE FOR
 GOING THROUGH THE CONFERENCE ROOM OR GOING THROUGH THE
 BREAK ROOM TO ACCESS THOSE FIRE-RATED STAIRWELLS.
 PROVIDE DATA/CRITERA AS PER NFPA 101 - CHAPTER 7 THAT
 ALLOWS THIS ARRANGEMENT
  
 10.HOW DOES A PERSON(S) GET IN OR OUT OF THE MODULAR
 OFFICES?PLEASE ACKNOWLEDGE
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-05 Cont ID  
Sent By mawillia Date 2007-09-05 Time 13:34 Rev Time 0.00
Received By mawillia Date 2007-09-05 Time 09:04 Sent To  
Notes
2007-09-05 13:32:41*****DENIED*****
  
  
 01.THE LOCATION OF THE PROJECT AS INDICATED ON THE
 LOCATION MAP (COVER SHEET) IS ILLEGIBLE.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.THIS PROJECT IS LISTED AS A NEW BUSINESS
 OCCUPANCY.IS THIS PROJECTED SCOPE OF WORK A CHANGE OF
 OCCUPANCY?
  
 04.IT APPEARS THAT THIS BUILDOUT WILL COMPRISE OF THE
 ENTIRE SECOND FLOOR.IF A SUITE NUMBER IS ASSIGNED TO
 THIS SITE,THE SUITE NEMBER SHALL BE INCLUDED IN THE
 ADDRESS LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 05.COULD NOT LOCATE SHEET A135.1 AS INDICATED IN THE
 SHEET INDEX OF THE COVER SHEET.
  
 06.IN THE EVENT OF A FIRE, STAIRWELLS INSTEAD OF THE
 ELEVATORS WILL BE USED.PLEASE EXPLAIN RATIONALE FOR
 GOING THROUGH THE CONFERENCE ROOM OR GOING THROUGH THE
 BREAK ROOM TO ACCESS THOSE FIRE-RATED STAIRWELLS.
  
 07.ACCESS TO AN EXIT SHALL NOT BE THROUGH ROOMS OR
 SPACES SUBJECT TO LOCKING.
  
 08.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR
 ACCESS CONTROL SYSTEM ENTRANCE/EGRESS DOORS.
  
 09.ON SHEET A120.1, THE SUPPLY CLOSET DOOR OPENS INTO
 THE PATH OF EGRESS.DURING ITS SWING, ANY DOOR IN A
 MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF
 THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, OR
 PASSAGEWAY.
  
 10.HOW DOES A PERSON(S) GET IN OR OUT OF THE MODULAR
 OFFICES?
  
 11.ON SHEET A120.1, IT IS SHOWN THAT THE DOUBLE DOORS
 (NEAR THE RECEPTION AREA) SWING OPPOSITE THE DIRECTION
 OF EGRESS TRAVEL.PLEASE EXPLAIN.
  
 12.WILL THE SCOPE OF WORK IMPACT THE FIRE SPRINKLER
 LAYOUT CURRENTLY ON THE FLOOR?IF SO, SEPARATE PLANS
 AND PERMIT WILL BE REQUIRED FOR THE SPRINKLER REMODEL
  
