Plan Review Details - Permit 07070465
Plan Review Stops For Permit 07070465
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-11 Cont ID  
Sent By rmcdouga Date 2008-01-11 Time 13:02 Rev Time 0.00
Received By rmcdouga Date 2008-01-11 Time 13:02 Sent To  
Notes
2008-01-11 13:05:23REVISED KNEE WALL FROM CONCRETE BLOCK TO SOLID POURED
 CONCRETE IS CODE COMPLIANT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-01 Cont ID  
Sent By rmcdouga Date 2007-11-01 Time 16:04 Rev Time 0.00
Received By rmcdouga Date 2007-11-01 Time 16:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-26 Cont ID  
Sent By rmcdouga Date 2007-09-26 Time 17:53 Rev Time 0.00
Received By rmcdouga Date 2007-09-26 Time 17:20 Sent To  
Notes
2007-09-26 18:14:362004 FBC W/2007 REVISIONS
 INSTALL PANEL WALLS AND SLAB
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE SIGNED AND SEALED DRAWINGS ARE REQUIRED TO HAVE
 THE ORIGINAL SIGNATURE OF THE ENGINEER. COPIED
 SIGNATURES OR SIGNATURE STAMPS ARE NOT ACCEPTABLE. SEE
 FS 471 AND FAC 61G15-23.002.
  
 3) SUBMIT PRODUCT APPROVALS FOR THE PANEL WALLS, DOORS,
 ETC. AS REQUIRED BY RULE 9B-72. PROVIDE TEST REPORTS
 AND INSTALLATION INSTRUCTIONS.
 SUBMIT THE TEST REPORT AND INSTALLATION INSTRUCTIONS
 FOR THE SWING DOOR AND THE TEST REPORT FOR THE WALL
 PANELS.
  
 4)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THE ENGINEER IS REQUIRED
 TO APPROVE THE PRODUCT APPROVALS IN WRITING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-13 Cont ID  
Sent By rmcdouga Date 2007-08-13 Time 13:47 Rev Time 0.00
Received By rmcdouga Date 2007-08-13 Time 13:13 Sent To  
Notes
2007-08-13 16:14:432004 FBC W/2007 REVISIONS
 INSTALL PANEL WALLS AND SLAB
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PERMIT APPLICATION SPECIFIES A NEW STRUCTURAL
 ROOF AND THE PLANS SPECIFY THE ROOF AS EXISTING. PLEASE
 CLARIFY.
  
 3) THE SIGNED AND SEALED DRAWINGS ARE REQUIRED TO HAVE
 THE ORIGINAL SIGNATURE OF THE ENGINEER. COPIED
 SIGNATURES OR SIGNATURE STAMPS ARE NOT ACCEPTABLE. SEE
 FS 471 AND FAC 61G15-23.002.
  
 4) SUBMIT PRODUCT APPROVALS FOR THE PANEL WALLS, DOORS,
 ETC. AS REQUIRED BY RULE 9B-72. PROVIDE TEST REPORTS
 AND INSTALLATION INSTRUCTIONS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 5)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 6) THE PRINTED NAME OF THE ENGINEER IS ILLEGIBLE ON THE
 SHEET CONTAINING THE DESIGN CRITERIA. PLEASE CORRECT.
  
 7) PROVIDE STRUCTURAL DETAILS FOR THE 1'- 6" HIGH
 CONCRETE KNEE WALL SHOWN ON SECTION 'A' OF THE
 DRAWINGS.
  
 8) DETAIL 'B' ON AN UN-NUMBERED SHEET SPECIFIES THE
 WIND SPEED AS 130 MPH. PLEASE CORRECT. THE CITY OF WPB
 HAS A WIND SPEED OF 140 MPH.
  
 9) PLEASE NUMBER OR OTHER WISE IDENTIFY THE SHEETS OF
 DRAWINGS THAT WERE SUBMITTED. FBC 106.1.3* AMENDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-31 Cont ID  
Sent By adarroug Date 2007-10-31 Time 10:20 Rev Time 0.00
Received By adarroug Date 2007-10-31 Time 10:20 Sent To B
Notes
2007-10-31 10:22:50TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 15:33 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 15:33 Sent To Z
Notes
2007-09-20 15:34:22TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-13 Cont ID  
Sent By rmcdouga Date 2007-08-13 Time 13:47 Rev Time 0.00
Received By rmcdouga Date 2007-07-17 Time 16:05 Sent To  
Notes
2007-07-17 16:05:11TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-24 Cont ID  
Sent By choops Date 2007-09-24 Time 14:56 Rev Time 0.00
Received By choops Date 2007-09-24 Time 14:56 Sent To B
Notes
2007-09-24 14:57:30SENT TO RMC

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-18 Cont ID  
Sent By choops Date 2007-07-18 Time 16:46 Rev Time 0.00
Received By choops Date 2007-07-18 Time 16:46 Sent To B
Notes
2007-07-18 16:50:24***FAILED***
  
  
 1)INCONSISTANT, SCOPE OF WORK INDICATES UNDER NEW
 STRUCTURAL ROOF.PLANS SHOW UNDER EXISTING...PLEASE
 CLARIFY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720