Plan Review Details - Permit 07070455
Plan Review Stops For Permit 07070455
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-10 Cont ID  
Sent By rmcdouga Date 2007-09-10 Time 17:16 Rev Time 0.00
Received By rmcdouga Date 2007-09-10 Time 17:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-27 Cont ID  
Sent By rmcdouga Date 2007-08-27 Time 12:59 Rev Time 0.00
Received By rmcdouga Date 2007-08-27 Time 12:59 Sent To  
Notes
2007-08-27 13:44:352004 FBC W/2007 SUPPLEMENTS
 INSTALL MODULAR STORAGE SHED
  
 DENIED BY BUILDING
  
 1) THE MODULAR SHED PLANS SUBMITTED FOR THE PROBUILT
 BUILDING IS FOR THE 2001 FBC AND IS NO LONGER VALID.
 THE CURRENT CODE IS THE 2004 FBC WITH 2007
 SUPPLEMENTS.
  
 2)THE MODULAR SHED PLANS FOR THE LARK BUILDERS
 BUILDING HAS BEEN REVISED TO COMPLY WITH THE CURRENT
 CODE SUPPLEMENTS. THE LATEST REVISION OF THE PLANS CAN
 BE DOWNLOADED FROM THE FLORIDA DCA WEBSITE AT
 WWW.FLORIDABUILDING.ORG. ONLY THE MANUFACTURED
 (MODULAR) BUILDING PLANS COMPLYING WITH THE CURRENT
 CODE WILL BE ACCEPTED.
  
 3) IN ADDITION TO THE STATE APPROVED MODULAR BUILDING
 PLANS WHICH ARE NOT REQUIRED TO TO HAVE THE RAISED SEAL
 AND ORIGINAL SIGNATURE OF THE DESIGNER OF RECORD, TWO
 SETS OF FOUNDATION / TIE DOWN PLANS ARE REQUIRED. THE
 FOUNDATION/TIE DOWN PLANS ARE REQUIRED TO HAVE THE
 EMBOSSED SEAL, DATE SIGNED AND ORIGINAL WET SIGNATURE
 OF THE D.O.R. SEE FAC 61G1-16.003. A TITLE BLOCK IS
 ALSO REQUIRED ON THE DRAWINGS PER 61G1-16.004.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-10 Cont ID  
Sent By rmcdouga Date 2007-08-10 Time 17:18 Rev Time 0.00
Received By rmcdouga Date 2007-08-10 Time 17:18 Sent To  
Notes
2007-08-10 17:25:132004 FBC W/2007 REVISIONS
 INSTALL STATE APPROVED MODULAR SHED
  
 DENIED BY BUILDING
  
 1)SUBMIT TWO SETS OF SIGNED AND SEALED FOUNDATION
 PLANS. THE FLORIDA LICENSED ENGINEER'S SIGNATURES ARE
 REQUIRED TO BE ORIGINAL. STAMPS OR PHOTOCOPIES ARE NOT
 ACCEPTABLE.
 SEE 2004 FBC* 106.1 AMENDED, FS 471 AND FAC
 61G15-23.002.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 15:57 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 15:57 Sent To B
Notes
2007-09-06 15:57:25TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 11:26 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 11:26 Sent To B
Notes
2007-08-27 11:26:28TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-10 Cont ID  
Sent By rmcdouga Date 2007-08-10 Time 17:18 Rev Time 0.00
Received By rmcdouga Date 2007-07-18 Time 13:37 Sent To  
Notes
2007-07-18 13:37:56TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2007-07-19 Cont ID  
Sent By choops Date 2007-07-19 Time 10:18 Rev Time 0.00
Received By choops Date 2007-07-19 Time 10:18 Sent To B
Notes
***NONE***