 13.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE ALARM INSTALLATION OR REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-10 Cont ID  
Sent By adarroug Date 2008-04-10 Time 11:13 Rev Time 0.00
Received By adarroug Date 2008-04-10 Time 11:13 Sent To E
Notes
2008-04-10 11:14:02TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-13 Cont ID  
Sent By adarroug Date 2008-03-13 Time 10:28 Rev Time 0.00
Received By adarroug Date 2008-03-13 Time 10:28 Sent To  
Notes
2008-03-14 09:19:19TO "COMM" BD#38
2008-03-13 10:30:26WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 11:08 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 11:08 Sent To  
Notes
2008-01-29 11:13:27TO "COMM" BD#24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 11:29 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 11:29 Sent To  
Notes
2007-11-05 09:25:08TO "COMM" BD#35
2007-10-15 11:29:28WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-05 Cont ID  
Sent By mawillia Date 2007-09-05 Time 09:04 Rev Time 0.00
Received By mawillia Date 2007-07-19 Time 14:35 Sent To  
Notes
2007-07-30 09:02:38TO "COMM" BD#62
2007-07-19 14:35:59WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-04-01 Cont ID  
Sent By rregueir Date 2008-04-01 Time 17:22 Rev Time 0.00
Received By rregueir Date 2008-04-01 Time 17:22 Sent To  
Notes
2008-04-01 17:23:52MISSING DOCUMENTATION FROM 3/20/08 REVIEW BY HMOSER WAS
 PROVIDED AND REVIEW STATUS CHANGED TO PASS. MECH PLANS
 HAVE BEEN STAMPED.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-03-20 Cont ID  
Sent By hmoser Date 2008-03-20 Time 18:25 Rev Time 0.00
Received By hmoser Date 2008-03-20 Time 18:25 Sent To  
Notes
2008-03-20 18:28:59PLAN DENIED
 CAN NOT FIND ANCERS TO REVIEW COMMENTS FOR 2/14/08
 PLAN REVIEW BY HAROLD MOSER561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-02-14 Cont ID  
Sent By rregueir Date 2008-02-14 Time 11:10 Rev Time 0.00
Received By rregueir Date 2008-02-14 Time 11:09 Sent To  
Notes
2008-02-14 11:10:46REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK. THIS COMMENT NO LONGER APPLIES AS THE BASE
 BUILDING HAS BEEN COMPLETED.
  
 2. OK FOR MECHANICAL PORTIONS OF FBC CHAPTER 13 ONLY.
  
 3 THROUGH 10: OK
  
 11. BY WHAT MEANS ARE THE MOTORIZED DAMPERS ON THE
 OUTSIDE AIR INTAKES CONTROLLED? WILL THEY CLOSE
 WHENEVER THE AHUS SHUT DOWN OR WILL THEY CLOSE WHEN THE
 BUILDING A/C IS IN UNOCCUPIED MODE? THE LATTER IS WHAT
 IS REQUIRED BY FBC 13-409.1.ABC.3.4.
  
 12. OK
  
 13. AS STATED IN PREVIOUS REVIEW COMMENT #13, WHEN
 COMBINED SYSTEMS EXCEEDING 2000 CFM SHARE A COMMON
 PLENUM, SMOKE DETECTORS SHALL BE INSTALLED ON THE
 SUPPLY AND RETURN SYSTEMS IN ACCORDANCE WITH FBC, M
 606.2.2. AC-1, 2, 4, 6 AND 8 SHOULD ALL HAVE SMOKE
 DETECTORS ON THE SUPPLY AND RETURN SIDES IN ACCORDANCE
 WITH THIS SECTION. PLEASE CORRECT AND RESUBMIT.
  
 14 THROUGH 17: OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-29 Cont ID  
Sent By rregueir Date 2007-11-29 Time 14:34 Rev Time 0.00
Received By rregueir Date 2007-11-17 Time 16:17 Sent To  
Notes
2007-11-29 14:33:58REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: MECHANICAL RESPONSES TO REVIEW COMMENTS WERE NOT
 SUBMITTED WITH THE PERMIT PACKAGE. MULTIPLE ATTEMPTS
 WERE MADE TO CONTACT DESIGNER AND OBTAIN COMMENTS
 BEFORE THEY WERE PROVIDED. AFTER WAITING FROM 11/17/07
 TO 11/28/07 THE REVIEW WAS STARTED WITHOUT THE
 RESPONSES. THE RESPONSES WERE RECEIVED ON 11/29/07
 AFTER THE REVIEW WAS UP TO COMMENT #11.
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THIS COMMENT HAS NOT BEEN ADDRESSED. THIS PERMIT
 WILL NOT BE ISSUED PRIOR TO A PASSED FINAL INSPECTION
 OF THE BASE BUILDING WITHOUT A SHOP DRAWING REVIEW OF
 THESE PLANS BY THE BASE BUILDING DESIGNERS OF RECORD.
 IT IS NOTED THAT THE BASE BUILDING IS CLOSE TO FINAL AT
 THIS TIME.
  
 2. METHOD A COMPLIANCE FOR A TENANT BUILD-OUT IN AN
 UNFINISHED SHELL BUILDING IS NOT THE CORRECT METHOD OF
 COMPLIANCE IN ACCORDANCE WITH FBC 13-101.1.6. ALSO, IF
 THE BASE BUILDING IS COMPLETE PRIOR TO RESUBMITTAL,
 COMPLIANCE SHALL BE DETERMINED AND DEMONSTRATED IN
 ACCORDANCE WITH FBC 13-400.0.C.4. METHOD A COMPLIANCE
 IS FOR A WHOLE BUILDING AND THIS IS NOT A WHOLE
 BUILDING PERMIT.
  
 3. EQUIPMENT SCHEDULE HAS BEEN CORRECTED TO CORRESPOND
 WITH OUTSIDE AIR CALCULATIONS. PLEASE SEE COMMENT #4
 BELOW FOR ADDITIONAL INFORMATION.
  
 4. FBC, M TABLE 403.3 DOES NOT MAKE ANY PROVISIONS FOR
 REDUCING THE RATE OF OUTSIDE AIR BY 50% BASED ON THE
 DURATION OF OCCUPANCY. NOTE THAT THE DESIGNER HAS THE
 OPTION OF DESIGNING THE MECHANICAL VENTILATION SYSTEM
 TO ASHRAE 62.1-2004 IN LIEU OF COMPLIANCE WITH SECTION
 403.1 THROUGH SECTION 403.3. HOWEVER, THERE ARE NO
 PROVISIONS FOR USING PARTS OF SECTION 403 AND PARTS OF
 ASHRAE 62.1. THE DESIGNER SHALL DECLARE WHICH METHOD IS
 TO BE USED AND DESIGN BY THAT METHOD EXCLUSIVELY IN
 ACCORDANCE WITH FBC, M 403.4. NOTE: IF THE DESIGNER
 CHOOSES TO DESIGN PER ASHRAE 62.1, THE MECHANICAL
 VENTILATION SYSTEM WILL BE REVIEWED FOR COMPLIANCE WITH
 ALL APPLICABLE SECTIONS OF THAT STANDARD, NOT JUST
 OUTSIDE AIR RATES.
  
 5. OK
  
 6. OK
  
 7. OK
  
 8. THE AIR BALANCE SCHEDULE SHOWS A POSITIVE PRESSURE
 OF 1410 CFM. WHILE FBC 13-409.1.ABC.2 REQUIRES THE
 BUILDING TO BE PRESSURIZED, COMPLIANCE WITH FBC, M
 403.1 SHALL ALSO BE SHOWN. THE AMOUNT OF SUPPLY AIR
 SHALL BE APPROXIMATELY EQUAL TO THE AMOUNT OF RETURN
 AND EXHAUST AIR AS REQUIRED BY FBC, M 403.1. SUPPLY AIR
 IS SHOWN AT 12,000 CFM AND RETURN PLUS EXHAUST IS SHOWN
 AT 10,590 CFM. IN ACCORDANCE WITH FBC 201.3, WORDS NOT
 DEFINED IN THE FBC SHALL HAVE THE MEANINGS IN WEBSTER?S
 THIRD NEW INTERNATIONAL DICTIONARY OF THE ENGLISH
 LANGUAGE, UNABRIDGED. APPROXIMATE IS DEFINED AS "NEARLY
 CORRECT OR EXACT." THE IMPLEMENTATION OF THESE TWO CODE
 SECTIONS TOGETHER WOULD REQUIRE THESE NUMBERS TO BE
 NEARLY EQUAL, WITH A SLIGHT VARIATION TO THE POSITIVE
 SIDE AND THE OUTSIDE AIR BEING APPROXIMATELY EQUAL TO
 THE AMOUNT OF EXHAUST. SHOW COMPLIANCE WITH THESE
 SECTIONS.
  
 9. OK. MANUAL BALANCING DAMPERS ARE SHOWN ON PLAN. THIS
 IS NOT THE SAME AS SHUTOFF DAMPER CONTROLS AS STATED IN
 COMMENT #11 BELOW.
  
 10. SEE COMMENT #8 ABOVE.
  
 11. THIS ISSUE WAS NOT ADDRESSED ON PLANS. DESIGNER'S
 RESPONSE STATES "NO MOTORIZED DAMPERS USED." IF NO
 MOTORIZED DAMPERS HAVE BEEN USED, THEN BY WHAT MEANS
 HAS COMPLIANCE WITH THIS SECTION BEEN DEMONSTRATED?
 MANUAL DAMPERS DO NOT MEET THIS REQUIREMENT. SHOW
 COMPLIANCE WITH FBC 13-409.1.ABC.3.4.
  
 12. THE EXAMPLE GIVEN IN PREVIOUS COMMENT WAS THE
 CONFERENCE ROOM. PLANS NOW SHOW 1200 CFM SUPPLY WITH
 940 CFM RETURN. THIS WOULD ALLOW FOR ONLY 260 CFM
 OUTSIDE AIR. THE OUTSIDE AIR SCHEDULE SHOWS 500 CFM
 OUTSIDE AIR IS REQUIRED IN THIS ROOM IF THE SYSTEM IS
 DESIGNED TO ASHRAE 62.1-2004 (SEE COMMENT #4 ABOVE).
 SHOW AN AIR BALANCE IN ALL HIGH-OCCUPANCY AREAS WHICH
 WILL ALLOW FOR COMPLIANCE WITH OUTSIDE AIR
 REQUIREMENTS.
  
 13. BASED ON THE A/C SYMBOL LEGEND ON PG M1, DUCT
 MOUNTED SMOKE DETECTORS ARE NOT SHOWN ON PLANS. ALSO,
 ELECTRICAL PLANS ONLY SHOW PROVISIONS FOR TWO DUCT
 SMOKE DETECTORS ON AC-1 AND AC-6. SEE PG E2 FLOOR PLAN
 AND E4 FIRE ALARM RISER. SHOW COMPLIANCE WITH FBC, M
 606.2.1 AND 606.4.1. COORDINATE MECHANICAL AND
 ELECTRICAL PLANS TO SHOW COMPLIANCE WITH THESE
 SECTIONS.
  
 14. OK
  
 15. RESPONSE TO THIS COMMENT PROVIDED BY ARCHITECT.
 NOTE ON TITLE PAGE STATES THAT STANDS ON ROOF WERE
 INSTALLED AS PART OF BASE BUILDING PERMIT AND HAVE
 MIAMI-DADE NOA. THIS IS ACCEPTABLE. HOWEVER, THE MEANS
 BY WHICH THE CONDENSERS ATTACH TO THE STAND IS PART OF
 THE NOA AND THEREFORE SHALL BE A PART OF THIS PERMIT TO
 GOVERN THE INSTALLATION OF THE CONDENSING UNITS FOR
 THIS PERMIT. PLEASE PROVIDE THE NOA FOR THE PREVIOUSLY
 INSTALLED STANDS HEN RESUBMITTING PLANS. OPTION:
 PROVIDE NOA # AND THE CORRESPONDING ATTACHMENT DETAIL
 ON PLANS.
  
 16. DESIGNER'S RESPONSE: "THIS DETAIL FITS MOST AC
 UNITS." MOST AC UNITS HAVE NOT BEEN SPECIFIED FOR THIS
 PROJECT. ONLY ONE BRAND HAS BEEN SPECIFIED. IN FACT THE
 CARRIER MODEL FA4C AIR HANDLER INSTALLATION
 INSTRUCTIONS DO NOT CORRESPOND WITH THE DETAIL AS SHOWN
 ON PLANS. SEE PAGE FROM INSTALLATION INSTRUCTIONS
 ATTACHED TO THESE COMMENTS. PROVIDE DETAIL WHICH
 CORRESPONDS TO THE ONE IN THE INSTRUCTIONS OR REMOVE
 DETAIL FROM PLANS. A NOTE INSTRUCTING TRAP TO BE IN
 ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS WILL BE
 SUFFICIENT TO DEMONSTRATE CODE COMPLIANCE IN ACCORDANCE
 WITH FBC, M 307.2.4.
  
 17. PLEASE SEE COMMENT #2 ABOVE REGARDING ENERGY CODE
 COMPLIANCE.
  
 NOTE: THE DESIGNER'S COMMENTS WERE NUMBERED INCORRECTLY
 AS COMMENT #1 WAS SKIPPED. THEREFORE, THESE COMMENTS
 WILL NOT CORRESPOND WITH DESIGNER'S RESPONSE. SEE FIRST
 ROUND REVIEW COMMENTS FOR CORRECT NUMBERING SEQUENCE.
  
 NOTE: DUE TO THE AMOUNT OF INFORMATION WHICH IS STILL
 OUTSTANDING, ADDITIONAL REVIEW COMMENTS ARE POSSIBLE
 BASED ON THE INFORMATION PROVIDED WITH NEXT
 RESUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-07 Cont ID  
Sent By rregueir Date 2007-08-07 Time 15:12 Rev Time 0.00
Received By rregueir Date 2007-08-06 Time 11:36 Sent To  
Notes
2007-08-06 16:38:101ST REVIEW
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 UPDATES
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. BASED ON THE DETERMINATION OF THE BUILDING OFFICIAL,
 APPLICATIONS FOR TENANT IMPROVEMENT PERMITS PRIOR TO
 C.O. OF THE BASE BUILDING REQUIRE SHOP DRAWING REVIEW
 BY THE BASE BUILDING DESIGNER(S) OF RECORD. HAVE
 DESIGNER(S) OF RECORD REVIEW CONSTRUCTION DOCUMENTS
 PRIOR TO RESUBMITTAL AND, IF FOUND SUFFICIENT, AFFIX
 THEIR SHOP DRAWING REVIEW STAMP AND SIGNATURE ON SAID
 DOCUMENTATION.
  
 2. THE ENERGY CALCULATIONS FOR THE BASE BUILDING ARE
 BASED ON ASSUMPTIONS FOR A SHELL BUILDING UNDER FBC
 13-101.1.6. UNLESS THE BUILDING IS COMPLETED AS PER ALL
 ASSUMPTIONS MADE IN THE ORIGINAL CODE COMPLIANCE
 SUBMITTAL, A REVISED CODE SUBMITTAL(S) USING METHODS A,
 B OR C SHALL BE SUBMITTED WHEN COMPLETION OF THE
 BUILDING (OR PART OF THE BUILDING) IS PERMITTED.
  
 3. M1: EQUIPMENT SCHEDULE SHOWS A TOTAL OF OUTDOOR AIR
 FOR ALL 8 SYSTEMS TO BE 1640 CFM. THE OUTDOOR AIR
 CALCULATIONS BOX SHOWS A TOTAL OF 1760 CFM. WHICH IS
 CORRECT? PLEASE COORDINATE SCHEDULE WITH CALCULATIONS.
  
 4. M1 OUTDOOR AIR CALCULATIONS: PLAN REFERENCES ASHRAE
 62-99. THE CORRECT REFERENCE STANDARD AS OF DECEMBER 8,
 2006 IS ASHRAE 62.1-2004. THE 2004 FBC ALLOWS
 COMPLIANCE WITH EITHER FBC,M SEC 403.3 OR ASHRAE
 62.1-2004. PLEASE DECLARE ON PLANS WHICH METHOD OF
 COMPLIANCE IS TO BE USED AND VERIFY THAT THE RATES AND
 CALCULATIONS COMPLY WITH THE METHOD BEING EMPLOYED.
  
 5. M1 THROUGH M7: THE COA NUMNER OF THE ENGINEERING
 BUISENESS DOES NOT APPEAR ON PLANS. PLEASE SEE FAC RULE
 61G15-23.002(2) "IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET. A
 TITLE BLOCK ON EACH SHEET CONTAINING THE PRINTED NAME,
 ADDRESS, AND LICENSE NUMBER OF THE ENGINEER OR IF
 APPLICABLE, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER, AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS WILL
 SATISFY THIS REQUIREMENT."
  
 6. VERIFY THAT PROVISIONS HAVE BEEN MADE TO PROVIDE THE
 REQUIRED 250 CFM OF VENTILATION FOR TOILET ROOMS PER
 FBC,M TABLE 403.3. ALSO, PROVISIONS SHALL BE MADE TO
 ASSURE ALL AIR SUPPLIED TO TOILET ROOMS IS EXHAUSTED IN
 ACCORDANCE WITH FBC,M 403.2.1.
  
 7. M2 THROUGH M5: WHAT IS THE SOURCE OF OUTDOOR AIR
 PROVIDED FOR ALL SPACES? NONE COULD BE FOUND ON PLANS.
 PLEASE SHOW THE SOURCE OF OUTDOOR AIR ON PLANS AND HOW
 IT IS TO BE INTRODUCED INTO THE SPACE. FBC,M 403.3
  
 8. BY WHAT MEANS WILL AIR BE EXHAUSTED FROM THE SPACE
 TO PROVIDE FOR THE INTRODUCTION OF THE REQUIRED AMOUNT
 OF OUTDOOR AIR? THE AMOUNT OF SUPPLY AIR SHALL BE
 APPROXIMATELY EQUAL TO THE AMOUNT OF EXHAUST AND RETURN
 AIR PER FBC,M 403.1.
  
 9. VENTILATION SYSTEMS SHALL BE DESIGNED TO BE CAPABLE
 OF REDUCING THE SUPPLY OF OUTDOOR AIR TO THE MINIMUM
 VENTILATION RATES REQUIRED BY SECTION 6.1.3 OF ASHRAE
 62. SYSTEMS MAY BE DESIGNED TO SUPPLY OUTSIDE AIR
 QUANTITIES EXCEEDING MINIMUM LEVELS, BUT THEY SHALL BE
 CAPABLE OF OPERATING AT NO MORE THAN MINIMUM LEVELS
 THROUGH THE USE OF RETURN DUCTS, MANUALLY OR
 AUTOMATICALLY OPERATED CONTROL DAMPERS, FAN VOLUME
 CONTROLS, OR OTHER DEVICES. FBC 13-409.1.ABC.1.1
  
 10. PROVIDE AN AIR BALANCE SCHEDULE TO SHOW THE SPACE
 TO BE PRESSURIZED WITH RESPECT TO THE OUTDOORS PER FBC
 13-409.1.ABC.2.
  
 11. ONCE THE SOURCE OF OUTDOOR AIR IS DETERMINED (SEE
 COMMENT #7), SHOW DAMPER SHUTOF CONTROLS AS REQUIRED BY
 FBC 13-409.1.ABC.3.3. IF MOTORIZED DAMPERS ARE USED,
 PROVIDE SUBMITTAL DATA SHOWING LEAKAGE RATES TO BE IN
 COMPLIANCE WITH FBC 13-409.1.ABC.3.4.
  
 12. SEVERAL AREAS ON FLOOR PLAN, SUCH AS THE HIGH
 OCCUPANCY CONFERENCE AND TRAINING ROOMS, ARE NOT
 DESIGNED FOR THE INTRODUCTION OF OUTDOOR AIR FOR
 VENTILATION. EXAMPLE: CONFERENCE ROOM SHOWS 1200 CFM OF
 SUPPLY AND 1200 CFM OF RETURN. HOW IS IT THAT THE
 REQUIRED 500 CFM OF OUTDOOR AIR IS TO BE SUPPLIED INTO
 THE SPACE? SEE COMMENT #9.
  
 13. UNITS AC 1, AC 2, AC 4, AC 6 AND AC 8 ARE SHOWN
 WITH A COMMON RETURN AIR PLENUM. WHERE MULTIPLE
 AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY OR RETURN AIR
 DUCTS OR PLENUMS WITH A COMBINED DESIGN CAPACITY
 GREATER THAN 2,000 CFM, THE RETURN AIR AND SUPPLY AIR
 SYSTEM SHALL BE PROVIDED WITH SMOKE DETECTORS IN
 ACCORDANCE WITH SECTION 606.2.1. DUCT SMOKE DETECTORS
 SHALL BE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM
 PER FBC,M 606.4.1
  
 14. M6: THERE ARE 8 CONDENSERS ON ROOF TO SERVE THE 2ND
 FLOOR, BUT THERE ARE ONLY 7 LINE SETS SHOWN ON PLAN.
 PLEASE CLARIFY.
  
 15. M7: ARE CONDENSERS TO BE MOUNTED ON INDIVIDUAL
 PRE-ENGINEERED A/C STANDS AS SHOWN ON CU MOUNTING
 DETAIL OR A RACK WHICH IS BEING PROVIDED BY THE BASE
 BUILDING? IF PRE-ENGINEERED STANDS ARE TO BE USED,
 PROVIDE CURRENT PRODUCT APPROVALS FOR THE SPECIFIC
 STANDS TO BE USED PER FAC RULE 9B-72. IF USING BASE
 BUILDING RACK, PROVIDE ENGINEERING SHOWING HOW
 CONDENSERS ARE TO BE ATTACHED TO THIS RACK TO MEET WIND
 LOAD REQUIREMENTS PER FBC,M 301.13 AND FBC CH 16.
 PROVIDE WIND LOAD CALCULATIONS.
  
 16. M7: CONDENSATE TRAP DETAIL, CHECK THE EQUIPMENT
 MANUFACTURER'S REQUIREMENTS FOR TRAPS AS ALL CONDENSATE
 DRAINS SHALL BE TRAPPED AS REQUIRED BY THE EQUIPMENT
 MANUFACTURER. FBC,M 307.2.4
  
 17. ENERGY CALCULATIONS: PROJECT SUMMARY SHOWS MAX
 TONNAGE AT ZERO. PLEASE CORRECT. ALSO, PLEASE INCLUDE
 COOLING LOAD CALCULATIONS AND THE INPUT DATA REPORT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-04-04 Cont ID  
Sent By kstevens Date 2008-04-04 Time 08:36 Rev Time 0.00
Received By kstevens Date 2008-04-03 Time 15:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-02-23 Cont ID  
Sent By kstevens Date 2008-02-23 Time 09:56 Rev Time 0.00
Received By kstevens Date 2008-02-23 Time 09:56 Sent To  
Notes
2008-02-23 10:14:46DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEWS
  
 1. SHT 210.1 DETAILS 4, 10 & 15. ALL SINKS SHALL BE
 ACCESSIBLE. SHOW COMPLIANCE WITH THE FOLLOWING:
 A. OK
 B. OK
 C. 11-4.24.4 SINK DEPTH
 ****NO RESPONSE, NOT ADDRESSED. (3RD TIME)
 D. 11-4.24.5 CLEAR FLOOR SPACE (FWD APPROACH REQUIRED
 - CABINET DOORS NOT APPROVED)
 ****NO RESPONSE, NOT ADDRESSED. (3RD TIME) ( THE CLEAR
 FLOOR SPACE IS NOT INDICATED ON ANY FLOOR PLAN).
 E. OK
 F. OK
  
 2. OK
 3. OK
  
 4. ALL MEP SHEETS. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER, AS WELL AS,
 THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET. FAC
 61G15.23.002(2) & FS 471.025. PLEASE INCLUDE THE CA
 NUMBER. ALSO THE ADDRESS DOES NOT REFLECT THE ADDRESS
 OF RECORD ON THE FLORIDA STATE DBPR WEBSITE. (SEE
 ATTACHED SHEET). PLEASE UPDATE THE ADDRESS ON EITHER
 THE DBPR WEBSITE OR THE TITLE BLOCKS PRIOR TO
 RESUBMITTING TO THE CITY WPB FOR REVIEW.
 ****RESPONSE NOTED, BUT THE ADDRESS IN THE TITLE BLOCK
 DOES NOT REFLECT THE ADDRESS ON THE FLORIDA STATE DBPR
 WEBSITE, (880 PEEPLES DRIVE WEST PALM BEACH). PLEASE
 UPDATE THE TITLEBLOCKS OR THE DBPR WEBSITE PRIOR TO
 RESUBMITTING FOR REVIEW.
  
 5. N/A
  
 **********NEW COMMENT**********
  
 1B. ONE SET OF PLANS WILL BE RETAINED FOR POSSIBLE
 REVIEW WITH THE STATE OF FLORIDA ARCHITECTURAL BOARD.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-05 Cont ID  
Sent By mperson Date 2007-12-05 Time 06:14 Rev Time 0.00
Received By mperson Date 2007-12-05 Time 06:14 Sent To  
Notes
2007-12-05 07:42:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE STILL
 REQUIRED FOR PLUMBING PLAN REVIEW TO MEET CODE
 COMPLIANCE.
  
 1. SHEET 210.1 DETAILS 4, 10 & 15: ALL SINKS SHALL BE
 ACCESSIBLE. SHOW COMPLIANCE TO THE FOLLOWING.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
  
 A. OK, COMMENT ADDRESSED.
  
 B. 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30"
 WIDE, AND 19" DEEP.
 **NOTE: COMMENT NOT ADDRESSED. FOWARD APPROACH
 REQUIRED, CABINET DOORS AND 4" KICK NOT APPROVED.
  
 C. 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 **NOTE: COMMENT NOT ADDRESSED. INDICATE THE SINK DEPTH
 ON THE RESUBMITTAL.
  
 D. 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR
 FLOOR SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH
 THE SINK.
 **NOTE: COMMENT NOT ADDRESSED. FOWARD APPROACH
 REQUIRED, CABINET DOORS AND 4" KICK NOT APPROVED.
  
 E. 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 **NOTE: COMMENT NOT ADDRESSED: PLEASE INDICATE ON
 RESUBMITTAL.
  
 F. 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
 **NOTE: COMMENT NOT ADDRESSED. DETAIL 10 INDICATES
 GOOSENECK FAUCET WITH PADDLE BLADE CONTROLS (TYP).
 PLEASE INDICATE THE FOLLOWING (TYP ALL SINK FAUCETS) ON
 THE RESUBMITTAL.
  
 2. OK, COMMENT ADDRESSED.
  
 3. SHEET P3SUBMIT MANUF. SPECIFICATIONS SHEETS FOR
 THE ELECTRIC WATER HEATER. SHEETS SHOW THE LSTING &
 MANUF, INSTALLATION INSTRUCTIONS. PER SECTION *303.4.
 **RESPONSE NOTED: HOWEVER THIS WAS NOT PROVIDED BY THE
 CONTRACTOR IN THE RESUBMITTAL. PLEASE COMPLY IN THE
 RESUBMITTAL.
  
 4. OK, COMMENT ADDRESSED.
  
 5. BASED ON THE DETERMINATION OF THE BUILDING
 OFFICIAL, APPLICATIONS FOR THE TENANT IMPROVEMENT
 PERMIT PRIOR TO C. O. OF THE BASE BUILDING REQUIRE THE
 DRAWINGS FOR TENANT BUILDOUT TO BE REVIEWED BY THE BASE
 BUILDING DESIGNERS OF RECORD, HAVE THE DESIGNERS OF
 RECORD REVIEW THE CONSTRUCTION DOCUMENTS PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW AND IF FOUND
 SUFFICIENT, AFFIX THEIR SHOP DRAWING REVIEW STAMP AND
 SIGNATURE ON SAID DOCUMENTATION.
 **NOTE: COMMENT NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIER COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-01 Cont ID  
Sent By kstevens Date 2007-09-01 Time 17:53 Rev Time 0.00
Received By kstevens Date 2007-09-01 Time 17:53 Sent To  
Notes
2007-09-01 18:07:05DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT 210.1 DETAILS 4, 10 & 15. ALL SINKS SHALL BE
 ACCESSIBLE. SHOW COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE (FWD APPROACH REQUIRED
 - CABINET DOORS NOT APPROVED)
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
  
 2. SHT P2 WATER RISER DIAGRAMS SHOW AIR CHAMBERS & SHT
 P3 GENERAL SPECIFICATIONS NOTE #$22 INDICATES AIR
 CHAMBERS. AIR CHAMBERS ARE NOT APPROVED. PLEASE DELETE
 FROM RISER DIAGRAMS AND DELETE NOTE #22. PDI-WH 201.
  
 3. SHT P3 SUBMIT MANUF. SPECIFICATIONS SHEETS FOR THE
 ELECTRIC WATER HEATER. SHEETS SHALL SHOW THE LISTING &
 MANUF. INSTALLATION INSTRUCTIONS. SECTION 303.4.
  
 4. ALL MEP SHEETS. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER, AS WELL AS,
 THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET. FAC
 61G15.23.002(2) & FS 471.025. PLEASE INCLUDE THE CA
 NUMBER. ALSO THE ADDRESS DOES NOT REFLECT THE ADDRESS
 OF RECORD ON THE FLORIDA STATE DBPR WEBSITE. (SEE
 ATTACHED SHEET). PLEASE UPDATE THE ADDRESS ON EITHER
 THE DBPR WEBSITE OR THE TITLE BLOCKS PRIOR TO
 RESUBMITTING TO THE CITY WPB FOR REVIEW.
  
 5. BASED ON THE DETERMINATION OF THE BUILDING OFFICIAL,
 APPLICATIONS FOR TENANT IMPROVEMENT PERMIT PRIOR TO
 C.O. OF THE BASE BUILDING REQUIRE THE DRAWINGS FOR
 TENANT BUILDOUT TO BE REVIEWED BY THE BASE BUILDING
 DESIGNERS OF RECORD. HAVE THE DESIGNERS OF RECORD
 REVIEW THE CONSTRUCTION DOCUMENTS PRIOR TO RESUBMITTING
 TO THE CITY FOR REVIEW AND, IF FOUND SUFFICIENT, AFFIX
 THEIR SHOP DRAWING REVIEW STAMP AND SIGNATURE ON SAID
 DOCUMENTATION.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-14 Cont ID  
Sent By eschneid Date 2007-08-14 Time 09:03 Rev Time 0.00
Received By eschneid Date 2007-08-14 Time 09:03 Sent To  
Notes
***NONE***